NG-17-0221, Fifth Inservice Inspection Interval Program Plan Relief Request No. RR-05
| ML17325B215 | |
| Person / Time | |
|---|---|
| Site: | Duane Arnold (DPR-049) |
| Issue date: | 11/16/2017 |
| From: | Dean Curtland NextEra Energy Duane Arnold |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| NG-17-0221 | |
| Download: ML17325B215 (26) | |
Text
November 16, 2017 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Duane Arnold Energy Center Docket No. 50-331 Renewed Op. License No. DPR-49 NEXTera ENERGY&
DUANE ARNOLD NG-17-0221 10 CFR 50.55a Fifth lnservice Inspection Interval Program Plan. Relief Request No. RR-05
Reference:
Letter, Curtland (NextEra) to U.S. NRC. "Fifth lnservice Inspection Interval Program Plan, dated March 7, 2017 (ML17069A172)
In the Referenced letter, NextEra Energy Duane Arnold, LLC (hereafter NextEra Energy Duane Arnold) submitted our Fifth 10-Year lnservice Inspection (ISi)
Interval Program Plan pursuant to 10 CFR 50.55a. In that letter, NextEra Energy Duane Arnold stated that an additional Relief Request for the Fifth 10-Year ISi Interval would be submitted under different correspondence at a later date.
Pursuant to 10 CFR 50.55a(z)(1), NextEra Energy Duane Arnold requests approval of the attached Relief Request No. RR-05 for the Fifth 10-Year ISi Interval Program for the Duane Arnold Energy Center (DAEC). The American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Rules for lnservice Inspection of Nuclear Power Plant Components,Section XI, 2007 Edition with Addenda through 2008 as amended by 10 CFR 50.55a, is the code of record for the DAEC Fifth 10-Year ISi Interval.
Relief Request No. RR-05 is requested in order to continue the implementation of the previously approved Risk-Informed lnservice Inspection Program (RI-ISi), as an alternative to the current requirements of Class 1 and 2 examination Categories 8-F, 8-J, C-F-1, and C-F-2 as specified in Table IWB 2500-1, and Table IWC 2500-1 of the 2007 Edition with 2008 Addenda of ASME Code Section XI.
NextEra Energy Duane Arnold requests approval of Relief Request No. RR-05 by August 1, 2018 to allow implementation of the RI-ISi program plan during the first period of DAEC's Fifth 10-Year ISi Interval.
NextEra Energy Duane Arnold, LLC, 3277 DAEC Road, Palo, IA 52324
Document Control Desk NG-17-0221 Page 2 of 2 This letter does not contain any new or revised commitments.
If you have any questions or require additional information, please contact Michael Davis at 319-851-7032.
n Curtland Site Director NextEra Energy Duane Arnold, LLC Enclosure cc:
NRG Regional Administrator NRG Resident Inspector NRG Project Manager
Enclosure to NG-17-0221 Fifth lnservice Inspection Interval Program Plan, Relief Request RR-05 23 pages follow
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
Proposed Alternative In Accordance with 1 OCFR50.55a(z)(1)
-Alternative Provides Acceptable Level of Quality and Safety-
- 1. ASME Code Components Affected All Code Class 1 and 2 piping welds previously subject to the requirements of ASME Section XI, Table IWB-2500-1, Examination Categories B-F and B-J, and Table IWC-2500-1, Examination Categories C-F-1 and C-F-2.
2. Applicable Code Edition and Addenda
The Duane Arnold Energy Center (DAEC) ISi Program for the Fifth lnservice Inspection (ISi) Interval is based on the ASME Boiler and Pressure Vessel Code Section XI, 2007 Edition with the 2008 Addenda as required by 1 OCFR50.55a.
3. Applicable Code Requirement
The selection process for Code Class 1 and Code Class 2 pipe welds to be examined in the Fifth Inspection Interval is required to be prescriptively determined in accordance with ASME Section XI, Table IWB-2500-1, Examination Categories B-F and B-J, and Table IWC-2500-1, Examination Categories C-F-1 and C-F-2.
- 4. Reason For Request Duane Arnold Energy Center is requesting the continued use of a risk-informed process as an alternative for the selection of Class 1 and Class 2 piping welds for examination of the Fifth ISi Interval.
Use of the risk-informed selection process has been shown to reduce the probable frequency of core damage and large early release when compared to the prescriptive deterministic selection method. The methodology will continue to be based on Electric Power Research Institute (EPRI)
Topical Report TR-112657, Rev. B-A, with identified differences and additional guidance taken from ASME Section XI Nonmandatory Appendix R.
5. Proposed Alternative and Basis for Use
In accordance with 1 OCFR50.55a(z)(1 ), Duane Arnold Energy Center requests to continue to use a risk-informed process as an alternative to the ASME Section XI Code requirements for Class 1 and Class 2 piping welds for examination. The risk-informed alternative will continue providing an acceptable level of quality and safety.
Other non-related portions of the ASME Section XI Code will be unaffected. EPRI TR-112657, Rev. B-A provides the requirements for defining the relationship between the RI-ISi program and the remaining unaffected portions of ASME Section XI.
1
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
Background
In 2002, a risk-informed (RI) methodology for the Third Interval inservice inspection of Class 1 and 2 piping welds was applied at the Duane Arnold Energy Center based on EPRI TR-1126S7, Rev. B-A, with identified differences and with additional guidance taken from ASME Code Case N-S78. On March 29, 2002, DAEC submitted a letter to the NRC requesting relief from the ASME Section XI Code examination requirements of Class 1 and 2 piping weld inservice inspections (Examination Categories B-F, B-J, C-F-1 and C-F-2) by implementing a Risk-Informed lnservice Inspection (RI-ISi) Program during their Third Interval. DAEC provided supplemental information in a letter to the NRC dated September 6, 2002.
Relief was granted by the NRC in a Safety Evaluation Report dated January 17, 2003.
In 2006, the RI-ISi application was evaluated and updated as DAEC entered its Fourth Interval. This resulted in the generation of Relief Request NOE-ROOS which addressed the continued use of the RI-ISi application for the Fourth Interval. By letters dated June 30, 2006 and December 21, 2006, DAEC submitted Relief Request NOE-ROOS to the NRC for the continued use of their RI-ISi application in lieu of the ASME Section Code examination requirements for Class 1 and 2 piping welds. Relief Request NOE-ROOS was approved by the NRC in a Safety Evaluation Report dated January 31, 2007.
RI-ISi Living Program Evaluations and Updates The original DAEC RI-ISi Program submittal to the NRC contained the following statement related to the evaluation/update process:
"The RI-IS/ program is a living program requiring feedback of new relevant information to ensure the appropriate identification of high safety significant piping locations. As a minimum, piping segments will be reviewed and Risk Ranking adjusted as necessary on an ASME period basis. In addition, significant RI-IS! changes may require more frequent adjustment as directed by NRG Bulletin or Generic Letter requirements, or by industry and plant specific feedback."
