Engineering Evaluation of Instrumentation Sys for Rev 3 to Reg Guide 1.97,St Lucie Plant Unit 1
ML17214A622
Person / Time
Site: Saint Lucie 
Issue date: 11/30/1983
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17214A621 List:
References
RTR-NUREG-0737, RTR-NUREG-737 GL-82-33, NUDOCS 8401040272
Download: ML17214A622 (96)


Text

ST. LUCIE PLANT UNIT NO. 1 ENGINEERING EVALUATION OF INSTRUMENTATIONSYSTEM FOR REGULATORY GUIDE 1.97, REV. 3 DATE: November 1983 8401 040272 83i230 PDR ADOCK 05000335.

F PDR gggggf QgKET ALE COPY

SECTION III.

V.

VI.

VII.

VIH.

TABLE OF CONTENTS DESCRIPTION Regulatory Guide 1.97, Rev. 3 Requirements Evaluation Criteria I'ethodology of Equipment Evaluation Type A Variable List of Parameters Parameter Listing Summary Sheets List of Systems Requiring Additions, Modifications or Analysis References Conclusions PAGE NO.

2p 3 4,5 7,8 10

SECTION I REGULATORY GUIDE 1.9V, REV. 3 REQUIREMENTS

Regulatory Guide 1.97, Rev. 3, titled "Instrumentation for Light-Water-Cooled Nuclear Power Plants to Assess Plant and Environs Conditions During and Following an Accident", divides all instrumentation used for Post Accident Monitoring into five functional types as shown below:

Type A Variables:

those variables to be monitored that provide the primary information required to permit the control room operator to take specific manually controlled actions for which no automatic control is provided and that are required for safety systems to accomplish their safety function for design basis accident events.

Primary information is information that is essential for the direct accomplishment of the specified safety functions; it does not include those variables that are associated with contingency actions that may also be identified in written procedures.

Type B Variables: those variables that provide information to indicate whether plant safety functions are being accomplished.

Plant safety functions are (1) reactivity control, (2) core

cooling, (3) maintaining reactor coolant system integrity, and (4) maintaining containment integrity (including radioactive effluent control).

Type C Variables:

those variables that provide information to indicate the potential. for being breached or the actual breach of the barriers to fission product releases.

The barriers are (1) fuel cladding, (2) primary coolant pressure boundary, and (3) containment.

Type D Variables:

those variables that provide information to indicate the operation of individual safety systems and other systems important to safety.

These variables are to help the operator make appropriate decisions in using the individual systems important to safety in mitigating the consequences of an accident.

Type 8 Variables:

those variables to be monitored as required for use in determining the magnitude of the release of radioactive materials and continually assessing such releases.

Post Accident Monitoring Instrumentation is divided into three categories based on the degree of equipment qualification requirements, redundancy, power

sources, channel availability, quality assurance, and display and recording requirements..

In general, Category 1 provides for fullqualification, redundancy, and continuous real-time display and requires on-site (standby) power.

Category 2 provides for qualification but is less stringent in that it does not (of itself) include seismic qualification, redundancy, or continuous display and requires only a

high-reliability power source (not necessarily standby power).

Category 3 is the least stringent.

It provides for high-quality commercial grade equipment that requires only offsite power.

SECTION II EVALUATIONCRITERIA

Our review of RG 1.97, Rev. 3 requirements applicable to operating plants shows that the requirements of this guide cover the requirements of 10 CFR 50.49 and NUREG 0'737 and its subsequent clarification and generic letter 82-33.

The following is the evaluation criteria used in this report for the three different categories as defined in the Regualtory Guide 1.97, Rev. 3, Table l.

1.

ENVIRONMENTAL UALIFICATIONCRITERIA a.

Cate o

1 Instrumentation (a).

Instrumentation located in harsh environment should comply with 10 CFR 50.49 requirements and NUREG 0588 Category 1

(IEEE-323, 1974).

(b).

Instrumentation located in mild environments do not have to be upgraded if they withstand their service location conditions under normal and emergency conditions.

b.

Cate o

2 Instrumentation (a).

For safety related instrumentation, follow the same criteria used for category 1 instrumentation.

(b).

Non-nuclear safety related instrumentation located in harsh environment has to be qualified per NUREG 0588 category l.

(c).

Instrumentation located in mild environment should follow the same criteria used for category 1 instrumentation.

c.

Cate o

3 Instrumentation Non-nuclear safety related instrumentation has to withstand its service location conditions.

2.

SEISMIC UALIFICATIONCRITERIA Category 1 and Safety Related Category 2 instrumentation:

The equipment shall comply with IEEE-344, 1975.

(Reg.

Guide 1.100)

Category 3 and non safety related related category 2 instrumentation:

No specific provision required.

3.

REDUNDANCE Only category 1 instrumentation should be provided with redundant or diverse channels, electrically independent, and physically separated from each other, and from non~fety equipment, in accordance with Reg. Guide 1.75 "Physical independence of electric systems",

up to and including any isolation device.

Category 2

and 3

instrumentation do not require redundancy, 4.

POWER SOURCES a.

~Cate or 1

Instrumentation to be supplied from 120 VAC uninterruptible power

source, or from 120 VAC Offsite Power supply, backed up by an Emergency Diesel Generator if momentary interruption of power is acceptable.

b.

~Cate or 2

Instrumentation to be supplied from high reliability power source which can be either from:

1.

2.

30 4,

120 VAC uninterruptible, or 120 VAC Offsite Power backed by an Emergency Diesel Generator, or 125 VDC safety-related battery, or 125 VDC nonwafety related battery 6.

o.

~Cate o

3 No specific provisions required.

UALITY ASSURANCE - Qualified equipment (category 1

and safety related category 2

should comply with the Regulatory Guides listed in Table 1 of Reg. Guide 1.97 Rev.3.

DISPLAY AND RECORDING Category 1 Instrumentation should be displayed on a real-time display.

The indicator may be on a dial, digital display, CRT or strip chart recorder.

~

Recording of instrumentation readout should be provided for at least one redundant channeL Where dedicated strip chart recorder is not provided, recording should be updated and stored in computer memory and displayed on demand.

Category 2 Instrumentation should be displayed on an individual instrument or it may be processed for display on demand.

Signal from effluent radioactivity and area monitors should be recorded.

Category 3 Instrumentation.

(Same as Category 2).

Signal from effluent radioactivity, area and meteorology monitors should be recorded.

SECTION III METHODOLOGYOF EQUIPMENT EVALUATION

I t

t I

I I

I I

We have evaluated existing system arrangements and identified components for variables Types A thru E and their conformance to Reg.

Guide 1.97, Rev.

3 requirements applicable to existing plant.

Based on our interpretation of Reg.

Guide 1.97, Rev, 3 all Post Accident Monitoring instrumentation can be divided into three groups as shown below:

1.

ORIGINALSAFETY RELATED INSTRUMENTATION The origina/ safety related instruments located in harsh environment has been or will be replaced by qualified instruments per our commitment in response to bulletin 79-01B, 10CFR 50.49 or by this report.

The instruments located in mild environment do not require specific qualification until revision of the Regulatory Guide 1.89 is published.

The original safety related instrumentation generally comply with the seismic qualification program which was the basis for plant licensing.

2.

ADDED OR REPLACED SAFETY RELATED INSTRUMENTATION The added or replaced safety related instrumentaton generally comply with the requirements of 10 CFR 50.49 or the latest IEEE standards.

3.

NON SAFETY INSTRUMENTATION These instruments are high quality, commercial grade equipment that require no specific qualification, however if the instrument is category 2

located in harsh environm'ent, should be environmentally qualified.

Once the evaluation of all the instrumentation has been completed, a schedule for the implementation of the required modification to comply with the Reg.

Guide requirements has been included.

Section V of this report is the Parameter Listing Summary Sheets which includes all the plant instrumentation by tag numbers, grouped in the same order as the Reg. Guide 1.97, by type and categories.

The listing summarizes all the required information to perform the evalution and the results of the evaluation are shown on the column justification/schedule.

If this column is blank, it means that the instrument corn plies with the requirements of the Reg. Guide 1.97.

The Parameter Listing Summmary Sheets provide the following information:

Item, tag number, variable description, type and category, instrument existing and required

ranges, Q.

A.

requirements, envir onmental and seismic qualification, redundance, power

supply, display
location, schedule for implementation or justifications.

I Variable description

column, described the variable as listed in the Reg.

Guide 1.97, Rev. 3.

The tag number column, lists all the sensors, indicators, displays and recorders associated with variable described.

In the column "Display Locations, Control Room C.R.",

Yes, means that the indicator is located in the control room; SAS means that the data is available in SAS.

In the Column "Display Location TSC and EOF", Yes, means that the data is available on the computer display in the TSC and EOF.

Finally, section VI, lists all systems requiring modification, additions or analysis to comply with the Regulatory requirements.

SECTION IV TYPE A VARIABLELIST OF PARAMETERS

The type A variable list of parameters, the basis for which is given in Reg. 1.97, Rev.

3, was established.

The following Emergency Operational Procedures (EOPS) were reviewed:

Main Steam Line Break Loss of Reactor Coolant Loss of Feedwater or Steam Generator Level Steam Generator Tube Leak/Failure As a result of these reviews the following parameters were designated as Type A variables:

1.

2.

3.

4, 5.

Pressurizer Pressure RCS Hot Leg Temperature RCS Cold Leg Temperature Steam Generator Level Narrow Range Containment Hydrogen Concentration

SECTION V PARAMETER uSTING

SUMMARY

SHEETS

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAMETER RY SHEET" TYPE ABLES DECEMBER 6, 1983 I

ITEMI TAC NO.

VARIABLE INSTRUMENT RANCE Qh I

TE-I I REQUIRE-I ENVIRONMENTAL I SEISMIC IDESCRIPTION ITYPE I

GORY I EXISTINC IREQUIRED I

MENT IQUALIFICATION IQUALIFICATION I

POWER I DISPLAY LOCATION SCHEDULE/

JUSTIFICATION Al IPT-1107 I

I I Pr-1108 I

I I ICC IDisplay A I

IICC IDisplay B I Pressur-I iver I Pressure I

I I

I 1

10 to 3000 I Plant I psia I Specific Comply Note 16 Note 16 Note ll Note 11 Note 17 Note 17 Note 19 Note 19 I PT-1108 I

I I IT-1107 I

I I ICC I Display I

I ICC I Display I

I INote 1

ISA I

INote 1

ISB I

INote 1

B ISA I

INote 1 A ISB I

SAS I Yesl I

SPDS I

I I

I I

I SAS I Yesl I

SFDS I

I Yes Yes YeslFor the ICC ISystem see INote 23.

Trend Yeslinformation is lavailable in ISAS.

A2 ITE-1112CA ICC IDisplay A I

ITF.-1112CB I

I I ICC IDisplay 8 I

ITF.-1122 CA I

I I ICC Display A TF.-1122CB I

IICC IDisplay B I

RCS Cold I Leg Temp I Loop 1A2 I

I I

I RCS Cold I Leg Temp I Loop Al I

I I

I RCS Cold I Leg Temp Loop 1B1 I

I RCS Cold Leg Temp Loop 182 I

I I

1 1212'F to I Plant I Comply 1705'F I Specific 1

1212'F to 1705'F I

Plant I Comply Specific 1

1212'F to I Plant 1705'F ISpecific I

I I

I I

I I

I Comply 1

1212'F to I Plant I Comply 1705'F ISpecific Note 16 Note 11 Note 16 Note ll Note 16 Note ll Note 16 I

I Note 11 I

I Note 17 Note 19 Note 17 Note 19 Note 17 Note 19 Note 17 Note 19 TE-1112CB ICC I Display B

I I TE-1112CA I

I I ICC I Display A I

I TE-1122CB INote 1

IMA I

INotd 1 ISA I

INote 1

IMB I

INote 1

ISB I

INote 1

IMA TE-1122CA ICC Display A INote 1

IMB I

INote 1

ISB I

ICC Note 1

Display B SA I

SAS I

I SFDS I

I Yes I

I I

SAS I

SPDS Yes I

Shs I

SPDS Yes I

SAS I

I SFDS I

I Yes I

I Yesl Yes SAS.

Yesl Yes Yes Yes Yesl Yes For the ICC ISystem see INote 23.

Trend linformation is Iavailable in 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAMETE RY SHEET" TYPE A V S (Cont'd)

DECEMBER 6, 1983 ITEM I

TAC NO.

DESCRIPTION TYPE CATE-I GORY I EXISTINC REQUIRED VARIABLE INSTRUMENT RANCE Qh REQUIRE-MENT ENVIRONMENTAL QUALIFICATION SElsMIc I

QUALIFICATION I PowER DIsPLAY LochTIDN I scHEDULE/

SUPPLY CR T

EOFI JUSTIFICATION A3 ITE-1112HA Icc Display A TE-1112HB Icc Display B

TF;1122HA I lcc IDisplay A I

ITE-1122HB I

IIce IDieplay B I

I RCS Hot I Leg Temp Loop 1A I

I I

RCS Hot I Leg Temp Loop 1B I

I I

I I

I I

1 l212 F to IPlant l705'F ISpecific 1

l212'F to IPlant I705'F ISpecific Comply I

I I

Comply Note 16 Note 11 Note 16 Note 11 Note 16 Note ll Note 16 Note 11 Note 17 Note 19 Note 17 Note 19 Note 17 Note 19 Note 17 Note 19 TE-1112MB Icc Display B

TE-1112HA Icc Display A TE-1122MB Icc Display B

TE-1122HA Icc Display A INote IMA Note SA INote I IMB INote 1

ISB I

INote 1

IMA INote 1

ISA I

INote 1

IMB Note 1

SB SAS SPDS Yes SAS SPDS Yes SAS SPDS Yes SAS SPDS Yee Yes I I Yes II I

I I Yes Yes SAS Yes I Yesl Yes Yeelpor the ICC ISystem see INote 23'rend linformation is lavailable in A4 ILT-9013A I

LT-9013B ILT-9013C LT-9013D ILIC-9013A I

I I

I I

ILIC-90138 I

I I

ILIC-9013C I

LIC-9013D LR-9013A SG 1A1 Level (Narrov Range)

I 1

IO to 132 I plant I Inches ISpecific Iwc 0 to 100X I

I Comply I Comply I

I I Comply I

I I comply I

I Comply I

I I comply I

I I comply I

I I Comply I

I I comply I

Note 16 Note 16 Note 16 Note 16 Note ll Note 11 Note 11 Note ll Note ll Note 17 Note 17 Note 17 Note 17 Note 12 Note 12 Note 12 Note 12 Note 12 I LT-9013D I

I I LT-9013C I

I I LT-9013B I

I I LT"9013A

-I I

I LIC-9013D I

I I LIC-9013C LIC-9013B LIC-9013A INote 1 I

IMA I

I I

INote 1 I

IMB I

I I

INote 1 I

IMc I

I I

INote 1

I IMD I

I I

INote 1 I

IMA I

I I

INote 1 I

IMB IINote 1

IMc I

INote 1

I IMD I

I I

INote 1 IMA I

I I

shs I

SPDS SAS SPDS SAS SPDS shs I

SPDS Yes Yes Yes Yes Yee Yeel Yes Yes Yes Yee Yee Yes Yee 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAMETE Y SHEET" TYPE A V S (Cont'd)

DECEMBER 6 1983 VARIABLE ITEM TAG NO.

DESCRIPTION TYPE CATE-GORY INSTRUMENT RANGE EXISTING REQUIRED Qh REQUIRE-ENVIRONMENTAL MENT QUALIFICATION SEISMIC QUALIFICATION REDUNDANCE POWER DISPLAY LOCATION I SCHEDULE/

SUPPLY T

I JUSTIFICATION ILT-9023A I

I ILT-9023B I

I ILT-9023C I

I ILT-90230 I

I ILIC-9023A I

I ILIC-9023B I

I ILIC-9023C I

I ILIC-90230 I

I ILR-9023h I

SG 1B1 I Level (Narrow Range) 1 lO to 132 lincbes lO to 100X I

Plant Specific Comply Comply I

I I Comply I

I

! Comply I

I Comply I

I

/ Comply I

I

! Comply I

I

! Comply I

I

) Comply Note 16 Note 16 Note 16 Note 16 Note ll Note ll Note 11 Note 11 Note 11 Note 17 Note 17 Note 17 Note 17 Note 12 Note 12 Note 12 Note 12 Note 12 I LT-9023D I

I I LT-9023C I

I I LT"9023B I

I I LT"9023A I

I I LIC-9023D I

I I LIC-9023C I

I I LIC-9023B I

I I LIC-9023A I

IMA' INote 1

IMB I

I Yes INote 1 IMC I

INote 1

IMD I

!Note 1 Yes I

I Yes I

I Yes IMA I

Note 1

SAS IMA I

SPDS I

I INote 1

I SAS IMB SPDS I

I INote 1

I SAS IMC I

SPDS I

I

)Note 1

I SAS IMD I

SPDS I

I INote 1

I Yes Yes Yes Yes(

I I

Yesl I

Yes Yes

! Yes Yes Containment I

Hydrogen Concentra-tion IHydrogen I Sampling

& Analyzers Cubicle SB!

