ML16256A641
Text
Enclosure 2 LR-N16-0113 LAR H15-01 NUREG-0800 Appendix 18-A Assessment, Crediting Manual Operator Actions in the Diversity and Defense-in-Depth Analyses 3-
Page 1 of 3 HCGS PRNM UPGRADE APPENDIX 18-A ASSESSMENT:
CREDITING MANUAL OPERATOR ACTIONS IN DIVERSITY AND DEFENSE-IN-DEPTH ANALYSES
- 1. Introduction Section 4.1.2, "Instability," of Appendix I (D3 Analysis) to NEDC-33864P (NEDO-33864),
Revision 0 (Enclosures 3 and 2 to LAR H15-01), identified that the diverse means for the safety trip function performed by the DSS-CD (Detect and Suppress Solution-Confirmation Density) algorithms at HCGS for the postulated common-cause failure (CCF) in Power Range Neutron Monitoring (PRNM) is Manual Operator Action. Two scenarios were identified that relied on manual operator actions; Two Recirculation Pump Trip (2RPT) and Loss of Feedwater Heating (LFWH).
This report provides supplemental information in accordance with NUREG-0800, Appendix 18-A, demonstrating that (1) the time available to perform the required manual actions is greater than the time required for the operator(s) to perform the actions, and (2) the operator(s) can perform the actions correctly and reliably in the time available.
The required Phases of Appendix 18-A are addressed below (note that Phase 2 is N/A for HCGS).
- 2. Analysis (Appendix 18-A Phase 1)
Time Available The time available to perform the actions should be based on analysis of the plant response to the AOO/PA using realistic assumptions, and the acceptance criteria of BTP 7-19.
The analysis provided in Appendix I (D3 Analysis) is consistent with Appendix 18-A. The time available for each event was analyzed and documented in Section 4.1.2 of Appendix I of NEDC-33864P (50 seconds for 2RPT and 392 seconds for LFWH). An assessment of the analysis performed against the guidance/criteria of Appendix 18-A is provided in Attachment A of this report.
Time Required The time required for operator action should be based on an HFE analysis of operator response time.
Prior experience with tasks or subtasks similar to the actions proposed to be credited in the defense-in-depth analysis may provide valuable insights for the analysis/estimates of operator response times.
The time required estimate was evaluated as follows:
As discussed in Appendix I (D3 Analysis), both scenarios require immediate operator action per existing procedures.
For the 2RPT scenario the required sole action is to immediately reduce power (lock the Mode switch in shutdown per procedure).
Page 2 of 3
For the LFWH scenario, the required sole action is to immediately reduce and maintain reactor power to the pre-feedwater heater trip or isolation value per procedure. (As explained in the D3 analysis, the LFWH event is initiated from a point near the minimum pump speed line and the Backup Stability Protection (BSP) Region I boundary. Since both recirculation pumps are at minimum speed, inserting rods is the only means available to reduce reactor power.)
Operators have existing experience (Simulator) with both the 2RPT and LFWH events using the diverse systems credited in the D3 analysis.
The diverse systems that are available are provided by control room annunciators and indicators (ie no remote operator action is required).
The diverse systems remain unchanged by the PRNM upgrade; the diverse operator actions are not performed on the PRNM system.
Based on the above it was determined, with Operations input and review, that the action(s) could be accomplished within the available time. As discussed below, the Integrated System Validation (ISV) validated that the actions can be accomplished within the time available with margin.
Time Margin A time margin should exist between the analyzed time(s) as the difference between time available and time required for operator action is a measure of the safety margin and as it decreases, uncertainty in the estimate of the difference between these times should be appropriately considered.
One acceptable method is for the time margin to equal the maximum recovery time for any single credible operator error.
As discussed under Time Required immediate operator action is required. Since all diverse indications are in the control room and since only one operator action is required, it was concluded that any potential errors would not jeopardize the time margin; sufficient recovery time is available (i.e. these are not complex situations as discussed in NUREG-0800 Appendix 18-A).
The ISV validated the time margin.
3.
Integrated System Validation (Appendix 18-A Phase 3)
The vendor/licensee/applicant should conduct an ISV of manual actions credited in the defense-in-depth analysis using a plant-referenced simulator in real time.
Performance times should be compared to the time available (per defense-in-depth analysis results) and previous estimates of time required.
As noted in Section 2 above, the diverse systems credited remain unchanged by the PRNM upgrade; therefore modification of the simulator with the PRNM upgrade was not required to accurately perform the ISV. As noted in Section G.1 of the PRNM LTR (NEDC-32410P-A):
The information available to the operator is the same as with the current system. No actions are required by the operator to obtain information normally used and equivalent
Page 3 of 3 to that available with the current equipment. However, the replacement system does provide more directly accessible information regarding the condition of the equipment, including automatic self-test, which can aid the operator in diagnosing unusual situations beyond those defined in the licensing basis.
Therefore, replacement of the system will not affect operator response to the events analyzed and will not affect the time required to perform the mitigating actions.
2RPT (Time Available = 50 Seconds)
Attachment B of this report provides the ISV results for the 2RPT scenario with the postulated common-cause failure (CCF) in PRNM. The plant referenced simulator was used and for all Operating crews the time margin was greater than 75%. The mean time required was 9.8 seconds, the maximum required was 12 seconds. All correct actions were taken and verified.
LFWH (Time Available = 392 seconds)
Attachment C of this report provides the ISV results for the LFWH scenario with the postulated common-cause failure (CCF) in PRNM. The plant referenced simulator was used and for all Operating crews the time margin was greater than 20%. The mean time required was 191 seconds, the maximum required was 304 seconds. All correct actions were taken and verified.
4.
Maintaining Long-Term Integrity / Monitoring (Appendix 18-A Phase 4)
The vendor/licensee/applicant should establish a strategy for long-term monitoring of operator ability to reliably perform the manual operator actions credited in a defense-in-depth analysis.
The two scenarios (2RPT and LFWH) identified in Appendix I (D3 Analysis) to NEDC-33864P (NEDO-33864) will be added to the HCGS procedure OP-HC-102-106, Hope Creek Master List of Time Critical and Time Sensitive Operator Actions. The scenarios will be added to the Master List of Time Critical Actions (MLTCA); i.e., actions required to be completed within a certain time period as identified in the plants licensing basis.
5.
Conclusions The manual operator actions credited in the HCGS PRNM D3 Analysis conform to the guidance provided in NUREG-0800, Appendix 18-A. The results demonstrate that the manual actions in response to a BTP 7-19 software CCF are both feasible and reliable, given the time available, and that the ability of operators to perform credited actions reliably will be maintained for as long as the manual actions are necessary to satisfy the defense-in-depth analysis.
Page 1 of 4 18-A ATTACHMENT A Phase 1 Time Available - Review Against Appendix 18-A Guidance App 18A Phase App 18A Requirement Action Completed 1 / Analysis The time available to perform the actions should be based on analysis of the plant response to the AOO/PA using realistic assumptions, and the acceptance criteria of BTP 7-19 (ie the time before the task must be completed to satisfy the diverse action)
The analysis conducted for Appendix I (D3 Analysis) is consistent with Appendix 18-A.
The time available for each event was analyzed and documented in Section 4.1.2 of Appendix I of NEDC-33864P (50 seconds for 2RPT and 392 seconds for LFWH).
Appendix 18A provides the following guidance for determining the time available (excerpts from Appendix 18A).
Section C. Staff Position Page 18-A-3 The time available for manual actions should be based upon the methods and criteria prescribed in BTP 7-19.
BTP 7-19 discussed below.
Section 1.A. Method Page 18-A-3 The time available to perform the actions should be based on analysis of the plant response to the AOO/PA using realistic assumptions, and the acceptance criteria of BTP 7-19.
This statement does not specify methods but does allow the use of realistic assumptions (see BTP 7-19 discussion later).
Section 1.B. Review Criteria Page 18-A-5 The analysis establishes the time available using an analysis method and acceptance criteria consistent with the guidance of BTP 7-19. The basis for the time available is documented.
The statement does not identify a specific method but refers to BTP 7-19 (BTP 7-19 discussed below).
BTP 7-19 provides the following guidance for determining the time available (excerpts from BTP 7-19).
Section 1.4 Four-Point Position, Point 2, Page 7-19-6 In performing the assessment, the vendor or applicant shall analyze each postulated common-mode failure for each event that is evaluated in the accident analysis section of
Page 2 of 4 the safety analysis report (SAR) using best-estimate methods. The vendor or applicant shall demonstrate adequate diversity within the design for each of these events.
o Concerning Point 2 Page 7-19-7 The term best-estimate methods is more accurately referred to as realistic assumptions, which are defined as normal plant conditions corresponding to the event. For example:
- power levels,
- temperatures,
- pressures,
- flows, and
- alignments of equipment.
Thus, in performing the assessment, the vendor or applicant should analyze each postulated CCF for each event that is evaluated in the SAR section analyzing power operation accidents at the plant conditions corresponding to the event. This analysis may use realistic assumptions to analyze the plant response to DBEs, or the conservative assumptions on which the Chapter 15 SAR analysis is based.
Point 2 and the clarification provided in Concerning Point 2 does not define a specific analytical method and allows for the use of realistic or Chapter 15 type assumptions (i.e, use a method capable of simulating the event and may use realistic or Chapter 15 assumptions as input). The TRACG stability analysis performed by GEH is consistent with this interpretation to determine the time available.
Section 1.6 D3 Assessment Page 7-19-10 In this assessment, the applicant may use realistic assumptions to analyze the plant response to DBEs (as identified in the SAR).
Repetitive guidance to Point 2 discussion above.
Section 3.1 Specific Acceptance Criteria Page 7-19-14 (Criteria applicable to the D3 stability assessment and time available discussed below).
(1) For each anticipated operational occurrence in the design basis occurring in conjunction with each single postulated CCF, the plant response calculated using realistic assumptions should not result in radiation release exceeding 10 percent of the applicable siting dose guideline values or violation of the integrity of the primary coolant pressure boundary. The applicant should (1) demonstrate that sufficient diversity exists to achieve these goals, (2) identify the vulnerabilities discovered and the corrective actions taken, or (3) identify the vulnerabilities discovered and provide a documented basis that justifies taking no action.
By conservatively using the SLMCPR as the acceptance criteria for the D3 stability assessment, no fuel fails as a result of the events. In addition, the stability events do not cause a pressurization which would challenge the reactor coolant pressure boundary. (If
Page 3 of 4 stability assumed to be an AOO; see (2) below if stability were assumed to be an accident (DBE). In either case BT 7-19 acceptance criteria is met).
(2) For each postulated accident in the design basis occurring in conjunction with each single postulated CCF, the plant response calculated using realistic assumptions should not result in radiation release exceeding the applicable siting dose guideline values, violation of the integrity of the primary coolant pressure boundary, or violation of the integrity of the containment (i.e., exceeding coolant system or containment design limits). The applicant should (1) demonstrate that sufficient diversity exists to achieve these goals, (2) identify the vulnerabilities discovered and the corrective actions taken, or (3) identify the vulnerabilities discovered and provide a documented basis that justifies taking no action.
By conservatively using the SLMCPR as the acceptance criteria for the D3 stability assessment, no fuel fails as a result of the events. In addition, the stability events do not cause a pressurization which would challenge the reactor coolant pressure boundary or mass / energy releases to the containment which would challenge containment integrity.
Section 3.3 Single Failure and CCF Page 7-19-16 Since CCF is not classified as a single failure (as defined in RG 1.53), a postulated CCF need not be assumed to be a single failure in design basis evaluations. Consequently, realistic assumptions can be employed in performing analyses to evaluate the effect of CCF coincident with DBEs.
Repetitive guidance to Point 2 discussion above.
Section 4.5 Identification of Alternate Trip or Initiation Sequences Page 7-19-21 Thermal-hydraulic analyses using realistic assumptions of the sequence of events that would occur if the primary trip channel failed to trip the reactor or actuate ESF are included in the assessment. (Coordination with the organization responsible for the review of reactor systems is necessary in reviewing these analyses.)
The TRACG analysis tool utilized by GEH to assess the plant response to the proposed D3 stability events is a thermal hydraulic analysis which used realistic assumptions (realistic assumptions as clarified above in item Concerning Point 2 above).
Section 4.6 Identification of Alternative Mitigation Capability Page 7-19-21 For each DBE, alternate mitigation actuation functions that will prevent or mitigate core damage and unacceptable release of radioactivity should be identified. When operator action is cited as the diverse means for response to an event, the applicant should demonstrate that adequate information (indication), appropriate operator training, and sufficient time for operator action are available in accordance with Appendix 18-A of SRP Chapter 18.
By conservatively using the SLMCPR as the acceptance criteria and the proposed manual operator actions for the D3 stability assessment, no fuel fails as a result of the events. In addition, the stability events do not cause a pressurization which would
Page 4 of 4 challenge the reactor coolant pressure boundary or mass / energy releases to the containment which would challenge containment integrity.
General Comment Note: the term time available is not a defined term, i.e., there is no Definition in either Appendix 18A or BTP 7-19. From the context of how the term is used in both documents, PSEG interprets the definition as:
Time Available:
The time from initiation of a Safety Analysis Report event with a common-cause failure (CCF) to the time when the acceptance criteria of BTP 7-19 would be exceeded.
Note: The BTP 7-19 acceptance criteria is 10% fuel failure. For the D3 analysis PSEG conservatively used the SLMCPR as the acceptance criteria, as discussed above.
18-A ATTACHMENT B 2RPT Independent System Validation
Hope Creek Operations Crew A Date 3/2/16 Scenario - 2RPT from 100 % power
- 1. Time available for Operator response - 50 seconds.
- 2. Time required for Operators to respond to initiating event - 8 seconds
- 3. Action expected to be taken -
- 1. Immediate Operator action from memory - Lock Mode switch in Shutdown per HC.OP-AB-RPV-0003(Q)
- 4. Indications available to Operators to diagnose event.
Overhead annunciators C1D4/D5 - A/B Reactor Recirc A/B trouble Recirc pump drive motor breaker flashing OPEN bezel indications - 10C651C
- 5. Actions taken by Operators.
Operators upon verifying trips of both Rx Recirc pumps with the reactor critical, from memory took their immediate operator actions and LOCKED the Rx mode switch in the shutdown position.
- 6. Procedures used that provided guidance.
HC.OP-AB-RPV-0003(Q)
- 7. Did Operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included.
The plots showing Rx power, A/B Recirc pump speed, Rx pressure, and the RPS mode switch position (Run,Shutdown). Time - 8 seconds TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Recirc pump trips - then the RPS Mode switch position change from Run to Shutdown. Time - 8 seconds HC.OP-AB.RPV-0003(Q) - RECIRCULATION SYSTEM/POWER OSCILLATIONS ABNORMAL. (First three pages only.)
I l
t I
I 0
.s=.
.8
"§ C/)
Q.l
"'0 0
- ?!
j
I f
.
Jbunder Simulation Tam.7eport Hope Creek Chris Kittredge, Wed Mar 0210:19:35 2016 PRNM Dual Recirc Pump Tl'ip Crew A iPOS A (D I)* Monitor
!OO: 17: 1 0
'""f
.POS A (DI) *Monitor
!00:17:10
- opios=si1/4ARr*1/2***--M
- 3/4o
-*-r
-**a
- R
- *¿-*--*--************
!SUCTIONLUBE OIL PUMP i(DT) -Monitor loPios:sr***
A
- *R
- *****r
.. M
- --. -*a
"* *r
- .... o R
!SUCl'lON LUBE OIL PUMP
!(DI) - Monitor foP1i 1:srAR:i fuRNiNG
!GEAR LUBE OIL PUMP (DI) *
!Monitor
- -'<._,...,=**-- ***- * **
- -******"********* ""V***""****'
17:06 loo:17:06 tOO: 17:06
- OPlll-START-TURNING
!GEAR LUBE OIL PUMP (DI) * !00:17:06 (Monitor jLV1785/LV1784 ON (DI) lMonitor w.***"*****""'"""*Â*-********cc-*-*-*'""
ILV1785/LVI784 ON (DI) -
- Monitor Blank
- . Description* Monitor
-Blank Description
- Monitor
!00:16:58
1oo:l6:57 j
., ** _.,. ** *** '"-' w< *
"" * *,Ã,-Å-**--- v*-*-***
"'*****Ç--* Nh*-***********É"""'*- *
- ACKNLDGB SECT (DI)
Monitoi"
- ACKNLDGE SECT (DI)
- iMortitor
-*w.. v.o.*******
- ACKNOWLED (DI) Monitor
'ACKNOWLED (DI)- Monitor
....-.. """ *.. '"* *-**... --.v, **-*--*****-********...........