The requirement to perform living program evaluations and updates of the RI-ISi Program on a period basis is still applicable. Guidelines for the performance of these living program evaluations and updates are provided in NEI 04-0S, "Living Program Guidance To Maintain Risk-Informed lnservice Inspection Programs For Nuclear Plant Piping Systems," published April, 2004. In accordance with NEI 04-0S, the following aspects were considered during the periodic reviews for DAEC:
Plant Examination Results Piping Failures Plant Specific Failures 2
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
Industry Failures PRA Updates Plant Design Changes Physical Changes Programmatic Changes Procedural Changes Changes in Postulated Conditions Physical Conditions Programmatic Conditions The updated RI-ISi Program resulting from these periodic reviews is the subject of this proposed alternative. The changes from the previous program are attributable to specific issues(s) identified in each review:
During the review after the First Period of the Fourth Interval, the following summary was published:
The DAEC RI-IS/ application is a Class 1 and 2 only application. As such, it is typical that there are little to no changes required of the program as a result of the update process. This review confirmed this assumption as there were some, but not significant, changes to inputs into the RI-IS/
program. These changes were captured within existing plant programs and processes (e.g., Generic Letter 88-01 program, FAG program) and had no impact on the risk ranking and element selection results.
During the review after the Second Period of the Fourth Interval, the following summary was published:
Based on this RI-ISi Living Program Evaluation, there is no need to update the RI-IS/ Program at this time. However, the interface between weld overlay examinations, /GSCC Program examinations, and RI-IS/ Program examinations should be clarified when the RI-IS/ Program is updated at the end of the Fourth Interval.
3
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
During the review after the Third Period of the Fourth Interval, the following issues were identified and incorporated:
Due to an update to the PRA Model, resulting changes to the Consequence Ranking on 21 Consequence IDs and associated 49 segments were updated in the Risk Ranking, Element Selection, and Risk Impact Analysis.
The Risk Impact Analysis was updated to reflect the new Upper Bound CCDP and CLERP, and the revised Risk Categories.
The susceptibility to crevice corrosion of the Recirculation Inlet nozzles, Feedwater nozzles and Core Spray nozzles was investigated in the RI-ISi Living Program Update. In November 2005, EPRI published Technical Update Report 1011945 which provided enhanced crevice corrosion criteria for RI-ISi evaluations. Applying the criteria in EPRI Report 1011945, crevice corrosion was eliminated as a degradation mechanism in the RI-ISi application for the Recirculation Inlet (N2) and Core Spray (NS) nozzles, but should remain as a degradation mechanism for the Feedwater (N4) nozzles.
The existing Risk Ranking Report was updated to a more efficient "one weld per line" format and Risk Groups were assigned. A Risk Group is defined as all welds in the same system that has the same Risk Category and Degradation Mechanism.
ASME Section XI Nonmandatory Appendix R was used for guidance to supplement EPRI Topical Report TR-112657 Rev. B-A instead of Code Case N-578.
As a result, the Risk Ranking Report was updated to replace the superseded Code Items Numbers originally assigned per Code Case N-578 with the Code Item Numbers identified in ASME Section XI, Nonmandatory R.
The interface between weld overlay examinations, IGSCC Program examinations, and RI-ISi Program examinations was clarified as follows:
Welds under the weld overlays have been removed from the RI-ISi Program and are examined as part of the weld overlay examination. The listing of these overlaid welds has been retained in the Risk Ranking to acknowledge their existence, but they are not selected or examined under the RI-ISi application. They have been assigned a RI-ISi Item No. of AUG-NRG in the Risk Ranking to indicate that they are being examined under Generic Letter 88-01 with a frequency specified by BWRVIP-75-A rather than the RI-ISi Program.
IGSCC Category "A" welds in the IGSCC Program, as defined in BWRVIP A, are subsumed by the RI-ISi Program.
Examinations of IGSCC Category "B" through "E" welds remain governed by the IGSCC (BWRVIP-75-A) Program. However, these welds remain listed in the population of the RI-ISi Program and are evaluated for susceptibility to degradation mechanisms in addition to IGSCC.
These welds may be examined concurrently for both the IGSCC Program and the RI-ISi Program.
4
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
Risk Impact Analysis All issues identified in the periodic reviews have been incorporated into the Risk Ranking, Summary, and Matrix. Limits are imposed by the EPRI methodology to ensure that the change in risk of implementing the RI-ISi Program meets the requirements of Regulatory Guides 1.17 4 and 1.178. The EPRI criterion requires that the cumulative change in core damage frequency (CDF) and large early release frequency (LERF) be less than 1 E-07 and 1 E-08 per year per system, respectively.
A new Risk Impact Analysis was performed, and the revised program continues to represent a negligible change in risk when compared to the last deterministic Section XI inspection program. The revised program continues to be less than the EPRI criterion with a total change in plant risk of 4.34E-09 in regards to CDF and 4.30E-09 in regards to LERF.
As indicated in the following table, this evaluation has demonstrated that unacceptable risk impacts will not occur for any system from implementation of the RI-ISi Program when the enhanced Probability of Detection (POD) is credited for the RI-ISi examinations as prescribed in (EPRI) Topical Report TR-112657, Rev. 8-A.
Risk Impact Results ARiskcoF ARiskLERF System w/POD w/o POD w/POD w/o POD 01RPV
-1.50E-11
-1.50E-11
-1.50E-11
-1.50E-11 02RCR 2.34E-09 1.30E-08 2.34E-09 1.30E-08 03RWCU 6.90E-11 8.50E-11 7.44E-11 7.60E-11 04RCIC
-1.50E-11
-1.50E-11
-1.50E-11
-1.50E-11 05RHR 6.45E-10 3.41 E-09 5.91E-10 3.24E-09 06CS 3.15E-10 3.15E-10 3.15E-10 3.15E-10 07HPCI 3.45E-10 3.45E-10 3.45E-10 3.45E-10 08MS 2.85E-10 2.85E-10 2.85E-10 2.85E-10 09FW 4.05E-10 4.15E-09 4.05E-10 4.13E-09 10CRD
-1.50E-11
-1.50E-11
-1.50E-11
-1.50E-11 11SLC
-1.50E-11
-1.50E-11
-1.50E-11
-1.50E-11 Total 4.34E-09 2.15E-08 4.30E-09 2.14E-08 5
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
Augmented Examination Programs The following augmented inspection programs were considered during the RI-ISi application:
DAEC applies the BWRVIP-75-A "Technical Basis for Revision to Generic Letter 88-01 Inspection Schedules", which provides alternative frequency requirements to NRC Generic Letter 88-01 for the examination of welds subject to intergranular stress corrosion cracking (IGSCC). Generic Letter 88-01 and BWRVIP-75-A will be implemented concurrently with the RI-ISi Program for the examination of piping welds that are subject to IGSCC. Generic Letter 88-01 specifies the examination extent and BWRVIP-75-A specifies the frequency requirements for austenitic stainless steel welds that are classified as Categories "A" through "G", depending on their susceptibility to IGSCC. In accordance with (EPRI) Topical Report TR-112657, Rev. B-A, piping welds identified as Category "A" are considered resistant to IGSCC, and as such are assigned a low failure potential provided no other damage mechanisms are present. The augmented inspection program for the other piping welds subject to IGSCC is not affected by the RI-ISi submittal.
The augmented examination program for flow accelerated corrosion (FAC) per Generic Letter 89-08 is relied upon to manage this damage mechanism but is not otherwise affected or changed by the RI-ISi program.
Additional Examinations Whenever RI-ISi examinations reveal flaws or relevant conditions exceeding acceptance standards, additional examinations shall be performed during the current outage using the criteria of ASME Section XI, Nonmandatory Appendix R, Section R-2430.