I Hydrogen Analyzer Ind IRecordfng ICubicle Shl I

IHydrogen 1 Analyzer llnd &

Recording Cubicle SB I

A5 IHydrogen Sampling

& Analyzer Cubicle SA 1

IO to 10Z Iplant l(Capable

!Specific lof Oper-lating Ifrom -5 Ipsfg to

)44 psig)

I I

I I

Comply Note 11 Note 11 Note ll Note ll Note 12 Note 12 Note 12 Note 12 INote 2 ISA I

I I

INote 2 ISB I

I I

(Note 2

ISA I

I I

Hydrogen Analyzer llnd &

I!Recording

!Cubfcle SA I

Note 2

SB IHydrogen

!Sampling I& Analyzer

!Cubicle SB I

!Hydrogen

!Sampling l & Analyzer

)Cubicle SA I

IHydrogen (Analyzer find &

IRecording ICubfcle SB SAS SPDS SAS S PDS Yes Yes Yes Yes Yes Yes

FLORIDA POHER AND LIGHT ST LUCIE UNIT NO 1

REGULATORY GUIDE 1.97 REV 3 "PARAMETE RY SHEET" TYPF IABLES DECEMBER 6, 1983 VARIABLE INSTRUMENT RANCE Qh

- I I REQUIRE-IENVIRONMENTAL I SEISMIC I

I PONER ITEMI TAG NO.

IDESCRIPTION ITYPE I

GORY I EZISTINC IREQUIRED I

MENT IQUALIFICATION IQUALIFICATION I REDUNDANCEI SUPPLYI DISPLAY LOCATION CR TS E

SCHEDULE/

JUSTIFICATION Bl

- IDetector INeutron F 1 IFlux Detector f2 Detector

$3 Detector f4 JI-001 JI-002 JI-003 JI-004 JR-011 1

I 10 to I 10 to I150X of llOOX of IFull IFull IPover IPover Comply I For the I detectors I refer to the I

I Justificationl Note ll Note 11 Note ll Note ll Note ll Note 19 Note 19 Note 19 Note 19 Note 12 Note 12 Note 12 Note 12 Note 12 INote 1

IMA I

INote 1

IMB I

INote I IMC I

I I

INote 1 IMD I

I INote 2AI INS I

I I

INote 2AI INS I

I INote 2AI INs I

I INote 2AI INs 2A Note Ns 4 Separate Channel I Yesl Yes SPDS I

I I Yesl Yes SPDS I

I I

SAS I Yesl Yes SPDS I

I I Yesl Yes S PDS Yes Yes Yes Yes Yes IThe Detectors land their lamplifiers are Iqualified fot Ishort term post Iloca and Iperforms its I intended safety lfunction (Rps IActua tion)

Ivithin this Ishort time Iperiod.

Seis-Imic analysis l<<r the detec-Itor holders Ivillbe com-Ipleted by the lend of the next I refueling out-Iase.

Trend linformation is lavailable in Ishs.

B2 IControl IControl Rod IRod Posi-IPosition I tion LimitI ISvitch l(Quantity I I 61)

I ICEA IDisplay I

IMetroscopel I

I IDDPs I.

I I

3 IFull in IFull in lor not lor not lfull in, lfull in IAnalog IPosition Ifor any ICEA I

N/A N/A N/A I

N/A INote 2AI INS I

INote 2AI INS I

Yes I

I INote 2hl INs I

I Yes SAS INote 2AI Yes INs I.

I I

Yes IYes SAS displays "All In" or I"AllNot In" 1539M

PLORIDA POWER AND LIGHT ST LUCIE UNIT NO ~

1 REGULATORY GUIDE 1.97 REV 3 "PARAMETER RY SHEET" TYPE B V S (Cont'd)

DECEMBER 6, 1983 VARIABLE INSTRUMENT RANCE Qh I

I CATE-I I REQUIRE-IENVIRONMENTAL SEISMIC ITEMI TAC NO.

IDESCRIPTION ITYPE I

GORY I EZISTINC IREQUIRED I

MENT IQUALIFICATION QUALIFICATION I

powER I

REDUNDANCEI SUPPLY I DISPLAY LOCATION I SCHEDULE/

B3 IAT-2203 IRCS Soluble I

B IBoron Con-Icentration IAR-2203 3

IO to 550 IO to 6000I N/A Ippm lppm I

I500 to I1050 ppm I1000 to I1550 ppm I1500 to l2050 ppm I

N/A N/A N/A INote 2AI INS I

INote 2A INS SAS Yes I Yesl YeslExisting range Iis acceptable.

ILab sample lanalysis to l25 x 103 ppm.

(see Item E17A)

B4 ITE-1115 I

I ITI"1115 I.

I ITR-1115 TF.-1125 TI-1125 ITR-1125 I

I IRCS Cold Legl ITemp 1A1 RCS Cold Legl Temp 1B1 3

lo'F to I600'F I50'F to I400 F B

3 IO F to I50 F to I600'F I400'F I

I N/A N/A N/A N/A N/A N/A N/A INote 2AI INS I

I I

INote 2AI INS I

I I

INote 2AI INS I

I I

INote 2AI INS I

I I

INote 2AI INS I

I I

INote 2AI INS I

Yes Yes SAS I Yes Yes Yes Yes SAS I Yesl Yes I

I B5 ITE-1112HA IRCS Hot Leg I

B ITemp Loop 1AI ICC Display A TE-1112HB I

ICC Display B I

I 1

l212'F to I50'F to I Comply I705'F I700'F I

Note 16 Note ll Note 16 Note 11 I

Note 17 Note 19 Note 17 Note 19 INote 1

I IMA I

I INote 1

I ISA I

I INote 1

IMB I

I INote 1

ISB I

I I

I TE-1112HB I

I I Icc I Display B I

I TE-1112HA I

I I Icc I Display A I

SAS I Yesl SFDS I

Yes I

SAS I Yes SPDS Yes Yeslgxisting Range ILicensed for I Subcoo1 ed IMargin Monitor.

IFor the ICC ISystem see YeslNote 23, Trend I information is lavailable in ISAS.

1539M

FLORIDA PONER AND LIGHT ST LUCIE UNIT NO. 1 REGULAT "P

TYPE UIDE 1.97 aEV 3 Y SHEET" LES (Cont'd)

ER 6, 1983 A

ITEN TAG Noo VARIABLE INSTRUMENT RANGE

.Qh GATE-I I azqUIRE-DESCRIPTION TYPE I GORY I EXISTING RE UIRED I MENT ENVIRONMENTAL VALIPICATION SEISMIC VALIPICATION I powza REDUNDANCEI SUPPLY DISPLAY LOCATION CR TSC EOP SCHEDULE/

JUSTIPICATION TE-1122HA IRCS Hot Leg I

B ITemp Loop 1BI Icc Display A ITE-1122HB I

I Ircc IDisplay B 1

l212'F to Iso'F to I Comply I705'F I700'F I

Note 16 Note 11 Note 16 Note ll Note 17 Note 19 Note 17 Note 19 I TE-1122HB I

I I Icc I Display B

I I TE-1122HA I

I I rcc I Display A I

MB INote 1 ISB I

SPDS Yes INote 1 I

~ SAS IMA I

SPDS I

I INote 1 I

Yes ISA I

I Note 1 I

SAS ISubcooled IMargin Monitor.

IFor the ICC ISystem see YeslNote 23.

Trend linformation is I Yesl available in SAS.

I Yesl Yeslaxisting Range I

I ILicensed for B6 TE-1112CA RCS Cold Leg Temp Loop lh2 Icc Display h I

I TE-1112CB IRCS Cold Legl Temp Loop lA1 Icc Display B l7os'F I7oo'F I

I I

I I

1 l212'F to I50 F to I

I7os F

I7oo F Comply 212'F to l50'F to I Comply Note 16 Note 11 Note 16 Note ll Note 17 Note 19 Note 17 Note 19 I TE-1112CB I

I I Icc I Display B I

I TE-1112CA I

I I Icc I Display A INote 1 I

IMA I

I I

INote 1 I

ISA I

I I

INote 1 I

IMB I

I I

INote 1 I

ISB ISubcooled IMargin Monitor.

IFor the ICC ISystem see I

I Yes SAS I

SPDS Yes Yes Note 23.

Trend linformation is Yes available in SAS.

SAS I Yesl Yeslazisting Range SPDS I

I ILicensed for ITE-1122CB I

I IIcc IDisplay B IRCS Cold Legl ITemp Loop I1B2 I

I I

TE-1122CA IRCS Cold Leg Temp Loop 1Bl Icc Display h 1

l212'F to I7os'F 50'F to I

700'P B

1 l212'F to Iso'F to l7os'F l7oo'F Comply Comply Note 16 Note ll Note 16 Note ll Note 17 Note 19 Note 17 Note 19 TE-1122CB I Icc I Display B I

I TE-1122CA I

I I Icc I Display A I

Note 1 Mh Note 1 SA INote 1 I

IMB I

I I

INote 1 I

SB SAS SPDS Yes SAS SPDS J

Yes Yes Yesl Yes Yes PT-1108 IPressurirer Pressure (RCS Pressure)

ICC Display A Icc Display B

I I

B7 PT-1107 B

1 Io to 3000 lo to 4000I Ipsia Ipsig Comply Note 16 Note 16 Note 11 Note ll Note 17 Note 17 Note 19 Note 19 PT-1108 PT-1107 INote 1 ISA Note 1 SB Icc Display Note 1 A

SB Icc Note 1 Display B Sh SAS SPDS Yesl Yes Yes SAS I Yes SPDS acceptable pending ATlS disposition.

Por the ICC System see Note 23.

Trend information is available in SAS.

Yes 1539M Yeslaxisting range Iconsidered

'e

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAME Y SHEET" TYPE B ES (Cont'd)

DECEMBER 6, 1983 ITEM VARIABLE INSTRUMENT RANGE Qh CATE-I I REQUIRE-IENVIRONMENTAL I SEISMIC TAG NO.

DESCRIPTION ITYPE I

GORY I EXISTING REQUIRED I

MENT IQUALIFICATION IQUALIFICATION I

POWER I DISPLAY LOCATION I SCHEDULE/

REDUNDANCEI SUPPLYI CR TSC EOFI JUSTIPICATION BB l45 Core I Core Exit IFxit Ther-ITemp lmocouples I

I ICC I

Display A I

ICC Display B 3

I32'F to I200'F to I

N/A I

N/A I2300'F I2300'F SA SAS SPDS Note 1

SB Yes SAS SPDS N/A INote 1

I ISA ISB I

INote 1 I

Yes I Yesl Yes I Yesl Yes B9 I16 Heated IJunction IThermo-Icouples I

IIce IDisplay A IRLEV-A Icc Display B RLFV-B ICoolant llnventory I

8 IBottom of IBottom ofl Comply IHot Leg IHot Leg I

Ito Top Ito Top I

lof Vessel lof Vessell Note 18 Note 11 Note 11 Note 19 Note 19 Note 19 I 8SA and I 8SB I

I I

I ICC I Display B

I (RLEV-B)

I I ICc I Display A I (RLEV-A)

INot'e 1

ISA, SB I

I I

INote 1 ISA I

I INote 1

ISB I

I I

I I

I I

I SAS I

I SPDS I

I I

SAS SPDS Yes Yes Yes Yes For the ICC System see Note 23.

Trend I information is Iavailable in SAS.

B10 IICC IDegrees of IDisplay A ISubcooling ITMARHEAD-AI TMARRCS-h I

TMARCET-A I TMARUR-A Icc Display B I

ITMARHEAD-BI ITMARRCS-B I TMARCET-B TMARUR-B 2

1700 F

I 200'F I Comply I Subcool-I Subcool-I ling to ling to I

I 2100'F I35'F I

ISuperheat ISuperheatl IRefer to EQ Ifor hl, A2, IA3, B9 and Icl IRefer to EQ I for Al, A2, IA3, B9 and Icl I

I I

IRefer to ISeismic Qual-Iification for IA1, A2, A3, IB9 and Cl I

I IRefer to ISeismic Qual-lification for I

IA1, A2, A3>

B9 and Cl ISystem see Note 23.

SAS I

Ish SPDS I

INote 1

I Yes I Zesl Yes ISB SAS SPDS N/A INote 1

I Yes I Yesl YeslFor the ICC 1539M

PLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAMETE Y SHEET" TYPE B V S (Cont'd)

DECEMBER 6, 1983 VARIABLE INSTRUMENT RANGE Qh

-I I REQUIRE ITEMI TAC NO.

DESCRIPI'ION ITYPE I

GORY I EXISTINC IREQUIRED I

MENT ENVIRONMENTAL I SEISMIC QUALIPICATION IQUALIFICATION POWER REDUNDANCE SUPPLY DISPLAY LOCATION SCHEDULE/

JUSTIP ICATION Bll PT-1107 IPT-1108 Pressurizer Pressure (Rcs Pressure)

Icc Display A I

I Icc I

Display B I

I B12AILT-07-14A IContainment I

ISump Water ILevel (Nar-LIS-07-14AIrow Range) 1 IO to 3000 I 0 to 4000 Comply Ipsia Ipsig 2

I-7 ft to INarrow I Comply IO ft El IRange l(Sump)

Note 16 Note 16 Note 11 Note 11 Note 16 Note ll Note 17 Note 17 Note 19 Note 19 Note 17 Note 17 PT-1108 PT-1107 ICC I Display I

I Icc I Display INote 1

I Ish I

INote 1

ISB I

INote 1

B ISA I

I I

INote 1 I

A ISB I

SAS I Yesl SPDS SAS S PDS Yes Yes Yes Yes l Existing range Iconsidered Iacceptable Yeslpending ATWS Idisposition.

IFor the ICC ISystem see INote 23.

Trend linformation is Iavailable in SAS.

N/A INote 2 I

SAS I Yesl Yes Ish I

sPDs I

I INote 2 I

Yes LR-07-13/

14A B12BI LIS-07-13A LT-07-13A IContainment ILevel (Wide I

Range)

LT-07-138 I-l to 26 IWide I Comply Ift El IRange I (Plant ISpecific)

Note ll Note 16 Note 16 Note 11 Note 17 Note 17 I

Note 17 Note 17 Ish I

INote 2 ISA I

LT-07-13B INote 2 SA LT-07-13A Note 2

SB Note 2

SA LIS&7-13B I

Yes SAS SPDS Yes Yes Yes SAS I Yes Yes S PDS LIS-07-13B Note 11 Note 17 LIS-07-13h Note 2

SB Yes LR-07-13/

I 14A I

I 813 I

PI-07-4A pR-07 48/

I SB I

I PT-07-4A IContainment I

8 Ipressure l(Mid Range)

PT-07-48 1

IO to 60 Ipsig I

I I

IO to IDesign Ipressure I

I I Comply I

I I Will I Comply I

I Comply I

I I Comply I

I Note 11 Note 16 Note 18 Note ll Note ll Note 17 Note 17 Note 19 Note 12 Note 12 I PT-07-48 I

I I PI'-07-4A I

I PR-07-4B/

5B PI-07-4A INote 2 SA INote 1

I IMA I

I I

INote 1 I

IMB I

I I

INote 1

I I MA I

INote I IMB I

Yes SAS S PDS SAS SPDS Yes Yes I Yesl YeslDesign Pressure I

I lis 44 psig.

I I

IPT-07-48 will I Yesl Yeslbe replaced by Ithe end of the Inext refueling Ioutage with a Iqualified transmitter.

FLORIDA POWER AND LIGHT ST LUCIF. UNIT NO.

1 REGULATORY CUIDE 1.97 REV 3 "PARAME RY SHEET" TYPE B ES (Cont'd)

DECEMBER 6, 1983 VARIABLE INSTRUMENT RANCE I

I

-I ITEMI TAC NO.

IDESCRIPTION ITYPE I

GORY I EXISTINC IREQUIRED B14 ICONTAINMEHT ISOLATION VALVE POSITION Qh REQUIRE-ENVIRONMENTAL SEISMIC MENT QUALIFICATION QUALIFICATION POWER SUPPLY DISPLAY LOCATION SCHEDULE/

JUSTIPICATION IFor manual iso-Ilation Valves Isee Table l6.2-16 in FSAR.

ITbese values lare locked Iclosed under IAdministrative IControl.

No CR I indication or linput to SAS Iprovided.

B14AIV-2515 I

I IV-2516 B14BIV-5201 CVCS Letdovnl B

Ipressurixer ISurge Line Isample V-5204 I

B14C B14DIMV-15-1 Iprimary Water Isola-tion Valve B14E V-2505 ISE"01-1 RCP Con-Itrolled IBleedoff I

I I

V-5202 I Pressurizer I

B ISteam Space I

ISample V-5205 1

I Closed lor Open 1

Iclosed lor Open 1

Iclosed lor Open 1

Iclosed lor Open I

1 Iclosed lor Open I

I I

I IClosed/

INot Iclosed I

I I

IClosed/

INot IClosed I

IClosed/

INot IClosed I

I I

Iclosed/

INot Iclosed IIclosed/

INot IClosed I

I I

I Comply I

I I comply I

I I Comply I

I I Comply I comply I

I I Comply I

I I Comply I

I I

I comply I

I I Comply I

I Note 16 Note 16 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 8 Note 17 Note 17 Note 12 Note 12 Note 12 Note-12 Note 12 Note 12 Note 12 Note 9

Note 9

I Note 9

I Note 9

Note 9

I I

Note 9

I Note 9

Note 9

Note 9 INote 3 I

ISA I

I I

INote 3 I

ISB I

I I

INote 3 I

ISA I

I I

INote 3 I

ISB I

I INote 3 I

ISA I

I I

INote 3 I

ISB I

I I

INote 2 I

ISB I

I INote 3 I

ISA I

INote 3 ISB I

SAS Yes SAS Yes SAS Yes SAS Yes SAS Yes SAS Yes SAS Yes SAS Yes SAS Yes I Yes I

I I Yesl I

I I

I I Yesl I

I I Yes Yes Yes Yes Yes Yes Yes Yes Yes I Yesl Yes Yes Yes I Yesl Yes 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1 ~ 97 REV 3 "PARAMETE Y SHEET" TYPE B ES (Cont'd)

DECEMBER 6, 1983 VARIABLE ITEM TAC NO.