_w...v
- Blank Descrlptio11 *Monitor
.i.POS A (DI) - Monitor jPOS A (DI) *Monitor
!Blank Description - Monitor
- oo:l6:26 00:16:26 00:16:11 00:16:11 16:11 i00:16:11 Ttue True Yes Yes Yes
!ACKNLDGE SECT (DI) -
IMotlitor j00:16:08
!A.ckNLDGE SEc;f(Di)
!Monitor
- 00
- 16:08 r
1Biank Descnpt10n Monitor jOO; 16:06 iBia1:k Description,.. Monitot
- !60:16:06
- '********---m****
- *-*n*'" *'-W********'-*M******
IAC:KNLDGE SECT (DI) -
!Monitor iACKNLDGE SECT (Dl) -
!Monitor f:Bf;;;:nkD$;c%iption
- Mmdtor
!Blank Description-Monitor
!XcK:NLDGE sricr (r>r) -
!Monitor
- ACKNLDGESECT (DI) *
'M*
- .. OllltOt
$S6-5 TRIP (DI) - Monitor
- BS65 TRIP (DI) - Monitor
- oo:16:06 i00:16:05
- oo:I6:o3 00:15:59 00:15:59 (BS2-6 TRIP-(Dif- :ionitor
- ooT558
'BS2-6 TRIP (DI)- Monitor
- 00:15:58
'*>A
- * ***-**" ¥'*>"*********-*o--p*****o****¥"0"'""'""""'""p
'm'" ***p'-'"" *q "' w*"
TURBINE-TRIP (DI) -Monitor,00:15:57
'"'""'"MV' '""
'TURBINE - RESET (DI) -
- Mo11ttor
'oo: lS:S?
h
"""********** *m*****
iTURBINE - TRIP (Dl)- Monitor,00:15:57
'1tJRBiNE - RESET(rii)
- Monitbt'
- rosA (DI) - Monitor
'POS A (DI)
- Monitor ACKNLDGE SECT (DT) -
Monitor ACKNLDGB SECT (DI) -
Monitor Blank Descriptio11-Monitor 00:15:31 00:15:3'0
!00:15:29
.00:15:24
'"w Blank Description - Monitor 100:15:23 ACKNOWLED (DI) :tv:fonitor 00:15:22 iACKNow1Eo (oi5=rvi;nitor oo: 1 5
- 2
- 2 iBiank Description-Monitor
'00: 15: 17 False True False True False
- * **** h ***
Tnw False Yes Yes Yes
- * * * -------r*;
Yes
J3iank.6ec1=iption Monitor oo:I5:16
>'****/'*-'**'1'=01--"/w.,,,..... o,,> "'""""""''"
w***
JRM F-GREEN PEN4
!RECORDER SELECT (DI)-
00:15:16
- Monitor IRM F-,GREEN PEN-
'RBCORDBR SELECT (DI)-
00:15:16 Monitor IRM B GREEN PEN-RECORDER SELECT (DI)-
00:15:16 Monitor
'" v**\\*,********
IRM B GREEN PEN-
- RECORDER SELECT (DI) -
- 00:15:15 Monitot 1TRM E-GREEN PEN-
- RECORDER SELECT (bi) *
'00:15:15
.Monitor
- * **"'* *******v** * * -
TRM E-GREEN PEN-
,RECORDER SELECT (DI) -
i00:15:15
'Monitor IRMA-GREEN PEN-RECORDER SELECT (Dl) -
00:15:15 Monitor IRMA-GREEN PEN RECORDER SELECT (DI) -
Monitor HV-t75JC CLOSE(DI)
- Monitor
- HV-1753C CLOSE (Dl)
Monitor
- IRM H-RED PEN-RECORDER SELECT (DI}- Monitot Ill"' ********1,.. **************AB-----'*"-1 *o******"*""'**"**""-""\\WM'*,*,oOA\\
}RM 11-RED PEN.;RECORDER SELECT (Dl) - Monito1*
URM D RED.PEN-RECORDER
- SELECT (Dl) - Monitor iHV1753B CLOSE (DT)
.Motlitor
- rRM D RED PEN-RECORDER
- SELECT (DI).. Monitor HV-1753B CLOSE (DT)
Mortitor
- 00:15:15
- 00:15:15
'00:15:14 OO:JS:.t4
'00:15:14
- oo
- 15:14
- 00:15:14 00:15:14 True Yes False
.False True Yes False True Yes False True False True False Yes Yes Yes False Yes True Yes True Yes
lRM 0-REO PENWRECORDER
'SELECT (Dl) "'*Monitor
- iRM*GREDilHNRECORDER
!sELECT (DI) - Monitor lfR.1Vfc=.R:f.:o PEN-REcoRDER
- SELECT (D1)- Monitor iivi753A CLOSE (DI) -
- Mo11itor liRM C-RED. PEN= RECORDER SELECT (DI) - Monitor Hv. i753A ciosl(nr) -
Monitor
.DRiVING IN/DRIVE IN DETECTOR DRIVE (DT) -
- Monttor 6R:rv1NoiN/riruvri!N*****
- DBT'ECTOR DRIVE (DIJ Monitor POWER ONJOFFiiETECTOR.....
DRIVE (DI) - Monitor POWER ON/OFF-DETECTOR
- DRIVE (DI)- Monitor
'H-IRM DEl'ECTOR SELECT
- (DI}- Monitor ii=iRM.. DEiEC;foR:**sELECT 00:1.5:14
!00:15:14 00:15:13 00:15:13 00:15:13
,Q0:15:13
- 00:15:12
'00:15:12 00:15:11 00:15:11 00:15:11 (DI) - Monitor fO-IRM DETECTOR SELECT
- o 15 11 0 :
'(DT}- Monitor
- G-lRlvrbEfECTOR SELECT OO
- lS:ld
!(D[) - Monitor
- F-iRM DETECTOR SELECT 00:15:10
- em). Monitor
- F1R:iVfD£i8cr6R:s-EiEcr oo:I5: 1 o (DI) Monitor E-IRM DETECTOR SELECT 00:15:10 (DI) - Monitor E*JRM DETECTOR SELECT 00:15:10 (Dl) - Mm1itor D-IRM DETECTOR SELECT
- 5 10 00;1:
(Dl). Monitor False Yes True Yes False Yes False Yes True Yes Tt'ue Yes False True False True False Yes False Yes True Yes False True False Yes True Yes False Yes
'
- 0 1 A
- DMIRM DEtECTOR SELECT OO:IS:09 iCDI) Monitor
- CiR:MDETEcfOR SELEC'r' 00:15:09 i(Dl)- Monitor iC*IRMDETECTOR SELECT OO*lS'09
!(Dl) - Mcn1ita1' B-IRM DETECTOR SELECT (D I) - Mo11itor BIRM DETECTOR SELECT OO; 15 :09 i(DI) - Monitor AIRM DETECTOR SELECT
'(DI) M 00:15:09
. -. omto.r h>
A-IRM DETBC'rOR SELECT (DI)- MonitM
- oo:Js:os
.B-SRM DETECTOR SELECT
{DI) Monitor OO:l5:0S
- B-SRM DETECTOR SELECT
{DI) Monitor A-SRM DETECTOR SELECT (DI) - Monitor OO:lS:OS A-SRM DETECTOR SELECT (DI) - Monitor OO: 15 :OS D-SRM DETECTOR SELECT OO:lS:OS (Dl)- Monitor
- **/******.. **
'D-SRM DETECTOR SELECT (DI)- Monitor OO:lS:07 c
0
-s 1
- )RN M
f DTECTOR SELECT OO:lS:O?
(
0111101' C-SRM DETECTOR SELECT (D. 1.
.M
- oo:l5:07
- ) -..
orntol' Blanlc Desc,dption Monitm*
Blank Description - Mo11itor Blanlc Desctiption - Monitor Blank Description.. Monitor Blank Desctiption - M.onltor Blank Description - Monitot Blank Description-Monitor Blank Description - Motlitor Blank Desc11ption - Monitor 00:15:05 00:15:04
,00:14:57 00:14:57 00:14:55 00:14:52 00:14:51 True False True Ttue False True False TrLLe False True False True False Ttue False True False True False True False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
POS A (DI)
- Monitor POS A (DI) Monitor Blank Description-Monito1*
> ***** L Blank Descripti011 - Monitt>r Blank Description., Monitt)r Blank Description Monitor Blank Description - Monitor 131£1( Desc1ipiii; Monitot Blank Description - Monitor RRCS MAN INTITIA TI (DI)
- Monitot RRCS MAN TNTITIATt (Dl)
- Monitor RRCS MAN INTIT PERM (DT)
-Monitor
'¥'
RRCS MAN TNTIT PERM (Dl)
-Monitor Blank Descrlptfoli - Monitor RRCS MAN lNTITIATl (Dl)
- Monitor RRCS MAN INTITIA TI (DI) -
Monitor
- RRCS MAN INTIT PERM (Dl)
-Monitor rBlank DescrlptiDn - Monitor rAACS MAN lNTlT PERM (Dl)
- Monitoi'
!RRCS MAN INTITIATI (DI)
- Monitor RRCS MAN INTITIATI (DT) -
Monitor RRCS MAN INTIT PERM (Dl)
- Monitot Blank Description Monitor RRCS MAN lNTIT PERM (DI)
- Monitot RRCS MAN INTITIA TI (DI) -
Monitor 00:14:50
.False
...... L.....
00:14:46 True
'00:14:44 False 00:14:43 True 00:14:42 False 00:14:42 True 00:14:40 False Yes
'00:14:40 True Yes 00:14:39 False 00:14:39 True Yes
' '"*-()o,_v_,___"
00:14:39 False Yes 00:14:39 False Yes
'00:14:38 True Yes
- oo:t4:3S 00:14:38 00:14:38 00:14:38
,00:14:37 00:14:37 False Yes 00:14:37 False 00:14:37 True 00:14:37 False Yes
- RFPT A 'ffilP (D.l) - Monitor
- RFPT A TRU1 (Dl)- Monitor
- RR:CS MAN INTITIATI (Dl) *
.Monitor
'00:14:36
. h......
00:14:36 00:14:36 False True True Blank Description-* Monitor 0014:36 True
- RRCS MAN INTIT PERM (DI)
- - Monitor
- oo
- l4:36 RRCS MAN INTITPERM (Dl) *oo:l4:36 True
-Monitor
- RPS TRIP LOGIC B l MAIN
!INIT PUSHBUTTON (DI) -
.Monitor
- R:rsfRrriomc Bl MAIN
- INIT *- PUSHBUTTON (DI) -
- Monitor lBlank Description Monitot 00:14:32
!oo:14:32
'rzps'fR:ii>.D5otc B2 11\\N IN It-ARM (DI) -Monitor OO: 14:31
. Blank Description Monitor
- RPS TRIP LOGIC Bl MAN lNIT - ARM (Dl) -Monitor
- RPS TRIP LOGIC Al MAIN JNIT - ARMED (DI) - Monitor IRPS TRiP LOGIC A 1 MAIN
.TNIT.. ARMED (DI)- Monitor
!RPS TRIPiOGIC A2 MAN llNIT-ARM (DI)- Monitor
]{PS TRIP LOGIC A2MAN IINIT-ARM (Dl) - M.onitor
!RPS TRIP LOGIC A2 MAN liN IT " PUSHBUTTON (Dl) -
Monitor Blank Description-Monitor RPS TRIP LdGIC Al MAN
!NIT -* PUSHBUTTON (Dl) -
.Monitor Blank Description -Monitor Blank Description - Monitor
- v.
- Blank Description - Monitor 00:14:31 00:14:31 00:14:30 00;14:30 00:14:29 00:14:29
.00:14:29
- oo:14:29 00:14:28 00:14:27 00:14:26 00:14:25 False True True True False True False True.
True False True True False Ttue Yes Yes Yes Yes Yes Yes Yes
- ** NM='"""u**O********
Yes Yes Yes Yes Yes Yes Yes
iBlat1k Desc1'iptlon-Monitor 1Blat1k Desctiption'"' Monitor
- RPS MODE SWITCH -
- REFUEL (Dl)- Monitor
!R.Ps MODE sWiTCH lREFUEL (DI) - Monitor iRPs MODE swn:ci-:I-00:14:24
'00:14:24 100:14:23
'00:14:23
- sTARTUP & HOT STDY (DI) '00
- 14:23
,Monitor iRPS MODE SWITCH -
False False True False
)STARTUP & HOT STDY (DI) - '00:14:23 True Monitor
- RPS MODE SWITCH.. RUN (DI)- Monitor
- 00:14:22 False
- Blank Description - Monitor Yes
PSEG Internal Use On!)!
HC. OP-AB.RPV
.. 0003(Q}
RECIRCULATION SYSiSM/POWER OSCILLATIONS Effective Date: 3 Feb 2016 I :
CATEGORY II REACTOR REClRC PUMPS TRIP REACTOR RECIRC PUMP VIB HI COMPUTER POINT IN ALARM LPRM UPSCALE LPRM DOWNSCALE OPRM TRIP ENABLE OPRMAL.ARM OPRM TRIP BYP/INOP/TRSL OPRM IRIP INDICATIONS Unexplained Change in:
ct
.. o3 C1-E4 C1.. F5 C3*D5 C3E5 C3F1 C3
.. F2 C3-F3 C5-B1
> Recirculation Pump Flowr Rx Water Levell Rx Power, Rx Recirc Pump Seal Performance.
Trip of EITHER Re.circ Pump as Indicated b :
> *Recite Pump RPT Breaker OPEN,
0f?f1 Recirc MG Field Breaker OPEN.
The indicated Recirculation loop flow differs by more than
> 10% from the established pump speed"loop flow characteristtcs, 10% from the established total core flow value derived from Recirculationfoopflow. lhe i!idicated diffllser/to-lower plenum differential pressure of any individual jet pump differsfrom the established patterns by more than 20%.
Reclrculatlon Pump Vibration Levels Rising,.
APRM OR LPRM power oscillations.
An OPRM Channel indicates a trip OR alarming condition.
Short Period afarmsl Positive and negative swings on the period meter.
Reclrc Pump seal cavity temperature greater than 160 degrees F (A2998,. A2999, A3008, A3009).
Recirc Pump #2 seal cavity pressure less than 200 paig OR greater than 800 psig.
(A2590, A2592).
TERMINATED Oate/Ti:me: _______ _
Hope creek Page 1: of 40 Rev.30
I.
HC.OP*AB.RPV
.. 0003(Q)
.RECIRCULATION SYSTEM/POWER OSCilLA1IONS RETAINMENt OVERRIDE CONDITION ACTION Affected Recite Pump seal cavity
La REDUCE the affected Reeirc pump temperature greater than 200 degrees F speed to mlnimum, TRIP the affected Reclrc pump and Date/Time:
enter Condition A
- -*
NOTES;
- 1., pg 3 or 4, "POWER TO FLOW MAP (OPRM INOPt:RAE3LE)" is required to be utilized as part of an alternate method to detect and suppress thermal hydraulic instability oscillations to corn ply with T/S 3.3, 11 action a.3 or b.1.
ADDITIONAl INFORMATION:
REFER to Attachment 4 forPOWER TO FLOW MAP Power Oscillations (Thermal Hydraulic Instabilities} are defined as any ofthe following:
10% peak to peak Power Oscillations on APRMs Periodic Upscale OR. Downscale LPRM Alarms (on the Full Core Display)
Strong* positive/negative swings an the Period Meters Hope Creek Page 2 of40 Rev. 30
PScG Internal. Use Ol'lly HC.OP*AB.RPV-0003(Q)
R.ECIRCULATION SYSTEM/POWER OSCILLATIONS Indications of Power Oscillations LOCK the Mode Switch ln SHUTDOWN.
(Thermal Hydraulic Instability)
[CD354F] [IER L2 15;.34, Rec. 1c]
Date/Tlme:
- NOTE 1**
OPRM's INOPERABLE AND ln REGION 1 Date/Time:
6UTOMATIC ACTIONS IF OPRMTRIP Hope Creek LOCK the Mode Switch in SHUTDOWN.
THEN Half or Full Scram Page 3 of 40 Rev.30
-
Hope Creek Operations Crew B, Date 3/22/16 Scenario - Dual recirc pump trip from 100 % power.
- 1. Time available for operator response - 50 seconds.
- 2. Time for operators to respond to initiating event - 8 seconds
- 3. Action expected to be taken -
- 2. Immediate operator action from memory - Lock Mode switch in Shutdown per HC.OP-AB-RPV-0003(Q)
- 4. Indications available to operators to diagnose event.
Overhead annunciators C1D4/D5 - A/B Reactor Recirc A/B trouble Recirc pump drive motor breaker flashing OPEN bezel indications - 10C651C
- 5. Actions taken by operators.
Operators upon verifying trips of both Rx Recirc pumps with the reactor critical, from memory took their immediate operator actions and LOCKED the Rx mode switch in the shutdown position.
- 6. Procedures used that provided guidance.
HC.OP-AB-RPV-0003(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included.
The plots showing Rx power, A/B Recirc pump speed, Rx pressure, and the RPS mode switch position (Run,Shutdown). Time - 8 seconds TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Recirc pump trips - then the RPS Mode switch position change from Run to Shutdown. Time - 8 seconds HC.OP-AB.RPV-0003(Q) - RECIRCULATION SYSTEM/POWER OSCILLATIONS ABNORMAL. (First three pages only.)
"[
Th er Shnulation Tam ort Hope Creek Chris Kittredge, Tue Mar22 12:43:23 2016 Shift.HPRNM Dual Recirc Pump trip
!Description
" *-'"N*-*m-*" ***
- Blank Description Monitor IB1a1ik Description-Monitor O**""*"*****4PY....,................ *,.-
- Q********-*Rum>*:*S"'<"*">>*-"*******'*****T**"*'
fRFPT B TRIP RESET (IJ!) -
]Monitor fRFPT B TRii>"R.iSE;f (DI) -
!Monitor IHV17S3CCLOSE (DI) "
!Manito!'
,HV w 1753C CLOSE (151) *
- Monitor JfV-l753B CLOSE (DI) *
!Monitor
,HV-1753B CLOSE (DI) -
1Monitot
]HV-l753A CLOSE {DlJ -
!Monitor
- -U*-----*********u=oow*v w '-=""
LHV-1753A CLOSE(Dl)
- Monitor Blank Descdptlon - Monitor lBlartk Description - Monitor tpos A (DI).. Monitor POS A (DI) - Mon.ltor
- Blank Description - Monitm A TRIP (DI) - Monitor
!RFPT A TRIP (Dl) Monitor iiJiMiiRED PEN-RECORDER
!SELECT (DI) - Monitor
'iizM B-REDPEN=r{ficdili>ER
- 00
- 08.:13
- 00:08:13
'00:07:55
'00:07:55 io6:o7:49
'00:07:49
!00:07:49
- 00
- 07:49
,00:07:48 False False True False 100:07:48' True
.00:07:46 False
- 00:07:46
- 00;07:24 00:07:18
- 00:07:17 00;07:17 True False True Yes Yes Yes Yes Yes Yes Yes
[SELECT (DI}" Monitor r**,GmH* ******N**"** woe
- iiRM D RED PENRBCORDER
[SELECT (DI) - Monitol'
[ii{M D RED PENRECORDER IS ELECT (DI) Monitor
- Q0:07:i 7 100:07:17 IIRM PENIREc**..,**a* ****R****n* ***E R,oo:o7:17
- sELECT (DI) Monitor
- *****'**-'*J*****'***********G"*'"W'K.,K--*L......w..................,,,,.,.,,,.,................
lJRM C-REIJ PEN RECORDER !00:07:
16
!SELECT (DI)- Monitor llRM G-RED PEN-RECORDER
\\SELECT (DI) - M.onitor fiRM G-RED PEN-RECORDER ISELECT (Dl).. Monitor
""""""""'""'""'"*"*W.".>..
w.,.... ******** *M* ******* """'"""=*m*_,_,o*o*=mwom""' *
!IRM F-GREEN PEN-IRECORDER SELECT (DI) lMonhot
- RECORDER SELECT (DI) -
!Monitor
'lRM B 6REEN PEN
'RECORDER SELECT (DT)
Monitor JRM B GREEN PEN
.RECORDER SELECT (DI) -*
,Monitor IIRM £:.GREEN PEl
)RECORDER SELECT (Dl)
'Monitor iiRM E -GREEN FEN
!RECORDER SELECT (DI)
- Monitor
- IRMA-GREEN PEN
!RECORDER SELECT (01) -
- Monitot IRMA-GREEN PEN RECORDER SELECT (DI)
Monitor DRIVING TN/DRIVE IN DETECTOR DRIVE (Dl) -
!Monitor ACKNLDGE SECT (DI) 00:0716 l
'00:07:16 100:07:15 00:07:15 00:07:14 00:07:14 00:07:14 00:07:14 00:07:14 00:07:13 00:07:12 00:07:12 False Yes Tme Yes Ttue False Yes True Yes False Yes False Yes
!Monitor 1ACKNLDGE SE(5T {DI)
Monitor iDRIVINO IN/DRIVE IN
!DETECTOR DRIVE (DI)
!Monitor Bla1k Desctiption - Monit:
'Ii;kDscription-Monitor
'fi-iRM DETECTOR SELECT
'(Dl) -*Monitor l'fi=rrzM'i::JEirricfoR -SELECT lcDI) Monitorw,.....