Living Program Requirements The RI-ISi program is a living program requmng feedback of new relevant information to ensure the appropriate identification of high safety significant piping locations. As a minimum, risk ranking of piping segments will be reviewed and adjusted on an ASME period basis. In addition, significant changes may require more frequent adjustment as directed by NRC Bulletin or Generic Letter requirements, or by industry and plant specific feedback.
Proposed RI-ISi Program Change Request DAEC requests to resubmit their RI-ISi application in accordance with 1 OCFR50.55a(z)(1 ). A comparison between the proposed RI-ISi Program and the previously approved RI-ISi Program is provided in Attachment 1. Per the RI-ISi Program, 11 % of Class 1 welds have been selected for examination.
6
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
Examinations shall be performed during the interval such that the period examination percentage requirements of ASME Section XI, paragraphs IWB-2412 and IWC-2412 are met.
The Risk-Informed process continues to provide an adequate level of quality and safety for selection of the Class 1 and Class 2 Piping Welds for examination.
Therefore, pursuant to 1 OCFR50.55a(z)(1) it is requested that the proposed alternative be authorized.
7. Duration of Proposed Alternative
The alternative will be used at DAEC until the end of the Fifth Ten-Year ISi Program Inspection Interval, subject to the review and update guidance of NEI 04-05. The Fifth Inspection Interval is currently scheduled to end October 31, 2026.
8. Precedents
- 1. Duane Arnold Energy Center - Risk-Informed lnservice Inspection Program SER dated January 17, 2003 (ADAMS Accession No. ML023530046).
- 2. Duane Arnold Energy Center Fourth Interval RI-ISi Relief Request NDE-R005 was authorized per NRC SER dated January 31, 2007 (ADAMS Accession No. ML070090357). This relief request utilized a similar methodology to the previously approved relief request.
- 9. References
- 1. Electric Power Research Institute (EPRI) Topical Report (TR) 112657, "Revised Risk-Informed lnservice Inspection Evaluation Procedure," Rev. B-A, dated December 1999.
- 2. Letter from W.H. Bateman (NRC) to G.L. Vine (EPRI), "Safety Evaluation Report Related to EPRI Risk-Informed lnservice Inspection Evaluation Procedure (EPRI TR-112657, Revision B, July 1999)," dated October 28, 1999 (ADAMS Accession No. ML993190460 and ML993190474).
- 3. NEl-04-05, "Living Program Guidance to Maintain Risk-Informed lnservice Inspection Programs for Nuclear Plant Piping Systems," dated April 2004.
- 4. NRC Regulator Guide 1.200, "An Approach for Determining the Technical Adequacy of Probabilistic Risk Assessment Results for Risk-Informed Activities,"
Revision 2, dated March 2009 (ADAMS Accession No. ML090410014).
7
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
- 10. Attachments -
DAEC Inspection Location Selection Comparison Between Previously Approved and Revised RI-ISi Program by Risk Category -
DAEC PRA Model Quality Summary 8
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed)
DAEC Inspection Location Selection Comparison Between Previously Approved and Revised RI-ISi Program by Risk Category Risk Failure Potential Previously Approved Updated System Consequence (Fourth Interval)
(Fifth Interval)
Category Rank Rank DMs Rank Weld Rl-151 Other<2J Weld Count<1l Rl-151 Other<2l Count<1l 2
High High TASCS Medium N/A<3l N/A(3J 5
02RCR 2 (2)
High (High)
High TT, (IGSCC)
Medium (Medium) 69 16 56 22 2 (2)
High (High)
High TT, CC, Medium (Medium) 8 N/A(4J N/A(4)
(IGSCC) 2 High High TT Medium 10 10 05RHR 3
4 2 (2)
High (High)
High TT, (IGSCC)
Medium (Medium) 4 4
2 (1)
High (High)
High TASCS,CC Medium (High) 12 12 09FW 2 (1)
High (High)
High TASCS, (FAC)
Medium (High) 3 11 3
6 2 (1)
High (High)
High TASCS, TT, Medium (High) 8 8
(FAC) 06CS 2 (2)
High (High)
Medium (Medium) 2 1
N/A(4l N/A(4J 01RPV 4
Medium High None Low N/A(3l N/A(3J 17 2
4 Medium High None Low N/A(3l N/A(3J 43 02RCR 11 4 (2)
Medium (High)
High None (IGSCC)
Low (Medium) 34 6
60 4
Medium High None Low N/A(3)
N/A(3) 23 03RWCU 3
4 (2)
Medium (High)
High None (IGSCC)
Low (Medium) 1 1
5 04RCIC 4
Medium High None Low N/A(3l N/A(3J 7
1 4
05RHR Medium High None Low 5
27 2
3 4 (2)
Medium (High)
High None (IGSCC)
Low (Medium) 2 2
4 Medium High None Low 16 46 06CS 8
3(5) 4 (2)
Medium (High)
High None (IGSCC)
Low (Medium) 6 8
1
Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed) (Cont'd)
DAEC Inspection Location Selection Comparison Between Previously Approved and Revised RI-ISi Program by Risk Category Risk Failure Potential Previously Approved Updated System Consequence (Fourth Interval)
(Fifth Interval)
Category Rank Rank DMs Rank Weld RI-ISi other2>
Weld Count<1>
RI-ISi other2>
Count<1>
07HPCI 4
Medium High None Low 52 6
52 6
08MS 4
Medium High None Low 60 6
60 6
09FW 4 (1)
Medium (High)
High None (FAC)
Low (High) 49 5
49 5
10CRD 4
Medium High None Low 2
1 8
1 11SLC 4
Medium High None Low 6
0 24 1(5) 02RCR 5a Medium Medium TASCS Medium 5
0 N/A13>
N/A<3>
03RWCU 5a Medium Medium TT Medium 2
0 2
1 05RHR 5a Medium Medium TT Medium 33 0
33 4
09FW 5a (3)
Medium (High)
Medium TASCS (FAC)
Medium (High) 4 1
4 1
6a Low Medium None Low 27 10 01RPV 6a (5a)
Low (Medium)
Medium None (IGSCC) 0 0
Low (Medium) 4 4
6a Low Medium None Low 43 N/A<3>
N/A<3>
02RCR 0
6a (5a)
Low (Medium)
Medium None (IGSCC)
Low (Medium) 26 6a Low Medium None Low 26 3
03RWCU 0
0 6a (5a)
Low (Medium)
Medium None (IGSCC)
Low (Medium) 23 9
04RCIC 6a Low Medium None Low 29 0
22 0
6a Low Medium None Low 431 409 0
05RHR 0
N/A<3l N/A<3>
6a (5a)
Low (Medium)
Medium None (IGSCC)
Low (Medium) 1 06CS 6a Low Medium None Low 158 0
106 0
07HPCI 6a Low Medium None Low 98 0
107 0
6a Low Medium None Low 184 185 08MS 0
0 6a (3)
Low (High)
Medium None (FAC)
Low (High) 7 5
2
System 09FW 10CRD 11SLC 02RCR 03RWCU 04RCIC 06CS 07HPCI 08MS 10CRD 11SLC Duane Arnold Energy Center 1 OCFR50.55a Request Number RR-05 (Risk-Informed) (Cont'd)
DAEC Inspection Location Selection Comparison Between Previously Approved and Revised RI-ISi Program by Risk Category Risk Failure Potential Previously Approved Updated Consequence (Fourth Interval)
(Fifth Interval)
Category Rank Rank DMs Rank Weld RI-ISi Other(2l Weld Count(1J RI-ISi Other(2l Count(1l 6a (3)
Low (High)
Medium None (FAC)
Low (High) 5 0
6 0
6a Low Medium None Low 60 0
39 0
6a Low Medium None Low 27 0
N/A(3l N/A(3l
?a Low Low None Low 4
0 4
0
?a Low Low None Low 2
0 2
N/A(3l N/A(3l 0
?a (6b)
Low (Low)
Low None (IGSCC)
Low (Medium) 10
?a Low Low None Low 12 0
12 0
?a Low Low None Low N/A(3l N/A(3l 22 0
?a Low Low None Low 21 0
12 0
?a (5b)
Low (Medium)
Low None (FAC)
Low (High)
N/A(3l N/A(3l 2
0
?a Low Low None Low N/A(3l N/A(3l 15 0
?a Low Low None Low N/A(3l N/A(3l 9
0 NOTES:
- 1.