DESCRIPTION CATE-TYPE I

GORY EXISTING IREQUIRED INSTRUMENT RANCE Qh REQUIRE IENVIRONMENTAL I SEISMIC I

I POWER I DISPLAY LOCATION I SCHEDULE/

B14FIFCV-23"3

)Steam Cen-Ierator Blovdovn FCV-23-4 FCV-23-5 FCV-23-6 FCV-23-7 IFCV-23-9 I

I B14C I MV-18-1

)cavity Sump I Pump Dis-LCV-07-llB)charge I

I V-6741 INitrogen ISupply to ISafety In-I)ection

)Tanks I

IContainment IVent Header I

B14II B14JIV-6554 I

IIv-6sss I

I B14KIV-5200

)Reactor

)Coolant ISample I

I V-5203 I Instrument lAir ISupply I

B14HILCV-07-llAIReactor 1

Iclosed Ior Open 1

IClosed

)or Open I

I 1

IClosed Ior Open I

1 IClosed

)or Open I

1 IClosed Ior Open I

I I

I 1

IClosed

)or Open I Closed INot Closed

)Closed/

)Not I Closed I

IClosed/

INot IClosed IClosed/

)Not I closed I

I I

Iclosed/

INot IClosed I

I II Closed/

INot IClosed I

I Comply Comply I Comply I

I I comply I

I I comply I

I I Comply I

I I comply Com)ly Comply Comply I Comply I

I I Comply I

I I Comply I

I I comply I

Note 10 Note 16 Note 10 Note 16 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 12 Note 17 Note 12 Note 17 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 9

Note 9

Note 9 Note 9

Note 9

Note 9

Note 9 Note 9 Note 9

Note 9 Note 9

Note 9 Note 9 Note 9

INote 3

ISA I

INote 3 I

ISB I

INote 3 ISA I

INote 3 I

ISB I

I I

INote 3 I

ISA' I

I INote 3

)

ISA I

INote 2 ISA I

I INote 3 AA INote 3 ISB I

INote 3 I

ISB INote 3 I

IAA INote 3 I

ISB I

I I

INote 3 I

Ish I

I I

INote 3 I

ISB I

SAS Yes Yes Yes SAS Yes Yes Yes SAS I Yes Yes I

I SAS I Yes)

Yes Yes Yes SAS Yes Yes SAS Yes Yes Yes SAS Yes Yes Yes SAS I Yes Yes Yes SAS I Yes)

SAS I Yes Yes I

I SAS I Yes Yes I

I SAS I Yes Yes I

Yes Yes Yes Yes SAS I Yes Yes Yes I

I SAS I Yes)

Yes Yes 1539M

FLORIDA POWER AND LIGHT ST LUCIE UHIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAME Y SHEET" TYPE B ES (Cont'd)

DECEMBER 6, 1983 ITEM TAG HO B14LIV-6301 V-6302 VARIABLE DESCRIPTION TYPE IReactor B

IDrain Tank I

I Pump Suction B14MIFCV-26-1 I Containment FCV-26-2 I Sample Isolation Valves CATE-GORY INSTRUMENT RANGE EXISTING REQUIRED 1

IClosed lor Open 1

IClosed lor Open I Closed/

INot IClosed I

I I

IClosed/

INot IClosed IFCV-26-3 FCV-26-4 FCV-26-5 FCV-26-6 Closed Closed/

or Open INot IClosed FCV-25-3 FCV-25-4 FCV-25-5 FCV-25-6 B14PII"FSE-27-llDome Area IF.1 213'-FSE-27-5 Dome Area El 190 '

1 1

IClosed lor Open Closed or Open IClosed/

INot I Closed I

IClosed/

INot IClosed I

B14NIFCV-25-1 IContainment I

I purBe hir I

ISupply and IFCV-25-2 IExbaust QA REQUIRE-MENT I Comply I

I I Comply I

I I Comply I

I Comply I

I I Comply Comply I Comply I

I I Comply I

I Comply I

I I Comply I

I I Comply I

I I Comply I

I I Comply I

I Comply I

I I Comply Comply Hote 10 Note 12 Note 10 Note 12 Note 16 Note 17 Note 10 Note 12 Note 16 Note 17 Hote 10 Note 12 Note 16 Note 17 Note 10 Note 12 Note 10 Note 12 Note 10 Note 12 Note 16 Note 17 Note 16 Note 17 Note 10 Note 12 Note 10 Note 12 Note 10 Note 12 Note 10 Note 12 ENVIRONMENTAL SEISMIC QUALIFICATION QUALIFICATION Note 9

Note 9

Note 9

Note 9

Note 9

Note 9

Note 9 Note 9 Note 9 Note 9

Note 9 Note 9

Note 9

Note 9 Note 9

Note 9

POWER SUPPLY ISA I

INote 3 ISA I

INote 3 I

ISA I

INote 1 ISA I

I INote 1

ISB I

INote 3 ISB I

INote 3 ISB I

INote 2

SA Note SB INote 3 I

ISA I

I I

I Note 3 I

ISB I

I I

INote 3 I

ISB I

I I

INote 3 I

Ish I

I I

INote 3 I

ISB I

I I

INote 3 I

ISA I

I I

INote 3 I

ISB I

I I

INote 3 I

SAS Yes SAS Yes SAS Yee SAS Yee SAS Yes SAS Yes SAS Yes SAS Yes SAS Yes SAS Yes I

I Yes Yee I

I I Yeel Yeel I

I I

I I

I Yesl Yee I

I I

I I Yesl Yes I

I I

I Yee Yes I

I

- I Yes Yes I

I I Yesl Yes Yes Yes Yee Yes Yes Yee SAS Yes Yes Yes SAS Yes SAS Yee SAS Yes Yes Yes Yes I Yesl I

I I Yes Yes Yes No No Yes No No DISPLAY LOCATION CR TS EOF SCHEDULE/

JUSTIPICATIOH 1539M

FLORIDA POHER AND LIGHT ST LUCIE UNIT Ho.

1 REGULATORY GUIDE 1.97 REV 3 "PARAMETE RY SHEET" TYPE B V S (Cont'd)

DECEMBER 6, 1983 VARIABLE INSTRUMENT RANGE QA I

I CATE-I I REQUIRE-IENVIRONMENTAL I SEISMIC ITEMI TAC HO.

IDESCRIPTION ITYPE I

GORY I EXISTINC IREQUIRED I

MENT IQUALIFICATION IQUALIFICATIOH I

POHER I DISPLAY LOCATION SCHEDULE/

JUSTIFICATIOH B14Q B14R B14S B14T B14U I-FSE"27-3 RCP 1A1 Area B

I-FSE-27-7 I"FSE-27-4 RCP 181 Areal B

I I

I RCP 1A2 Area I B

I-FSE"27-6IRCP 1B2 Areal B

I-PSE-27-8 Penetration 48 I-FSE ll I-FSE-27-9 Penetration I 51 I-FSE 10 I-FCV lE I-FCV 1F Safety Infection Tanks Samp-ling System I-FSE-27-2 Pressurizer I

B Sample Point I 1

IClosed lor Open 1

Closed lor open I

I 1

IClosed lor Open I

I 1

IClosed lor Open I

I 1

IClosed lor Open 1

Closed lor Open IClosed/

INot I Closed I

IClosed/

INot IClosed I

IClosed/

INot IClosed II Closed/

INot IClosed I

IClosed/

INot IClosed I

IClosed/

INot IClosed I Comply Comply I Comply I

I I

I Comply I Comply Comply Comply 1

IClosed lor open None Ex-I isting in IControl Room Closed/

INot I Closed Comply Comply Closed/

I Comply INot I

IClosed I

I Comply Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 8 Note 8 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 9

Note 9

Note 9

Note 9

Note 9 Note 9

Note 9 Note 9 Note 9

Note 9

Note 9 INote 2 I

ISA I

I INote 2 Ish Note 2

SB INote 2 I

Ish '

I I

I I

INote 2 I

ISB I

I INote 2 I

Ish I

I I

!Note 2 I

ISA I

I I

INote 2 I

Isg I

I I

INote 2 I

Isg I

I I

INote 3 I

ISA I

INote 3 ISB I

Yes Yes I No I No I

I No I

No I

Note 15 Note 15 Yes No No Note 15 Yes I No No Note 15 Yes I No No Note 15 Yes Yes I No I

No I

Note 15 I

I I

I I

I I No I No I

Note 15 I

I No I No I

I Note 15 Yes No No I No I No I

I I

I I No I No I

I I

I ICR indication lwill be provid-led by the end lof the next re-lfueling outage.

I Yes I No I

No I

Note 15 1539M

FLORIDA PONER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1,97 REV 3 "PARAMETB" RY SHEET" TYPE B ES (Cont'd)

DECEMBER 6, 1983 ITEMI TAC NO.

B15 PP-07-4A PI'-07-4B PI-07-4A PR-07-4B/

5B Qh REtIUIRE-IENVIRONMENTAL SEISMIC MENT IQUALIFICATION. QUALIFICATION Containment I

B I Pressure I

l(Mid Range)

I 1

IO to 60 Ipsig I-5 psig Comply Ito Designl Pressure I

I Niii I Comply I

I Comply I

I I Comply Note 16 Note 18 Note 11 Note ll Note 17 Note 19 Note 12 Note 12 VARIABLE INSTRUMENT RANCE I

DESCRIPTION I TYPE I

GORY I EXISTINC IREQUIRED SCHEDULE/

~

JUSTIPICATION PT-07-4B Pf-07-4A I PR-07-4B/

I 58 I

I Pl-07-4A INote 1 IMA I

INote 1

IMB I

I INote 1

IMA I

I I

INote 1

IMB I

I SAS I

SPDS SAS SPDS Yes Yes Yesl Yes YeslRange provided Idoes not cover Ithe lower end Yeslof the required Irange (-5 to I44 psig).

IAdditional Ipressure trans-mitters covers

-5 to 175 psig (see Item Cll).

PT-07-4B will be replaced by the end of the next refueling outage with a qualified transmitter.

PONER DISPLAY LOCATION REDUNDANCE SUPPLY 13 1539M

FLORIDh POHER AND LIGHT ST LUCIE UNIT,NO. 1 REGULA

~ep GUIDE 1+97 REV 3 UMMARY SHEET" VARIABLES

""vMBER 6, 1983 VARIABLE ITEM TAG NO DESCRIPTION cl I45 Core ICore Exit Exit Ther-ITemp mocouple Icc Display h I

Icc Display B I

INSTRUMENT RANGE TYPE I

GORY I EXISTING RE UIRED 1

l32'F to l200'F to I

l2300 F l2300'F Qh REQUIRE-MEHT Comply ENVIRONMENTAL UALIFICATION Note 18 Note ll Note 11 SEISMIC UALIFICATION Note 19 Note 19 Note 19 I Minimum Ifour (4)

Ithermocou-Iples per Ichannel Iper core Iquadrant I

I Icc I Display B

I I

I Icc Display A POHER SUPPLY DISPLAY LOCATION CR C

EO SCHEDULE/

JUSTIPICATION INote 1 I

ISA ISB INote 1 I

Yes ISA I

SAS I

I SPDS I

I INote 1 I

Yes ISB SAS SPDS I Yesl Yesl I

I I

I I

I I

I Yesl Yes IPor the ICC Isystem see INote 23.

Trend linformation is available in SAS.

C2 None IRadioac-tivity Con-centration or Rad Levell in Circula-ting Primary Coolant ll/2 Tech Ispec ILimit to I100 times I Tech Speci ILimitJ Pending the results of the Study regarding Equipment Ihvailability, Ito be completed Iby Dec 1983.

I C3 Pc-I-131 IAnalysis of I

IPrimary ICoolant Pc-ZE-133 I (canna Spectrum) lpc-co-60 PCS-134 C

3 ll to I107 luci/ml I 10 uci/ml I Ito 10 I Ci/ml lor TID 114844 ISource ITerm in ICoolant IVolume N/A N/A N/A N/A Note 2h NS SAS INote 2AI SAS INS I

I I

INote 2hl SAS INS I

I I

INote 2hl SAS INS I Yesl Yesl I

I I

I I Yesl Yes I

I Yesl Yes I

Yesl Yesl PT-1108 (Rcs Pressure)

Icc Display A I

Icc Display B

C4 IPT-1107 IPressurirer Ipressure C

1 IO to 3000 IO to 4000 Ipsia Ipsig Comply Note 16 Note 16 Note ll Note ll Note 17 Note 17 Note 19 Note 19 PT-1108 I PT-1107 I

I I Icc I Display I

I Icc I Display I

Note 1 ISA I

INote 1 I

ISB I

INote 1 B ISA I

Note 1 A

SB SAS SPDS SAS SPDS Yes Yes Yes Yesl Yes Existing range Iconsidered lacceptable Yes pending ATWS disposition.

Por the ICC System see INote 23.

Trend linformation is available in SAS ~

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 RFGULATORY GUIDE 1 ~ 97 REV 3 "PARAHE RY SHEET" TYPE C LES (Cont'd)

DECEMBER 6g 1983 VARIABLE INSTRUMENT RANGE I

I CATE-I ITEMI TAG NO.

IDESCRIPTION ITYPE I

GORY I EXISTING REQUIRED Qh REQUIRE-MENT ENVIRONMENTAL SEISMIC QUALIFICATION QUALIFICATION POWER DISPLAY LOCATION REDUNDANCE SUPPLY SCHEDULE/

JUSTIFICATION C5 PT-07-4A I Containment I

C I

I Pressure I

I l(Mid Range)

I I PT-07-4B PI-07-4A IPR-07-4B/

I 5B 1

IO to 60 Ipsig

-5 psig Ito Designl I Pressure I

I I

I I

I I

I Comply

'Will Comply Comply Comply Note 16 Note 18 Note 11 Note ll Note 17 PT-07-4B Note 19 Pf"07-4A Note 12 PI-07-4A Note 12 I PR-07-4B/

5B Note 1

I IHA I

INote 1

IHB I

I I Note 1

I IMA I

INote 1 IMB SAS SPDS Yes Yes Yes SAS I Yesl S PDS YeslRange provided Idoes not cover Ithe lower end Yeslof the required Irange (-5 to I44 psig).

IAdditional Ipressure trans-lmitters covers I-5 to 175 psig l(see Item Cll).

IPT-07-4B will Ibe replaced by Ithe end of the Inext refueling loutage with a Iqualified Itransmitter.

C6A LT-07-14A IContainment ISump Water ILevel (Nar-LIS-07-14Alrow Range)

LR-07-13/

14A 2

I-7 to 0 ftlNarrow I

lgl IRange I(sump)

Comply Note 16 Note ll Note ll Note 17 Note 17 Note 17 N/A INote 2 I

SAS Ish sPDs I

INote 2 Yes ISA I

INote 2 I

Yes ISA I

Yes Yes C6B ILT-07-13A I Containment I

C I

ILevel I

I l(Wide Range)l ILT-07-13B I

IILIS-07-13AI I

I I

I ILIS-07-13B I I

I I

I ILR-07-13/

I I

14A I

I I

1 I-1 to 26 IWide I Comply Ift El I Range I

l(Plant I

ISpecific)l I

I I

I I

I I

I I

I I

Note 16 Note 16 Note ll Note ll Note ll Note 17 Note 17 Note 17 Note 17 Note 17 I LT-07-13B INote 2 I

I IsA I

I I

I I LT-07-13A INote 2 I

I Isg I

I I

I I LIS-07-13BINote 2 I

I ISA I

I I LIS-07-13AINote 2 I

ISB I

I I

INote 2 I

I Ish I

I I

~

I SAS S PDS Yes Yes Yes Yes Yes SAS I Yes Yes SPDS 1539H

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAME RY SHEET" TYPE C ES (Cont'd)

DECEMBER 6, 1983 VARIABLE ITEM TAC NO.