G-1RM DETECTOR SELECT (DI) - Monitor lG-lRMDETBCTORSELECT
{DI) - Monit,)t
- P:IiMnET.Ect6R:sii1£cT***
1(DI)- Mot1itor F-iR:!VibETECTOR SELECT (Dl) - Monitor E>IRM DETECTOR SELECT (DI) - Monitot E=IRM DETECTOR SEl.ECT
- (DI} - Monitor
'D-IRM DETECTOR SELECT (DI) - Monitor D-fRTVfOETECTOR SELECT (DI)- Monitor G-IRM DETECTOR SELECT
,(DI) *. Monitet CiiDEiiicroR SELEct*
- (DI) - Mo.nitor
'B=IRM DETECTOR SELECT (DI) - Monitor
- B-IRrvfiJETECTOR SELECT
'(DI) -Monitor A-lRM DETECTOR SELECT (Dl) Monitor A-IRM DETECTORSELRCT (DI) - Moni?t' 00:07:11
- 00:07:11 00:07:11 00:07:11 00;07:10 00:07:10 00:07:09 00:01:09
'00:07:09
'00:07:09 00:07:09 00:07:09 00:07:09 00:07:08 00:07:08 00:07:08 00:07:08 00:07:0&
00:0:7:08
- 00
- 07:08 True True False True False Tnle False False True False True False True False Trne False True False T11.1e Yes Yes Yes Yes Yes Yes Yes
- D-SRM DETECTOR SELECT
'(DI)- MM.itol'
- <dY h- <*o *->********
])-SRM DETECTOR SELECT (DI) Monitor
- c
... SRM DETECTOR SELECT (DI) Monitor
'Blank Description - Monitor C-SRM DETECTOR SELECT (Dl)
- Monitot Blank Description - Monitor N ** NM'"""
o
< * \\
tB-S.RM DETECTOR SELECT
- (Dl) '"Monitor B-
- SRM DETECTOR SELECT...
- (D I)
- Monitor ASRM DETECTOR sBr:EcT i(Dl) -Monitor
"*,,Yv...,* *,*3*-
""**4 "*****
""1*-== ' *'***----._......
A-SRM DEtECTOR SELECT
.(Dl) - MOititor
!POWER ON/OFF-DETEGT;OR DRIVE (D1)
- Monitor POWER ON/OFF-DETECTOR DRIVE (Dl) Monitor ROD SELECT ACCUMULATOR TROUBLE A.CKNOWL8DGE (DI)-
!Mmtitor
'ROD SELECT-
.ACCUMULATOR TROUBLE ACKNOWLEDGE (DI)-
.Monitor ACKNOWLED (DI)- Monitor ACKNOWLED (Dl)- Monitor RFPT C TRIP (DI)- Iv1ortitor POS A (DI) -Monitor RFPT C TRIP (DI)
- Monitor POS A (DI) - Monitor
'****
.B lat1k Descriptim'l
- Monitor Blank Description - Monitor iBlank Desc1:iption - Mottitor
- 00:07:07 00:07:07 00:07:07
,00:07:07 00:07:07 00:07:07
"""' " 'N * -
'00:07:07 00:07:07 00:07:06
.00:07:06 00:07:05
.00:07:05 00:.07:04 00;07:03
- 00:07:01 00:07:00 00:07:00 00:07:00 00:.07:00 00:07:00 00:06:57 00:06:57 00:06:55 False Yes
- --
- 1 True Yes False Yes False Yes True Yes Tme Yes False Yes Trt1e False True Yes False Yes True Yes False Yes True Yes False Yes True Yes False Yes False True True False True False Yes
iBlank Description Monitor 6if06i5s
!Blank DeSCL'iption-Monitor
- '00:06:54
'Blank Description Monitor 00:06:53
- Blank Description.. Monitor Blank Descdption - Monltot n3IatllDestlption *Monitor 1Blank Description " Monitor Blank Description
- Monitor Blank Description -Monitor
- * ****'-'**** ********h**>>Y<
o*******
Blank Description - Monitor Blank Description - Mon:itor Blank Description-Mot1itor
. '<**-- ""i----j*-'"**" w
- - *-*-** -* ***-"*-***-**--**********"***k'-"""'"'"""""l'-""'
!Blank Des.cdption - Monitor
!Blank Description Monitor lBlatlk Description - Monitor Blank Description-Monitor
'Bla11k Descdption - Monitor Blank Description-Monitor Blank Description -Monitor Blank Descl'iption-Monitor Blank Description - Monitor Blank Description - Monitor
- 00;06:52 00:06:52 00:06:52 00:.06:52 00:06:51 00:06:51 "m*******
00:06:49 00;06:49 00:06:49
- -'***i"'"""
- *******' *'w"'"'""'.. """'""'"
00:06:48
,00:06:48 s00:06:48 n*********'-********* ****o**w."'""'">**
00:06:48 00:06:48 00:06:48 00:06:47 00:06:46 00:06:46 00:06:41 Blank Description - Monitor
- 00:06:41 Blank Description-Monitor
'00:06:39 Blank Descl'iption - Monitol' 00:06:39 Blank Descd.pticm Monitor 00:06:37 Blank Description-Monitol' 00:06:37 Blank Description Monitor 00:06:35
- Brank Descdptim:l: - Monitor
,00:06:34 Blank Desctiption Monitor 00:06:34 Blank Description Monitor 00:06:34 Blank Description-Monitor 00:06:32 Blai;k.,Description-Mon
.. i
... t o
.... r
. 00:06:32 Blank Description-Monitor 00:06:30 Blank Description-Monitor 00:06:30 True False True False True False Tl'ue Fa:lse True False Ttue False True False True False Tiue False Tme False True
- "o***.. ******* """""""'"
False True False True False True False True False True False True Yes Yes Yes Yes Yes Yes
........ -p******
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
BIHnk Description - Monitor Blank Description
- Monitor h ** u..
- '*o*.-'w************* ** **¥*
Blank DesctiptiOI1 Moriitor RRCS MAN INTITIA TI (Dl) m Monitor 00:06:30
,00:06:29
- 00
- 06:29 100:06:29
,Blank Description $Monitor
- 00:06:29
,RRM.
- C MAN fNTITIA TI (DI) -
'00:06:29 omtor False True False False Tl'ue
- mank Descdption *Monitor 00:06:29 False
.. RRCS MAN TNTlT PERM (DI)
- 00:06:2<1 False
- Monitor
!RRCS MAN INTIT PERM (Dl)
, M.
00:06:28 True omtor Blank Description
- Monitor mlank Description..
. Monitor
,Blank Desctiption - Monitor RRCS MAN INTITIATI (Dl) -
Monitor Bl.ank Desctiption - Monitor RRCS MAN INTITIATI (DI) -
Monit01' RFPT A TRIP RESET (DI)
- Monitor 00:06:28 00:06:28 00:06:28 00:06:28 00:06:28 00:06:28 00:06:28 RRCS MAN INTIT PERM (DI) 00:06:27
- Monitor Blank Desctiption - Mo11it01' RRCS MAN INTIT PERM (DI)
Monitor Blank Desctiption-Monitor Blank Description - Monitor Blank Description - Monitor Blank Description - Monitor Blank Description* Monitor Blank Description - Monitor Blank Description - Monitor Blank Description-* Mot1itot Blank Description - Monitor 00:06:27 00:06:27 00:06:27
- 00:06:27 00:06:26 00:06:26 00:06:26 00:06:26 00:06:25 00:06:25 00:06:25 False Tme False False True False False True True False True False True False True False Ttue False Yes Yes
,.1 '.
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
.... '* *'*****.. n: *...
Yes Yes Yes Yes Yes Yes Yes
jBla11k Description* Monitor f'Bianl( Description
- Monitor iBianr<bcdption - Mo11itor
- ¥*****---.. ---******
- Blank Description* Monitor
.Blank Description - Monitor
.Blank Description - Monitor iRPSTRTP LOGIC l32 MAN
- IN IT.PUSHBUTTON (Dl) -
- Mot1itm
!RPS TRLP LOGIC B2 MAN 1INIT-PUSHBUTTON (DI) *
- 1Monitor
]Blank Description - Monitor fi31nk Dest{ption - Monitot IRP.srru.P.io.cnc n2 MAN
- fNIT-ARM (DI) - MonitOl' Blank Description-Monitor
- Blank Description-* Monitor RPS TRIPLOGlC Bl IVIAIN INIT
- PUSHBlJTTON (DI)
Monitor RPS TRIP LOGIC B 1 MAIN 00:06:25 00:06;24 00:06:24 00:06:24
>00:06:24
,,,,,,,., *******,,, *** m ** u.o.,,,,
- 00;06;24 00
- 06:23 00;06:23
.oo:06:23
!00.;06:23
.... :............. n.... *
'00:06:23 00:06:22 00:06:22 INIT *PUSHBUTTON {Dl)-
00:06:22 (fvlotritor
'"""'"" *o<*****N*****o*
Blank Description-Monitor 00:06:22
- ma:nk Description - Monitor RPS TRIP LOGIC B 1 MAN INlT
- ARM (DI) Monitor
.Blatlk Description - Monitor
.Blank Description.,. Monitol' RPS TRIP LOGIC A2 MAN
- INIT ARM (Dt)- Monitor
'Blank Descriptim1 - Monitor y*
y RPS TRIP LOGIC A2 MAN
Monitor
'00:06:22 00:06:22 00:06:22 00:06:21 00:06:21 00:06:21 00:06:21 00:06:21 Trne False nue False True False False True False True True False False True True true False False Twe True Tme Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
,Blattk Description Monitor
\\00:06:21
.1 ***"-"***-->>.m**'m'*"***** <
nN-;w>Now******** '
- Blank Desctiption* Monitot
- Q0
- 06:ZO iRPS TRIP LOOJC 1\\1 M A
l N
i00:06:20
- INLT-ARMBD (DI) - Monitor
................. *******¥*********....*
- ................... 1,,, ******-*****----->-----.
Blank Description - Monitot
- RPS TRIP LOGIC A iMAlN iiNIT-ARMED (Dl)
- Monitor fRPSTRi?LOarCAI MAt*T
[INIT -PUSHBUTTON (DI) "
!Monitot' iBiank Description*** Monitor 1Blank Description - Monitot
!Bia;}i i::>escription M;itor
!Blank Description " Monitor
]Blank Descripii6i1 -Monji0t;
- i3iakDescription Monit6r
,Blank Description -Monitor
'BlankDecription.Monitor
'Blank Description-Monitor
,R.fp;r; A TRIP (DI) M-nitor r0:;f!r A Tru.Pcor5=M;;;ii0f:
Description Monitor iRPS MODE SWITCH
- REFUEL (DI) - Monitor i:RPS MODESWITCH -
,REFUEL (D I) - Monitor
- MN,,.., *
'-** """'**********-***"*---*-******<--WJ.'k-O.W*M<' ____..,.... "
iRPS MODE SWITCH-
'STARTUP & HOT STDY (Dl)
!Monitor
'RPS MODE SWITCH
- 00
- 06:20
- oo:o6:2o 00:06:20
- 00:06:18
'00:06:17 00:06:17
- 00
- 06:17
- *** wuxyz-{l**-*}-*-~*"*
- 00:06:17
'00:06:17
- oo:o6:l5
- oo:06:15 00:06:15
'00:06:15 Yes True Yes True Yes Tme Yes False True False Yes True Yes
& HOT STDY (Dl)
- Monitor
!RPS MODE SWITCH RUN l(Dl) Monitor
- ---*.. m*-.,.......
- Blank Description -Monitor
- Toggte event 21 00
- 06:15 False
- oo:06:15
.False
Hope Creek Operations Crew C, Date 3/16/16 Scenario - Dual recirc pump trip from 100 % power.
- 1. Time available for operator response - 50 seconds.
- 2. Time for operators to respond to initiating event - 10 seconds
- 3. Action expected to be taken -
- 3. Immediate operator action from memory - Lock Mode switch in Shutdown per HC.OP-AB-RPV-0003(Q)
- 4. Indications available to operators to diagnose event.
Overhead annunciators C1D4/D5 - A/B Reactor Recirc A/B trouble Recirc pump drive motor breaker flashing OPEN bezel indications - 10C651C
- 5. Actions taken by operators.
Operators upon verifying trips of both Rx Recirc pumps with the reactor critical, from memory took their immediate operator actions and LOCKED the Rx mode switch in the shutdown position.
- 6. Procedures used that provided guidance.
HC.OP-AB-RPV-0003(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included.
The plots showing Rx power, A/B Recirc pump speed, Rx pressure, and the RPS mode switch position (Run,Shutdown). Time - 10 seconds TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Recirc pump trips - then the RPS Mode switch position change from Run to Shutdown. Time - 10 seconds HC.OP-AB.RPV-0003(Q) - RECIRCULATION SYSTEM/POWER OSCILLATIONS ABNORMAL. (First three pages only.)
I Recirc Pumps Tripped
- 08:40 08:40 I
08:42 0&:44 Times are from TAMs which does not show tenths of seconds.
**
r
rhunder ?lmulation Tam Regort Hope Creek Shaffer, Wed Mar 16'10:19:54 2016 PRNM test C shift
!Desctiption
- ACKNLDGE SECT (DI)
,Monitor Value 00:11:44 False IACK.NLDOE SECT (DI)..
!Monitor 00: 11 :44 True A (Dl) Monito1*
00:11:33.
,J?'Qs *x*cor):*M:onitor********** *********************
!oO:.ii;33 mfik riesc1:iJ;ii011. M.oi1i1:0r * ****
- !oo: 11 :31 False
- J:uank Description Monitor.
'*'*'-""*****.v***********-******'***** ** **--***-**
- Blm1k Description -Monitor
.Blank Description
- Monitor lACKNLbGE SECT (Di)~
Monitor
- ACKNLDGE SECT (Dl)
!Monitor
........._,m,,w=*=** ***- ---**
!00:11:30 00:11:19 ACKNOWLED (DI) Monitor
'00:11:18
- -*-***-*-**-**o* on*"*w**v iACKNOWLED (Dl)- Monitor
!00:11:18 jPOS A (Dl) - Monitor 00:11:17 False Tme False
- pos A (DI) - Monitor
">VU
- Blank Description-Monitor 00:11:10
-'** *""-v**-v * ** *v***---* -,
ACKNOWLED (DI)- Monitor
'00:11 :09 Blank Description - Monitor
'"'="W """"')"A,VO.W.>O'OWU.*'""''"'-"'''"'+" **v**, W.* "''''''',.""''".. ""
ACKNOWLED (DI)- Monitor ACKNLDGE SECT (DI)
Monitor ACKNLDGE SECT(DI)
Monitor Blank Description Monitot Blank Description - Monitor 00:11:09
'oo;Ic6&********
00:11:04 00:11:03 00:11:02 00:11:02 True False False True True Valid Yes Yes:
Yes Yes
n¥
!AM. Cl<;NLDOE SECT (DI)
!OO:l0:$9
--f-Ollltor---78-
iACKNLDGE SECT (DI) *
!Monitor
!rRi?nxcnE:R FIELD
- EREAKER(DI) - Monitor
[TRIP-EXCITER FIELD
!BREAKER (DI) - Monito-t iBS6-5 TRIP (Dl) " Monitor
- , ***** *w*****A>"
- "" +****
)BS6.:5 TRIP (DI)
- Monitor iEs2-6 TRiP-(nr):}rvronitot IBS2--6 TRIP (DI) Monitor lrtrR.Bri,fE:=*REsiS1' cor) -
!Monitor
!00:10:59 100:10:58 i
j00:10:57 00:10:56 00:10:56 00:10:55
- TURBINE TRIP (DI)
- Monitor 100:10:55
- TURBINE - TRIP (DI) -6 Monitot
- l00j6l55
!TURBINE.,. RESET (DI) -
1
!Monitor
,OO: lO:SS
- c...........................
HV -1753A CLOSE (DI) -
Monitor
- HV -1753A CLOSE (Dl) -
,Monitor
**c. * ----
[HV-1753B CLOSE (DI)-
- Monitor BV1753B CI,OSE (DI)
Monitor HV-1753C CLOSE (DI)
!Monitor HV-1753C CLOSE (DI) -
Monitor Blank Description Monitor
'Blank Description - Monitot Blank Description - Monitor Blank Description-Monitor ACKNOWLED (DI)., Monitor ACKNOWLED (DI) - Monitor
'00:10:39
- 00
- 10:38
.00:10:37
'00:10:37
- 00:10:37 00:10:36 iOO:l0:32
- 00:10:32
.00:10:32 00:10:32 00:10:28 00:10:18 00:10:18 True True True Tme False True False True False True False True Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
)
'POS A (DI) MonitoY 00:10:14 Ftlse Yes 1 -d*
---mit)f1,e A*(DI)l-Motrito1' --*oo:to:13 -----;-
True:--=:::.: __ -==:.::::.::_i:===:ye=s..-******_* ____,
IRMBREDPEN-RBCORDER OO:lO:lO
- SELECT (DI) - Monitor f*
1RMJIRED PEN-RECORDER OO;l0:10 iSELECT (DI).. Monitor v""
- - *-*g**-*-.****-******
IRM D RED PEN-RECORDER
,SELECT (DI)
- Monitot OO:lO:IO HRM D RED PEN-RECORDER OO:IO:lO SELECT (Dl) - Monitor IR:M'aR"EDrENREC6RriER 00:1 o: 10 SELECT (DI)
- MonitOl'
- IRM.G-RED PENRECORDER
- s*E* L. 'ECT (.DI).M.
iOO:lO:lO l
omtor
- iiM.c:R:EDPEN*RECORDER fSELECT (DI) *Monitor OO: l O: 1 O tiR.Mc:REDPEN-RECORDER oo:lO:lO
'SELECT (DI) - Monitor FGREEN PEN
- RECORDER SELECT (Dl)-
00:10:09 Monitor
- y ******
Monitor 00:10:09
--h*"'--¥-----i---*-*--*--j-**-*
-*k-- ----
IRM B GREEN PEN RECORDER SELECT (DI)..