The total weld count is less in the Fifth Interval than in the Fourth Interval due to welds under weld overlays being removed from the RI-ISi Program and examined as part of the weld overlay examinations.
- 2.
The column labeled "Other" is generally used to identify augmented inspection program locations that are credited beyond those locations selected per the RI-ISi process, as addressed in Section 3.6.5 of EPRI TR-112657 Rev. B-A. This option was not applicable for the DAEC RI-ISi application. The "Other" column has been retained in this table solely for uniformity purposes with other RI-ISi application template submittals.
- 3.
The Not Applicable "N/A" is the result of changes resulting from the RI-ISi Program Living Program Evaluation and Update performed after the Third Period of the Fourth Interval as described within this relief request. In these instances a change to the Consequence Rank or Failure Potential resulted in the overall Risk Ranking changing within the associated system.
- 4.
In the Fifth Interval update, Crevice Corrosion (CC) is not applicable in these two systems. The associated nozzles screened out per EPRI document 1011945, "Enhanced Crevice Corrosion Criteria in RI-ISi Evaluations", dated November2005.
- 5. The SLC system only has one (1) circumferential weld, which was selected for examination in the Fifth Interval. Two (2) circumferential welds in the CS system were selected in lieu of two (2) additional socket welds in the SLC system to improve the robustness of the Fifth Interval RI-ISi selections. All associated welds are Class 1 with a Risk Category of 4.
3 DAEC PRA Model Quality Summary The PRA model quality summary addresses (1) the peer review summary and F&O finding status for internal and flood initiating events, and (2) model change database (MCDB) open items. Based on review of peer review finding resolutions and MCDB open items, the DAEC PRA model is of sufficient quality to support the RI-ISi consequence evaluation.
Internal Events Peer Review Summary The PRA model utilized for the evaluation of risk impact is the DAEC Full Power Internal Events Revision 7 model of record. The model includes analysis of both Core Damage Frequency (CDF) and Large Early Release Frequency (LERF), and includes changes made to incorporate findings and observations of the most recent PRA peer review. The review was performed against the ASME PRA Standard and Regulatory Guide 1.200.
The DAEC Internal Events PRA model is maintained and upgraded in accordance with DAEC PRA maintenance and update procedures. The model routinely incorporates plant design changes, procedure changes, plant operating data, current industry PRA methods, review comments, and general improvements identified by the NRC. The PRA has undergone a variety of assessments of its technical capability, as summarized in the following paragraphs.
DAEC was the first non-pilot plant to have a PRA Peer Evaluation in 1997. The PRA certification process used a team of experienced PRA and system analysts to provide both an objective review of the PSA technical elements and a subjective assessment based on their PRA experience regarding the acceptability of the PRA elements.
During 2005 and 2006, the PRA model results were evaluated in the BWR Owners' Group (BWROG)
PRA cross-comparisons study performed in support of implementation of the mitigating systems performance indicator (MSPI) process.
Following issuance of the ASME PRA Standard and its endorsement by the NRC in RG 1.200 Rev. 1, DAEC performed a detailed self-assessment of the DAEC PRA model and documentation in preparation for the BWROG PRA Peer review in the fall of 2007.
In December 2007, a peer review was held at the NextEra Energy offices in Juno Beach, FL, under the auspices of the BWROG and using the NEI 05-04 PRA Peer Review process. This was a full-scope review of all the Technical Elements of the internal events, at-power PRA. Approximately 83 supporting requirements were identified for which potential gaps to Capability Category II existed. The PRA model was revised to address these gaps.
In March 2011, a focused PRA Peer Review was held at the NextEra Energy offices.
Technical elements of the internal events, at-power PRA were reviewed with a focus on
DAEC's disposition of findings and suggestions as a result of the Full Scope Peer Review conducted in 2007. The peer review team determined that a review of all supporting requirements for the Human Reliability Analysis technical element was needed since it involved a broad based change in methodology for calculating human error probabilities. Other upgrades received enhanced attention by the review team, but did not require rereview of all supporting requirements within the respective technical element category. These included use of the Alpha Factor Method for calculating common cause factors, use of convolution methods for calculating AC power recovery terms, incorporation of revised pipe break frequency data to differentiate between steam line breaks and water line breaks, and incorporation of new internal flood frequency data. The set of supporting requirements that needed to be reviewed for each technical element was determined by the peer review team consistent with ASME/ANS Standard RA-Sa-2009. In summary, the 2011 Focused Peer Review entailed a comprehensive review of all PRA upgrades, updates and previous F&Os and is considered to be the Internal Events PRA Peer Review of record.
The full scope PRA Peer Review conducted in 2007 used version RA-Sb-2005 of the ASME Standard as endorsed and clarified by the NRC in Regulatory Guide 1.200, Revision 1. The focused scope peer review conducted in March 2011 focused PRA Peer Review utilized version RA-Sa-2009 of the ASME Standard as endorsed and clarified by the NRC in Regulatory Guide 1.200, Revision 2.
Internal Events F&O Impact Summary The Focused Peer Review team found that NextEra Energy had appropriately incorporated most of the previously identified gaps into Revision 6 of the PRA.
However, not all of the closures were found to fully meet Capability Category I or Capability II requirements. Twelve findings were identified. All of these findings have been addressed and are summarized in Table C-1 for completeness. Given that all findings are addressed, there is no impact on the quantitative risk results and PRA conclusions of the RI-ISi consequence evaluation.
2
Table C-1 SY-A3-03A The remarks made by the previous peer review under finding SY-A3-03 are still open and still valid. Failure of either vital 4kV bus Start Up Transformer (SUT) breaker, 1A302 [1A402]. to trip on LOSP is not modeled - this failure would prevent associated EOG breaker from closing onto the bus. Omission of this is nonconservative. The model should include the necessary dependencies for this event.
Specifically, the fault tree model omits a dependency; the failure of the normal supply breaker to each vital 4kV bus to trip upon a loss of offsite power to allow the associated EOG to close onto the bus. More importantly, a common cause failure between the two breakers for the two busses is omitted. This CCF may contribute significantly to SBO sequences. Also, not modeling these breakers will have an impact on the fire model.
RECOMMENDATION: These components should be modeled to remove nonconservatism and to address future PRA a lications.
SY-C2-02A There are no system level cutsets included in the notebooks and as such no evidence that the system models were evaluated to validate they are complete and accurate [i.e. a description of model results]. Based on discussions with DAEC, system level cutsets were reviewed to validate the models, however the results of the review were not documented and the system level cutsets were not included in the notebooks.
RECOMMENDATON: Include system level cutsets in the system notebooks along with an assessment.