DESCRIPTION ITYPE INSTRUMENT RANCE Qh CATE-I I RE(IUIRE-IENVIRONMENTAL I SEISMIC I

I POWER I DISPLAY LOCATION I

SCHEDULE/

C7 IRF.-26-58 IContainment IArea IRadiation RE-26-59 IRIS-26-58 I

RIS-26-59 RR-26-58 RR-26-59 3

Il R/hr to ll R/hr tol N/A I10 R/hr I10 P/hr I

H/A N/A IHote 2 I

SAS ISA I

SPDS I

I INote 2

I SAS ISB SPDS I

INote 2

Yes ISA I

INote 2 I

Yes ISB I

I I

INote 2 I

Yes ISA I

I I

INote 2 I

Yes ISB I

I I

Yes Yes Yes Yes C8 IRE-26-35 I

I IRIS-26-35 I

I IRR-26-1D IEffluent C

IRa dios ctiv-lity Noble Icas Efflu-lent from ICondenser Ihir Removal System Exhaust 3

I 101 to I10-6 I 10 CPM luci(cc tol luhich is I10 lequivalentluci/cc Ito ) x Ilo 'o l2 x 10 2 luci/cc N/A N/A N/A INS I

INote 2A INS I

INote 2A INS S PDS Yes Yes N/A INote 2AI SAS I Yesl Yesl C9 PT-1107 I PI'-1108 I

I I Ice I Display I

I Icc IDisplay I

I pressurizer I

I Pressure I(RCS I Pressure)

I I

I Al I

I B

I I

C 1

IO to 3000 IO to 4000I Ipsia Ipsig Comply Note 16 Note 16 Note 11 Note ll Note 17 Note 17 Note 19 Note 19 PT-1108 I

I I PI'-1107 I

I I Icc I Display B I

I Icc I Display A I

I Note 1

I Ish I

INote 1 ISB I

INote 1

I ISA I

INote 1 ISB I

I SAS SPDS Yes Yes Yes SAS I Yesl SPDS Yeslgxisting range Iconsidered

. Iacceptable Yeslpending ATWS IDisposition, IFor the ICC ISystem see INote 23.

Trend information is available in SAS. 1539M

FLORIDA POMER AND LIGHT ST LUCIE UNIT NO.

1 REGULATORY GUIDE 1.97 REV 3 "PARAME RY SHEET" TYPE C ES (Cont'd)

DECEMBER 6, 1983 I

ITEMI TAG NO.

VARIABLE C TE-DESCRIPTION ITYPE I GORY INSTRUMENT RANGE EXISTING REQUIRED Qh REQUIRE-ENVIRONMENTAL MENT QUALIFICATION SEISMIC QUALIFICATION PONER REDUNDANCE SUPPLY DISPLAY LOCATION SCHEDULE/

JUSTIPICATION Hydrogen Sampling

& Analyzerl Cubicle SBI Hydrogen Analyzer Ind 6 IRecording I

ICubicle SAI Cll Hydrogen Analyzer Ind 6 Recording I

Cubicle SBI I

PI'-07-8A IContainment I Pressure l(Hide Range)l Pr-07-88 PIS-07-8A I

PIS-07-SB IPR-07-8A C10 IHydrogen Containment ISampling IHydrogen l& AnalyzerlConcentra-I Cubicle SAI tion l(Capable lof Oper-leting lfrom -5 Ipsig to l44 psig)

IVol I I

I (Capable I

lof oper-lating Ifrom -5 Ipsig to I maximum Idesign Ipressure) 1 I-5 to 175 I-5 psig Ipsig Ito 4 I Comply I

I I comply I

I I Comply I

I I comply I

I I Comply Itimes Design Pressure 1

0 to 10X 0 to 10 I Comply Note ll Note ll I

Note ll Note 11 I For the I Transmitters I

refer to the I

Justificationl Note ll Note ll Note 11 Note 12 Note 12 Note 12 Note 12 Note 17 Note 17 Note 17 Note 17 Note 17 IHydrogen I Sampling I& Analyzer ICubicle SB I

IHydrogen ISampling I& Analyzer ICubicle SA I

I Hydrogen IAnalyzer I lnd 6 IRecording ICubicle SB I

IHydrogen IAnalyzer llnd 6 IRecording ICubicle SA I

I PT-07-8B I

I Pf-07-8h I

I I PIS-07-8B I

I I PIS-07"8A I

I I

I shs I

SPDS INote 2

Ish I

I I

INote 2 ISB I

I I

INote 2 ISA I

I I

I INote 2 ISB I

I I

I I

shs I

sPDs I

I Yes Yes INote 2 I

Ish I

I INote 2 ISB I

INote 2 I

ISA I

I I

INote 2 I

ISB I

I I

INote 2 I

ISA I

SAS SPDS SAS I

SPDS Yes Yes Yes Yesl Yes Yes I I

I Yesl YeslDesign Pressure lis 44 psig.

Yee YeslDesign Pressure Iis 44 psig.

ITransmitters Yeelare qualified Iper IEEE I323-1971 and for thermal aging by analysis.

C12 IRSC-26-L IConteinment I

C IEffluent IRadioactiv-lity - Noble IGases from IIdentified IRelease IPoints I

I8 x 10-8 I10"6 2

luci/cc to luCi/cc l9x10 4 Ito 102 luci/cc luCi/cc I

I N/A Note ll Note 11 N/A N/A INote 2A INs I

INote 2h INS SAS S PDS Yes 1539M

FIORIDA PSKR hND LIGHT ST LUCIE UNIT NO. 1 REG Y GUIDE 1.97 REV 3 "P

SUMMARY

SHEET" LES (Cont'd)

EMBER 6, 1983 ITEMI TAG NO.

fO I Pane I DISPLAY LOCATION I SCHEDULE/

UALIFICATION I UALIFICATION I REDUNDANCEI SUPPLYI IDESCRIPTION ITYPE GORY I EXISTING UIRED MENT VARIABLE INSTRUMENT RANGE Qh I

CATE-I I REqUIRE-IENVIRONMENTAL I SEISMIC I

C13 IRSC-26-1L I

I IRSC-26-1M I

I IRSC-26-2L I

I IRSC-26-2M I

I IRSC-26-3L I

I IRSC-26-3M RSC-26-4L IRSC-26-4M I

I ICT-2 I

I IEffluent C

IRadioactiv-lity - Noble I

IGases (fron I

Ibuildings lor areas Iwhere pene-Itrations land hatches I

lare located,l le.g., sec-londary con-I Itainnent andi lauxiliary Ibuildings land fuel Ihandling Ibuildings Ithat are in I

Idirect con-I Itact with I

Iprinary con-I Itainment 2

I8 x 10~

I10"6 luCi/cc to luCi/cc tol l4 x 103 1103 luCi/cc luCi/cc N/A Note 11 Note 11 Note ll Note ll Note 11 Note ll Note ll Note ll Note ll N/A N/A INote 2hl INS I

I I

INote 2hl INS I

I I

INote 2AI INS I

I I

INote 2hl INS I

I I

INote 2AI INS I

I I

INote 2hl INS I

I I

INote 2hl INS I

I I

INote 2hl INS I

I I

INote 2hl INS I

I I

SAS SPDS SAS SPDS SAS SPDS SAS SPDS SAS SPDS SAS SPDS SAS SPDS SAS SPDS Yes I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl 1539M

FLORIDA POlKR AND LIGHT ST LUCIE UNIT NO. 1 REG Y GUIDE 1.97 REV 3 "P

SUMMARY

SHEET" D VARIABLES CEMBER 6, 1983 I'O to 8000 IO to 110ZI Comply Note 11 I shutdown I

D Dl I FT-3306 I

I I FIC-3306 I

I IFR-3306 I gpm IDesign I

IFlow ICooling IFlow to IRCS Note 11 Note ll VARIABLE INSTRUMENT RANGE Oh I

I CATE-I I REqUIRE-IENVIRONMENTAL I ITEMI TAC NO.

IDESCRIPTION ITYPE I

GORY I EZISTINC I

UIRED I

MENT I UALIFICATION I Note 12 Note 12 Note 12 N/A INote 2 I

Ish I

I I

INote 2 I

Ish I

I I

INote 2 I

SA SAS SPDS Yes Yes Yeel YeslDeeign Flow is I5920 gpm (Refer Ito Item D22 for Icontainment Ispray flow).

sEIsMIG I

I PONER I DISPLAY LOCATION I SCHEDULE/

D2 TE-3303X Shutdown ICool HZ lh loutlet Temp I

TI"3303X ITR-3303Z TE-3303Y I

ITI-3303Y Shutdown Cool HX 1B Outlet Temp I

TR-3303Y D3 LT-3311 ISI Tank lhl ILevel (Ac-Icumulator)

ILIA3311 I

D LT-3331 ISI Tank 1B1 I

D Level (Ac-cumulator)

ILIA-3331 I

I LT-3321 ISI Tank IA2 I

D ILevel (Ac-I Icumulator)

ILIA-3321 2

IO'F to I400 F 140 F to I350'F N/A O'F to 400'F 40'F to 350 F N/A l20 to 60X I

2 10 to 90Z IVolume IVolume l(approx)

I N/A 2

l20 to 60X I10 to 90XI" N/A IVolume IVolume I (approx)

I I

I 2

l20 to 60Z ll0 to 90ZI N/h IVolume IVolume I

I (approx)

Note 16 Note 11 Note ll Note 16 Note 11 Note ll Note 20 Note 11 Note 20 Note 11 Note 20 Note 11 N/A N/A N/A N/A N/A N/A N/h INote 2hl INs I

I I

INote 2AI INS I

I I

INote 2hl INs I

I I

INote 2hl INs I

I Note 2hl Ns I

I INote 2AI INs I

I I

N/A N/A N/A INote 2AI IIA I

'I I

INote 2hl Iza INote 2hl IIA I

I,I INote 2AI IIB I

I

~

I INote 2AI IIB I

I I

INote 2hl I.-.n I

~r SAS I Yeel Yeel SFDS I

I Yes Yes SAS I Yes Yes SPDS Yes SAS I Yeel Yesl Yes SAS I Yesl Yeel I

Yes SAS I Yesl Yesl Yee 1539M

0

PMRIDA POHER AND LIGHT ST LUCIE UNIT NO 1

"P RY GUIDE 1.97 REV 3 SUMHARY SHEET" LES (Cont'd)

EHBER 6, 1983 I

ITEMI TAG NO ILT-3341 I

I I LIA-3341 I

I IPT-3311 I

I IPIA-3311 I

I IPT-3321 I

I IPIA-332L PT-3331 IP IA-3331 I

I IPT-3341 I

I IPIA-3341 VARIABLE TYPE I

IDESCRIPTION I

ISI Tank 1B2 ILevel (hc-Icumulator)

Note 20 INote 2hl INS I

I I

I D

N/A N/A N/A 2

120 to 60Z I10 to 90ll IVolume IVolume l(approx)

INote 2AI INS I

I I

INote 2hl Note 11 I

n N/A N/A N/A 2

IO to 300 IO to 750 I

Ipsig Ipsig ISI Tank lhl IPressure l(Accumula-Itor)

I I

ISI Tank 1A2 IPressure l(hccumula-Itor)

I I

ISI Tank 1B1 IPressure l(hccumula-Itor)

I I

ISI Tank 1B2 IPressure l(hccumula-Itor)

Note 20 INS I

I I

INote 2AI INS I

I I

Note 11 N/A

'Note 2AI 2

IO to 300 IO to 750 I

Ipsig Ipsig I

n N/A N/A Note 20 INS I

I I

INote 2AI IHS I

I I

INote 2hl INS I

Note ll I

n 2

IO to 300 IO to 750 I

Ipsig Ipsig N/A N/A N/A Note 20 I

I INo'te 2hl Note ll INS I

I I

INote 2hl INS I

I I

INote 2AI I

n 2

IO to 300 IO to 750 I

, Ipsig Ipsig N/A N/A N/A Note 20 Note ll INS INSTRUHEHT RANGE I

OA

~cicz-l~

I cz<czcc-Innncccmrrcc I

sczsc<c I

POHER I

GORY I EXISTING I~UIRED I MENT I UALIPICATION I UALIPICATION I REDUNDANCEI SUPPLYI SAS I Yesl Yesl Yes SAS I

Yes Yesl YeslSI tank is Idesigned for l300 psig.

SAS I Yesl Yesl Yes SAS I Yesl Yesl Yes SAS I

Yes Yesl Yesl DISPLAY LOCATION I SCHEDULE/

V-3614 IV-3624 I

I IV-3634 I

I IV-3644 I

I ISI Tank 1A2 I

D IDisch Valve I

I I

ISI Tank 1A1 I

D IDisrh Valve I

I I

ISI Tank 181 I

D IDisch Valve I

I I

ISI Tank 1B2 I

D Inisch Valve I

I I

Closed or Open 7.

IClosed lor Open I

2 IClosed lor Open I

2 IClosed lor Open I

IClosed lor Open I

IClosed lor Open IClosed lor Open I

IClosed lor Open I

I Comply I

I I Comply I

I Comply I

I I Comply I

I Note 8 Note 8 Note 8 Note 8 Note 12 Note 12 Note 12 Note 12 N/A N/A N/A N/A INote 2 ISB I

INote 2 ISA I

INote 2 ISB I

INote 2 ISA I

SAS Yes SAS Yes SAS Yes SAS Yes I Y<.<<l Yes I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I Yesl Yes I

I I

I

- 20 1539H

FIDRIDA POHER AND LIGHT ST LUCIE UNIT NO 1

REG "P

TYPE GUIDE I 97 REV 3 UMMARY SHEET" LES (Cont'd)

BER 6, 1983 VARIABLE INSTRUMENT RANGE

. qh I Ponm I

DESCRPIION ITYPE I GORY I EXISTING IRED I

MENT I UALIFICATION I UALIFICATION I REDQNDANCEI SUPPLYI DISPLAY LOCATION I SCIIHXILE/

D5 FT-2212 IFIA-2212 Boric Acid Charging Flow D

~ 2 IO to 150 IO to 110XI N/A Design Note 16 Note ll H/A N/A INote 2AI INS I

I I

INote 2AI INS I

SAS I Yeel YesIDesign flow is I 132 gpm ~

SPDS Yes I

IFT-3313 I

I I FI-3311 I

I IFR-3313 I

I I

Flow D

I IAI I

I I FT-3321 IHISI I

ILoop I

IFT-3323 I

I I FI-3321 I

I IFR-3323 I

I I FT-3331 IHFSI I

ILoop I

IFT-3333 Flow 1B1 FI-3331 D6 I FT-3311 IHISI Flow I

I Loop IA2 2

IO to 300 lgpm 2

IO to 300 Igpm 2

IO to 300 Igpm I

IO to 110XI N/A IDesign I

I Flow I

I Comply Note ll Note 11 N/A Note ll Comply Note ll IO to llOZI N/

IDesign I

I Flow I

I Comply I

Note ll Note 11 N/A Note ll Note ll Note ll Note ll N/A Note ll I Comply I

I IO to 110XI N/A IDesign I

I Flow I

I Comply N/A Note 12 N/A Note 12 N/A Note 12 N/A Note 12 N/A Note 12 N/A N/A N/A N/A INote 2AI INs I

I I

INote 2 I

IsB I

I' INote 2AI INs I

I I

INote 2 I

IsB I

I I

INote 2hl INs I

I I

IHote 2 I

ISA I

I I

INote 2hl IHs I

I I

INote 2 I

ISA Note 2A Ns INote 2 I

IsB I

I I

INote 2hl SAS SAS Yes Yee SAS SAS Yee Yee SAS Yes I Yesl I

I I

I I Yesl I

I Yesl I

I I

I I Teel Teel I

I Yes I Yes Yee Yeel Yesl Yesl Design flow ie l320 gpm.

IExisting range Yeslwill be changed IO to 400 gpm by Ithe end of the Inext refueling l outage.

FR-3333 I Comply I

I Note 11 Note 12 INS I

INote 2 ISB I

Yes 21-1539M

PIORIDA POHER AHD LIGHT ST LUCIE UNIT NO 1

RRCUIh "p

TYPE GUIDE 1.97 REV 3 UMMARY SHEET LES (Cont'd)

ER 6, 1983 ITEM TAC NO DESCRIPTION ITYPE INSTRUMENT RAKE GORY EXISTINC I

IRED ENVIRONMENTAL I SEISMIC I

I PONER I DISPLAY LOCATION I SCHEDULE/

IFT-3341 I

I IFT-3343 I

I IFI-3341 I

I I FR-3343 INPSI Flow IIoop IB2 I

N/

IO to 300 I

D 2

0 to 110X A

Igpm IDesign I

I Flow I Comply N/A I Comply Note ll Note ll Note ll Note 11 N/A Note 12 N/A Note 12 N/A INote 2AI INs I

I I

INote 2 I

ISA I

I I

INote 2AI INS I

I I

INote 2 I

ISA I

SAS SAS Yes Yes I Yesl I

I I

I I Yesl Yes Design flow is l32O gpm.

IEzisting range Yes lwill be changed IO to 400 gpm by Ithe end of the lnezt refueling outage.

D7 IFT-3312 I

I I FI-3312 I

I IFT-3322 FI-3322 IFT-3332 FI-3332 I FT-3342 I

I IFI-3342 I

I ILPSI Flow ILoop 1A2 ILPSI Flow ILoop 1A1 LPSI Flow Loop lBl ILPSI Flow lloop 1B2 2

IO to 2000 lgpm 0 to 110XI Design Flow N/A D

2 0 to 2000 IO to 110XI gpm I Design I Flow N/A D

2 IO to 2000 IO to 110XI Igpm I Design I Flow N/A D

2 IO to 2000 Io to lloXI N/A Igpm I Design I Flow Note ll Note ll Note ll Note 11 Note ll Note 11 Note ll Note 11 N/A N/A N/A N/A N/A N/A N/A N/A INote 2AI INs I

I I

INote 2AI INS I

I I

INote 2AI INs I

I I

INote 2AI INS I

INote 2A INS I

INote 2AI INs I

I I

INote 2AI INs I

I I

INote 2AI INS I

I I

SAS I

Yes Yes l SAS I Yesl Yesl Yes SAS I Yesl Yes I

I Yesl Yes Yes YeslDesign flow is ll763 gpm per lloop.