'00:10:09 1Manitor
'RECORDER SELECt (DI)-
00:10:09
.tvionitor 1RM E-GREEN PEN"
,RECORDER SELECT (Df) X 00:10:09 Monitor h..
'RECORDER SELECT (DI) M 1Monitor
'IRM AGREEN PEN iRECORDER SELECT (DI)
'Monitor IRM AGREEN PEN 00:10:09 00:10:09 00: 10;08 True Yes False Yes True False True False True False Yes True Yes False Yes True Yes False Yes True False True Yes
!RECORDER SELECT (bl) -
.... --------!Monitor---------
'DRIVING IN/DRIVE IN
!DETECTOR DRIVE (Ol) -
'Monitor hRlVING IN/DRIVE IN
'DE'lECTOR DRIVE (Dl)
Monitor HlRM DETECTOR SELECT
'(DI) - Monitor 1H-IRM DETECTOR SELECT
'(Dl).. Monitor 1G-IRM DETECTOR SELECT
- (DI) - Monitor
'n-IRM DETECTOR SELECT
- (DI) - Monltor lFIRM DETECtOR SELECT
!(DI) - Monitor
- ' *w*****--*** "'"'"* "* *
. F-IRM DETECTOR SELECT 1(01) - Monitor
!E:IRM DETECTOR SELECT
'cor) -Monitor 00:10:08 00:10:07 00:10:07 00:10:06
- 00
- 10:06
- oo:1o:o6 00:10:06 00:10:05
- E-IRM oEi'EcrORs£ri3cr *** oo:lo:os
- cor) Monitor jJS:sRM DET*E*******--c--***--T --.. 0**---**R*******--. SELECT
{DI) - Monitor D-SR:M DETECTOR SELECT
'(Dl) - Monitor
'C-SRM DETECTOR SELECT I (DI) - Monitor
- C-SRM DETECTOR SELECT******
'(Dl)- Monitor m-IRM DETECTORSELICT i(Dl) - Monitor
- rirRM Dlii'E:croR: sELECT (Dl) "" Monitor C*IRM DETECTOR SELECT
.(Dl) - Monitor C-lRM DETECTOR SELECT (Dl) - Monitor 00:10:05 00:10:05 00:10:05 0:05 00:10:04 00:10:04 00:10:04 00:10:04
'-------------1 False Yes True
.False Yes True Yes False Yes True Paise True False True Yes False Yes Ttue False Yes True False True False True
B JRM DETECTOR SELECT
--- --(Dl}--Monitor
OO:IO:OJ iB1RM DETECTOR SELECT
- (DI) Monitor wo "2*"'"'"" *
- AlRM DETECtOR SELEt:<r
- (Dl) X Monitor AIRM DETECTOR SELECT i(Dl) - Mmtitor B-SRM DETECTOR SELECT
- (DI) Monitor BSRM DETECTOR SELECT kDI) - Monitor iA-SRM DETECTOR SELECT
'(DI) Monitor IA
.. SRM.DETECTOR SELECT l(DI) - Monitor POWER ON/OFF-DETECTOR DRIVE (DI) -Monitor POWER ON/OFF-DETECTOR DRIVE(Dl) - Monitor ACKNLDGE SECT (DI)
Monitor ACKNLDGE SECT (DI) -
Monitor POS A (D I) - Monitor
'POS A (Dl)- Monitor
'Blat1k Description - Monitor Blank Descdption-Monitor
- 3 Blank Description - Monitor Blank Description-Monitor
'Blank Description - Monitor
- Blank Description-Monitor Bltiltk Description.. Monitor Blank Descdptlon-Monitor Blank Description-Monitot Blank Description* Monitor Blank Description-Monitor Blank Description Monitot 00:10:03 00:10:03
- 00:10:03
- 00:1 0:03 00:10:03
'00:10:02 00:10:02 00;10:02
- oo:lO:Ol 00:09:58 00:09:58 00:09:55 00:09:54 00:09:39
'00:09:39 00:09:34
- 00
- 0934 00:09:31 00:09:31 00:09:25 00:09:25 00:09:22 00:09:22 00:09:20 00:09:20 False True False True False True False True False True False True False True False True
,.. **4 False Tl'ue False True False Tru.e
" OO OOOOOOO OOHHOOOOUH False Ttue False Tl'ue
.................................................................. * * * **** ****-***.-.,*m****
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 5*-*
Yes Yes Yes
'Blank Dzsc{ipifon-Monitor 66:09:15
-**-:stanJ<Desci ft:Jtlo116*M:ot1ito17. -:oo:o9:t5 --5
- Blanl Desc1
- it)tim1 Mottitor
'Blank Descriptiot1-Monitor RRCS MAN INTITIA 11 (Dl) -
Monitor
.RRCS MAN TNTITIA TJ (DI)
Monitor R
RCS*****
M
- A******
N
- I NTil;IATl (DI) -
Monitor 00:09:12 00:09:12 00:09:12 00:09:11 00;09:11 RRCSMAN JNTITIATI (Dl) -
'00:09:11 Monitot RRCS MANlNTtTIATI (DI)-
(\\
- 00:0;:10 Monitor RRCS MAN TNTITIATI (DI)
,00:09:10
- Monitor RRCS MANiNriiiATI (Dl)-
oo:o9:Jo
'Monitor
,RRCS MAN INTITIATI (DI) -
00:09:10
- Monito1*
- J3iank Description-Monitor 00:09:09
'Blank Description Monitor
...... ??:?_xy----
- RRCS MAN INTIT PERM (DI) 00
- 09:09
- Monitor RRCS MAN fNTIT PERM (DI)
... Monitor tiuicSMAN.INTIT PERM (DI)
'-Monitor 00:09:09 00:09;08 n{RCS MAN fNTIT PERM (DI) 00:09:08
-Monitor RRCS MAN INTJT PERM (DI) :oo:Og:QS Monitor RRCS MAN INTIT PERM (DI) 00:09:08
. Mot1itor RRCS MAN INTJT PERM (DI)
-Monitor RRCS MAN INTJT PERM (DI)
- Monitm*
Blank Description-Monitor 00:09:07 00:09:06 False Ttiie False True False True False True False True False True False True False True False True False True False True False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
CBimtk Description Moititor Blank Descdption Monitor
- 2-
,Blank Description Monitor iRPS TRIP LOGIC B2 MAN iiNIT - ARM (DI) - Monitor IRPS TRIP LOGIC B1 MAIN
- rNIT.- PUSHBUTTON (Dl)
Monitor Bfan1< Descdption-Monitor
- RPS TRIP LOGIC B l MAIN
.INIT - PUSHBVTTON(DI)
Monitor Blank Description-Monitor
'RPS TRIP LOGIC Bl MAN
- tNlT ARM (DI) -Monitor
...... 3-*"
"4 RPS TRlP LOGIC A2 MAN INIT -. ARM (Dl) Monitor RPS TRIP LOGIC A2 MAN INIT - ARM (DI) Monitor
- --5---*****
RPS TRIP LOGIC A2 MAN 00:09:06
- 00
- 09:04 100:09:04 00:09:02 00:09:01 00:09:01 00:09:01
'00:09:01 00:09:01 00:09:00
,QQ:09:00 True False True True False False True Ttue True False True INIT - PUSHBUTTON (DI) -
00:08:59 True
'Monitol' RPS TRIP LOGICAl MAIN F al*se*
11NIT ARMED (DI) - Monitor 00:08:*59
'Blank Description -*Monitor tRPS TRIP LOGIC A 1 lv1AIN INlT ARMED (DI) - Monitor
!Blank Description
- Monitor
- RPs TRIP LOGIC AI MAN INIT - PUSHBUTTON (DI),.
Monitor m
Blank Descdption - Monitor Blank Description - Monitor RFPT C TRIP (DI) -*Monitor Blank Description
- Monitox
,Blank Description - Monitor
- RFPT C TRIP (DI) -. Motlitot Blank Description - Monitor 00:08:58 00:08:58 00:08:58 00:08:58 00:08:55 00:08:54 00:08:53 00:08:53 00:08:53 00:08:53 00:08:51 False True True True False True False False
'ltue True False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes.
Yes
Descdption - Monitor
"' a,_h *** o. *.-.
- J&PJ :MODE!S\\Y,[Tt;kl*
$.lf1JJ1'0)WN*(D!) ::*Mol1itor RPS MODE SWITCH REFUEL (DI) Monitor RPS MODE SWITCH
- REFUEL (DI) Monitor IR:Ps.:Mboriswirci1 100:08:51
- fJO
- (JS';p 0;
'00:08:50 00:08;50
!STARTUP &.HOT STDY (DI).. '00:08:50
'Monitor
"" "'M"
,RPS :tvfODE SWITCH-STAR1'UP & HOT STDY (DI)- 00:08:50 1Monitor fRPS MODE SWITCH - RUN
- (DI)- Monitor
.Blank Description - Monitor
[Blank Description-Monitor tG't:ltbl111p A2.Ql tiili rrowgie t2i.
'Failure ofRPS to SCRAM
{ATWS)
- toggle event 20 IHalfcore ATWS - right side
-
- w **
- Half-core ATWS left side 00:08;50 O*w******* ******
'00:08:49 mH,,v,h,.,,.,. """"
WO;OSAO 00:08:40 00:07:37 00:07:37 Tme True
.False True False True False Ttue 0.0 0.0 0.0 True Yes Yes Yes Yes Yes r
I I
Hope Creek Operations Crew D Date 2/24/16 Scenario - 2RPT from 100 % power
- 1. Time available for Operator response - 50 seconds.
- 2. Time required for Operators to respond to initiating event - 12 seconds
- 3. Action expected to be taken -
- 4. Immediate Operator action from memory - Lock Mode switch in Shutdown per HC.OP-AB-RPV-0003(Q)
- 4. Indications available to Operators to diagnose event.
Overhead annunciators C1D4/D5 - A/B Reactor Recirc A/B trouble Recirc pump drive motor breaker flashing OPEN bezel indications - 10C651C
- 5. Actions taken by Operators.
Operators upon verifying trips of both Rx Recirc pumps with the reactor critical, from memory took their immediate operator actions and LOCKED the Rx mode switch in the shutdown position.
- 6. Procedures used that provided guidance.
HC.OP-AB-RPV-0003(Q)
- 7. Did Operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included.
The plots showing Rx power, A/B Recirc pump speed, Rx pressure, and the RPS mode switch position (Run,Shutdown). Time - 12 seconds NOTE: Crew D was the first to perform the scenario and a TAMS report and Alarm chronolog from the simulator was not captured as they were for the subsequent crews. The transient plots alone clearly document the required time.
HC.OP-AB.RPV-0003(Q) - RECIRCULATION SYSTEM/POWER OSCILLATIONS ABNORMAL. (First three pages only.)
!Mode Switch to Shutdown I 1
I Recirc Pumps Tripped
Hope Creek Operations Crew E, Date 3/8/16 Scenario - Dual recirc pump trip from 100 % power.
- 1. Time available for operator response - 50 seconds.
- 2. Time for operators to respond to initiating event - 11 seconds
- 3. Action expected to be taken -
- 5. Immediate operator action from memory - Lock Mode switch in Shutdown per HC.OP-AB-RPV-0003(Q)
- 4. Indications available to operators to diagnose event.
Overhead annunciators C1D4/D5 - A/B Reactor Recirc A/B trouble Recirc pump drive motor breaker flashing OPEN bezel indications - 10C651C
- 5. Actions taken by operators.
Operators upon verifying trips of both Rx Recirc pumps with the reactor critical, from memory took their immediate operator actions and LOCKED the Rx mode switch in the shutdown position.
- 6. Procedures used that provided guidance.
HC.OP-AB-RPV-0003(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included.
The plots showing Rx power, A/B Recirc pump speed, Rx pressure, and the RPS mode switch position (Run,Shutdown). Time - 11 seconds TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Recirc pump trips - then the RPS Mode switch position change from Run to Shutdown. Time - 11 seconds HC.OP-AB.RPV-0003(Q) - RECIRCULATION SYSTEM/POWER OSCILLATIONS ABNORMAL. (First three pages only.)
Mode Switch to Shutdown Recirc Pumps Tripped
Thundet imulati n Tatn Re rt Hope Creek Chris Kittredge, Wed Mat 0910:28:25 2016
[Description Blank Description - Monitor Blank Description - Monitor
- m********* *** ****c****w***o***-n****,***wv<-...<**->>.;,,mv * ******,
N *-*.
iLV1785/LV1784 ON (DI)
!Monitor
- Lv i *7******s****s*****"IL* *
- v******wl*
..,7 "g
" *4 ON (DI)-
- Monitor Description - Monitor Y*-.Y*<Y>>'-""'""'"*M*h*>*"Y*
o:*O,_,,>>.*,*,-,,,,*********'**'********
lB1a11k: Description - Monitor
- Blatlk. Description-Mmtitor iBlank Descriptimi - Monitor
- Blank Description - Monitor Grew E Dual Recirc Pump Trip Value
- :oo:l9:09 True iOO: 19:08 False Ram.p Valid Yes Yes
........................................... *****='-""'*****h******'*"'-
- mank Description Motritor 100:19:00
- 00
- 19:00
,00:18:59
,00:18:59 False True False
- ¥**1*--*m-********-**-** *2,**<<*...., --.- '.<<' '>'ff >'Y"""'""'
- Blank Description-Monitor
!Blank Descrtption - Monitor iBJank Description-Monitor
!00:18:58
'N*oWoh=#-....,1****<'*7-*>*"*,,,,_...,.-.,. -_,_,-.,*3
'Blank Description # Monitot
- 00:18:58
!BV.oF004 CLOSE-PMP SUCT
,CQNT OUTBDISOLATION
!00:18:57
'VALVE (D I). Monitor
'l-IVF004 CLOSEPMP SUCT
'CONT OUTED--ISOLATION
,VALVE (DI) *- Monitor w
IHV-FOOI CLOSE-PMP SUCT CONT INBDmTSOLATION 00:18:57 VALVE (Dl) - Monitor HV..;FQOl CLOSE-PMP SUCT CONT INBD-ISOLATION
- 00:18:56 VALVE (DI) Monitor Blank Description - Monitor 00:18:55 Yes Yes True False Yes Yes True Fa.lse i
I
- n * ** > ** N
- Blank Desci'iption Monitor
-* -rsiarlk Dect*iptioii. Monftcr--rooiT8:54 *
- Blank Description - Mitot:
00: 1 8:54
- Blank Description -Monitor
'Blank Desotipt}o; Monitor:
fBiailk Description
- Monitor
- Blank Description Monitor
- .**¥**""""" '
'Blank Description
- Monitor iBlcl<.Dsc.fption" Monitor
- Bla11k Descdption
- Monitor
!Blank Description
- Mm1itor
.Blank Description - Monitor
- Bfani(i)escription-Monitor
- EHank Desciiptiail.- Moito*.
c()Q; 18:53 00:18:53
- oo.
- Ts:s2
\\00:18:52 00:18:36
,00:18:36
'00:18:36
- .**....,.-... /.
00:18:36
'00:18:35 00:18:35 00:18:34 True
- .False*-+**..
False True False False True False True False Trae False jBtank Descriptloil
- Mor1itor
)Bianl<. Desc1;iptia.11:Monitor iBiank Description -Monitor (Blank Description - Monitor
- Blank Description - Monitol'
!Blank Description - Mo11itor iBiacl<JS:;crlptin
- Monitor Blanl<. Descdption Monitor Blank Description-Monitm
.Blank Description Monitor
.FIC-R600 tOWER (DI)
!Monitor
!:f'iC-R600 LOWER (l)I) -
00:18:33
'00:18:31 00:18:30 00:18:29 00:18:29 00:18:28 00:18:28 00:1828 Ttue False True True False False Tme Yes
- <*)
Yes Yes Yes Yes Yes Yes Yes
- Monitor
-9-- :niankDesc:dptton:-:;;Monit11t--:00:18:26*--9--;
HV *1753C CLOSE (Dl)
- Mon.itor HV 1753C CLOSE {Dr)
- Monitor
- Blank Descl'iption.. Monitot
- r* ** "W'"
h"'
.HV-l753B CLOSE(DI)-
Monitor
- Blank Description. Monitor
'HV--l753B CLOSE (DI)
Monitor Blank Description - Monitor HV.c1753ACLOSE(DI)
- Monitor
'Blank Descdption - Monitot HV:...t753A CLOSE (DI) -
Monitor Blank Description-Monitor Blank Description - Monitor Blank Description-Monitor
- * *=,_....