DA-C10-01A No evidence of failure mode level information is provided. This requires documentation of a review of test procedures to determine that test covers all failure modes of a component. For example, a check associated with a pump may or may not be cycled based on the recirculation configuration.
RECOMMENDATION: Address this issue by component type (e. g. pump test likely covers all pump failure modes but not failure modes of all downstream valves.
DA-D4-01A Appendix C.1 provides graphs of prior and posterior distributions; however, there is no discussion of the reasonableness of the posterior. For example, for TC AS1 K FR has a prior mean of 9 E-5 with evidence of 3 failures in 544. It appears that the data is inconsistent with the rior.
MU-F1-01 Update PRA procedures to meet all MU SRs.
IE-B3-01A Several findings and suggestions under HLR-A and HLR-B have been dispositioned I resolved, but the subsuming (IE-B3) and screening (IE-C4 (C6)) of initiating events does not meet the standard. The following provides example summarizes (IE Notebook, including Appendix H):
RBCCW (fails CRD, which is credited for early injection) is subsumed by TT, but RBCCW is not failed given TT.
GSW fails RBCCW, CRD, Feedwater, Supporting requirement SY-A3 was assessed as MET in the 2011 focused peer review. This associated finding was closed by adding startup transformer breakers 1A302 and 1A402 to the PRA model. The change includes new random and CCF basic events for these breakers.
D4160VENCB1A302-FO--
CCF-CKTB-D4160-FT0_1_2 Breakers 1A302 and 1A402 are described in the AC Power System Notebook, Revision 4.
Supporting requirement SY-C2 was assessed as MET in the 2011 focused peer review. To address this associated finding, system cutsets were prepared and reviewed. As a result, several changes were made to the Revision 6 model and documented in supplements to the PRA notebooks.
Supporting requirement DA-C10 was assessed as MET CC I in the 2011 focused peer review. To address this associated finding, test procedures were reviewed against their related component failure modes. The assumed failure modes for components were found to be covered. No changes to the PRA model were required. The evaluation is documented in Supplement 2 to the DAEC PRA Data Analysis Notebook.
Supporting requirement DA-04 was assessed as MET CC I in the 2011 focused peer review. To address this associated finding, the reasonableness of the prior and posterior distributions was reviewed; it was concluded no model changes were required. The evaluation is documented in Supplement 1 to the DAEC PRA Data Analysis Notebook.
Fleet procedure EN-AA-105-1000, "PRA Configuration Control and Model Maintenance" has been developed to meet all MU su ortin re uirements for Ca abilit Cate o 1111/111.
Supporting requirement IE-B3 was assessed as NOT MET in the 2011 focused peer review. To address this associated finding, support system initiating event fault trees listed in the finding--with the exception of Reference and Variable Leg Breaks and RBCCW--were developed and incorporated into the Rev 7 model.
Reference and Variable Leg Breaks:
were left as an open item needing additional review. The following provides the basis justifying deferral:
Using the Rev 7 model, the conditional core damage 3
Table C-1 etc.) is subsumed by TC, but these systems are not failed given TC.
The impacts of Reference and Variable Leg Breaks are not adequately described and are subsumed by Loss of FW. Most likely would be a manual shutdown with complications verses a Loss of FW. Given that immediate shutdown would occur given a break, these should be modeled.
Section 2.4.8 described the low risk from these, but this does not meet standard for screening.
1A1/1A2 bus failures and partial loss of feedwater (one pump) are binned to TT, but this impact is not modeled given TT.
1A3/1A4 bus failures are subsumed with TT. Impact on loss of chargers [TS 3.8.4.]
etc. and possibility that failure is a problem could lead to an immediate shutdown.
Notes 11 and 12 suggest that only normal power source is lost, but emergency power is also unavailable if bus fails.
RECOMMENDATION: Follow IE-B3 and IE-C6 with regard to subsuming and screening or more importantly model the above initiating events.
SY-A5-01A The SBO event tree does not take credit for containment venting using an alternate alignment when the pneumatic supply is lost.
DAEC procedure SAMP 706 provides detailed direction for venting PC given an unavailable pneumatic supply. The Containment Vent notebook does not credit/discuss this procedure.
RECOMMENDATION: Add containment ventin to the event tree.
SY-C2-01A There is no Fire Water System (Alternate Injection) notebook or equivalent information in another notebook. The operator action to align fire water for injection is modeled but the components are based on the argument that the probability of the action subsumes the component failure rates.
RECOMMENDATION: Develop new system notebook for use of fire water as an alternate in*ection source.
HR-A1-01A HRA Notebook (Appendix J, Table J-1) includes a systematic approach to identifying test and maintenance activities through a system by system review of potential misalignments. This meets the high level requirement to use a "systematic approach" and is judged to be adequate by the Peer Review team. However, the SR wording requires "a review of procedures and practices" which was not followed. As a result, the PR team must assess this SR as "not met."
RECOMMENDATION: Reassess this SR when the Addendum B of the PRA Standard is released. The current proposed revision deletes the requirement for "a review of rocedures and ractices".
HR-A2-01A HRA Notebook (Appendix J, Table J-1) includes a systematic approach to identifying calibration activities through a system by system review of potential miscalibrations. This meets the hi h level re uirement to use a probability (CCDP) was calculated assuming a plant trip and loss of FW, HPCJ, and RCIC. The resulting CCDP was 2.60E-
- 5. The CDF is 1.34E-4/yr x 2.6E-5 = 3.5E-09/yr (0.12% of the Rev. 7 PRA CDF). However, there are conservative factors inherent in these bounding values; Operators may detect a leak and take corrective actions before the second leak occurs. Note that the frequencies used are yearly. Two leaks must occur in close proximity of each other to result in a plant trip.
Breaks are less likely than leaks -mitigation of leaks will likely be successful.
Factors that lead to two lines failing concurrently most likely result from a more significant initiating event.
RBCCW: An initiator fault tree was developed but not included in the model. It is planned to be added in a future revision. The impact of the RBCCW is not significant since GSW fails RBCCW. The GSW initiator is in the model.
Supporting requirement SY-A5 was assessed as MET in the 2011 focused peer review. To address this associated finding, fault tree logic was developed for venting the primary containment using SAMP 706. The logic was incorporated into the Revision 7 PRA update.
Supporting requirement SY-C2 was assessed as MET in the 2011 focused peer review. To address this associated finding, new HEPs for aligning the in-situ diesel and electric fire pump were updated and failure rates for key components were added. A fire water notebook was prepared but still needs to be reviewed and approved.
Addendum B of the PRA Standard has not yet been released.
The approach used in the DAEC PRA was different than currently prescribed in the standard, but is considered capable of accurately identifying pre-initiators. As such this variance from the standard has no impact on this application.
Supporting requirement HR-A1 was assessed as NOT MET in the 2011 focused peer review.
Addendum B of the PRA Standard has not yet been released The approach used in the DAEC PRA was different than currently prescribed in the standard, but is considered capable of accurately identifying pre-initiators. As such this variance 4
Table C-1 "systematic approach" and is judged to be adequate by the Peer Review team. However, the SR wording requires "through a review of procedures and practices" which was not followed. As a result, the PR team must assess this SR as "not met."
RECOMMENDATION: Reassess this SR when the Addendum B of the PRA Standard is released. The current proposed revision deletes the requirement for "a review of rocedures and ractices".
HR-C1-01A FINDING HR-C1-01A: A number of pre-IE HFEs are identified for modeling in the PRA.
