From: Scace S
Dominion Energy Kewaunee
To:
Document Control Desk, NRC/NMSS/SFPO
References
09-554
Download: ML092650293 (2)


Text

YDominion Dominion Energy Kewaunee, Inc.

N490 Hwy 42, Kewaunee, WI 54216 Web Address: www.dom.com SEP 11 209 ATTN: Document Control Desk Director, Spent Fuel Project Office Office of Nuclear Material Safety and Safeguards U. S. Nuclear Regulatory Commission Washington, DC 20555-0001 Serial No.09-554 LIC/NW/RO Docket No.: 72-64 50-305 License No.: DPR-43 DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION INDEPENDENT SPENT FUEL STORAGE INSTALLATION CASK REGISTRATION FOR SPENT FUEL STORAGE Pursuant to 10 CFR 72.212, "Conditions of general license issued under §72.210,"

paragraph (b)(1)(ii), Dominion Energy Kewaunee, Inc. (DEK) hereby provides the Nuclear Regulatory Commission (NRC) notification regarding the registration of spent fuel storage casks approved under NRC Certificate of Compliance No. 1004.

Licensee Name:

Licensee Address:

Reactor License No.:

Reactor Docket No.:

Cask Certificate No.:

Cask Model No.:

Cask Identification Nos.:

Licensee Contact Name/Title:

Dominion Energy Kewaunee, Inc.

N490 Highway 42 Kewaunee, WI 54216 DPR-43 50-305 1004 Standardized NUHOMS -32PT Canister KPS32PT-S100-A-HZ001 Initial Use: 8/22/2009 KPS32PT-S100-A-HZ003 Initial Use: 8/27/2009 Diana Fried, Supervisor Nuclear Fuel Operation The above named casks are in use under Amendment 9 of Certificate of Compliance No. 1004.

In addition, pursuant to the General Requirements and Conditions of the Technical Specifications for Certificate of Compliance No.1004, Amendment 9, Paragraph 1.1.7, "Special Requirements for First System in Place," a summary of the thermal performance of the highest heat load Standardized NUHOMS-32PT Dry Shielded Canister (DSC) placed in service at the Kewaunee Power Station independent spent fuel storage installation is provided. KPS32PT-S100-A-HZ001 was loaded with Unit 1 spent fuel and stored in a NUHOMS Model 102 Horizontal Storage Module (HSM). The calculated thermal loading for this DSC is approximately 15.9 kW. The inlet and outlet air temperatures for the HSM were measured consistent with the method provided in Certificate No. 1004 Technical Specification 1.2.8. Upon obtaining equilibrium conditions, the measured inlet air temperature was 62 degrees F and measured outlet air temperature was 116 degrees F, corresponding to a temperature difference of 54

Serial No.09-554 Page 2 of 2 degrees F. This temperature difference is within the thermal performance temperature differential of 65 degrees F expected for a Model 102 HSM containing a DSC with a thermal loading of 15.9 kW at the given ambient conditions.

If you have questions or require additional information, please feel free to contact Mr.

Jack Gadzala, at 920-388-8604.

Very truly yours, S~teph

.' Scace Site Vice President, Kewaunee Power Station Commitments made by this letter: NONE cc:

Regional Administrator, Region III U. S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Mr. P. S. Tam Sr. Project Manager U.S. Nuclear Regulatory Commission One White Flint North, Mail Stop 08-H4A 11555 Rockville Pike Rockville, MD 20852-2738 NRC Senior Resident Inspector Kewaunee Power Station