Blank DescriptloJi-Monitor
'Blank Descfipti11=Mrtit;r Blank Description - Monitor Blank Description - Monitor 00:18;26 00:18:25 iQO:J8;24
- oo:ls24 00:18:24 00:18:24
.00:18:23
!00:18:22
!00:18:22 00:18:22
¥'"
00:18:21
,oo:18:20 Blank Description-Monitor 00:18:18 Blank Descriptim1: Mr;i*tc; ** *************** '00.:18: 17 Blank Description-Monitor 00:18:17 Blank Descl'iption. - Monitor Blank Description - Monltot Blank Description Monitor Blank Desc:tiption - Monitor Blank Description -*Monitor Blank Description - Monitot Blank Description - Monitor Blank Description., Monitot
]00:18:17
'00:18:17 00:18:12 00:18:12 00:18:11 00:18:11 00:18:10 00:18:10 False False Tnte True False False True False True False True False Tme False False True False True False True Yes Yes
TRIP-EXCITER FIEL OO:lS:I 0
l:BREAKER(DT).-cMomtOI'-----/--
- TRI11-EXCITER FIELD
!BREAKER (Dl)
- Monitor
- Blank Description - Monitor jBS6-5 TRIP (DI) Monitor iBS6-5 TRIP (DI) - Monitor 00
- 18:10
,00:18:09
!oo:l8:69 00:18:09
'Blank Descriptiot1 Monitor 00:18:09
' '""""""O'"""***w"'"""yO""'O"h"M""W"'"'""""""
'" '>'**z*>> * *******""*"******'
Blank Descriptiort - Monitor 00:18:08 iBS2-6 TRIP (Dl) - Monitor iBS2*6 TRIP (DI) Monitor
- {*********w"l'"M""ov*v
"" ***<- --}*-*
lBlank Description
- Monitor jBianlD-esctlption-Monitor Bla11k Description Monitor 00:18:08
,00:18:08
- oo:ts:o8 **
Blank Description Monitor
,00:18:07
.i3Irli<oeclfption MOI1iior
'oo: 1s:o1 ii'D"RBINB-TRIP (DI) - Monitor :oo: 18:0_7.,...
- TURBINE.. RESET (DI)
Monitor Blmik Description - Motritor iBlank Description - Monitor 00:18:07 00:18:07
,00:18:06 iBiank Description-Monitor
'00: 18:06 V
, 0.,WA"Y"0'
--*oo**oo TURBINE TRIP (DI) -Monitor :00:18:06 TURBINE-RESET (DI)..
Monito1' 00:18:06
,QQ:18:06 False True False False True Ttue False False Ttue False False False True True True Biank Description Monitor Blank Descdption - Monitor 00:18:05 False
- -******-*-*************-****-**************'=
Blank Desctiption - Monitor FIC-R600 LOWER (DI}
Monitor
. FIC-R600 LOWER (DI) -
Monitor FICR600 MAN (Dl) -Monitor
-..................,.............. --Q-*-**
FIG-R600 MAN (DI) - Monitor FICR600 LOWER SET POINT (DI) Monitot*
Blarik Description* Monitoi' 100:18:05 True i00:18:03 00:18:01 00:17:59 00:17:59:
False True False True False False Yes Yes Yes Yes Yes Yes Yes
- Yes, Yes Yes Yes Yes Yes Yes Yes Yes Yes I
!I
'Blank Description Monitor
-OO: 17:59 Ttue Yes
-!Bltn11c-Descriptian;;;-M6i1itm*---roo(n:s6----)-
False--,.-
*Yes-}"--
- Blank Description Monitor 00
- 17:56 FTC.*l600 LOWER SET POINT (DI) Monitor
'FTC>R600 LOWER
'(DI) - Monitor 00:17:55 FICR600 LOWER SET POINT OO:l1:54
{D I) - Monitor
'Blank Description - Monitor Blm1k Description -Monitor Blank Description" Monitor Blank Description-Monitoi' 00:17:54 00:17:53
,FICR60G OWER SET POINT iOO:l7:SJ
- (Dl) Momtot
'FiC-R600 LOWER SET POINT..
. 00. 17 52.
(DI).. Monitor
- ""**+********
Blank Description Monitor Blank Description - Monitor Blank Description - Monitor Blank Description Monitor
- FIC-R600 LOWER SET.POINT
-(lJX) *" Monitor
'**h'"** * ' ' '
.FICR600 LOWER SET POINT (DI) Monitor
.FICR600 LOWER SET POINT
.(DI) 2Monitor FICR600 LOWER SET POINT
'(DI)- Mortitor
-Blank DesoriptiOt1 :Monitor
'Blank Description Monitor
,Blank Description-Monitor
'Blank Description - Monitor Blank Description - Monitor Blank Description Monitor Blank Description.- Monitor c
"""'
- wn h
Blank Description - Monitor
'""h
- 00:17:51
- 00
- 17:51
,00:17:51 00:17:50
.00:17:48 00:17:48 00:17:47
- 00:17:47
- 00:17:44 00:17:44
- 00:17:43 00:17:43 00:17:43 00:17:41 00:17:41 00:17:40 Tl*ue T1LlC False
'true False True False True False True False True False True False True False True False True False True Yes Yes Yes Yes Yes i
Blank Description+ Monitor
\\00:17:29
- 'Blank-Desct'itition Monttm*- 00:17:38 ;--
- Blank Description
- Monitor
,00:17:38 iBiarlk Description, Moito
- 'Blank Description - Mo11itor Blank Description
- Monitor Blank Description-Monitol' v _,,
Blank Description Monitot
,Blank DescriptiOri. - M()nitor
,Blank Description M Monitm
!Blank Descdption Monitor m1ank Description Monitor
,Blank Description... Monitor
- Blank Description Monitor
!Blank Description,. Monitor
'Blank Desctiptiot1 - Monitor
- DRIVING IN/DRIVE IN DETECTOR DRIVE (DI)
Monitor DRlVING IN/DRIVE IN DETECTOR DRIVE (DI)
Monitor
- Blank Description.... Monitor
..,..,......... _6*-*
- Blank Description 7* Monitor
,POWER ON/OFF.,.DETECTOR
!DRIVE (DI).,. Monitor
- PO\\VER ON/OFFDETECTOR
- DRIVE (DI) - Monito1' Blank Description.,. Monitor Blank Description.,. Monitor
.H-IRM DETECTOR SELECT (DI).,. Monitor Blank Description-Monitor H-IRM DETECTOR SELECT (DI) - Monitor Blank Descdption - Monitor G-IRM DETECTOR SELECT 00:17:37 00:17:37 00:17:36
- 00
- 17:36
- 00:17:35 00:17:35 00:17:35 i60:17:35..
'oo:i7:34 00:17:34
.00:17;31 00:17:31 00;17:30 00:17:50 00:17:30 00:17:30
- *******ouhHn#H***h=#w>">
00:17:29 00:17:29 00:17:29 00:17:29 00:17:29 00:17:28 00:17:28 00:17:28
, *** N ** **
- False Ttucr**---
: -----"Yes:---- !- ---
True False True True False False True False True False Ti'ue False True False False True True False
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
,. ; t
(DI).. Monitor Blank Description Monitor GlRM DETECiOI SELECT
- cor) Monitor.
13iaiiF.Description Monitor 00:17:28 00:17:28 00:17:28
- F-IRM DETECTOR SELECT 00:17:28 (DI) - Monitol' F-IRM DETECTOR SELECT 00:17:28 (Dl)..,. Monitor
,E>IRM DEiECTOR SELECT 00:17:27 (DI) - Monitor E-IRIVf DETECTOR SELECT 00:17:27 (DI)- Monitot
- D-IRMDE1ECTOR SELECT 00
- 17:27
- (DI) - Monitor D-IRM DETECToR SELECT OO:l?:27 False True False True False True False True
{DT) Monitor C-IRM l)In7Ec;fOR SELECT
,00:17:26 False (DI)- t\\tfonitor.
C-IRM OETECTORSELECT
- 00:17:26 (DI) - Monitor FIC-R6oo :Lcfw£.RsEr PoiNT
.(DI} Monitor
- s-ir{IVirifir'Ec;roR. s£tEcr (Dt) -Monitor
'FIC.R600 LOWER SET POINT
- (Dl)- Monitor B-IRN1 DETECTOR SELECT (DI) Monitor A-IRMDETECTOR SELECT (DI) Monitor A-IRMDETECTOR SELECT (DI) Monitor E3Jank oesrii)iin = rVinitor D-SRM DETECTOR SELECT (DI).. Monitor i3iaiiDes1:ipt1ol1-Monitor FICR600 LOWER SET POINT (DI) - Monitor 00:17:26
'00;17:26 00:17:26 00:17:26 00:17:25 00:17:25 00:17:25 00:17:25 00:17:25 00:17:25 True False False True True False Tme False False True False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
- D-SRM DETECTOR SELECT
- OO:l7:25
.(DI) - Monitor
- p{c:R600 LOWER SET POINT :OO: 17:25 (DI) - Monitor
- C:>SRM DETECTOR SELECT 00:17:25
.(Dl) '" Monitor
.C-SRN1 DETECTOR SELECT
- 00:17:24
'(DI)- Monitor B-SRM DETECTOR SELECT OO: 17:24
.(DI).. Monitot*
tB-SRM DETECTOR SELECT 00:17:24
- (DI) - Monitor 1FIC-R600 LOWER SETPOINT,00:17:24
- em) - Monitor
- ASRMDETBCTOKSBLECT OO
- J7:24 (DI) - Monitor
- A-SRM DETEC;fOR.SELECT oo: 17:23 (DI}- Monitor IRMfi-REriPEN-RECORDER oo:l7:::n SELECT (D1) - Monitor H-RED PEN-RECORDER 00:17:23 SELECT (DI) - Monitor IRMD RED PEN-RECORDER 00:17:22 SELECT (Dl) - Monito1*
TRM D RED PEN-RECORDER 00:17:22 SELECT (Dl) - M011itor IRM G-RED PEN-RECORDER OO: 17:22
- SELECT (Dl) - Monitor IRM G-RED Pri1\\f-RECORDER 00:17:22 SELECT (Dl)-.Mdriitor IRM C-REDPE;N:RECORDER 00:17:22 SELECT (Dl)-.Monitor IRM. c-REm PEN-RECORDER oo: 17:22 SELECT (Dl) - Monitot IRM F-GREEN PEN-RECORDER SELBCT(DI) 00:17:21 Monitor IRM F-GREEN PEN RECORDER SELECT (DI)
Monitor 00:17:21 True Trne False Ttue False True False Fatse True False True False True False True False True False True Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
- JRM l3 GREl:::N PEN RECORDER SELECT (DI) -
.Monitor JRM B GREEN PEN lRECORDER SELECT (DI)
!Monitor liRM E-GREEN PEN 1RECGRDER SELECT (Dl) -
- RECORDER SELECT (Dl) '"
'Monitor Blank Description - Monitor IRMA-GREEN PEN
.RECORDER SELECT (DI) -
Mo11itot Blank Description - Monitor
"('
'IRMA-GREEN PEN-RECORDER SELECT (DI) -
Mo.n.itor Blank Description - Monitor Blank Description-Monitor Blank Description-Monitor Blank Description - Monitor
. Blank 6esc**ipti;;=Mt1iti****
Blank Description - Monitor
- '<* "'""*' **** w *.,=.
Blank Description
- Monitor Blank Description - M011itor Blank Description Monitor Blank Descriptton Monitor Blank Description Monitor Blank Description Monitor FIC*R600 LOWER SET POINT (DI) Monitor Blank Description - Monitor Blartk Description Monitor Blank Description - Monitor Blank Description Monitor
- oo:17:21 00:17:21 00:17:20 00:17:20 00:17:20 00:17:20 00:17:20
,00:17:20 00:17:17 17:17 00:17:16 00:17:16 00:17:16 17:16 00:17:16 00:17:15 100:17:15
- 00
- 17:15 00:17:15 00:17:15 00:17:14 00:17:14 False True False True False False True True False True False True False True False True False Tn1e True True False Tl*ue Yes Yes Yes Yes Yes Yes Yes Yes Yes.
Yes Yes Yes Yes
Blank Description Monitor n*m
- Blank Description Monitor Blank Description Monitor
'Blank Description"' Monitor
'Blank Description - Monitot
,Blank Description Monitor Description - Monitor
- Bl.ank Description - Monitor
- Blank Descdption - Monitor
!Blank Description-Monitor
.Blank Description Monitor iBlnk Desc1*iption - Monitor
- Blank Description.... Monitor
!Blank Description - Monitor
- " """"""""""'""'m""'"'""""'"*.. *
- Blank Description - Monitot iBlank Description - Monitor
- Blnk Des.cription M;nitor lBiank Description" Monitor Blank Description-Monitor
!Blank Description - Monitor Blank Desc.riptio11 - Monitor
- Blank D$cdptfo11 - Monitor *
-* ---.***'"'"/0*-"""'
1Blank Description Monitor
'Blank Desc.ription-Monitor Blank Description-Monitor
- Blank Description Monitor Blank Description**1 Mo11itor Blank Description. "' Monitor Blank Desctiptfon
- Monitor
. Bla11k Description Monitor Blank Desl'iption Monitot Blank Description Monitor Blank Description Monitor Blank Description.. Monitor Blank Description - Monitor 00:17:12 00:17;12 00:17:12 00:17::10
- 00:17:10 00:17:08 00:17:08
- oo:t7:o8 00:17:08
- 00
- 17:06
- 00
- 17:05
- 00
- 1705
- oo:17:04
'00:17:04
- 00:17:04
'00:17:03 00:17:03 00:17:02 2
>00:17:02 00:16:57 00:16:57
- 00:16:57
!00;16:56
.....,.,.. -¥---"'---..........
- 00
- 16:56
- oo
- .16:55
- 00
- 16:55
- 00
- 16:54
- oo:l6:52 00:16:51
- 00
- 16:51 00:16:51
,QQ:l6:50 00:16:50 00:16:50 True False True False T1'ue True False True False True False True False True False True False True Trne
- False, True False Trtte False True False True False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
'Blak Description - Monitot
- Blank Description Monitor
'Blank Descl'iption -Monitor Blank Description * !vlonitor Blank Description - Monitor
[Blank: Descl'iption Monitor
'BlallkDesc1*iption 1\\!Ionitor
'Blailk DescriptLon Monitor
.Blank Description.. Monitor
'Blank Descl'iption Monitor iBlank: Description - Monitor
'Blank Description-Monitor 00;16:49 00:16;49 00:16:49 00;16:49 00:16:49 00:16A8
- 00:16:48 00:16:48 00:16:48 00:16:47 00:16:46 00:16:46
'Blank Des"ii)'il:on-Motiior **** * *** ********* ;'oo:16:46
':BinkDescription Monitor
!ob:l6:45 Blank Description - Monitor
. [00:16:45 Blank Description "' Monitor
- 00:16:45
- -...... w.
Blank Description - Monitor Blar1k DescripticHl - Monitor Blank Description-Monitor Blank Description-Monitor Blank Description-Monitor Blank Description-Monitor
- Blank Description-Monitot
- 00:1645
- 00:16:44 00:16:44 00:16:44
- 00;16
- 44 00:16:43
"<< c" **.,
00:16:43
"'"'"""v......., **
'Blank Description-Monitor
- oo:l6:43 Blank Des6*iption-Monitor
'00: 16:43 Blank Description Monitor 00:16:42 Blank Description-MoJ1itor
,QQ: 1 6:42 Blank Description-Monitor
,00:16:42 RRCS MAN INTITIATI (DI)
'OO: I 6:42 Monitor RRCS MAN INTITIATI (DI)
Monitot' Blank Description. Monitor RRCS MAN INTIT PERM (DI)
Monitor Blank Description Monitor 00:16:42 00:16:42 00:16:41 00:16:41 True False True False Ttue False True False True False True False True False True False True False True False True False True False True False False True True False False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
- ***********Vc** ********
RRCS MAN INTIT PERM (Dl)
-Monitor Blank Description Monitor RRCS MAN LNTITIATI (Dl)
)Monitor 00:16:41 00:16:41
- 00:16:41 lRRCS MAN rN'ffriAT'I (DI) -
OO:IG:4l
!Monitor
'Blank Descdption.. Monitor 00:16:41 00:16:40 Blank Description - Monitor
- RRCS MAN INTlf PERM (DI)
-Monitor OO:l6:40
'RRCS MAN INTIT PERM (DI)
- -Monitor
- -*****'*'"'"""'...-"=-'-c *'w*m*.wh.. ' - 7
'Blank Description - Monitm'
- ,Rrfcs'"MAN rNTrTiA.ri(Di)
!Monitor 00:16:40
'()0:16:40 00:16:40
!Blank Description-Monitor 00: 16:40 tRRCS MAN INTITIATI (Dl)
- M.
'00:16:40
> omtor Blank Descdption - Mcm.itor
- 00:16:40 Blank Description-Mo11itor 00:16:39 RRCS MAN INTIT PERM (DT.)
00:16:39
-Monitor RRCS MAN INTIT PERM (DI)
. Monitot
- '********h***
Blank Description-Monitor Blank Description-Monitor
,v****
- RRCS MANJNTITIAT! (DI)-
Monitor
'RRCS MAN INTITIA TI (DI) -
Monitor Blank Description
- Monitor
,RRCS MAN INTlT PERM (DI)
-Monitor Blank Dscription Monitor RRCS MAN JNTIT PERM (DI)
.. Monitor Blank Description - Monitor
- 00;16
- 39 00:16:39
'00:16:39
{l0:16:39 00:16:39 00:16:39 00:16:39 00:16:38 00:16:38 00:16:38 True..
True False True False True False True False True True False True False True
.False True False False True True False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes c,.............................