FIBRIDA POWER AND LIGHT ST LUCIE UNIT NO 1

"P TYPE CUIDE 1.97 REV 3 UNMARY SHEET LES (Cont'd)

ER 6, 1983 ITEM ThC NO VARIABLE INSIRUMENT RANGE Qh I

PONER I DISPLAY LocATION I scEEDULE/

DEscRIPTIDN ITYPE I coRY I ExlsTINc I

UIRED I MENT I UALIPIcATICN I ALIFIcATICN I REDUNDANcEI sUPPLY JUSTIFICATION CR TSC EOF D8 ILT-07-2A I

I ILT&7-2B I

I ILT-07-2C I

I ILT&7-2D I

I ILIS-07-2A I

IIL~7-2B I

I ILIS-07-2C I

I IL~7-2D I

I IIR-07-2A IRefueling IWater IStorage ITank Level 2

Io to 50 ftlTop to Bottom I Comply Note 11 Note ll Note 11 Note ll Note 11 Note 11 Note 11 Note 11 Note ll Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 N/A INote 1 IMA I

INote 1 IH8 I

INote 1 I

l~

I I

I INote 1 I

IMn I

I I

INote 1 I

IMA I

I I

INote 1 I

IMB I

I I

INote 1 I

lm I

I I

INote 1 I

IMn I

I I

INote 1 I

IMA SAS I Yes spns I'I SAS I Yesl SPDS I

I I

I SAS I Yesl I

I I

I SAS I Yesl Yes Yes Yes Yes Yes Yes 'Ihe range pro-vided covers the useful vol-Yes ume of the tank (2.6Z to 100X nk lof total ta Yes Iheight).

I I

Yesl D9 IAH-101 AH-105 IAH-109 IReactor D

Icoolant Pump l llAl Status I

IReactor D

ICoolant Pumpl llBl Status I

IReactor D

ICoolant Pump I llA2 Status 3

IO to 800A IMotor ICurrent I

I 3

IO to 800A IMotor ICurrent I

I 3

IO to 800A IMotor ICurrent N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Ns Ns Ns Yes SAS Yes SAS Yes SAS Yes Yes I Yesl Yes I

I I

I Yesl Yes IAH-113 Reactor D

Coolant Pumpl llB2 Status I

I I

3 lo to 800A I

I I

Motor Current N/A N/A N/A N/A Ns Yes SAS Yes Yes 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO+ 1 REGUIhTO GUIDE 1 97 REF 3 "P

Y SHEET" TYPE (Cont'd)

DF ER 6, 1983 I

TAG HO IDESCRIPTION I D10 I FT-1402 I

I IFT-1404 I

I I FI-1402 I

I IFI-1404 I

I I FT-1200 I

I IFT-1201 I

I I FT-1202 I

I IFI-1200 I

I I FI-1201 I

I IFI-1202 IFORM I Safety IRelicf I Valves I REqUIRE-IEHVIRONmne.

CATE-I TYPE GORY I EXISTING UIRED I MENT D

2 IO to 100X Iclosed/

I Comply UALIFICATION Note 16 I (Closed INot I to Open)

IClosed Note 16 Note ll Note 11 D

2 IO to 100X Iclosed/

I Comply Note 16 I (closed INot Ito Open)

Iclosed Note 16 Note 16 Note 11 Note 11 Note ll SBISHIC UALIFICATION Note 17 Note.17 Note 17 Note 17 Note 17 Note 17 Note 17 Note 17 Note 17 Note 17 N/A N/A

'Hote 2hl Ils I

I I

INote 2AI

'IB I

I I

INote 2hl IIs I

I I

INote 2AI Ils I

I I

IHote 2AI Irs I

I I

INote 2hl IIB I

I I

INote 2A,I 1?B

=

I I

I INote 2AI IIB I

I I

INote 2hl IIB I

I

=

I INote 2hl SAS SPDS SAS SPDS Yes Yes SAS SPDS SAS SPDS SAS SPDS Yes Yes Yes I Yesl I

I I

I I Yes l I Yesl I

I I

I I Yesl I

I I

I I Yesl YeslTo achieve a

Ihigh quality lmeasurement Yeslqualified lequipment was lused for this lnonsafety Imeaeurement.

Yesl I

I Yee I I

I Yes l I

POHER I DISPLAY MCATION SCHULE/

IIB Dll ILT-1110X IPressurizer I

ILevel l(Arrow LT-1110Y Range)

LIC-1110X I LIC-1110Y ILR-1110 Comply IO to 100X I

I Comply Comply I comply 1

ll75" to ITop to I Comply l349" WC I Bottom Note 16 Note 16 Note 11 Note ll Note ll Note 17 Note 17 Note 12 Note 12 Note 12 I LT-1110Y I

I I LT-1110X I

I I LIC-1110Y Note 2A IA INote 2AI IIB I

I I

INote 2AI IIA Note 2A IA LIC-1110X Note 2A IB SAS I Yes SPDS I

I SAS

[ Yesl SPDS Yes Yes Yes Yes A wide range Hon-Safety IChannel is also Yes lavailable.

The Iwide range Ichannel meets Ithe required Irange (cold Icalibrated).

24

PLORIDA POlHR AND LIGHT ST LUCIE UNIT NO+ 1 REGUIATO UIDE 1 97 REV 3 "P

Y SHEET" TYPE D (Cont'd)

D 6i 1983 VARIABLE DESCRIPTION TYPE I GORY I EXISTING I REQUIRE-IEmiRONMENTAL I SEISMIC I

I PONER I DISPLAY MCATION Snn am'/

JUSTIPICATION D12 AM-943 AM-944 IPreseurirer I

D Heater Status 2

0 to 150A Electric I

N/A Current Note 11 Note ll N/A N/A NS NS SAS Yesl Yesl the CR only llocal indica-tion provided.

I Yesl Yes No continuous I

I indication in I

D13 ILT-1116 IQuench I

I Tank I

I Level ILIA-1116 D

3 I0 to 100X ITop to I Bottom I

N/A N/A N/A N/A INote 2AI INS I

I,I INote 2AI INS I

SAS Yes I Yeel YeslThe range is I9,5Z to 90.5I lof top to Ibottom of the Iquench tank.

I D14 TE-1116 Quench ITank ITemperature I

ITIA-1116 I

I I

D 3

O'P to 350'F 50'F to 750'P N/A N/A N/A N/A INote 2hl SAS I

INS I

I I

INote 2AI Yes INS Teel YeslEzisting range lis acceptable Ibased on Irupture disc leetting for lsaturated steam Iconditions.

I D15 PT-1116 I

IPIA-1116 Quench Tank I

Pressure 3

0 to 100 IO to Ipeig I Design IPreeeure I

N/A N/A N/A N/A INote 2AI SAS I

INS I

SPDS I

I INote 2AI Yes INS I

Yesl Yesl Design pressure lie 100 psig.

D16 ILT-9013A I

SG 1Al I

I Level I

I (Narrow ILT-9013B I Range)

I I

ILT+013C LT&013D D

1 IO to 132 I prom Tubel Comply Inches ISheet to I

WC I Separa-I Itore I Comply I

I I Comply I

I I Comply Note 16 Note 16 Note 16 Note 16 Note 17 Note 17 Note 17 Note 17 I LT&013D I

I I LT+013C I

I I LT-9013B I

I I LT&013A INote I I

IMA I

INote 1 IMB I

INote 1 I

IMC I

I I

INote 1 I

SAS I Yesl SPDS SAS SPDS Yes SAS SPDS Yes SAS SPDS I Yeel Yeel Yes h wide range Non-Safety Channel is also Yes available.

The lwide range channel meets Yes the required range (cold Icalibrated). 1539M

PLORIDA POWER AND LIGHT ST LUCIE UNIT NO. 1 GUIDE 1.97 REV 3 UMMARY SHEET" ABLES (Cont'd)

ER 6, 1983 ITEM TAG NO.

VARIABLE INSTRUMENT RANCE DESCRIPTION TYPE CATE-I GORY I EXISTINC RE UIRED I

I RF4UIRE-IENVIRONMENTAL I SEISMIC I

POWER I DISPLAY LOCATION I SCHEDULE/

JUSTIFICATION LIC-9013h I

SC lhl I Level I (Narrow LIC-9013B Range)

LIC-9013C LIC-9013D IR-9013h 1

IO to 100X IProm Tubel ISheet to I

ISepara-Itors I

I I

I I

I I

I I

I Comply Comply Comply Comply Comply Note 11 Note ll Note 11 Note ll Note 11 Note 12 Note 12 Note 12 Note 12 Note 12 LIC-9013D LIC-9013C LIC-9013B LIC-9013A INote 1 I

IMA I

I I

INote 1 I

IMB I

I I

INote 1 I

IMC I

I I

INote 1 I

IMD Note 1 MA Yes Yes Yes Yes Yes LT-9023h LT-9023$

LT-9023C I

I ILT-9023D I

LIC-9023A I

LIC-9023$

SC 1B1 Level (Narrow Range) 0 to 132 IPlant Inches ISpecific IO to 100X I

Comply Note 16 Comply Note 16 Comply Note 16 Comply Note ll Comply Note 11 Comply Note 16 Note 17 Note 17 Note 17 Note 17 Note 12 Note 12 I LT-9023D I

I I LT-9023C I

I I LT-9023B I

I I LT-9023A I

I I LIC-9023D LIC-9023C INote 1 IMA I

I I

INotc 1 I

IMB I

INote 1 MC Note 1 MD Note 1 MA Note 1 MB SAS I

SPDS I

I SAS I

SPDS I

I SAS I

SPDS SAS SPDS Yes Yes Yes I I

I Yesl Yes Yes Yes h Wide Range INon-Safet IChannel is also Yeslavailable.

The IWide Range Channel <<acts Yes the Required Range (cold calibrated)

~

Yesl LIC-9023C LIC-9023D I Comply I

I I Comply I

Comply Note ll Note 11 Note ll Note 12 Note 12 Note 12 I LIC-9023$

I I

I LIC-9023h I

INote 1 IMC I

INote 1 I

IMD Note 1 Mh Yes Yes Yes 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO. 1 REGVIA "P

TYPE VIDE 1 97 REV 3 UMMARY SHEET" LES (Cont'd)

ER 6, 1983 ITEM TAG NO.

DESCRIPTION INSTRUMENT RANGE CATE-I TYPE GORY I EXISTING RE UIRED ENVIRONMENTAL ALIFICATION SEISMIC ALIFICATION POHER SUPPLY DISPLAY LOCATION CR TSC EOF SCHEDULE/

JUSTIFICATION PI-8013 B I

IPI&013C I

I IPI-8013D PR-8013A IPT-8023h I

I IPT&023B I

I I PT-8023C I

I IPT-8023D SG 1B Pressure PI"8023A IPI-8023B I

D17 PT-8013A ISG lh IPressure PT&013B I

I PT&013C I

I IPT-8013D I

I IPI&013h 2

I I

D 2

0 to 1200 IFrom AIM psia IPressure I

Ito 20X I

labove thel ILowest I

Isafety I

IValve I

Isetting I

Comply Comply Comply I

I I

I I

I I

I I

I I

I I

I I

I I

I I

From ATM I Pressure I

lto 20X I

labove thel ILowest I

ISafety IValve ISetting Comply Comply Comply Comply Comply Comply 0 to 1200 peia Comply Comply Comply Comply Comply Comply Note 16 Note 16 Note 16 Note 16 Note 11 Note 11 Note 11 Note ll Note 11 Note 16 Note 16 Note 16 Note 16 Note ll Note 11 Note 17 Note 17 Note 17 Note 17 Note 12 Note 12 Note 12 Note 12 Note 12 Note 17 Note 17 Note 17 Note 17 Note 12 Note 12 N/A N/A SAS I Yesl Yesl SPDS I

I I

I I

I SAS I Yesl Yesl SPDS I

I I

I I

I SAS I Yeel Yeel SPDS I

I I

I I

I SAS I Yeel Yesl INote 1 I

IMA I

I I

INote 1 I

INB I

I I

INote 1 I

IMC I

I I

INote 1 I

IMD I

I I

lkote 1 I

IMA I

I I

INote 1 I

IMB I

I I

INote 1 I

IMC I

I I

INote 1 I

IMD I

I I

INotc 1 I

IMA I

INote 1 IMA I

INote 1 IMB I

INote 1 I

IMC I

I I

INote 1 I

IMD I

I I

INote 1 I

I I

Note 1 I

MB I

Yes Yes Yes Yee Yes SPDS Yes Yes SAS I Yesl Yes SPDS I

I I

I SAS I Yesl Yesl SPDS I

I I

I I

I SAS

.I Yesl Yesl I

I I

I I

I SAS I Yeel Yesl 1539M

PLORIDA POHER AND LIGHT ST LUCIE UNIT NO. 1 REGULA "P

TYPE VIDE 1 97 REV 3 Y SHEET" LES (Cont'd)

BER 6, 1983 TAC NO.

PI-8023C IPI&023D I

I IPR&023h SG 1B Pressure D

2 VARIABLE DESCRIPTION TYPE GORY INSTRUMENT RANGE gh EZISTINC 0 to 1200 From ATM Comply psia Pressure to 20Z labove thel Comply I Lowest I

Isafety I

IValve I Comply ISetting ENVIRONMENTAL UALIPICATION Note ll Note ll Note 11 SEISMIC VALIPICATION Note 12 Note 12 Note 12 N/A I

PONER SUPPLYI INote 1 IMD I

INote 1 MA Note 1 I

MC I

I I

DISPIAY IOCATION I SCHEDULE/

TSC EOF JUSTIFICATION Yes Yes Yes 8-1A ISafet /

D18 FT-0 y Re-Ilief Valve IPositions IFT&8-IB lor Main I

ISteam Flow I

IF1&8-Ih I

I IF1&8-IB 2

0 to'losed-l6 z 106 INot Ilb/hr IClosed N/A Note 22 Note 22 Note ll Note ll N/A N/A Note 6 INS I'Note 6 INS I

INote 6 INS I

INote 6 INS I

SAS I Yesl Yesl SPDS I

I I

I I

I SAS I Yesl Yesl SPDS Yes Yes D19 IFT-9011 I

I IFIC-9011 I

I IFR-8011/

9011 I

I FT-9021 I

I IFIC-9021 FR-8023/

9023 ISG lh Feed-Iwater Flow ISC 1B Feed-lwater Flow 3

IO to IO to 110ZI l6 z 106 IDesign Ilb/hr Flow N/h 3

IO to IO to 110ZI N/h I6 z 106 IDesign Ilb/hr IFlow N/h N/h N/A N/A N/A N/A INote 6 I

INS I

I I

INote 6 I

INS I

I I

INote 6 I

INS I

I I

INote 6 I

INS I

I I

INote 6 I

INS I

INote 6 INS I

SAS I

Yes Yes SAS I

Yes Yesl Yes I Yes I Yes Yes lDesign Flow is l6.2 z 106 lib/hr. 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO. 1 REGULA "P

TYPE VIDE 1.97 REV 3 Y SHEET" LES (Cont'd)

ER 6, 1983 TAG NO.

DESCRIPTION TYPE INSTRUMENT RANGE CATE-GORY EXISTING RE UIRED Qh REQUIRE-ENVIRONMENTAL MENT UALIFICATION SEISMIC UALIPICATION REDUNDANCE POWER SUPPLY DISPLAY LOCATION CR TSC EOF SCHEDULE/

JUSTIFICATION D20 IFI&9-2A I

I I FR&9-2A I

I IFT-09-2B I

IIFI-09-2B I

I IFR&9-2B I

I IFT&9-2C I

I IFI&9-2C I

I I FR-09-2C Ihuxiliary D

IFeedwater IFlow HDR 1B I

Ihuxiliary IFeedwater IFlow HDR 1C FT&9-2A Auxiliary IFeedwater IFlow HDR lh I

0 to 400 gpm 0 to 110X Design Flow 2

IO to 400 IO to 110XI Igpm IDesign IFlow 2

IO to 600 IO to 110XI Igpm I Design I

I Flow N/A N/A N/A Note 16 Note ll Note 11 Note 16 Note ll Note 11 Note 16 Note 11 Note 11 N/A N/A N/A N/A N/A N/A INote 2A IIA I

INote 2AI IIA I

I I

INote 2hl IIA I

I I

INote 2hl IIB I

I I

INote 2hl IIB I

I I

INote 2AI IIB I

I I

!Note 2AI IIAB I

I I

INote 2hl IIAB I

I I

INote 2hl IIAB SAS I Yesl Yes Yee SAS I

Yes Yee SAS I Yeel Yes Yes Yes lDesign flow is l320 gpm ~

YeslDesign flow is 1320 gpm.

YeslDesign flow is I500 gpm.

D21 LT-12-11 ILT-12-12 I

IILIS-12-11 I

I I

I I

ILIS-12<<12 I

I I

I I

Condensate IStorage ITank Level D

1 0-40 ft I

Plant I

Specific Comply Note 11 Note 11 Note 11 Note ll Note 17 Note 17 Note 17 Note 17 I LT-12-11 I

I I LIS-12-12 I

I I LIS"12-11 I

I Note 2 SB INote 2 I

ISA I

I I

INote 2 I

ISB I

I I

LT-12-12 Note 2 ISA SAS SPDS SAS I

SPDS Yee Yee Yes Yesl Yes The range pro-vided covers 3.4X to more Yeslthan 100X of Ivessel height.

