PLA-7521, Registration for the Use of Dry Fuel Storage Module D-16 and Thermal Performance Assessment

From kanterella
(Redirected from ML16273A275)
Jump to navigation Jump to search
Registration for the Use of Dry Fuel Storage Module D-16 and Thermal Performance Assessment
ML16273A275
Person / Time
Site: Susquehanna, 07201004  Talen Energy icon.png
Issue date: 09/29/2016
From: Franke J
Susquehanna, Talen Energy
To:
Document Control Desk, Office of Nuclear Material Safety and Safeguards, Office of Nuclear Reactor Regulation
References
PLA-7521
Download: ML16273A275 (2)


Text

Jon A. Franke Site Vice President Susquehanna Nuclear, LLC 769 Salem Boulevard TALEN ~

Berwick, PA 18603 Tel. 570.542.2904 Fax 570.542.1504 ENERGY SEP 2 9 2018 jon.franke@talenenergy.com ATTN: Document Control Desk 10 CFR 72.212 Director, Division of Spent Fuel Storage and Transportation Office of Nuclear Material Safety and Safeguards U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 SUSQUEHANNA STEAM ELECTRIC STATION REGISTRATION FOR THE USE OF DRY FUEL STORAGE MODULE D-16 AND THERMAL PERFORMANCE ASSESSMENT PLA-7521 Docket No. 72-28 Pursuant to 10 CFR 72.212(b)(2), this letter is being submitted to register Susquehanna Nuclear, LLC's use of Dry Fuel Storage Module D-16 at the Susquehanna Steam Electric Station. The required information follows:

Licensee Name: Susquehanna Nuclear, LLC and Allegheny Electric Cooperative, Inc.

Licensee Address: Susquehanna Steam Electric Station 769 Salem Boulevard Berwick, PA 18603 Reactor License Numbers: Unit 1 NPF-14 Unit2 NPF-22 Reactor Docket Numbers: Unit 1 50-387 Unit2 50-388 Dry Fuel Storage Docket Number: 72-28 Person Responsible for Providing Additional Information: Melisa Krick, Nuclear Regulatory Affairs Cask Certificate Number: 72-1004, Amendment 10 Cask Model Number: NUHOMS-61BTH

Document Control Desk PLA-7521 Horizontal Storage Module (HSM) Model: NUHOMSModel 102 Cask Identification (Serial Number): SSE-61BTH-1-C-2-066 HSM Identification: D-16 Load Date: September 9, 2016.

In addition, this letter provides information for the Dry Shielded Canister (DSC) required by Technical Specification (TS) for Certificate of Compliance (CoC) No. 1004, Amendment No. 10, Section 1.1.7, "Special Requirements for First System in Place." Technical Specification 1.1. 7 requires the submittal of a thermal performance assessment for all DSCs that are loaded with higher heat loads than previously reported. The following is the thermal performance assessment data for the identified DSC:

HSM Identification Number: D-16 Dry Shielded Canister: SSE-61BTH-1-C-2-066 Calculated Heat Load: 17.237 kW Calculated Temperature Rise: 71.0°F Measured Temperature Rise (Note 1): 48.4°F Note 1: The measured temperature rise represents the measured change in temperature during equilibrium conditions.

There are no new or revised regulatory commitments contained in this letter.

Should you have any questions regarding this submittal, please contact Mr. Jason Jennings, Manager- Nuclear Regulatory Affairs at (570) 542-3155.

J 1\. Franke Copy: NRC Region I, Regional Administrator Mr. J. E. Greives, NRC Sr. Resident Inspector Ms. T. E. Hood, NRC Project Manager Mr. M. Shields, PA DEP/BRP