Yes
Blank Descdption - Monitor Blank Description-Monitor Blank Description-Monitot
.Blank Description - Monitor
'Blank Description - Moiior
'Blank Description Monitor 1Blartk Description.- Monitor
'RFPT B TRIP RESET (Dl)
'Monitor Blank Description - Monitor
'Blank Description Monitor Blank Description - Mmlitot m'>
- '*'***'>>>>>***><*****************r**v'* "
IRFPT 13 tRIP RESET (DI) -
'Monhor
- ****>** **************************************m****N**V."**"
lBlank Description - Monltor lBlcmk Description -* Monitor
!Bimk Descri})tlon-Monitor Blank Description -Monitor RPS TRIP LOGIC B2 MAN
!NIT PUSHBUTTON (DI)
Monitor
'Blank Description - Monitor
>
- mm M""*>>*Nv*" '"*v>*'-****
'-""" *O***>vv* "'"""""""""""""'""""">"' *****
iRPS TRIP LOG1C 132 MAN INIT-PUSHBUTTON (DI)
- Monitor Blank Description.. Monitor RPS TRIP LOGIC B2 MAN
- Blank Description -.Monitor 00:16:38 00:16:38 00:16:37
- 00:16:37 toa:16:37 00:16:36 00;16:36 00:16:36 00:16:36 00:16:36 00:16:35
- 00:16::35
'00:16:35 00:16:35
- 00:16:35 00:16:34 00:16:34 00:16:34 00:16:34
- 00:16:34 00:16:34 00:16:34 Blan[( Description u Monitot 00: 1 6;33 RPS TRIP LOGIC B I MAIN INIT - PUSHBUtTON (DJ) *
- 00;16:33 Monltot Blank Description-Mon.itor 00:16:33
.RPS TRIP tOGJC B 1 MAIN
!INIT
- PUSHBUTTON (DI)-
00:16:33
'Monitor Blank Descdption *Monitor 00:16:33 True False True False True False True False False True False Tttte True False True False False True True False Ttue True False False True Title False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Blank Description k Mo11itor
$.PS TRIP LOGIC B I MAN
.!NIT AR1vl (DI) Mot1itot Blank Description Monitor Blank Description-Monitor
- o*,-,-*
,Blank Desctlption - M()nitor fR.ps TRIP LOGIC A2 MAN UNIT-* ARM (D I) - Monitor
- Blank Descl'iption Mottitor
.RPS TRIP LOGIC A2 MAN liN IT - ARM (Dl).. Monitor
- RPS TRIP LOGIC A2 MAN
.INIT - PUSHBUTTON (Dl)
- Monitor RPS T:RH> LOGICAl MAIN ilNTf ARMED (DI)
- ! Monitor
!RPS TRIP LOGIC AI MAIN 1INit - ARMED (Dl) - Moi1itor Blank Description - Monitor
,_....*.., **,.****-v-- -.- *
'RPS TRIP LOGIC A 1 MAN
.IN IT PUSHBUTTON (DI) -
'Monitor Blank Desctiption-M.onitor
'Blank Description - Monitor Blank Description-Mm1itor
'Blank Desoriptlon.. Monitor Blank. Description-Monitor Blank Description -Monitor Blank Description - Monitor Blank Descriptio11 - Monitor Blank Description Monitor Blank Description - Monitor Blank Description - MonitOl' Blank Description " Monitor Blank Description - Monitor iBlank Description-Monitor Blank Description-Monitor 00:16:33 True Yes 00:16:33 True 00:16:33 00:16:32 00:16:32 False Yes 00:16:32 False
. 00:16:32 True 00:16:32 true Yes 00:16::31
'true Yes
- 00:16:31 False Yes
.00:16:31 True 00:16:31 False 00:16:30 True Yes 00:16:30 True Yes 00:16:30 False 00:16jO True 00:16:30 False 00:16:30 True 00:16:30 False 00:16:29 True False True 00:16:27 False
- 00:16:27 Tme Yes 00:16:19 False Yes 00:16:18 True Yes 00:16:tS False Yes 00:16:18 Tme
'-M.... :
- on************'"-*'-"**""*"
Blatxk Description - Monitor.
00: 16: 18 False
,Blank Description.. Mo11itor f00:16: 17
- x*
,RFPT B TRIP (DI) - Monitor Blank Description Monitor
,RFPT B TRIP {DI) Monitor 00:16:17 False
- 00:16:17 True
!Blank Description Monitot
- oo: 1 6 : 1 7 True
- Blank Descdption Monitor iBlank Desct*iption - Monitor
'Blank Description - Monitot*
1Blank Description - Monitor
- Blank Description - Monitor lBfank Description - Monitot' jB1ank Description - Monitot IR.fi'f!T*c riiiP (ni) -Monitor IRFPT C TRfP (DI)M;nitr...
fBinkDescription - Monitor
- vv_. *******
Blank Description.. Monitm
- Rg! MOOJ S.WITQH "
StJUTDOWN{DI).. Monito.r
]RPS MODE SWITCH - RUN
- (DI) - Monitol'
ý.ÿ!frg p*nrup ûP:;üO.h
....... t
.. rip
'Toggle event 21 00:1 6:.16 False
'00: 1 6:16
- 00: 16: 1 6
- * ********* ********'*FN**'"**
00: 1 6: 1 6 00:16: 15 00:1 6:1 5 i00;l6:15
]00:16;15
- 00: 16: 1 4 00: 16: 13 00: 1 6:13
.\\Jl)rJ.d;tO
'00:16: 1 0
- 00:1 5:59 True False True False True False Tme False True True False 0.0 0.0 True Yes
18-A ATTACHMENT C LFWH Independent System Validation
Hope Creek Operations Crew A Date 5/12/16 Scenario - Loss of A - Feed water heating - entire string. Reactor Recirc pumps at minimum speed.
- 1. Time allowed for operator response - 6 min and 32 seconds.
- 2. Time for operators to respond to initiating event - 1 min and 44 seconds
- 3. Action expected to be taken -
Immediate operator action from memory - Reduce and Maintain Reactor power to the Pre-Feedwater Heater Trip or Isolation Value.
- 4. Indications available to operators to diagnose event:
Overhead annunciators A7-E2 - Feedwater Heater Trip Extraction steam isolation valves going close, FWH Trip lights lit and FWH reset lights extinguished on 10C650 section A Feedwater temperature lowering, followed by reactor power rising on both APRMs and core thermal power (OD-3).
Main Generator (MWE) rising.
- 5. Actions taken by operators.
Operators verified trips/isolations of Feedwater heaters.
From memory took their immediate operator actions: Reduced and Maintained Reactor Power to the Pre-Feedwater Heater Trip or Isolation Value. With Reactor Recirc pumps at minimum speed, the only means to reduce power is to insert control rods.
- 6. Procedures used that provided guidance.
HC.OP-AB-BOP-0001(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included:
The plots showing Rx power, A/B Feed Line Temperature, APRM A power. And Total Core Flow. Heater switch failure (initiating event) at 00:13:18. Feedwater temperature shows a slow lowering in temperature followed by a slow rise in reactor power. Rod Insertion begins at 00:15:02 and continues for the next several minutes to maintain power.
TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Heater switch failure (initiating event) - at time 00:13:18. Rod insertion Commences - at time 00:15:02, and continues.
HC.OP-AB.BOP-0001(Q) - Feedwater Heating (First three pages only.)
I Feed water temp. 1\\
I Rx oower I Heater 2A Hi lvl
- 13:18 11:33 13:12 I Time allowed 392 sec - 19:50 14:51 19:48
Thunder Sbnulation Ta1n ReJlort Hope ()*eek Kepley, Thu May 12 12:52:13 2016 "A" Shift PRNM. Loss of FWH rn;scriptiou
!R:o¬*siiti3cr : INsERT.
(ni)***********
lMomtor 19:48 Value False True False True Valid Select 384 7 (DI) Monitor Select 3847 (DI)- Monitor
\\JDL,.uvT-
!"--#'(&-$-r--*----
-- -"*i*
%------,------------1
!ROD SELECT-INSERT (DJ)
!Monitor False True Select 38-15
-Monitor False Yes Yes Yes fR.0cisciet 3iTs(I5i)**=-MonTto -i6o: 17:5_8
_____ ;**- *---Trte ----
- ROâ SELECT-INSERT (DI)- loo
- l7:46
- Monttor 1
False
!Ron sliréEcr*:1Ns£R:i (I5I)":**,
. 1
.. 7.:
3 8
...... r. -rne IMonitor
.----w--.----.W'<N*""-=-*-°-+/-
..... o IRodSelect 100:17:33 False iR:otrs;rci-22=4 :;*cni5-=-Mortii;:-- [aa*;T7:*;*i3
__________ r --*-**-*rrt²
--*³*-**********"
jRon**s£113ct-: "iNsERT (Di)( ****l)-0**1*.*6*+, 1*****
lMonitor
.................. _.. µ*-*-.--......
!Rod Select 3&31 (DI) AA Monitor
,ROD SELECT ¶* INSERT (DI)
- Monitor rR.ç-cfSIect22=3i(DI) -1Yiot;itor Yes
{"""-'"'-"-'"'*
!Rod Select 2231 (DI) Monitor Select 2231 (DI} Monitor sELBcr7msEiR:F("I5n**=-- $o %&'-----
. onitor False P-P-
)00:15:.54 CKNOWLED (DI) Monitor 1Xc:KNowr=E:ncn!f=11á-ni!o;:
- !aa:i
- 3::3i l--------;-;-_-_,_.
.. r.RESET -HI LEVEL
!5/TRN A (10) lHTR TRIP-HI LEVEL TRIP IHTR 5/TRN A (LO) 3:28
!HTR TR1PHI LEVEL TRIP
'HTR 4/TRN A (LO)
\\00:13:28
- HTR TRIPBI LEVEL TRIP-
!HTR 3/TRN A (LO)
- HV-1361A CLOSE-FWH#5
- SHELL SIDE-SHELL-MSTRE iSEP A DRN ISLN (DI)
!Monitor True False Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No
.----***---*`**--*********--
r*---------***------* -
c*-------.........
- HV-1360A CLOSE-FWH#5
'SHELL SIDE-SHELL-MSTRE True
- Monitot t'"j*k _,_
...... We "'N--o-ffc""'-** *>----------.
IHVMl362A CLOSEFWH #5
!SHELL SIDESHELLCROSS
!AROUND STM ISLN (Dl) *
!Monitor
!00:13:18
!IS-i CLOSE-FWH# 6 jSHELL SIDE-SHELL-EXTR
- 00:13:18
- Monitor ;
it-r\\Li§'ss*A:--*c1osE:F'wfiTi4"----#,
- SHELL SlDESHELL-EXT
!STM ISLN (Dl) *Monitor
.rv1--3s6A.
.... cios1rsrfvfs£At
- EVAP DRN (DI) - Monitor
-> * 'w * * '>> <-*********,...*----
!HV-l357A CLOSB-FWH#3
!sHELL SlDE-SHELL-BXT I !STM ISLN (DI} Monitor
!Fis:T3(i5A-cLosE"CFwH.iF6 lSHELL SIDESHELL-EX!R lSTM DRN VL VS (DI)
!00:13:18 13:18 True 1
- HV-1361A CLOSE-FWH#5
'SHELL SIDE-SHELL-MSTRE j00:13:18 lSEP A DRN ISLN (D I) lHV-1360A CLOSE-FWH#S tSHELLSIDE-SHELL-MS11<.E t00:13:.18
- =******
- HV-1362A CLOSEFWH #5
!SHELL SIDE-SHELL-CROSS
,00:13:18
- AROUND STM ISLN (DI)
!HV-1358A CLOSEFWH#4
- sHELL STDESHELL-EXT
!00;.13:18
- STM ISLN (DI)
- Lvi356A: ci.Osii's1isEAL !"o:1;:1#-
\\HV1351A CLOSE-FWH #3 rsHELL SIDE-SHELL-EXT
'STM ISLN (Dl)
- Toggle event 2
,"Rdsiect-3039 (DI)- Monitor ou h ******
- oo:13:18 Rod Select 30-39 (DI)- Monitor )00:11 :46 1
Yes No
PSEG Internal Use Only Effective Date ___ 6_M_a_.y"--2_0_15 __ _
CATEGORY II l
FEEDWATER HEATING ALARMS
- 56i.1W¥tlii11f1EAT!JrJBliS; FEEDWATER HEATER PNL 1AIB/G C102 CROSSFLOW ALARM/TRBL INDICATIONS iiWW<ilftt.FixdwØ1,fMi\\!&HÚ.Ü1r
- Rlslng:Mairlf*otatq:.w:.
P.eW@.: D!"#$r H:t%aYE:4.:fglf? @A OQ.&'(.
'.:C *'**,. -;-<s,.,,.-. -
.-c---, o_:_,, _--m_:;_-,-,;*,c. :r <,
TERMINATED Date/Time:*-----
Hope Creek Page 1 of 20 ArS:*M*
A7*F2 B3*F2
. Rev. 18
PSEG Internal Use Only RETAINMSNT OVERRIDE CONDITION I.
Reactor power is >70% RTPAND>0.04 Increase in FLFWTR (CRIO$
II.
00*3) dua to a Loss of FeMwater Heating from a feedwaler heater trip that has OC6t,Jrred, *
[CD*979BJ Pate/Time:
Reactor power Is >70% RTPAND>0.02!ncrease*in FLFWTR(CRIDS Ob*J due to a Lm1s of Feedwatet Heatin from a feedwater heatertrlp thatMs occurred. "'*
[C0"979SJ Date/Time:
H C.OP
.. AB.BQP
.. QOO 1 (Q)
FEEOWATER HEATING ACTION I.A Within 5 tnlnutas, R!EOUCE Reactor PoWer 20%
ll.A.
BELOW the Pre-Feedwater Heater Trio Value.
Within 5 minutes, REDUCE R13actor PoWwS%
.BElLOW. the Pte*Feedwater Heater Trlp Value.
0;04 ln FLFWif{ (CRibS Otl3) Js Indication of a20"!= reductionln !=iiledwater T$mperature due to a feedwater heater trip. This e'Y!SIIW:ation should he made by.compErlng the current steadystate. FLFWTR to thf:l pre-trtp value,.
The resultant change in FLFWTR is independent ofreactor power or initial FWH configur$11on. IF >,l:WF reduction In Feedwater temperature due to a feedwater heater trip Is noted, the R.etarnment Override a.otlons Sh6uld be taken.
'<! 0.02 in FLFWTR (GRIDS QD-3) is indication of a >1 Cl"F reduction In PMdiNatr Temperature due to a reedwater heater trip, Thia evaluation shduld be made by comparing the currentsteady,state FLFWIR to ths pre-trip value, The resultant Ghange rn FLFWTR Is independent of reactor powe:r or lrHilar FWH configuration.. LE>109F reduction in Feedwater nmperature due to a feedwater hi:latertrlp Is noted, fhe Retail"lment Override action<> should be taken, ForSub$equMt FWHTR trip$, 1E subsequent.a¢tlon steps from the ABarE! tken for the lnitl.al FWHTR trip., and the plant has stabilize¢, the new Initial FLFWTRvaJue.shquld be vsed. lF a $econdFWHiR trrp: oc.curs beforeth.e plant Is stabilized from the first FWHTR ttfp, the lniUal PLFWTRValue should be used.
AtiDiifONALINFORMATION:
VALVE.
AF'-LV1532A(B,C)
ACl*HV*1633A(B,C)
AD*HV,.1620A(B,C)
AF-LV-152M(B,C)
.AF*LV*1356A(B,C)
AF*HV-1 351A(B1C)
AFHV*t388A(B,Q).
AF*LV-t514A(8,C)
AF*HV*1358A(B,Cj AF-HV*1377A{B,CJ AF*LV*1506A(B,:C)
AF*LV-1363A(B',C}
AF*LV*13&<iA(B,G}
AF*HV-1362A(B,C)
AF-HV-1<3$7A(B,C)
AF-XV1369A(B,C)
AF*fW*136i5A(B,C)
AF;HVi'366A(B,C)
AF*HV1.361A(B,d)
AF-HV-1$59A(B,C)
AF* LV*1505A(8,C)
AP., LVisl3A(B,C)
AF* LV-:15Z1A(B,Q)
AF* LVA531A(B,C)
AF'- LV"1451A(B,C)
AHV1753A(S,C)
At=*HV,1768A(B,C)
AE*HV1<744A(B,G)
AD*HVi600A(B,C)
AD-HV"HH3A(S,C)
AD*HV*l 7 4SA(8,G)
AD-HV-1625' Hope Creek OESCRIPTION FDW HTR 3 DRN VALVE HTRS 1&2 DRN OLR INLET HTRS *1 &2 DRN CLR OUTLET FDW HTR 4 DRN VALVE FWH # 3 SHELL,. SIDE. SSE: tlRAIN PWH#3 SHELL SIDE E:XTR STM!SLN FWH# 3 SHf.;U, SIDE EXTR LINE ORAIN FDW HIR5DRNVALVS FWH # 4 SHEkLSIDE E:XTRSTM ISLN FWH # 4 SHELL SIDE EXTR LINE DRAIN FDW HTR 6 DRN VALV MSIRE SEP 8 ORN LINE MSTRE St:P A bRN LINE FWH # 5 SHELL SIDE CROSS ARdtJND STM iSLN FWH # 5 SHELL SIDE XARND SIM LJNE DRAIN HTR 6 BLEEDER TRfPVALVE flWH#$SHELLS!OE EXTRSTM ISLN FWH # 6' SHE:LL SIDE EXTR STM DRN VLV FWH # 6 SHELL SIDE EXTR STM DRNVLV FWH # 6 SHELL SIDE EXTR LINE DRAIN fDW HTR e DUMP VALVE FDW HTR 5 DUMP VALVE FDW HTR 4 DUMP VALVE FDWHTR 3 DUMP VALVE FDW HTR2 DUMP VALVE HTRSOUTLET HTR6INLET HTR l;l OUTLEiT BYPASS HTRs 3 & 4 & 5 OUTLET HTRS3&4 &51NLET HTRS 3.& 4 & 5 OUTLET SYP HTRS 1&2 DRN CLR. BYPASS Page 2 of 20 CRIDS Page 27, 02854(5,6)
Page 27, 02842(3,4)
Page.27, D2830(1,2')
Page 27 D21lt8(19,20)
Page 36, D2i'79(80,81)
Page36; D27B2(B3,84}
Page 28, 02815(6,.7)
Page 21, 02627(8,9)
Page 2.7, D2839(4D.41/
Pagl!l 2.7,. 02851(2,3)
Page 25, 02757(819)
Page.28 Page28 f:lage 28, A3112( 3;4)
Pall:ec 21 Page 27 Page 27, A2916(7,B)
Page 25 Rev. 18
PSEG Internal Usa Only Dateffime:
AUTOMATIC ACTIONS IF THEN Hi-Hi level in #1 (29") or #2 (25';)
L V1532A(B,G) CLOSES FWHTR after a 1 0 second time delay li HV1633A(B,C) CLOSES
- HV--1620A(B,C) CLOSES Hi-Hi level (29") in #3 FWHTR
- LV-1523A(B,C) CLOSES
- LV-.1356A(B,C) CLOSES
'i HV-1357A(B,C) CLOSES
- HV1388A(B,C) OPENS Hl-HIIevel {29") ln #4 FWHTR L V1514A(B,C) CLOSES
- HV-1358A(B,C) CLOSES
- HV-1377A(B,C) OPENS HiHi level (29") in #5 FWHTR
- L V1506A(B,G) CLOSES L V:-1363A(B1C) CLOSES
- LV-1364A(s,C) CLOSES
., HV-1362A(B,C) CLOSES
- HV1387A(B,C) OPENS Hi-Hi level (29") in #6 FWHTR
- XV-1369A(B,C) CLOSES
- HV-1365A(B,C} CLOSES
- HV1366A(B,C} OPENS
- HV1367A(B,C) OPENS
- HV-1359A(B) OPENS FWHTR #6A(B or C) HI level of 22.5"
.. LV-150'5A(B or C) OPENS FWHTR #5A(B or C} HI level of 27.5"
- LV1513A(B or C) OPENS FWHTR #4A(B or C) HI level of 28.5"
- LV-1521A(B or C) OPENS FWHTR #3A(B or C) HI level of 25"
- LV-1531A(B or C) OPENS FWHTR #2A(B or C) HI level of 21"
- LV-1451A(B or C) OPENS Hope Creek Page3 of20 Rev.18 i
I l
Hope Creek Operations Crew B Date 4/29/16 Scenario - Loss of A - Feed water heating - entire string. Reactor Recirc pumps at minimum speed.