Generally, these HFEs are at the train or system level, as appropriate. However, a small set were identified at the system level without related train-level HFEs. It is possible that the train level HFE may be important to system unavailability. For example, miscalibration of DG fuel oil level transmitters is done at the system level, but not at the train level. At the train level, the HFE would be Se-3, compared with independent failure of the level transmitter of Se-4. In other cases, the HFE is at the train level, but no corresponding system level dependent HFE is included. For example, failure to restore RHR SW post TM is developed at the train level, but no common misalignment of both trains is considered.
RECOMMENDATION: Review the differences between the modeling of system impact vs train.
QU-D6-01A Table P-1 and P-2: plant position is that initiating event fault trees are not required by the standard (IE) and therefore equipment level of detail is not available or required to meet this SR. A future enhancement has been identified to document in the notebooks the importance of operator actions in support system initiating events, but is awaiting industry clarification.
Fault trees are required for support system initiating events in order to satisfy this SR.
RECOMMENDATION: Fault trees are required for support system initiating events in order to satis this SR Cat II].
Model Change Database Impact Summary Supporting requirement HR-A2 was assessed as NOT MET in the 2011 focused peer review.
Supporting requirement HR-A1 was assessed as NOT MET in the 2011 focused peer review. To address this associated finding, train level preinitiating event HFEs were added to the Revision 7 PRA.
Supporting requirement QU-D6 was assessed as MET CC I in the 2011 focused peer review. To address this associated finding, fault trees for support system initiating events have been developed and incorporated into the Revision 7 PRA as discussed in the description of resolution for finding IE-B3-01A.
The DAEC Full Power Internal Events PRA was recently updated from Revision 6 to Revision 7.
The DAEC PRA model change database was reviewed for potential impacts of open items on the RI-ISI consequence evaluation (Table C-2). In addition, plant modifications assessed as potentially having a PRA impact were reviewed (Table C-3). There are no open items that are judged have a substantial impact on the RI-ISI evaluation.
5
Table C-2 Ii ';:!*>*:
.¢ql1c~J"-'"
<stall*~
t:sti~a,t~~~f-151t.
'~~m ** p:;:
1,1
~.. *,:>
.~;l:c~~.- ;; *... *;*,;i*
'.;ijQ~ ;. 1,* {:;
- 1* *.*.:
.*. v.!.'!:,., E~ *... /(JJ;0 I**.*
Impact *.
1 Shutdown Cooling added to various event Shutdown cooling is trees.
incorporated into the Revision 7 PRA 2
RHR Containment Spray Heat Removal (CSS)
Containment Spray valves are added to various event trees.
added to suppression pool cooling fault tree logic in the Revision 7 PRA 3
Power Conversion System Recovery (PCSR)
Deferred to future update This item was considered for added to various event trees. See new basic consistency with the NRC SPAR event called PCSR-F.
model only and not for addressing plant modifications or procedures.
Therefore, there is no impact on the RI-ISi aoolication 4
Main Condenser Available (0) added to IORV Top event CNDSR is added to and Small LOCA event trees to be consistent various event trees in the with SPAR. See top event CNDSR.
Revision 7 PRA 5
Feedwater/Condensate for High Pressure Node 01 is included in large Injection (01) added to large LOCA event LOCA event trees in the trees.
Revision 7 update 6
Early and late flooding HEP logic and recovery Incorporated into the Revision rule changes.
7 update 7
Turbine building flood impact on Startup Top event Transformer.
TB_FLOOD_SU_XNSFMR was added under gate P1 01 in the Revision 7 PRA to address this issue 8
TSC Fails to use EMG and identify need for Incorporated into the Revision SAMPs.
7PRA 9
Operator Fails to identify EAL or Identify need Incorporated into the Revision for EMG and SAMPs.
7PRA 10 SAMP 701 - Bypass of PCIS Group 4 SOC Incorporated into the Revision isolation from high drywell pressure and low 7PRA RPV water level.
11 SAMP 702 -Alternate water source for SBDG Incorporated into the Revision cooling.
7PRA 12 SAMP 703 - Operators fail to locally start RCIC Incorporated into the Revision with no DC power. Actions associated with 7PRA SAMP 703 are added to RCIC components.
13 SAMP 704 - Powering 125 VDC battery Incorporated into the Revision chargers from a portable generator. Includes 7PRA failure of TSC to identify need for implementing the SAMP.
14 SAMP 705 - Powering non-essential 480 VAC Incorporated into the Revision bus using offsite diesel generator. This action 7PRA allows the Electric Fire Pump to be used for alternate RPV injection per AIP-404.
15 SAMP 706 - Venting the primary containment Incorporated into the Revision when pneumatic supply or DC power for the 7PRA primary containment vent valves is not available.
16 SAMP 707 - Depressurizing the RPV when Incorporated into the Revision normal DC power is unavailable or when 7PRA operation from the control room and/or remote shutdown panel is not available.
17 SAMP 708 - Injecting water into the RPV using Incorporated into the Revision the Portable Diesel Fire Pump (PDFP). See 7PRA also SAMP 715.
18 SAMP 709 - Supplying makeup water to the Logic is added under gate 01-Impact of this severe accident hotwell with the Portable Diesel Fire Pump 14-10 per section 1.2.11, but management procedure on the RI-(PDFP).
only an undeveloped basic ISi application is judged to be very event small. The current PRA is conservative with respect to this item.
19 SAMP 71 O - Transferring water from the Circ Deferred to future update Impact of this severe accident Pit to the CSTs using the PDFP.
management procedure on the RI-ISi aoolication is iudaed to be verv 6
20 21 22 23 24 25 26 27 28 29 30 Table C-2 SAMP 711 - Supplying water for cooling of core Deferred to future update debris and scrubbing of fission products.
SAMP 712 - Supplying makeup greater than Not applicable to the FPIE 500 gpm or spray greater than 200 gpm to the PRA spent fuel pool.
SAMP 713 - Spraying of reactor building or Deferred to future update primary containment to reduce the magnitude of fission product releases.
SAMP 714 - Manually isolating RWCU to Deferred to future update minimize risk of LOCA outside containment and resultant fission product release.
SAMP 715 - Staging and operating guidance for the PDFP.
SAMP 716 - Initial actions for responding to an extreme damaging event with loss of the control room command and control function.
SAMP 717 - Supplying cooling water from an available ESW pump to the opposite loop.
Incorporate new operator action to address giving the operators a second change at emergency depressurization. Applies to late alternate injection in Station Blackout se uences.
Incorporate new operator action to address giving the operators a second change at emergency depressurization. Applies to late alternate injection in Station Blackout se uences with no DC ower.
Add strainer bypass function for ESW, RHRSW, and GSW strainers.
Improve modeling of operator actions in response to ECCS suction strainer blockage.
Suggestions include 1) backflushing of ECCS strainers, 2) aligning core spray suction to the CSTs, and 3) crediting CST to hotwell makeup in water-LOCA se uences. See also Item #55 Incorporated into the Revision 7 PRA in conjunction with SAMP708 Deferred to future update Deferred to future update Operator action DADS--
ANOPSB001-HE-has been added to assessment of Station Blackout sequences in the Revision 7 PRA Operator action DADS--
ANOPSP707-HE-has been added to assessment of Station Blackout sequences in the Revision 7 PRA Incorporated into the Revision 7PRA Improvements 1) and 2) are incorporated into the Revision 7 PRA. Improvement 3) is deferred 31 Improve modeling of flood induced failure of the Incorporated into the Revision diesel fire pump, the electrical fire pump, and 7 PRA the ortable diesel fire um.