ITrend informa-Ition is avail-lable in SAS.

- 29 1539M

FLORIDA POMER AND LIGHT ST LUCIE UNIT NO. 1 REGULATOR IDE 1.97 REV 3 "P

Y SHEET" TYPE D ES (Cont'd)

D

~ER 6, 1983 ITEM TAG NO.

DESCRIPTION TYPE CATE-GORY INSTRUMENT RANGE EXISTING

~ RE UIRED Qh REQUIRE-ENVIRONMENTAL MENT VALIPICATION SEISMIC DALIFICATION PONER I DISPIAY LOCATION I SCHEDULE/

REDUNDANCE SUPPLY TSC EOP JUSTIFICATION D22 FT-07-Ih F1&7-lh I

IFR-07-lh Containment Spray from Shutdown Heat Ex-changer lh FT&7-IB Containment ISpray from IShutdown F1&7-IB IHeat Ex-Ichanger 1B I FR-07-1B 2

I 0 to 3500 0 to 110X gpm IDesign IFlow I

0 to 3500 0 to 110X 2

Igpm IDesign I Flow N/A Note 16 Note ll Note 11 Note 16 Note 11 Note 11 N/h N/A N/A N/A Note 2A SAS IIA' INote 2AI Yes IIA I

I INote 2hl Yes IIA I

I I

INote 2AI SAS IIB I

I I

INote 2hl Yes IIB I

I I

INote 2hl Yes IIB Yesl Yes Design flow is l2970 gpm.

I Yesl Yes D23 TE-25-1 TE-25-2 ITE-25-3 ITE-25-5 I

I ITE-25-6 TE-25-7 Heat Removall D

Iby the Con-I Itaiament Fanl I

IHeat Removal l I

Isystem 2

IO'F to l300'F IPlant ISpecific N/A IRefer to IJustification I

Column N/A N/A NS NS NS NS NS NS The thermo-Icouple assem-Iblies have been Ipurchased as lnonsafety Iequipment.

IThey do aot Iperform a Isafety function Iduring or after laa accident.

Ihfter an ac-Icident, all Ifour contain-Iment'an cool-lers are started lead remain op-erational.

ITE-25-8 I

I ITR-25-1 I

I Note ll NS I

Yes I Yesl YeslSAS (

INote 2A Alarm INS I

SAS I

I IPoints only)

I I

I I

I 30 1539M

l 0

SECTION VI LIST OP SYSTEMS REQUIRING ADDITIONS, MODIPICATIONS OR ANALYSIS

The following is a list of the St. Lucie Unit ¹1 instrument system, which as a result of this evaluation, requires addition, modification or analysis.

Item B-14 Containment Isolation Valve Position The following valve limit switches willbe qualified per our commitment in 10 CFR 50-49 report:

FCV-23-3 FCV-23-5 FCV-23-7 FCV"25-1 FCV"25-2 FCV-25"5 FCV-25%

FCV"26-2 FCV-26-4 FCV-26"6 I-FSE-27-1 I-FSE-27-2 I-FSE-27-3 I-FSE-27-4 I-FSE-27-5 I"FSE-27-6 I-FSE"27-7 I-FSE-27-8 I-FSE-27M I-FSE-27-10 I-FSE-27-11 LCV7-11A LCV&7-1lB MV-15-1 MV"18-1 V-2505 V-5200 V-5201 V-5202 V-5203 V-5204 V-5205 V-6301 V&302 V&554 V&555 V-6741 2.

30 4,

Item B-14 Containment Isolation Valve Position The following valves will be equipped with qualified limit switches and valve position indication willbe provided in the control room by the end of the next refueling outage:

I-FCV&3-1E I"FCV<3"1F Item C-2 Radioactivity Concentration Level in primary coolant.

A study regarding equipment availablity willbe completed by December 1983.

Item D-6 HPSI Flow The following transmitter willbe recalibrated to 400 gpm by the end of the next refueling outage:

FT-3311 FT-3313 FT-3321 FT-3323 FT-3331 FT-3333 FT-3341 FT-3343

Item D-11 Pressurizer Level Cabling for the pressurizer level instrument loops will be up-graded to Class IE by the end of the next refueling outage.

Item D-15 Quench Tank Pressure Existing range for this instrumentation is being changed to (0-100 psig) dur ing the present refueling outage.

Item D-25 Containment Sump Water Temperature Temperature elements willbe qualified per our commitment in 10 CFR 50-49 report:

TEOV-5A TERV-5B Item D-32 Decay Tank Gas Pressure Existing pressure gauge ranges will be changed to 300 psig by the end of the next refueling outage:

PI-6650 PI<651 PI-6652 Item D-33 Emergency Ventilation Damper Position Position indication for the following damper willbe provided in the control room by the end of the next refueling outage:

D1, D2, D3, D4, DVA, DVB, D8A, D8B, D11A, D11B.

Item D-33 Emergency Ventilation Damper Position The following damper limit switches willbe qualified per our commitment in 10 CFR 50-49 report:

D-12A, D-12B, D-13, D-14, D-15, D"16 Item B-15 and C-ll Containment Pressure Mid Range and Wide Range.

The transmitters PT07-4B and PT07-8A willbe replaced with Rosemount model by the end of the next refueling outage.

Item B-1 Neutron Flux.

Seismic analysis for the detector holders will be performed by the end of the next refueling outage.

ICCS qualification report is expected to be received from the vendor by January 31, 1984.

-8"

SECTION VII REFERENCES

REFERENCES Regulatory Guide 1.97, Rev. 3 10 CFR 50.49 Regulatory Guide 1.89 Regulatory Guide 1.100 NUREG 0737, Supplement 1

NUREG 0588 IEEE-323, 1974 IEEE-344, 1975

SECTION VIH CONCLUSIONS

CONCLUSIONS Based on the information presented in this report, St. Lucie Plant Unit S1 willconform with the requirements of Reg. Guide 1.9V, kev. 3 by the end of next refueling outage.

2.

For some instrumentation which does not fully comply with the requirements of Reg. Guide 1.97, Rev. 3, a justification has been provided (Section V).

"10-

FLORIDA POlKR AND LIGHT ST LUCIE UNIT NO. 1 "P

TYPE GUIDE 1.97 REV 3

SUMMARY

SHEET" LES (Cont'd)

ER 6, 1983 ITEM D24 TAG NO.

TEE)7-3h YE&7-38 TI&7-3A ITR&7-3B/

I I

5B I

VARIABLE DESCRIPTION Containment Ihtmosphere ITemperature TYPE 2

50'F to I350'F 40'F to I400'F INSTRUMENT RANGE CATE-GORY EXISTING RE UIRED Comply Note 8 Note 8 Note ll Note 11 Qh REQUIRE-ENVIRONMENTAL MENT UALIFICATION SEISMIC UALIFICATION Note 12 Note 12 Note 12 Note 12 N/A INote 1 I

I MA I

I I

INote 1 I

I MB I

I I

INote 1 I

IMA I

I I

INote 1 IMB I

PONER REDUNDANCE SUPPLY SC11EDULE/

JUSTIPICATION SAS SPDS Yes Yes I No I

I I

I I

I Yesl No IThe range pro-Ivided is ade-Iquate'ecause Yeslthe mazimum MSLB tempera-ture is 290'F.

DISPLAY LOCATION CR TSC EOP D25 ITE&7-Sh I

I ITE-07-5B IITI&7-Sh I

I ITR&7-3B/

5B IContainment ISump Mater ITemperature I

2 I50'F to I50 F to I Comply I350'F I250'F Note 10 Note 10 Note 11 Note ll Note 12 Note 12 Note 12 Note 12 N/A INote 1 IMA I

INote 1 IMB I

INote 1 IMA I

INote 1 IMB I

SAS Yes Yes I No I No I

D26 IFT-2212 IMakeup I

I Flow-In I

IFIA-2212 2

IO to 150 IO to 110II Igpm IDesign I Flow N/A Note 16 Note 11 N/A N/A INote 2AI INS I

I I

INote 2hl INS I

SAS I

SPDS Yes Yesl YeslDesign Plow is ll32 gpm.

D27 FT-2202 Letdown Flow FIA-2202 2

IO to 140 0 to 110Z Design Flow N/A Note ll Note 11 N/A N/A INote 2hl INS I

I I

INote 2AI INS I

SAS I

SPDS Yes Yes Yes Design Plow is 132 gpmo D28 ILT-2226 IVolume Con-Itrol Tank ILevel LIC-2226 D

2 IO to ITop to 1125" NC I Bottom I

I lo to 100I I

I

'I I

I N/A I

Note 11 Note ll N/A N/A INote 2hl INS I

I I

INote 2hl INS I

I I

SAS I

Yes YeslRange is ade-Iquate to cover Ithe tank Ivolume ~

I I 1539M

0

PLORIDA POWER AND LIGHT ST LUCIE UHIT NO 1

REGUIA Wp TYPE UIDE 1 97 REV 3 Y SHEET" LES (Cont'd)

ER 6, 1983 ITEM VARIABLE TYPE TAG NO+

DESCRIPTION INSTRUMENT RANGE Qh EXISTING EHVIRONMEHTAL ALIFICATION SEISMIC ALIPICATION POWER REDUNDANCE SUPPLY DISPLAY LOCATION TSC EOP SCHEDULE/

JUSTIFICATION D29 TE"14-3A ITE-14-3B I

I ITR-25-1 Component Cooling IWater Temp Ito ESF ISystem D

2 O'F to 300 F

40'F to 200'F N/A Note 11 Note 11 Note 11 N/A N/A INote 2A INS I

INote 2AI SAS INS Yes I

INote 2AI INS I

I I

I Yesl YeslSAS (Alarm IPoints only)

I D30 IFT-14-1A IComponent ICooling Water Flow FT-14-1B to ESF System IFIS-14-lh I

I I

I I

I FIS-14-1B I

D 2

IO to IO to llOZI I15,000 gpmf Design I Flow N/A Note 11 Note ll Note 11 Note 11 N/A N/A I Yesl YeslDesign flow I

I lis 8500 gpm.

INotc 2hl Yes IIA I

I I

INote 2hl Yes IIB I

INotc 2AI SAS IIA I'

I INote 2h SAS f Yesl Yes IIB I

D31 ILT&607 LT&608 ILT&609 I

I ILT&610 I

I ILIA"6607 Lib&608 LIAM609 Lib&610 IHigh Level D

I IRadioactive I

I ILiquid I

I IHoldup Tank I

llA,18,1C, I

I llD Level 3

IO to 524" ITop to fBottom IO to 1002 I

I N/A N/h N/A N/A INote 2hl INS I

I I

INote 2hl IHS I

I I

INote 2hl INS I

I I

INote 2AI IHS I

I INote 2AI INS I

INote 2A INS I

INote 2hl INS I

I I

INote 2hl INS I

I I

Yesl Yes SAS Ycs Yes Yes Yesl Yes Yes Yes SAS I Ycal I

I I

f SAS I Yesl

-. 32-1539M

FLORIDA POMER AND LIGHT ST LUCIE UNIT No+ 1 REGULA GUIDE 1.97 REV 3 "P

UMMARY SHEET" TYPE ABLES (Cont'd)

"HBER 6, 1983 ITEH TAC NO.

INSTRUMENT RANGE CATE-I DESCRIPTION TYPE GORY I EXISTINC R

UIRED EHVIRONHENTAL UALIFICATION SEISMIC UALIFICATION I

POMER DISPLAY LOCATION I SCHEDULE/

JUSTIFICATION SUPPLY CR TSC EOF D32 IPI-6650 I

I IPI&651 PI-6652 IDecay Tank ICas Pressurel 3

lo to 200 Io to 150XI Ipsig IDesign IPressure N/A N/A N/A N/A N/A No No No No I No I

I I No I No I

I I

I I No I No Design Pressure is 200 psig.

Only local lindication lis provided.

IExisting range Iwill be changed IO to 300 psig Iby the end of Ithe next re-Ifueling outage.

D33 IEHERGENCY VENTILATION IDAMPER POSITION D33h D-1 ID-2 ID-&

D33B D-Sh D-5B D-6B hir Supply Dampers to IECCS Pump Rooms h & B IECCS Area IIsolation IInlet and loutlet I Dampens 2

INo Indi-I Icating I

Lights open/

Closed Status 2

IOpen/

Open/

IClosed Closed IStatus I Status I Mill I Comply I

I Mill I comply I

I Mill I Comply I

I Mill I Comply I

I comply I

I I Comply I

I I Comply I

I I comply I

I Note 18 Note 18 Note 18 Note 18 Note 8 Note 8 Note 8 Note 8 Note 19 Note 19 Note 19 Note 19 Note 12 Note 12 Note 12 Note 12 N/A N/A Note 2 ISA I

INote 2 I

Ish I

I I

INote 2 I

Isg I

I I

INote 2 I

IsB I

I I

INote 2 I

Ish I

I I

INote 2 I

Isg I

I I

INote 2 I

ISA I

INote 2 ISA I

No No SAS Yes SAS Yes SAS Yes Yes I Yesl I

I I

I I Yesl I.

I I

I No I No I

I No I No I

I I

I I

No I No I

I I

I I

SAS I Yesl Yes No CR Indication I+ill be rovi Yes Yes Yesl I

I p

d-Ied by the end No lof the next re-lfueling outage.

I No I

I I

No I

I I

Yes I

- 33 1539M

PLORIDA POWER AND LIGHT ST LUCIE UNIT NO+ 1 REG "P

TYPE GUIDE 1 97 REV 3

SUMMARY

SHEET" LES (Cont'd)

"EMBER 6, 1983 ITEM TAG NO.

D-7A ID-78 I

I ID-BA I

I ID-BB I

I ID-9A I

I I D-9B ID-11B I

I D33CID-12A I

I ID-12B I

I D33DID-13 I

I ID-W I

I ID-15 I

I ID-16 I

I D33EID-17 D-18 ID-19 I

I DESCRIPTION ECCS Area Isolation IInlet end

)Outlet IDampers I

I I

)Pipe Tunnel I

D IDampers to I

INormel ISystem I

I I

I I ECCS HVE-9A, I D

l98 Suction

)

I& Discharge IDampers Ibefore and Isfter HEPA IFilter

)Control Room)

Emerg Fil-tration Fan HVE-13h, 13B ISuction IDampers INSTRUMENT RANGE GORY EXISTING No Indi-cating ILights Open/

Closed Status IOpen/

IClosed Istetus INo Indi-

)cating

)Lights I

I I

2 lopen/

IClosed

)Status I-I I

2 IOpen/

IClosed IStatus lopen/

IClosed lstatus lopen/

)Close IStatus 2

IOpen/

)Open/

Closed Closed Status Status Will I Comply I

I Will I Comply I

I Will I Comply I

I Will I Comply I

I Comply Comply Will Comply I

I Will I Comply I

I Comply I

I I Comply I

I I Comply I

I f Comply I

I I Comply I

I I Comply I

I I Comply Comply Comply ENVIRONMENTAL UALIPICATION Note 18 Note 18 Note 18 Note 18 Note 8 Note 8 Note 18 Note 18 Note 10 Note 10 Note 10 Note 10 Note 10 Note 10 Note 11 Note 11 Note ll SEISMIC ALIPICATION Note 19 Note 19 Note 19 Note 19 Note 12 Note 12 Note '19 Note 19 Note IZ Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 N/A N/A N/A POWER SUPPLY INote 2 I

Ish I

I INote 2 I

IsB I

I I

)Note 2

I Ish I

I I

INote 2 I

Isg I

I I

)Note 2 I

ISA I

)Note 2 ISB I

INote 2 I

ISA I

I I

INote 2 I

Isg I

I I

)Note 2 I

Ish I

I I

INote 2 I

IsB I

I INote 2 I

Ish I

I I

)Note 2 I

IsA I

I I

)Note 2 ISB I

I I

INote 2 I

ISB I

INote 2 IshB I

INote 2 I

Isg I

I I

INote 2 I

Ish I

I I

SCHEDULE/

JUSTIPICATION No No SAS Yes SAS Yes No No SAS Yes SAS Yes Yes I No I

I I

I I No I

I I

I I No I

I I

I I

I No I

I I

I I Yes)

I I

I I

I Yea f I

I I

I I No I

I I

I I

I No I

I I

I I Yes)

I I

I I

I Yes)

I I

I I

I No I

I I

Yes INo I I

I I

I I No I

I I

Yes Yes SAS Yee I

I INol I

I I

I Yes)

No ICR Indication

)will be provid-led by the end No lof the next re-Ifueling outage.

I No I

I I

No I

I I

Yes)

Yee No ICR Indication

)will be provid-led by the end No lof the next re-

)fueling outage.