- 1. Time allowed for operator response - 6 min and 32 seconds.
- 2. Time for operators to respond to initiating event - 2 min and 54 seconds
- 3. Action expected to be taken -
Immediate operator action from memory - Reduce and Maintain Reactor power to the Pre-Feedwater Heater Trip or Isolation Value.
- 4. Indications available to operators to diagnose event:
Overhead annunciators A7-E2 - Feedwater Heater Trip Extraction steam isolation valves going close, FWH Trip lights lit and FWH reset lights extinguished on 10C650 section A Feedwater temperature lowering, followed by reactor power rising on both APRMs and core thermal power.
Main Generator (MWE) rising.
- 5. Actions taken by operators.
Operators verified trips/isolations of Feedwater heaters.
From memory took their immediate operator actions: Reduced and Maintained Reactor Power to the Pre-Feedwater Heater Trip or Isolation Value. With Reactor Recirc pumps at minimum speed, the only means to reduce power is to insert control rods.
- 6. Procedures used that provided guidance.
HC.OP-AB-BOP-0001(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included:
The plots showing Rx power, A/B Feed Line Temperature, APRM A power. And Total Core Flow. Heater switch failure (initiating event) at 00:10:22. Feedwater temperature shows a slow lowering in temperature followed by a slow rise in reactor power. Rod Insertion begins at 00:13:16 and continues for the next 5 minutes to maintain power.
TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Heater switch failure (initiating event) - at time 00:10:22. Rod insertion Commences - at time 00:13:16, and continues.
HC.OP-AB.BOP-0001(Q) - Feedwater Heating (First three pages only.)
I Feed water temp.
I Rx oower 1/
I First Rod inserted-13:16 Time allowed 392 sec - 16:54
Thunsler Shuu\\at\\gn Tam Report Hope Creek Chris Kittredge, Fri Apr291504=32 2016 "B" Shift PRNM - Loss ofFWli
- ** **',. *'*'*'-****"=*******',__...... ".Y'*******"--#"'*'"""""""'W"
!Description jfiV-1753A CLOSE (DI)
!Monitor
!I-N-l753A CLOSE (Dl)
!Monitor
!R.0ciseieci***i4=39.. (Di)***=**Monit0;:****
IR.od.seieüti4=3'9(DJ.)- Monitor tRoo sl3L:E:cf=-iNsE:ii:r..
(I5'i)*=*******
!Monitor
!ROD SELECT-INSERT (DI)
!Monitor Ramp Yes Yes Yes Yes Yes Yes
'""""""""""""""'"""'"'"""""""'"".........................,--******--- i
!Rod Select 22k15 (DI)-
18:17 frioøfselect 22-15 (DI) - Monitor !oo:18:17 (DI)-
'00:17:29
!RODSELECT :*iNSERT (DI) -
T !oo:J7:20
.Monitor iRodSeiect 38-47 (DI) - Monitor 16:48
!Rod Select 38-47 (DI) Monitor !00:16:48
!'R{5ns£L.:Ecr:*tNsfiiff(nrYL-** io*o*-*1-5.:*9....
'M
..J omtor
- Rod Select 38-15 (DI)- Monitor rRod Select 3 8-15 (DI) - Monitor
"' Ü
!ROD SELECT-INSERT (DI)
,Monitor
!iionsiii1Scr; ú*il\\is.£R1û*cni) -
lMo11itot
`
iRod Select 22-47 (DI) - Mohitor i00:14:54 Yes Yes Yes Yes Yes Yes Yes Yes Yes True Yes
jRorisl3I:nci INSERT (Dr}
,Monitor
. [""'"':--..*-!*-"-***...
Select38#Jl (DI) -Monitor 100:14:34 Select 38-31 (DI) Monitor jQo:i4:34 IRO÷ SELECT-INSERf(DI) - ;:-14:27
\\Momtot t
IR.oD.sEilic>{ i:Ns£Ri (ni) =
!Monitor
[Rodsirect22-3l (Dt)- Monitor
- r**.. *:**.. *.:.. ** *#.........
[Rod Select 22-31 (l)I)- Monitor t00:14:l3 True False True jROD
" INSERT (DI)
!Monitor 14:03
[RMOD,SELECT-INSERT (DI) - loo:l3:57 J.
. om tor
- Rod SelectJ0-23 (DI) Monitor !00:13:50
'Rod Select 30-23 WN
- "-'"'""""' ******* * * *** * "***'-***'******>>*{'"""********
'ROD SELECT-INSERT (DI)
- 1Monitor lRod 30-39 (DI)- Monitor iA.c:K'i,fow113i5(rii): Motito:
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
..............-*x---Ø*---.........
- ACKNOWLED tDI) Monitor h:-iii{i.RrJ?fiTLEVEL.TRIP 1HTK2/'tRN A(LO)
,OO:J0:27 True No
Ú.*,,,,,,,,,,,,,,,,,,,,,,,o,,,, ''''''''''"'""'""Y*"<-,YO****'*<->>.*....-"'"wxy*-=-,...-,z{*"""-M*Yz*l'-zzAAV l}<*~¥oo*-*M-*-** ****O***VVO-**--?-.-.... -
- HTR TRIP HI LEVEL TRIP
- HTR 1/TRN A (LO)
OO:l0:27 1HTR TRIP.;Hl LEVEL TRIP.,
- HTR 6-.TRN A (LO)
HTR TRIP,.HI LEVEL TRIP HTR 5/TRN A (LO)
- 00:10:27
- 00
- 10:27 No
'1-ITR TRIP-HI LEVEL TRIP
- HTR 4!TRN A (LO) 00
- 10:27 No TRIP-.Hl LEVEL tRIP-
'00:10:27
""'--._.- !-"------_,.,*#-$__,...-._ ------"""'"- __,_,Ñ.....,.,.,..,........
1 No
iHTR 3/TRN A (LO)
:HV!l361ACLOSE"FWH#S--#----
iSHELL SIDESHELLMSTRE
- OO: !0:22
!Monitor HVl360A CLOSEFWH #5 1SHELL SIDESHELL-MSTRE lSEP B DRN ISLN (Dl)....
lMon1tor 00:10:22 HV-l362A CLOSE-FWH #5 SH.ELL. SIDESHELL-CROSS AROUND STM ISLN (DI) -
.. OO: l0:22
'Monitor lHS:l365ACiOSE-FWH# 6
- sfiELL SIDE-SHELL-EXTR 100:10:22
- STM DRN VLVS (DI) - Monitor 1 llV-1358A CLOSE-FWH #4
!SHELL SIDE-SHELL-EXT
- 00
- 10:22
'STM ISLN (Dl) - Monitor LV-1356A CLOSE STMSEAL OO:l0:22 EV AP DRN (DI) - Monitor HVl357A CLOSE-FWH#3 SHELL SIDE-SHELL-EXT 00:10:22 STM ISLN (DT) Monitor il-IS-1365A CLOSE-FWH# 6 SHELL SIDE-SHELL-EXTR 00:10:22
,STM DRN VLVS (DI) lHV-1361A CLOSE-FWH #5
- SHELL SIDE-SHELL-MSTRE
'00:10:22
- SEP A DRN ISLN (DI) iHV:l3.60A CLOSE-FWH#s iSHELL SIDE-SHELL-MSTRE 00:10:22 SEP B DRN ISLN (Dl) 1HV-1362A CLOSE-FWH#5 SHELL SIDESHELL-CROSS 00:10:22 AROUND STM ISLN (DI)
HV-1358A CLOSE-FWH #4
- sHELL SIDB-SHELLEXT
'STM ISLN (DI) 00:10:22 LV-1356A CLOSE STM SEAL OO*.l0*.22 EV AP DRN (DI)
Yes Yes Yes Yes l
No 1
No No 1
No
iJ;IV-l357A CLOSE-FWH#3
_ ;SHELL SIDE-SHELL-EXT------ ;00;1 0;22 ----É-
isTM ISLN (Dl) if-ggievent 2
- j.\\f)i{MFgain (Range
- 0.800
[1,500) 00:10:22
- 00;08:39 iA_p_RóTEgain (Range: 0.800 Ç-
i00:08:34 h.500)
APRM D gain (Range:
a.SOO)
!00:08:30
.A.PRM c gin (Range: o.soo -
-oo:os :23
- 1.500)
- 1\\riiMB--gaft--(Rang o:sOO :
oo:os: 19 i 1.500) iA:J?R.iViA.iail(Range: o.soo 4
!1.500)
Ttue 1.157000 1.038000 1.127000 1.045000 No
Hope Creek Operations Crew C Date 4/19/16 Scenario - Loss of A - Feed water heating - entire string. Reactor Recirc pumps at minimum speed.
- 1. Time allowed for operator response - 6 min and 32 seconds.
- 2. Time for operators to respond to initiating event - 5 min and 4 seconds
- 3. Action expected to be taken -
Immediate operator action from memory - Reduce and Maintain Reactor power to the Pre-Feedwater Heater Trip or Isolation Value.
- 4. Indications available to operators to diagnose event:
Overhead annunciators A7-E2 - Feedwater Heater Trip Extraction steam isolation valves going close, FWH Trip lights lit and FWH reset lights extinguished on 10C650 section A Feedwater temperature lowering, followed by reactor power rising on both APRMs and core thermal power.
Main Generator (MWE) rising.
- 5. Actions taken by operators.
Operators verified trips/isolations of Feedwater heaters.
From memory took their immediate operator actions: Reduced and Maintained Reactor Power to the Pre-Feedwater Heater Trip or Isolation Value. With Reactor Recirc pumps at minimum speed, the only means to reduce power is to insert control rods.
- 6. Procedures used that provided guidance.
HC.OP-AB-BOP-0001(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included:
The plots showing Rx power, A/B Feed Line Temperature, APRM A power. And Total Core Flow. Heater switch failure (initiating event) at 00:49:42. Feedwater temperature shows a slow lowering in temperature followed by a slow rise in reactor power. Rod Insertion begins at 00:54:46 and continues for the next several minutes to maintain power.
TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Heater switch failure (initiating event) - at time 00:49:42. Rod insertion Commences - at time 00:54:46, and continues.
HC.OP-AB.BOP-0001(Q) - Feedwater Heating (First three pages only.)
I Feed water temp. 1,\\i I Rx oower 1/
49,30 51:09 52:48
$5 I First Rod inserted
- 54:46 I Time allowed 392 sec - 56:14 54:Z7 56:06 57:45 DataChart -Training Load:1962
- C Shift: Loss of FWH data ID 1
Name NMAPMFX(l) c91al709 fwtina ription APRM CH.A PWR Total Core Flow Feed Line A Inlet Tem...
Feed Line B InletTem...
Value Units PCT MLB/
degF degF 500 450 400.
350 300
- 250 200 Data Chart Min Max 5.5 65 0
5e+004 0
500 0
500
Tlnuder Simulation Tam Report Hon Creek Chris Kitt;edge, Tue Aur 19 15:16:32 2016 PRNM Shift C Loss of FWH jnescripti{)n jJTime HTRTRIPHI LEVEL TRIP-HTR (ol:02:49 2/TRN A (DI) - Monitor HTR TRIP-HI LEVEL TRfP.. HTR 01;02:49 2/TRN A (DI),. Monitor CHANNEL B APRM MONITOR lo1:02:17
-. F (Dl) - Mot1itor ROD SELECT INSERT (DT)- lol:oo:ss Monitor RO SELECT INSERT (DI) - lo I :00:46 Monitor
!Rod Select 46-23 (DI) -Monitor. )jo I :00:41 IJZod Select 46-23 (DT)_ Monior [Jol:00:40 101:00:04 ROD SELECT-INSERT (DI) -
Monitor ROD SELECT E-INSERT (DI) D Monitol' IRod Select 14-39 (Dl)- Monitor
]Rod Select 14-39{DI) - Monitor ROD SELECT-INSERT (DI)-
Monitor ROD SELECT.. INSERT (DI) C Monito.r Rod Select 22-15 (DI) B Monitot IIRod Select 22-15 (DI) - Monitor IROD SELECT-INSERT(DI) F*
Monitor ROD SELECT-INSERT (DI)-
Monitor Rod Select 38Y47 (DI) Monitor Rod Select38-47 (D[)- Monitor ROD SELECT-INSERt (DI) ""
Monitor loo:S9:54
[joo:59:46 lloo:s9:45 00:59:28 00:59:19 00:59:16 00:59:15 00:58:51 00:58:42 00:58:38 100:58:38 loo:s8:30 II Value fl False I
True II True Jl False II True II False II True I
False I
True II False II True I
False r
True I
False I
True False True I
False I
True II False It II Ramp II II" II I I I[
II I I II II II II II II I I
I I
I II II 11 II [
I II I II II II
' I I II II II II fi.le:I!/C:/Users/pseg/Desktop/PRNM%20Data/Crew%20C%20Loss%20ot"%20FWH.html Page 1 of 5 Valid I Yes J Yes I Yes I Yes J Yes I Yes I
Yes I
Yes I Yes I Yes I
Yes Yes Yes Yes J
Yes I
Yes I Yes I Yes Yes Yes 6/7/2016 i
+
Page 2 of5 I?==x=; =LE =C=I='
- =IN=S='E =.R =T=( =D=l) =
- 0=0=:5_8: =2=1 =*** *=* =lli"'==T=l'l=Ie =w jj Yes I
[Rod Select 38-15 (Dl) - Monitor loo:58:20 False t::=-=]1 Yes R=oc""""
I s=, e=l e=ct=3=8=l=S=( D:::;:.,
I+/-::
_) -=Jv=l=on =
..it=o.r=
.*==li:::=
o =o
- =58 =
- =18== i====T=tu=e= I II Yes... I
[R=od =S=e=le =ct =3=8*=3 =1 ("=D"""I) =* "'=M=.o=m='to=rJ2a=0=:5=5:=46=* = P::[ =F=al=s e=*..
L Yes I
1J=e:(R=od=S=e=le=ct=3 =8*=3lJD=* **** *1=)=-1v=f=.on=it=or=::;!IW=a=:5=5:=45 =.
- =o::::!:)tt:;
l==Tr=:u.e=* *==:!r l!
Yes l
- ROD SELECT -INSERT (DI) -.I II If I
IP:,M=o=n=ito=t======== *:=00=:5= 5 =:3 =5===l zalse Yes.
ROD SELECT -INSERT (DI)- Joo_:55:28
.. )j Ttue II Yes I
Monitor IF======================
Rod Select 22.. Jl (DI)- Monitor j00:55::22 I[
Fals I
l Yes
]
olect 22-31 (DT)- Mon\\tor ?=loo=:5=5=:2=1==:=:jl:l==Tr=u=e=-* =**
- =j **- = = = =::jl==Y= e=s=l
=* S=E=L=E=C=T = =IN =S=E=R=T=(D =I=) _
m::::;10=0 =:5 =5:=14_ =* ='
False I
y es I
,,...
- omtor
{l}t~;LECT
-@ INSERT (DI) - joo:SS :o7 II True r I
Yes I Rod Select 3023 (DI) - Monitor ]00:55:05 II False II rc Yes I
Rod Select 30,23 (DI) - Monitor too
=
- s
=
s
=
- 0
4===111
=
r
=* n
=
te="]i-=1=====liJ===Ye=s=
- ROt: SELECT INSERT (DI)
? joo:s4:53 '"']
False II II Yes ll.v-30-
=
- 5
=
4
=
=
=
=
L
=
=
=
=
=
=
=::j ll II :: j
?=R
od = S=e=le=c t
3 =0-=39"""('==D"""
I) =- =M=on =it=or =* =jlf=:oo=
- 5=4 =:3=8==liI=
T
rt=Je =* =9[
-A"... :=JI Yes I
KNOWJwEP (DI)
- Monitor
!00:50:08 II False II Jl Yes ACKNOWLED (DI) ** Monitor I00:?0:08 1,
True 1, PQR YY:s' l 100:49:42 True f1le:///G:/Users/pseg/Desktop/PRNM%20Data/Crew%20C%20Loss%20o£U/o20FWH.httnl 6/7/2016
PageJ of5 HV-1361A CLOSE-1'WH #5 LJLJLJl_Oj SHELL SIDE-SHELL-MSTRE SEP A DRN ISLN (Dl)"' Monitor HVB60ACLOSE-FWH #5
[LCJ SHE.* LL SIDE.-SHELL*
MSTRE 00:49:42 Tru*
- );:::;
Monitor 00:49:42 True Yes HS-1365ACLOSE.-FWH#6 8..
8 SHELL SIDESHELL-EXTR 00:49:42 Ttue Yes STM DRN VL VS (DI) < Monitor HV-1358ACLOSE.-FWH#4 E
8 SHELL SlDE-SHELLEXT StM 00:49:42 True Yes I SLN (DI) ** Monitor L v
> 1356A CLOSE STM SEAL l II l\\
11 I
EVAPDRN (DI Monitor
,00:49:42.
Ttue Yes
.dcb
.1a ni:;:ti`_
.^3STM 100:49:4.2 r-M.e
. ?
]
Y. es ISLN (Dl) Momtor eL__jf HS-l365ACLOSE-FWH#6 EJDCLN S
HELL SIDE-SH ELL-EXTR 00:49:42 1
HV-l36lACLOSE-FWH#5 EJDCJ8 S.