32 Improve modeling of injection with fire water Incorporated into the Revision durin station blackout.
7 PRA 33 Update PRA with changes made to EOOS in Incorporated into the Revision January 2014. These are 1) correct modeling of 7 PRA switchyard breakers J and K, 2) add 36 KV breaker CB5960 as an alternate power supply to LLRPSF transformers XR1 and XR2, 3) Add 161 KV breakers CB7510, CB5950, CB8090, 7
Estift1Ci!~cJ,~.1;.ISL..
- lmpe1~t.
small. The current PRA is conservative with respect to this item.
Impact of this severe accident management procedure on the RI-IS! application is judged to be very small. The current PRA is conservative with respect to this item.
Not applicable Impact of this severe accident management procedure on the RI-ISi application is judged to be very small. The current PRA is conservative with respect to this item.
Impact of this severe accident management procedure on the RI-ISi application is judged to be very small. The current PRA is conservative with respect to this item.
Impact of this severe accident management procedure on the RI-ISi application is judged to be very small. The current PRA is conservative with respect to this item.
The Revision 7 PRA is conservative for the RI-ISi application with respect to this item. Incorporating SAMP 717 would lower importance measures for i e segments The Revision 7 PRA is conservative for the RI-ISi application with respect to this item. Crediting CST to hotwell makeup would lower importance measures for i e se ments
Table C-2 lt~ffi
,/.
i~,...
~.~
~_:~::x <:
<'.~~~d,~~"f~ !:;/* :;::;;;;,
- ~~ ;.>.,
- ; ; ' '?
'estirnate~R1-is1.
- ~*
- j*~~]*
- ***.z*,
- - *T;;itTll~
~JR8~.
.:.1!;.:~~!:,t:z;r; "' * :~3~:cz: '5~~ ~f
- !~~ti
- . y
~. x Impact
- J '..*
,; ** y
- 'i. ;'.;'.!*.* ;,;,:; ;
and CB9180 to the switchyard fault tree, 4) add strainer bypass valve V46-0009 to the GSW svstem fault tree.
34 Update PRA with a change made to EOOS in Incorporated into the Revision July 2014 to correct high CDF value with both
?PRA EDG and the startup transformer out-of-service.
35 Consider revising credit for EDG recovery (SDP Incorporated into the Revision related chanae: section 5.0)
?PRA 36 Develop a diesel fire water notebook that Deferred to future update EOP updates which extend RPV includes a basis for crediting successful injection options in Station Blackout application of the diesel fire pump or portable sequences were implemented after diesel fire pump before 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (SDP related the Revision 7 PRA update freeze change: section 5.0) date. The changes however, are expected to be conservative with respect to pipe segment importance measures for RI-ISi 37 Develop a TSC notebook that includes a basis Deferred to future update OP updates which extend RPV for crediting successful applications of the TSC injection options in Station Blackout diesel for more than 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (SDP related sequences were implemented after change: section 5.0) the Revision 7 PRA update freeze date. The changes however, are expected to be conservative with respect to pipe segment importance measures for RI-ISi 38 Incorporate FLEX improvements in the ED Deferred to future update OP updates which extend RPV procedure to clearly define the option to extend injection options in Station Blackout RCIC operation beyond 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (SDP related sequences were implemented after change: section 5.0) the Revision 7 PRA update freeze date. The changes however, are expected to be conservative with respect to pipe segment importance measures for RI-ISi 39 Consider revising credit for AC power recovery Incorporated into the Revision (SDP related chanae: section 5.0l
?PRA 40 Review Rev 6 system cutsets with more than Incorporated into the Revision one maintenance basic event to assess
?PRA inclusion in the CAFTA mex file. See Item #56 41 Update the SBO event tree structure to 1) take Deferred to future update The Revision 7 PRA is credit for containment venting with alternate conservative for the RI-ISi external make-up as a success path, 2) take application with respect to this credit for portable diesels that will improve the item. Incorporating the suggested reliability of long term DC power during a FLEX improvements would lower station blackout (FLEX), and 3) accommodate importance measures for pipe other FLEX improvements such as portable segments diesel pumps for low pressure injection, etc.
42 Modify top event TSC in the SBO event tree to Incorporated into the Revision include both the TSC diesel and the portable
?PRA diesel aenerator under an AND aate.
43 Modify top event V1 in the SBO event tree to 1)
Incorporated into the Revision include diesel fire pump failure modes, 2)
?PRA correct the portable diesel fire pump model, 3) re-assess use of human action basic events for aligning the diesel fire pump and the portable diesel fire pump, and 3) address three time frames to support more realistic HEP development.
44 Add top event W1 to the SBO event tree to Incorporated into the Revision ensure a successful stable state for days, as in
?PRA the aeneral transient event tree.
45 Re-evaluate top events X and X150 in the SBO Deferred to future update The Revision 7 PRA is event tree in light of differences between conservative for the RI-ISi depressurizing when high pressure injection is application with respect to this successful versus when it fails, in light of item. Incorporating the suggested procedure changes, and in light of FLEX.
improvements would lower importance measures for pipe seqments 46 Revise the event tree for LOOP with one EDG Incorporated into the Revision available to 1) remove top event A1 for
?PRA 8
Table C-2 it~fu
.*r:-:"':.::'-~-
<*;7~;:(4 ";. :~ _J.*... *...*.**
- Estimat~fi.~I-ISL l:t.*******:*; *.
--;5:-.,.::'!****(
.. /
- ~:£4~Y~ :;;¥;:.;(:;: ***...*
- ! ~.~.z;,
~L?~;;.~jg~4~ f
- 1i~f:.s12~\\. / *.,** >
.. :1rnpact.**
- feedwater since it is unavailable for LOOP sequences, 2) add top event AC-REC for recovery of AC power after top event QUV, 3) incorporate convolution interface, and 4)
Update Event Tree Notebook Table 2-5 footnote to be more complete.
47 Incorporate FLEX Phase 2 equipment into the Deferred to future update The Revision 7 PRA is SBO event tree to support the alternate conservative for the RI-ISi injection function.
application with respect to this item. Incorporating the suggested improvements would lower importance measures for pipe seoments 48 Incorporate MAAP insights for maintaining Deferred to future update The Revision 7 PRA is RCIC operation with aggressive cooldown into conservative for the RI-ISi the SBO event tree.
application with respect to this item. Incorporating the suggested improvements would lower importance measures for pipe seoments 49 Level 1 gates have been applied in Level 2 Deferred to future update Given that Level 2 results are often event trees without adjusting for the actual the determining parameter for initiating events and configurations reflected in assignment of consequence the accident classes that are transferred to the category in the RllSI evaluation, containment event trees. A solution would be to this item is judged to have little expand the CETs.
influence on its results.
50 Basic events inserted in the model to address Deferred to future update The Revision 7 PRA is future credit are prevalent in the Level 2 model.
conservative for the RI-ISi These are assigned a value of 1.0. These application with respect to this item appear to generate cutsets that are nonsensical since LERF is overestimated when high value basic events are present 51 Investigate if credit for operator initiation of Deferred to future update The Revision 7 PRA is drywell sprays for debris cooling is useful to conservative for the RI-ISi include in the Level 2 model. The current HEP application with respect to this item is 1.0.