I Yes I I

I Yes I I

I No I

f I

No I

I I

No I

I I

No I

I I

Yeel SAS Yes Yes Yee SAS Yes Yes Yee 1539M DISPLAY LOCATION TSC EOP

PLORIDA PONER AND LIGHT ST LUCIE UNIT NO. 1 REGULA Op TYPE GUIDE 1.97 REV 3 UMMARY SHEET" ABLES (Cont'd)

"" MBER 6, 1983 ITEM TAG NO VARIABLE CATE-DESCRIPTION TYPE GORY EXISTING UIRED ENVIRONMENTAL UALIFICATION SEISMIC UALIFICATION POR?R REDUNDANCE SUPPLY DISPLAY LOCATION I SCHEDULE/

JUSTIFICATION D34 ISTATUS OF STANDBY POlKR AND OTHER IENERGY SOURCES IMPORTANT TO SAFETY D34A MOD 4 D34B D34C VM/916 IVM/917 I

MOD 5 vM/eeel I

I IIStart-up/

IStandby ITransfornersl Iprius ry IBreakers l(240 kV)

I IIStart~p/

IStandby ITransfornersl

, Iprinary I

IVoltage I

l(East I

liest 240 kV I IBus)

IIstart-up/

IStandby ITransforner ISecondary Open/

Close Plant ISpeci fic 0 to 5.25 IPlant kV ISpecific 2

IO to 300 IPlant IkV ISpecific N/h

<</h N/A Note 11 Note ll Note ll Note ll Note ll Note 11 Note 11 N/A N/A Nlh N/A NS NS N/A INS I

INS I

INS I

INS I

N/A INS Yes Yes" Yes Yes SAS Yes Yes Yes I No I No I

I I

I I No I No I

I I

I I No I No I

I I

I I No I No I

I I

I I Yesl Yesl No No No No D34DIAM/916 I

IAM/917 IVoltage l(4 kV Buses Ilh2 & 1B2 IVoltage)

IIStart-up/

IStandby ITransformer ISecondary ICurrent l(4 kV Buses llA2 & 182 ICurrent)

I 2

IO to I3000 A IPlant ISpecific N/A Note ll Note ll N/A N/h INS I

INS Yes I No I No I

I I

'I Yes I No I No I

35 1539M

I I

f I

PMRIDA PONER AND LIGHT ST LUCIE UNIT NO. 1 REG "P

TYP GUIDE 1.97 REV 3 SUMHARY SHEET" LES (Cont'd)

".EHBER 6i 1983 VARIABLE ITEN TAG NO DESCRIPTION TYPE CATE-GORY INSTRUMENT RANGE EXISTING RE IRED Qh REQUIRE-ENVIRONMENTAL HENT VALIPICATION SEISHIC ALIFICATION I

PONER I DISPLAY LOCATION SCHEDULE/

D34GI4 kV Bus llh2 Bkr 4 kV Bus 1B2 Bkr D34H 4 kV Bus llh3 Bkr I

I4 kV Bus I1B3 Bkr D34I AH/942 IVH/942 I

IIIL/942, I

D34JIVM/954 VM/964 In/954 I

IL/964 D34E 4 kV Bus lA3 Bkr l4 kV Bus llB3 Bkr I

I D34PI4 kV Bus I 1AB IBreakers l4 kV Buses I1A3 & 1B3 I

l4 kV Bus llh2 & 1B2 IBkr Status Ito 4 kV Buses lh3 &

1B3 14 kV Bus Ilh3 & 1B3 IBkr Status Ito 4 kV IBus 1AB I

l4 kV Bus 1AB

IVoltage, ICurrent IStatus I

I D

I I

I I

I I

D I

I I

I I

I D

I I

I I

l4 kV Bus llA3 & 1B3 IVoltage 4 kV Bus lh3

& IB3 IBkr Status I from 4 kV IBuses 1A2 &

IlB2 I

l4 kV Bus 1ABI D

I IBreakers I

IStatus from I

I Open/

Close IPlant Specific Comply 2

lopen/

Iclose IPlant ISpecific I comply 2

lopen/

IClose IPlant ISpecific 2

I IPlant ISpecific Open/

Close I

Iplant ISpecific 2 'O to I400 A lo to I5250 V 2

IO to IPlant I

I5250 V ISpecific N/A Comply I

Comply I

I Comply Note 11 Note 11 Note 11 Note 11 Note 11'ote 11 Note ll Note ll Note ll Note ll Note ll Note ll Note 11 Note ll Note 12 Note 12 Note 12 Note 12 I

Note 12 I

Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 N/A N/A N/A N/A N/A N/h INote 3 ISA I

INote 3 ISB I

I INote 3 ISAB I

Yes I

I I

Yes I

I I

I Yes I

INote 5 I

INA I

INote 5 INB I

I INote 3 I

ISA I

I I

INote 3 ISB I

I SAD I

I ISAB I

I ISAB I

ISA SB SA SB Yes I

Yes SAS I

Yes I

SAS I

Yes SAS Yes SAS Yes I

I SAS I

Yes I

I SAS I

Yes I

I shs I

Yes I

I SAS I

Yes SAS Yes No I No I

I I

I I

No I No I

Yesl Yesl Yes Yes Yes Yes Yesl Yesl I

~ I Yesl Yes I

I Yesl Yesl Yes Yes I

I Yesl Yes I

I Yesl Yes I

I I No I No I

I I

I I

I I

I No I No I

I I

I I

I No I No I

36 1539H

PLORIDA POWER AND LIGHT ST LUCIE UNIT NO. 1 REGULAT "p

TYPE VIDE 1,97 REV 3 Y SHEET" LES (Cont'd)

PER 6, 1983" ITEM VARIABLE TAG No.

DESCRIPTION GORY INSTRUMENT RANGE EIISTING RE UIRED Qh REQUIRE-ENVIRONMENTAL MENT ALIFICATION SEISMIC ALIPICATION REDUNDANCE POWER SUPPLY DISPLAY LOCATION SCHEDULE/

JUSTIPICATION D34K VM/954D VM/964D Diesel IGenera tor llA & 1B IMetering AM/954D AM/964D D34L D34M 4 kV Bus IA3 Breaker 4 kV Bue 1B3 Breaker 480 V Bus lh2 Breaker IStatus from I

l4 kV Buses llh3 & 1B3 I

I l480 V Buses Ilh2 & 1B2 IBkr IStatus Ito 480 V IBus 1AB I

l480 V Bus llhB Bkre Istatus Ifrom 480 V IBuses 1A2 &

I llB2 I

I125 V DC I Battery llA & IB IVoltage I

I 480 V Bus 1B2 Breaker D34N 480 V Bue llh2 Bkr I

l480 V Bue llB2 Bkr I

I D34PI480 V Bus IIAB IBreakere I

D34Q IVM/1001 ~

VM/1002 l4 kV Bus D

Ilh3 & 1B3 IFdr Bkr Sta-I Itus to 480 Vl IBuses lh2 &

I IlB2 I

I 1480 V Buses llh2 & 1B2 IFdr Bkr 2

0 to Plant I 5250 V

ISpecific I

Comply I

lo to IPlant 800 A Specific Open/

Close IPlant Specific Comply Open/

Close 2

I Plant I

Specific Comply 2

lopen/

IClose IPlant ISpecific

'Comply 2

l open/

IClose IPlant I

ISpecific.

Comply 2

I Comply 0 to 150 IPlant I

V DC ISpecific Note 11 Note ll Note ll Note ll Note ll Note 11 Note ll Note 11 Note 11 Note 11 Note ll Note ll Note ll Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 Note 12 N/A N/A N/A N/A N/A N/A IsA I

I ISB I

I ISA I

I ISB I

I INote ISA I

I INote ISB I

I INote Ish I

I INote ISB I

I INote Ish I

INote ISB I

I INote IshB SAS Yes SAS Yes SAS Yes SAS Yes 3

I Yes 3

I Yes 3

I SAS I

Yes SAS Yes Yes Ish I

I ISB I

I SAS Yes SAS Yes 3

I SAS I

Yes I

3 I

shs I

Yes I

I ~

3 I

shs I Yeel Yeel I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I Yesl Yesl I

I I

I I

I I No I No I

No No I

I Yesl I

Yee I Yes Yes 1

I I Yeel Yesl I Yes Yesl I

I I

I Yes Yes I Yesl Yesl I

I I

I I

I Ycel Yesl I

I 1539M

PLORIDA PONER AND LIGHT ST LUCIE UNIT NO. 1

~

~

VIDE 1.97 REV 3 "P

UHHARY SHEET" TYPE ABLES (Cont'd)

ABER 6, -.1983 ITEH TAG NO.

VARIABLE DESCRIPTION TYPE GORY EXISTING INSTRVHENT RANGE qh ENVIRONMENTAL VALIFICATION SEISMIC VALIPICATION v

I PONER I DISPLAY LOCATION I SCHEDULE/

D34R PT-18-16 IPI-18-16 I

I D34SIPT-18"9 I

IIPI-18-9 I

I Station Air Pressure llnstrunent IAir Pressurel 2

0 to 150 Ipsig Plant Specific 2

IO to 150 IPlant Ipsig ISpecific N/A N/A Note ll Note ll Note 11 Note 11 N/h N/A N/A N/A I

INote 6 I

SAS INs I

I I

INote 6 I

Yes INs I

I I

INote 6 I

SAS INs I

I I

INote 6 I

Yes INs I

I I

Yes I Yes I.

I I Yesl Yesl 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO. 1 REGULA "P

GUIDE 1 97 REV 3 UMMARY SHEET" VARIABLES EMBER 6, 1983

~,

I ITEM TAG NO.

I DESCRIPTION TYPE INSTRUMENT RANGE CATE-GORY EXISTING RE UIRED gh REqUIRE-IENYIRONMENTAL MENT I UALIPICATION SEISMIC UALIFICATION I

POWER I DISPLAY LOCATION I SCHEDULE/

JUSTIFICATION El IRE-26-58 I

I IRE-26"59 I

I IRIS-26-58 I

I IRIS-26-59 I

I I RR-26-58 I

I IRR-26-59 IContainneat Ihrea Radia-ltioa (High IRsnge)

I I

I I

I I

1 1 R/hr ll R/hr I

to Ito 107 ll x 108 IR/hr IR/hr Conply Note 16 Note 16 Note ll Note ll Note ll Note 11 Note 17 Note 17 Note 17 Note 17 Note 17 Note 17 I RE-26-59 I

I I RE-26-58 I

I I RIS-26-59 I

I I RIS-26-58 I

I I RR-26-59 I

I I RR-26-58 INote 2 ISA I

I INote 2 I

Isg I

I I

INote 2 I

ISA I

I I

INote 2 I

ISB I

I I

INote 2 I

ISA I

I I

INote 2 I

ISB SAS I Yesl Yee sPDs I

I I

I SAS I Yesl Yeel SPDS Yes Yee Yes Yes E2 INone IRadiation IExposure IRate (inside I Ibuildings lor areas lwhere ac-Iceee is re-Iquired to Iservice lequipnent linportant Ito safety) ll0 1 R/hrl Ito IIOh R/hr N/A N/A N/A N/A IFixed high Irange area Iradiation son-litors located lin areas in-Iportant to Isafety willnot Ibe useful to an loperator.

He Iwill be carry-Iiag a portable Ihigh range area

!detector on the Itrip to, at, land frow the larea lnportaat Ito safety.

IThere ie a coa-Iplete low raage

'larea radiation lmoaitoring Isystea in the IRAB.

I 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO 1

REGULATE IDE 1 97 REV 3 "P

Y SHEET" TYPE E LES (Cont'd)

ER 6, 1983 ITEM TAG NO DESCRIPTION INSIRUMENT RANGE GORY EXISTING RE UIRED Qh

~UIRE-ENVIRONMENTAL MENT ALIFICATION SEISMIC UALIFICATION POWER SUPPLY DISPLAY LOCATION C

EOF SCHEDULE/

JUSTIFICATION RSC-26-1L RSC-26-1M Containment or Purge IEffluent-Noble Gas IRSC-26-1H I

I I

I I

IRSC-26-1F IVent Flow IRate 5 z 104 ll0t uCi/cc luCi/cc IO to I150,000 Icfm IO to 110X IVent I Design IFlow 8 z 10~

10~

uCi/cc to uC /cc to N/A Note ll Note 11 Note 11 Note 11 N/A

/A INote 2AI N

INS I

I I

INote 2AI INS I

I I

INote 2AI INS I

INote 2A INS SAS I Yeel SPDS I

I I

I SAS I Yeel SPDS I

I I

I SAS I Yesl I

I I

I SAS I Yesl Yes IFlow is dilut-led, therefore, Irange is Yeeladequate.

I I

Yee I I

I Yee I ICT-2 E4 IRSC-26-1L I

I I RSC-26-1M RSC-26-1H RSC-26-1F ICT-2 IReactor IShield IBuilding Ihnnulus-Noble Gas IVent Flow IRate I

I IO to 1150,000 Icfm IO to 110XI I Vent IDesign I Flow I

2 8 z10%

I10 6 uCi/cc IuCi/cc Ito lto I5 z 104 I104 luci/cc luci/cc N/A Note ll Note 11 Note ll Note 11 Note 11 Note ll N/A N/A INote 2AI Yes INS I

INote 2hl INS I

I I

INote 2hl INS

!Note 2A INS I

INote 2AI INS SAS

'PDS SAS I

SPDS SAS SAS I

I INote 2hl Yes INS Yesl Yesl I

I I

I Yesl Yesl I

Yes Yes Yesl Yesl E5 IRSC-26-1L IAuxiliary E

I I Building I

I (including I RSC-26-1M Iany building I Icontaining I

Iprimary sys-I Item gases, leg, waste Igas decay Itank)-

INoble Gas I

2 IS z10~

luCi/cc Ito l4 x 103 luCi/cc l10~

1uci/cc Ito l103 luCi/cc N/h Note ll Note 11 N/A N/A Note 2A NS INote 2hl INS SAS Yesl Yes SPDS I

I SAS I Yesl Yesl SPDS I

1539M

FLORIDA POHER AND LIGHT ST LUCIE UNIT NO 1

REGULA "P

TYPE VIDE 1+97 REV 3 Y SHEET" LES (Cont'd)

ER 6, 1983 ITEM TAG NO DESCRIPTION TYPE GORY INSTRUMENT RANGE Qh I RzqUIRE-I ENVIRONMENTAL zxlsTING Rz UrzzD I

MENT VALIFICATION szlsMIc I

POHER UALIPICATION I REDUNDANCE SUPPLY DISPLAY LOCATION CR TSC ZOF SCHEDULE/

JUSTIPICATION RSC"26-1F IVent Flow IRate I

Icfm IDeeign I Flow F

2 IO to IO to 110XI N/A I 150,000 IVent I

Note ll N/A N/h Note 2A Ns SAS Yee Yes E6 RE-26-35 IRIS-26-35 I

I IRR-26-1D Condenser Ihir Removal I

Isystem IExhauet-INoble Gae 101-10-6 I

ll06 c/m

" luci/

I5 z 10~

Ito I2z102 luci/cc CC twhich is Ito lequiva-I105 lieut luCi/cc N/A Note 11 Note ll Note ll Note 11 N/A INote 2AI Yes INS I

N/A INote 2hl SAS I

INS SPDS INote 2hl Yee INs I

I I

INote 2AI Yes INS Yes YeslVent flow lis normally ldirected to I the plant lets'.

None Vent Flow Rate IO to 110X IVent I Design IFlow I

No No I No I

RSC-26-1L ICommon Plantl E

IVent or IMultipur-RSC-26-1M Ipose Vent IDischarging I

Ihny of hbovel RSC-26-1H IReleasee Noble Gas RSC-26-1F Vent Flow Rate CT-2 IO to 110XI Ivent.

IDesign Flow 2

IS z 10~

I10~

luci/cc to luci/cc tol I5 z 104 I103 luci/cc luci/cc I

I I

I I

I I

IO to I150,000 Icfm N/h Note ll Note ll Note 11 Note 11 Note 11 N/A N/A INote 2A INS I

INote 2AI INs I

INote 2A INS Note 2AI Ns INote 2h INs I

SAS SPDS SAS I

SPDS SAS SAS Yes Yee Yes Yes Yee Yeel Yesl I

I Yesl 'Yee 1539M

FIORIDA PONER AND LIGHT ST LUCIE UNIT NO~ 1 REG GUIDE 1.97 REV 3 "P

UMMARY SHEET" TYPE ABLES (Cont'd)

BER 6, 1983 ITEM TAG NO DESCRIPTION TYPE CATE-GORY qh RElPIRE-ENVIRONMBKLL MENT VALIFICATION SEISMIC UALXFICATION POWER REDUNDANCE SUPPLY DISPLAY LOCATION TSC EOF SCHEDULE/

JUSTIFICATION E8 RE-26-62 RE-26-63 CT-2 Vent from Steam Gener-ator Safety I Relief IValves or IAtmospheric IDump Valves I

l(Noble Gas)

I 2

1 mR/hr 10 1 to uci/cc ll05 Ito ImR/hr I103 luci/cc N/A Note 21 Note 21 Note 11 N/A N/A INote 2h INS I

INote 2AI INs I

I INote 2AI INS SAS Yes Yesl Yeslgzieting range I

Icompliee with

)the required Yesl Yeslrange.

IIn operation, Ithe radiation Iemanating from Ithe main steam lline is mea-leured in mR/hr, Iwith hand Icalculetione Iconverting'the Ireadinge to the lappropriate uCi/cc reading.

IRSC-26"2M I

I IRSC-26-2H I

I IRSC-26-2F IPoints-INoble Gas I(ECCS IArea A)

I I

IVent Flow IRate I

I l(Eccs Ihrea B)

I I

II.