52 Re-evaluate the binning of several Level 2 end-Deferred to future update The Revision 7 PRA is states as 'early'.
conservative for the RI-ISi application with respect to this item since some Level 2 end-states are binned as 'early' that could instead be 'intermediate' 53 There are redundant basic events in the BE Incorporated into the Revision database for operator action to open M01942.
7PRA The unused event should be deleted.
54 Add a basic event for two portable diesel Incorporated into the Revision generators that can be rented from Cedar 7PRA Rapids.
55 Add credit for back-flushing RHR A and RHR B Incorporated into the Revision torus suction strainers. See also Item #30 7PRA 56 Delete co-maintenance terms from the RCIC Incorporated into the Revision fault tree. See Item #40 7PRA 57 Add the capability to address an electronic Incorporated into the Revision governor failure by throttling RCIC valve 7PRA M02405.
58 Modify logic under the RCIC test line failure gate to maintain consistency with the change made in Item #57.
59 Delete the gate described as 'Inlet Drain Pot The subject gate (RCIC The subject gate is a very low not Drained Causes Water Hammer" from the
- 01) is retained in the Revision contributor to RCIC system failure.
RCIC fault tree.
7 model, but is supplied with Therefore this item has essentially screening values for events no influence on the RI-ISi leadinq to water hammer application.
60 Incorporate convolution of AC power recovery Incorporated into the Revision into the Level 1 PRA.
7PRA 61 Correct the power supply for HPCI steam Incorporated into the Revision suPPlv drain line valve CV2211.
7PRA 62 Credit the annunciator response procedure that Incorporated into the Revision 9
63 64 65 66 67 68 69 70 71 72 addresses high level in the HPCI system drain ot lo ic tree.
Research the technical basis for consideration of water hammer in the HPCI and RCIC systems.
Combine human actions for control of RPV level following a plant trip into a single human action.
Review all fault tree negation logic to assure FTREX quantification does not result in overly conservative probabilities.
Correct offsite AC power logic where having both transformers in maintenance is not going to LOOP and SBO.
Revise the Level 2 Notebook to reflect removal of SBGT heaters by EC 283827.
Incorporate a new human action into the CRD fault tree for opening of CRD room doors for alternate room coolin.
Develop HRACOMB events for the two combinations of human actions causing GDF and LERF to spike when both trains of Control Buildin HVAC are set to unavailable.
Add logic to the Control Building HVAC fault tree which facilitates quantification of both trains of HVAC in maintenance at the same time.
Benchmark the MAAP thermal-hydraulic code to the DAEC simulator Add logic to the RHRSW system fault tree to recognize the possibility of RHR Service Water pump failure due to overheating when started without their normal discharge pathway. See res onse to CR 02103035 for more detail.
Table C-2 Deferred to future update; the water hammer question for HPCI and RCIC drain pots remains open Deferred to future update A fairly extensive review of negation logic in the PRA model has been performed, but it was not comprehensive, nor were clear recommendations made for model chan es Incorporated into the Revision 7PRA The notebook has not yet been updated Incorporated into the Revision 7PRA Incorporated into the Revision 7PRA Incorporated into the Revision 7PRA Deferred to future update Incorporated into the Revision 7PRA 10 Modeling of water hammer is a very low contributor to HPCI and RCIC system failure. Therefore, this item has essentially no influence on the RI-ISi a lication.
The current treatment of human actions to manage water level following plant trips, including AT-NS, is believed to be overly conservative and would benefit from refinement. The current model is conservative for the RI-ISi ap lication with res eel to this item No instances of issues involving not-gates were noticed in quantification of RI-ISi cases.
Since such issues have previously been found to be conservative, it is not likely to adversely impact any of the RIIS! results.
This item is a documentation issue only and has no impact on RI-ISi results No specific issues have been identified where thermal-hydraulic modeling with MAAP is insufficient or nonconservative with regard to the DAEC PRA. Therefore, there is no im act on the RI-ISi a lication
282081 156057 156110 155991 281991 156026 272555 CABLE REPLACEMENT FOR 1G031AND1G021 WETTED CABLE PROJECT 1 P099B ESW PUMPCONTROL CIRCUIT APPENDIX R ISSUES INSTALLATION OF WELL WATER ISOLATION VALVE V44-0509 B.5.B PHASE 2 AND 3 ENHANCEMENT MODIFICATIONS RELIABLE HARDENED CONTAINMENT VENT - WETWELL NRC ORDER EA-13-109 REPLACE EXISTING REACTOR FEEDWATER PUMPS (RFP) AND MOTORS WITH RFP AND MOTORS OF LARGER CAPACITY ADD BATTERY CELLS TO 101 AND 102 125 voe BATTERIES Table C-3 Closed 3/21 /2016 Closed 2/11/2014 Closed 1 /13/2011 Closed 3/13/2008 Active 10/14/2016 Active 10/13/2016 Closed 4/24/2015 11 24.01 54.00 8.00 13.01 73.01 45.01 2.00 Per the DAEC fire protection engineer, further review is needed to determine whether updating of the Fire PRA is needed for this EC. Revision of the FPIE PRA however, is not necessarv.
Change already incorporated into Fire PRA for NFPA 805 implementation. No impact for FPIE PRA Failure of new isolation valve V44-0509 to remain open should be added to the Well Water system fault tree. Due to resource constraints however, update of the fault tree and update of the Well Water system notebook are being postponed until after the Rev 7 rollout. This is acceptable based on the low safety significance of well water system isolation valves.
This mod implements phase 2 and phase 3 strategies of the NRC's B.5.b order regarding beyond design basis accidents. These strategies have either been integrated with or superseded by post-Fukushima FLEX mods. Such changes are being incorporated into the Rev 7 PRA as practical through modeling of severe accident management procedures (SAMPs)
This mod installs a new hardened containment vent system which satisfies requirements set forth in NRC Order EA-13-109. Changes to the PRA are necessary, but are not incorporated in Rev 7 since completion of the mod is after the Rev 7 freeze date.
Although the feedwater pumps have been replaced, their function and behavior remains essentially the same. In addition, success criteria for the system is unaffected. Due to resource constraints however, update of equipment IDs and update of the feedwater system notebook are being postponed until after the Rev 7 rollout.
This mod adds two additional cells to 125 voe batteries to allow them to remain operable when battery cells fail testing.
Revision of the 125 VDC system fault tree is not necessary since battery reliability is not adversely impacted. However, the system notebook should be reviewed and updated as
278862 274778 FEEDWATER LOW SUCTION PRESSURE TRIP INSTALLATION WELL WATER CROSS-TIE INTO PLANT CHILLED WATER (ESSENTIAL LOOP)
Table C-3 Closed 3/26/2015 Closed 9/6/2012 12 45.01 30.00 necessary to reflect the actual desi n.
This mod installs pressure switch logic for a low pressure suction trip of the Feedwater pumps. The change prevents pump damage when low suction pressure conditions occur. Although the Feedwater system fault tree does not contain trip logic, the system notebook should be updated to reflect the new tri si nal.
This mod provides an alternate cooling source for the Control Building Air Conditioner Units.
The essential chilled water loop has been supplied by a tap from the well water system.
The current Control Building HVAC system fault tree should be reviewed to determine whether an alternate source of cooling water is already modeled. There is no need for an immediate update however; worth of the Control Building chillers is low since they are essential for cooling only during extreme hot weather conditions.