I I

I IVent Flow IRate I

I(Fuel IHandling IBuilding)

I l

I I

I I

IRSC-26-3L I

IRSC-26-3M RSC-26-3H IRSC-26-3F I

IIRSC-Z~L RSC-26-4M IRSC-26-4H I

I E9 RSC"26-2L Ihll Other IIdentified IReleaee E

I I

I I

I I

I I

I I

I I

I l8 x 10~

ll06 lo to l4o,ooo Icfm Io to 110X IVent IDeeign IFlow I

2 Iuci/cc to luci/cc I5 z 10 Ito luci/cc Ilo I

luci/cc N/A Note 11 Note ll Note ll Note ll Note 11 Note 11 Note ll Note 11 Note 11 Note 11 Note ll 42-N/A N/A SAS I Yesl Yeal SPDS I

I I

I I

I SAS I Yesl Yeel SPDS I

I I

I SAS I Yesl Yee INote 2A INs I

INote 2hl INS I

I I

INote 2hl INs I

I I

INote 2hl INs I

I INote 2AI INs I

I I

INote Zhl INs I

I Note 2AI Ns I

I INote 2hl INs I

I I

INote 2hl INs I

I I

INote 2hl INs I

I I

INote 2hl INs I

I I

I I

Yesl Yeel SAS I Yesl Yeel SPDS I

I I

I I

I SAS I Yesl Yesl SPDS SAS Yes Yes SAS I Yesl Yes I

I I

I SAS I Yeel Yesl SPDS I

I I

I I

I SAS I Yesl Yesl SPDS I

I I

SAS I Yee I Yes I I

I I

I I

I 1539M

FLORIDA POWER-AND LIGHT ST LUCIE UNIT No. 1 REG VIDE 1.97 REV 3 "P

UMMARY SHEET" TYPE ABLES (Cont'd)

ER 6, 1983 ITEM TAG No.

Qh

@QUIRE-I ENVIRONMENTAL VARIABLE INSTRUMENT RANGE CATE-I ALIFICATION DESCRIPTION TYPE GORY I EXISTING RE IRED MENT sEISMIC I

I POWER I DISPLAY LOCATION SCHEDULE/

JUSTIFICATION IRSC-26"4F I

I IcT-2 IVent Flow IRate I

I E

2 lo to Io to 110XI l40,000 IVent Icfm IDesign I Flow N/A Note ll Note ll N/A N/A INote 2AI SAS INS I

I, I

INote 2hl Yes INS I Yesl Yesl Elo IPARTICULATES AND I HALUGENs I

I I

IEFF-PART Ihll Identi-I Ified Plant IEFF"HALO IRelease IPoints (ez-I leapt Steam IGenerator I

ISafety Re-I Ilief Valves I

lor htmo-Ipheric ISteam Dump IValves and ICondenser Ihir Removal I

ISystem Ex-Ihaust)

ISampling Iwith On-site I IAnalysis ICapability 3

Ilo 3 luci/cc Ito Ilo2 luci/cc llo-3 luci/cc Ito llo2 luci/cc Io to 110XI IVent IDesign Flow N/h

'/A N/A N/A N/A SAS I Yesl Yesl I

I I

SAS I Yesl Yesl ISee Other I Effluent IPathways IPortab Ell le Iby FP&L Ihirborne IRadio-Ihalogens andi IParticulatesl l(Portable ISampling Iwith On-site Analysis Capability)

E 3

IO-9 Ilo-9 luci/cc to I luci(cc to Ilo llo-3 Iuci/cc Iuci/cc I

N/A N/A N/A N/h N/A N/A I N/A N/AI 1539M

FIORIDA PONER 'AND LIGHT ST LUCIE UNIT NOo 1 REGULA "P

TYPE GUIDE 1.97 REV 3 UMMARY SHEET" ABLES (Cont'd)

"EMBER 6, 1983 ITEM TAC NO.

DESCRIPTION TYPE INSTRUMENT RANCE GORY EXISTING RE UIRED Qh REQUIRE-ENVIRONMENTAL MENT UALIFICATION SEISMIC ALIFICATION PONER SUPPLY DISPLAY LOCATION TSC EOF SCHEDULE/

JUSTIFICATION E12 Portable by FP&L Plant and Environs Radiation l(Portable I

IInstrumen-Itation)

I I

E13 Portable IPlant and by FP&L IEnvirons IRadio-lactivity I

10 3 R/br to 10a R/hr 3

IIsotopic IAnalysis 10"3 R/br to 10s R/hr Photons 10 3 IR/br to I 104 IR/hr Betel IRadie-I Itions andi ILou-lenergy IPhotons I

IIsotopic Analysis I

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/AI N/A N/A N/A E14 IWD10-DL I lumeter I

INind I

IDirection IWD10-HN I

3 lo'o 1540 lo to N/h I360'+5'I laccuracy I

Iwith a Ideflee-I Ition of Ilo').

I Istarting I

I speed I

Iless thanl I0.4 mps I (1.0 Imph).

IDamping Iratio Igreater Ithan or lequal to I

10.4, de-I lay dis-Itance lless thanl Ior equal Ito 2 lmeters I

N/A N/A N/A INote 4 I

SAS I Yes l YeslSee Note 7.

INs I

I I

I I

I I

I I

INote 4 I

SAS I Yesl Yesl INS

- 44 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO. 1 REGULA "P

TYPE E IDE 1+97 REV 3 Y SHEET" LES (Cont'd)

ER 6, 1983 ITEN TAG NO VARIABLE DESCRIPTION TYPE CATE-GORY INSIRUHENT RANGE Qh I aZquiRE-ENVIRONMENTAL DALIPICATION SEISMIC ALIPICATION POWER REDUNDANCE SUPPLY DISPLAY LOCATION SCHEDULE/

JUSTIFICATION IWD60-DL l60-meter I

IWind I

IDirection IWD60-HW 3

IO to 540'Same as IAbove N/A N/A N/A N/A INote 4 I

SAS INs I

I I

INote 4 I

SAS INS I

I Yeel YeslSee Note 7.

I I

I I

I I

I Yesl Yesl E15 IWS10-DL I

I I

I lwslo-Hw IWS60-DL I

I I

lws60-Hw I

I 10-meter Wind Speed 60-meter Wind Speed 3

0 to 1120 mph 3

IO to I120 mph IO to 22 Imps (50 lmph) +

I0.2 mps l(0.5 Imph) ac-Icuracy Ifor lepeede llese thanl l2 mps I

l(5 mph),

I IIOZ for Ispeeds I

lin ezcessl lof 2 mpe I

l(5 mph),

I Iwith a I

lstarting I

I threshold I lof lese I

Ithan 0.4 I

Imps (1.0 I

lmph) and I

Ia dis-I Itance I

Iconetant I

lnot to lexceed l2 meters I

ISame as IAbove N/A N/A N/A N/A N/A N/A N/A INote 4 INS I

INote 4 INS I

Yes Yes SAS I Yesl Yesl I

I I

I I

I See Note 7.

N/A INote 4 I

SAS I Yesl YeslSee Note 7.

INs I

I I

I I

I I

I I

INote 4 I

SAS I Yesl Yesl INs

- 45 1539M

C

~

~

FMRIDA POHER AND LIGHT ST LUCIE UNIT NO. 1 REGULA

%P TYPE E UIDE i+97 REV 3 Y SHEET" LES (Cont'd)

ER 6, 1983 DESCRIPTION TYPE GORY EXISTING gh REIIUIRE-ENVIRONMENTAL MENT VALIFICATION SEISMIC VALIPICATION I

PONER I DISPLAY IAKATION I SCHEDULE/

Inset Central Data Station I

Estimation of Atmo-spheric I

Stability I PRIMARY COOLANT IAND SUMP E

3

-15'F to 15'F.

This is Iacquired Iby taking lthe dif-lference Ibetween Ithe 60-lmeter Itemp and Ithe 10-lmeter Itemp.

Based on vertical ltempere-Iture Idiffer-lence from Iprimary lmeteoro-llogical

Isystem, I-5'c to I10'C I(-9'F to I

118'F) andi I+ 0.15'C laccuracy Iper 50-Imetec in-Itervals I(+ 0.3'P leccuracy I

Iper 164-I ffoot in-I Itervals)

I lor anelo-I Igous Irange forl lalterne-I Itive sta-I Ibility I

lestimatesl N/A N/A N/A INS IVariables for litem E17h are Imanually input-lted to SAS.

N/A INote 4 I

SAS I Yesf YesISee Note 13.

PEA E17A IGross Ihctivity I

I PC-I-131 IIodine I

E 3

1 uCi/ml lto Ilo Ci/ml I

3 ll uci/ml to 10 Ci/ml ll uci/ml lto I 10, Ci/ml I

IIsotopic IAnalysis N/A I

I I

N/A I

N/A N/A N/A N/A N/A N/A N/A SAS I Yes Yes SAS I Yesl Yesl Pc-XE-133 IXenon 3

1 uci/ml Ito llO Ci/ml I

Isotopic IAnelysis I

I N/A I

I I

N/A N/A N/A N/A SAS Yesl Yes 1539M

FLORIDA POMR AND LIGHT ST LUCIE UNIT NO. 1 REC "P

TYPE UIDE 1.97 REV 3 Y SHEET" LES (Cont'd)

BER 6, 1983,~

ITEN TAC NO V

LE TYPE DESCRIPTION EXISTING RANCE Qh REQUIRE-EHVIROHHEHTAL HEHT VALIFICATION SEISHIC UALIFICATION POMR REMNDANCE SUPPLY DISPLAY LOCATION CR TSC EOF SCHEDULE/

JUSTIFICATION IPC-C~O ICobalt I PC-B I

II PCS I

IPC-H2 IPC-02 IBoron IContent I

IChloride IContent I

I Dissolved IHydrogen I

I IDissolved lozygen PC-pH 'pH I

IPC-CS-134 ICesium E

I I 1 uCi/ml IIsotopic Ito IAnalysis

. I10 Ci/ail I

I I

I10 6 to IIsotopic I10 lhnalysis luci/ml I

I I

IO go 25 x IO to I10~ ppm l6000 ppm N/A I

N/A I

N/A I

N/A H/h N/h IO to 10 ppm lo to I

20 ppm IO to I

100X Ill to 13 Il to 13 I

N/A I

I 115 to Inf IO to 20 Ip Ip I

0 to 100X IO to 2000 Total Gas Icc (STP)/I Iby Volume Ikg I

I IO to IO to 20 I

5 p Ippm N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A H/h N/h N/A N/A N/A N/A N/h N/A N/A N/A N/A SAS N/A SAS N/h SAS N/A SAS N/h SAS I Yesl Yeel I

I I

I I

I I Yesl Yesl I

I Yesl Yes See Note 14.

N/A SAS I Yeel YeslSee Note 14.

N/A SAS Yeel YeslSee Note 14.

I I

I Yesl YeslVariables for IItem E17h are Imanually input-Ited to SAS.

I Yesl Yesl E17B SWA S-I-131 ICroes IActivity I

I IIodine IS"XE-133 IXenon E

I 1 uCi/ml lto I10 Ci/ml I

I 1 uCi/ml lto

.I10 Ci/ml 1 uCi/ml to 10 Ci/ml I

N/A I

I I

I N/A I

N/A I

Il uCi/ml Ito I10 Ci/ml I

IIsotopic IAnalysie I

IIIsotopic Analysis N/A N/A N/A H/h N/A N/A N/A N/A N/A N/A SAS N/A SAS N/A SAS I Yesl YeslVariablee for IItem E17B are lmanually input-Ited to SAS.

I Yesl Yesl Yesl Yes IS"CO"60 ICobalt I 1 uCi/ml to 10 Ci/ml IIsotopic IAnalysis I

I N/A N/A N/A N/A N/A SAS Yes Yeel 47 1539M

FLORIDA POWER AND LIGHT ST LUCIE UNIT No. 1 REGUQLTO VIDE 1 97 REV 3 "P

Y SHEET"

'TYPE E LES (Coat'd)

DP MBER 6, 1983 ITEM TAG No VARIABLE INSTRUMENT RANGE Qh I RE IRE-IENVIRONMENTAL I SEISMIC I

I POWER I DISPLAY LOCATION I SCHEDULE/

CR TSC EOF I JUSTIPICATION DESCRIPTION ITYPE I

GORY I EXISTING IREQUIRED I

MENT IQUALIFICATION IQUALIPICATION I REDUNDANCEI SUPPLY S-CS-134 I

IS-B S-CL S-pH Cesium IBoron IConteat IChloride ICoatent I

IpH E

I 10"6 to IO7 uCi/ml Isotopic Analysis lo to 25 z IO to Ilo~ ppm l6000 ppm I

I Io to 20 Io to 20 lppm I

I ll to ll to I 13 I 13 N/A N/A N/A N/A N/A N/h N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A SAS N/A SAS N/A SAS N/A SAS I Yesl YeelVariables for litem E17B are lmanually input-Ited to SAS.

Yesl Yesl I

I I

I Yesl Yesl I

I I

I I

I I Yesl Yesl CONTAINMENT IAIR E18 CA-H2 Hydrogen Content ICA-I-131 IIodine I

ICA-CS ICesium ICA-0TH Iothers I

I I

ICA&2 Iozygen I

Icontent I

ICA-XE-133 IXeaoa 0 to 10 Vol - I 0 to 30 IVol - I Ill0 6 to 106 luCi/ml I10-10 Ito llo5 luCi/ml I

I 10-10 lto 103 uCi/ml Ilo 6 to llo3 luCi/ml I

Io to 10 IVol I I

lo to 30 IVol - I I

IIsotopic IAnalysis I

I IIsotopic IAnalysis IIsotopic Analysis I

Nlh N/A N/h I

N/A I

N/A N/A N/A N/A N/A N/A N/A N/A N/h N/h N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/h SAS N/A SAS N/h SAS N/h SAS I Yeel Yeel N/h SAS I Yesl Yesl I

N/A SAS I Yesl Yesl IVariables for IItem EI8 are lmaaually input-Ited to SAS.

I I Yesl Yesl I

I I

I I

I I Teel Yesl I

I I

I I

I Yeel Yesl 1539M

l I

t I

t t

f

FLORIDA POWER AND LIGHT ST LUCIE UNIT NO 1

"P GUIDE 1.97 REV 3 UMMARY SHEET" OTES BER 6, 1983 Note 1:

120 VAC, Class 1E, uninterruptable power supply.

Note 2:

120 VAC, Class 1E, offsite power backed by an emergency diesel generator.

Note 2A:

120 VAC, Non Class 1E, offsite power backed by an emergency diesel generator.

Note 3:

125 VDC, Class lE battery.

Note 4:

120 VAC, non-Class 1E offsite power.

Note.5:

125 VDC, non-Class 1E battery.

Note 6t Note 7:

120 VAC~ non-Class 1E, uninterruptable power supply.

Wind Direction and speed is fed to the Inmet Central Date Station (Control Room) via FM Signal Transmission (Analog signal provided to SAS).

Also, a future telephone line link will provide a redundant input to SAS.

At the Central Data Station, Wind Direction and speed are recorded on analog recorders.

Note 8:

Qualify per 79.018 analysis.

Note 9:

Category 1 redundancy does not apply because a secondary containment isolation valve is normally available on each line penetrating the containment.

Exceptions to the rule are explained in FSAR Section 6.2.4.

Note 10:

Will.comply with IOCFR50.49 and NUREC-0588 Category II (IEEE-323-1971) for environmental qualification.

To be qualified according to the commitment schedule stated in the 10CFR50.49 Equipment Report.

Note ll:

The equipment is located in a mild environment and willwithstand its service location conditions.

Note 12'ote 13:

Comply with the seismic qualification program which was the basis for plant Licensing.

60 meter temp and 10 meter temp is fed to the Inmet Central Data Station (Control Room) via Fm signal transmission (Analog signal provided to SAS).

Also> a future telephone line link will provide a redundant input to SAS.

A differential amplifier accepts the two signals and produces a voltage which represents differential temperature.

This differential temperature is recorded in the central data station.

Note 14:

Indicator and recorder are located on post accident sampling control panel.

Note 15'heseH sampling valves are manually operated and therefore are not displayed as part of the SAS system.

These valves do not receive CIAS 2

signal.

Note 16:

Note 17:

Comply with 10CFR50.49 and NUREG-0588 Category I (IEEE-323-1974) for environmental qualification.

Comply with IEEE-344-1975 for seismic qualification.

Note 18:

Will comply with 10CFR50.49 and NUREC-0588 Category I (IEEE-323-1974) for environmental qualification.

Note 19:

Will comply with IEEE-344"1975 for seismic qualification.

- 49

'1539M

PLORIDh POHER AND LIGHT ST LUCIE UNIT NO. 1 GUIDE 1.97 REV 3

SUMMARY

SHEET" (Cont'd) vCEMBER 6, 1983 4

Note 20:

The sensor is located in a harsh environment post accident.

However, it is not required to perform a safety function or mitigate the consequence of an accident, it is provided for plant surveillance during normal operation.

High quality instrumentation is utilized.

Note 21'ote 22:

The sensor is located in a harsh environment only during MSLB-trestle.

However, it is not required to perform a safety function or mitigate the consequences of an accident.

It is provided for plant surveillance only.

The sensor is located in a harsh environment post accident.

The equipment was provided for plant surveillance during normal operation and non-accident transients.

The type of equipment utilized has been generically qualified to a lesser environment than in-containment accident environment for this plant.

Note 23:

The ICC System (excluding the In-Vessel Components) alification Report is expected to be received from the Vendor by January 31, 1984.

50-1539M

I lv I