. HELL SI
- D E-SHELL
-MSTRE 00:49:42 l
No.
rq:rsituvw;x?syRE 100:49:42 I[=]CJ8 HV-1362ACLOSE-FWH#5 EJ c
. [_K8 SHELL SID 13SHELL-CROSS 00:49:42
. 1 No AROUND STM ISLN (DI)
- z{ilfl)}:~?it:4srM EJCCJ8 iCfESTMSEAL 100,49:42 op 1 [C II No I jklc{mnoiopqiristuSTM 00:49:42 r--;111
.. r:r..
rn ghL__ji Lo.o. II Yes I
ll=T=ogg""'le=e=v=er=1t=2=*=========P=;;;t;::::=====91 True IJ IL-*Yes I
APRM F gain (Range: 0.800-II 11 Jl I
LsOo)
- ---L..-___...__L_iso_ooo-----'-*-.... ---
No f1Ie:///C:;Users/pseg/Desktop/PRNM%20Data/Crew%20C%20Loss%20of0/o20FWH.html 6/7/2016
APRM E gain (Range: 0.800
1500)
APR1v1 D gain (Range: 0.800 -
1.500)
APRM C gah1 (Range: 0.800-1.509)
APRM F gain (Range: 0.800-l.5QO)
APRM E gain (Range: 0.800 -
1.500)
APRM D gain (Range: 0.800-1.500)
APRlv{ C gain (Range: 0.800-1.500)
AP.R.MB gain (Range: 0.800 8 1.500)
APRM A gain (Range: 0.800 -
1.500)
APRMF gain (Range: 0.800..
1.500) 00:44:50 00:44:46 00:44:42 00:44:21 00:44:16 00:44:12 00:44:08 00:44:05 II i1VV.""t.57
[oo:43:3o APRM E gain (Range: 0.800 7 loo:43:25 1.500)
APR D gairl-(Rangœ; o:soO ; -- ;43,-19 mn c gain (Range: 0.800- 100,43,15 1,.;00)
APRM B gain (Range: 0.800 -
1.500}
APRM A gain (Range: 0.800 "*
1.500)
'f ACS clg valvel BE 126, to redrc MIG set.B (Q-100%)
T ACS clg valve, AE--I 26, to recirc M/G set A (0-100%)
ACKNLDGE SECT (Dl) *9 Monitor ACK1\\""LDGE SECT (Dl) -
Monitor
!ACKNOWLED (DT) - Monitor JACKNOWLED (Dl) - Monitot*
ACKNLDOE SECT (DI) -
Monito1' loo:43:o7 loo:42:ss loo:42:to 00:42:06 00:41:13 Joo:41:12 lloo:4I :09 Jloo:4l:09
!oo:41:o4
[00:41:04
[ 1,04000 II II I
1.141000 II II 1.052000 I
T.
I 1.038000 I II I
I 1.134000 1.045000 I I
uuu I I
I 1.059000 II II II 1.136000 II II II 1.031000 I l
I
[
ll 1.127000 II 1.038000 II II II 1.144000 II II II 1.052000 II II II 0.150000 I I
0.150000 I II True II I
II False I
II II True II II II False II II 11 True II II t1le:///C:/Users/pseg/Desktop/PRNM%20Data/Crow%20C%20Loss%20of%20FWH.htmi Page4of5 No l No I No I No No No No No No I No I
No I
- -N\\........... ]
No I No I No I No*
No Yes Yes Yes I
Yes I
Yes I Yes I
6/7/2016
ACIZNtDGE SECT (.Dl) -
Monitor ACKNLDGE SECT (DI) 6 Monitor ACKNLDGE SECT (DI) -
Monitor JBlank Descdption 5 Monitot*
!Blank Desctiption 4 Monitor ACKNOWLED (DT) Monitor ACKNOWLED (Dl) Monitor JBlank Description - Monitor
!Blank Description - Monitor JPOS A (DI}- Monitor jPOS A (DI) 3 Monitor Blank
Description:
- Monitor Blank Description Monitor Recirc system B inadvertent xunback Recirc system A inadvertent full run back jToggle even.t 1 I
00:41:01 I
00:41:01 I
- IID0:40:55 II lloo:4o:s5 II Joo:40:54 Jl (oo:4o:s4 II 1Joo:40:51 I[
1Joo:40:51 II 1[00:40:48 II IJ.oo:40:47 II joo:4Q:46 11 00:40:45 I
00:40:21 I 00:40:21 I
1 oo:4o:21 I
II I
False II I
True II II False I
I True I
=:J!
False II True J
I False JL.
Jl True II II False II II True II II False I
True I
0.0 I 0.0 II II True I
I file:///C:/Users/pseg/Desktop/PRNM%20Data/Cre\\v%20C%20Loss%20ofU/o20FWH.html Page 5 of5 Yes Yes I Yes I
Yes I Yes Yes :=]
Yes I
Yes I
Yes I
Yes I
Yes res Yes Yes I Yes I
6/7/2016
Hope Creek Operations Crew D Date 5/3/16 Scenario - Loss of A - Feed water heating - entire string, Reactor Recirc pumps at minimum speed.
- 1. Time allowed for operator response - 6 minutes and 32 seconds.
- 2. Time for operators to respond to initiating event - 2 minutes and 23 seconds
- 3. Action expected to be taken -
Immediate operator action from memory - Reduce and Maintain Reactor power to the Pre-Feedwater Heater Trip or Isolation Value.
- 4. Indications available to operators to diagnose event:
Overhead annunciators A7-E2 - Feedwater Heater Trip Extraction steam isolation valves going close, FWH Trip lights lit and FWH reset lights extinguished on 10C650 section A Feedwater temperature lowering, followed by reactor power rising on both APRMs and core thermal power.
Main Generator (MWE) rising.
- 5. Actions taken by operators.
Operators verified trips/isolations of Feedwater heaters.
From memory took their immediate operator actions: Reduced and Maintained Reactor Power to the Pre-Feedwater Heater Trip or Isolation Value. With Reactor Recirc pumps at minimum speed, the only means to reduce power is to insert control rods.
- 6. Procedures used that provided guidance.
HC.OP-AB-BOP-0001(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included:
The plots showing Rx power, A/B Feed Line Temperature, APRM A power. And Total Core Flow. Heater switch failure (initiating event) at 00:11:34. Feedwater temperature shows a slow lowering in temperature followed by a slow rise in reactor power. Rod Insertion begins at 00:13:57 and continues for the next several minutes to maintain power.
TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Heater switch failure (initiating event) - at time 00:11:34 Rod insertion Commences - at time 00:13:57, and continues.
HC.OP-AB.BOP-0001(Q) - Feedwater Heating (First three pages only.)
I Time allowed 392 sec - 18:06 I
\\
Thunder Sb11 ulation Tam Renort HoveCrpek Chris Kitt:rüdge, Tue 'May 03 lO:ll:58 2016 D Shift Loss of FWH IDNscription jiThne I
Value I
Ramp.
Ia SELECT. INSERT (Dl) - !oo:18!45 I tor ROD SELECT - INSERT (DT)-
00:18:35 True Rod Select 14-23 (D!)- Monitor jOO:l8:32 II False I
JRod Select *1423 (DI) -.Monitor jJoo:18:31 II Ttue II ROD SELECT - INSERT (DI),., ioo:r8::22 II False II Monitoi:
ROD SELECT -INSERT (DI) loo:J8:13 II True ll Monitor IRod Select 46-39 (Dl) - Monitor lloo:I8:10 II False II jRod Select 46-39 (DI)- Monitor 1Joo:I8:09 II True í ROD SELECT-INSERT (DI) - 100:17:58 II False I Monitor ROD SELECT - INSERT (DI) *
.A
( "rA I
True I Monitor v
jRod Select 46-23 (DI) - Monitor 1M False
[Rod Select 46-23 (DI) - Monitor IJ;oo:17:45 I
Trne 1[
ROD SELECT -INSERT (DI) - 100:17;34 II False II Monitor ROD SELECT - INSERT (DI) ioo: L7:25 II True I!
1v[o11ito1*
!Rod Select14-39{DI)- Monitor 1Joo:17:21 II False J
Rod Select 14-39 (DI)- Monitot Joo:l7:21 II 1'rue I
ROD SELECT - INSERT (DI) - loo:l7:o4 II Fad[
Monitor ROD SELECT* INSERT (DI) -
00:16:55 I
True IL Moi1itot bc-Joo:16:49 II False II Joo:I6:49 IQrue II 1;
u*u)* T
- JNSi'.RT (DJ) * [oo:l6:36 II False II tor II ll II Page 1 of4 II Valid I Yes Y"'
Yes II Yes I
II Yes I II Yes I I!
Yes I
Yes Yes
[
Yes I I
Yes I
I Yes I
II Yes I II Yes I I
Yes I
I Yes I
II Yes I II Yes I II Yes I
I Yes l
Yes file :///C:/Users/pseg/Desktop/PRNM%20Data!PRNM%20Loss%20of0/o20FWH%20D%20S... 6/7/2016
Page 2 of4 ROD SELECT INSERT (DI) w *¥00:16:27 Monitor
====
Ttue I
Yes I jRod Select 38-47 (DI)- Monitor jjoO:l6:22 False II True I
I Yes I
I Yes I
!Rod Select 38-47(DI) "Mohitor jjoo:16:21 ACKNOWLED (DI) *Monitor jo0:16:J 7 II False I
I yes I
ACKNOWLED (Dl) - Monitm ROD SELECT INSERT (DI) -
Monitor 00:16:.17 00:16:12
__ j Tme II I
False II I
Y""'
I Yes I
Yes II I
ROD SELECT., INSERT (DI) 1. 0:1.6:03. II II Monitor
- =*====*::=*
==T
==
n
=
re==*l?=====4 i======
jRod Select 38-15 (DI)- T\\dot1itor
. Jioo:l6: 01 II False II Yes Yes I
I Yes I
jRod Select 38-15 (DI)- Mo11itor jjoo:l6:01 II True II RO
=
D=S=E=LE=c
=
=
=
I
=
N
=
R
=T
==
(D
=
I)
=
?::=oo=:=
15=:4=9
=*
=
=
=
9::=1
=
Fa=ls=
e
=*==l:
l
?========i i========
D SELECT... INSERT (DI) _
1 T
1 *r
========{
rue Yes II Yes I
II Yes J Monitor=**=
- ====
- . =
====li====9?*
jRod Select 22-4 7 (DI) Monitor lloo: 15:36 II False I I
?R
=
od
=S
=
e=l e
=
ct""'* 2=2=4=7:2::
( D
=
I==)
=_ M
=*
=om=.t
=
or =
- 9P=o
=
o:
=
15 = 3=6===
ŽF=
I
==T
=r L
=le
=
=lj["=*
===z===""'ll IIRODSELECTC INSERT (DI)
I II M.
00:15:07 False onrtor D SELECT M INSERT (DI)
Monitor joo:15:oo II True I I[ Yes I Yes Rod Select 3 831 (DI) - Monitor Rod Select 3 831 (DI) Monitot ROD SELECT INSERT (DI),..
Monitor joo:14:54
[00:14:53 00:14:44 II True I.
II False I
ROD SELECT INSERT (DI)-
OO:l4:37 True I 11 y
I Monitor
- . eé F=j R =od =. S=e=lec =t =22 =* =31 """(=D""'=I) =-
=M=on=it=or =*
- I*I:==
00=:1=4=:3=2===11 F==F=al=se='
II Yes I
):==
Rod=Se=le=ct =n* =31 """(=D=t)=M =or=1tt=m=*9IF=oo=:l=4=:3 =2====1F=I
==T= r=ue==l::=l======"=== Y=e=s=l IJKtL;LECT INSERT (DI)
00:14:23
)
Flse II II Yes--J IERODSELECf'T
=
INSE RT(
DI)
=
-==:it======
111:=======§¨©=======91 I F=M=* o=n=ito = r =*
========0=0.:1=4:=17===l==T=r=tre
Yes
[Rod Select 30-23 (DI)- Monitor IIOO:l4:12 II False IC II Yes I
j Rod Select 3023 (DI) Monitm* jjOO:l4:12 II..... True II
¢ DEFtGHECT ûINSERT (DI)- E'J[ £li====::::=:JI
]^_Q;l3`7j II True Jl II Yes I II 11 H
II II I
+/-1le :/ 1/C :/U sers/pseg/Desktop/PRNM%20Data/PRNM%20Loss%20o:fU/o20FWH%20D%20S... 617120 16
Page 3 of 4 Yes j'Rod Select 3039 (Dl).. Monitor 1100:13:27 1:=1
=T=l'=ue=: çII I
B=la=úk=D=e=ûs=üý=ti =on =ÿ=M=o=h=ito=r==:/Fo=O:=l1=.:5=6====Jl/===F=al=se==ll:=======l :=====
- =B=Ta=nl ={ D=_ e=s=ct'"""'
ip=ti =on==M=o=n=ito=r=*==:::=li=:l@=o: =11=:5=5=11 Ttue l:========l===Y=e=s===ll jBl Descl'iption. Monlto1'
!joo=:=11 =:5 =2====lj1[==*F='a=ls=e
=::;(11/====[?==Y=e=s===ll l jBlankDescription*Monitor jloO:l1:51 II Tme I
[
Yes RESEtHr LEVEL TRIP HTR [
II
.0.
II II 1
5/TRN A(L0) 00:11:44 No
==;===f R
n ===P=t=L
=
.=v
=
E=L
==
=
oo
=
- 1
=
1
=
- 4
=
4
==
::;(1l:=====o===:::=jlti========*====N-o=
RESET HI LEVEL TRIP-HTR
[
II 0
II II
.N*o*
I 3/TRN A (LO) lB:ll:44 HTR TRIP-I-n LEVEL TRIP-HTR 00
... 1.1.44
- l.
j j]
N.*. 0 1
12=/T=R=N=A=(=L=0=)==========
- ==*====9:=======9:=======**=======:::=l*
HTR TRIP-HI LEVEL TRIPHTR 0.0.11.. 44 1
I 11 N*..
o I
1/TRN A (LO)
HV "'l362A CLOSE-FWH #5 SHELL SIDESHELLCROSS OO:ll :34 AROUND STM TSLN (DI) -
Monitor Tnle Yes TUiV5Si;EWXYsZi[\\T6R. loo.
. :l..,34 123lllr-;.-;1.
S1M DRN VLVS (DI)- Momtor AL___JL:.:__j HY"l358ACLOSEFWH#4 EJGCJ[0J SHEL L SIDESHEI. J_,*EXTSTM 00:11 :34 True.
Yes lSLN (DI) - Monitor flle:///C :/Usets/pseg/Desktop/PRNM%20Data/PRNM%20Loss%20of%20FWH%20D%20S... 6/7/20 16
Page 4 of4 HV--1357ACLOSE-FWH.#3 LJ.
L_j.LJ SHELL SIDESHELLEXT STM lSLN (DI) Monitor HS-1365ACLOSEFWH#6
=
- [:]
S:t-lELL SIDE-SHELL-EXTR
.. 00:11:34 No STM DRN VL VS (DI)
^H=v=-
I=3 =6 1=A=c=L=o=s=E-=F=w
=
H""""#""""s===ilo*o:l..
l.:"'.4 ICl*. c
... [:]
- '... N*o*
SHELL SlD:E-SHELL-MSTRE
HV-l360ACLOSE-FWH#5 EJ.
CCJ/]
SHELL SIDE-SHELL-MSTRE 00:11 :3.. 4.
H=v=-1=36=2=A=c=>
L=o =s E_-=F wb* *"""H""""
- =s =`r
- lc=JCJ SHELL SIDE-SHELL-CROSS 00..
- 11 :34.
. l No AROUND S1'M ISLN (DI)
HV-l358A CLOSE-FWH #4
- c lcS;;;;H;::::E,;;,
LL*,;;,;
S1 """"
D
=
E-
=
S
=
HE
=
L
=
L
=
-E
=
'X
=
T
=
S
=
'T
=
M a 00:11:34 l
No JSLN(DI)
LV-lJ56ACLOSESTMSEAL,
I
- .00:11:34 1
HV-1J57A CLOSE.-FWH#3 SHELL Sitm-SHELL-EX"t' STM 00:11:34 ISLN (Dl)
[:]
0,0
}==='IJ[-
Yes I
=T
. r =ue==
II Yes file:///C:/Users/pseg/Desktop/PRNM%20Data/PRNM%20Loss%?0of%20FWH%20D%20S... 6/7/2016
Hope Creek Operations Crew E Date 9/19/16 Scenario - Loss of A - Feed water heating - entire string. Reactor Recirc pumps at minimum speed.
- 1. Time allowed for operator response - 6 min and 32 seconds.
- 2. Time for operators to respond to initiating event - 3 min and 50 seconds
- 3. Action expected to be taken -
Immediate operator action from memory - Reduce and Maintain Reactor power to the Pre-Feedwater Heater Trip or Isolation Value.
- 4. Indications available to operators to diagnose event:
Overhead annunciators A7-E2 - Feedwater Heater Trip Extraction steam isolation valves going close, FWH Trip lights lit and FWH reset lights extinguished on 10C650 section A Feedwater temperature lowering, followed by reactor power rising on both APRMs and core thermal power.
Main Generator (MWE) rising.
- 5. Actions taken by operators.
Operators verified trips/isolations of Feedwater heaters.
From memory took their immediate operator actions: Reduced and Maintained Reactor Power to the Pre-Feedwater Heater Trip or Isolation Value. With Reactor Recirc pumps at minimum speed, the only means to reduce power is to insert control rods.
- 6. Procedures used that provided guidance.
HC.OP-AB-BOP-0001(Q)
- 7. Did operators respond as expected?
Yes, all correct actions were taken and verified.
- 8. What deltas if any between crews?
None observed.
- 9. The following data has been included:
The plots showing Rx power, A/B Feed Line Temperature, APRM A power. And Total Core Flow. Heater switch failure (initiating event) at 00:03:38. Feedwater temperature shows a slow lowering in temperature followed by a slow rise in reactor power. Rod Insertion begins at 00:07:28 and continues for the next several minutes to maintain power.
TAMS report from simulator - Tracks the manipulation of each switch in the simulator - Heater switch failure (initiating event) - at time 00:03:38. Rod insertion Commences - at time 00:07:28, and continues.
HC.OP-AB.BOP-0001(Q) - Feedwater Heating (First three pages only.)
I Feed water temp.
-.v I Rx oower I
\\
I First Rod inserted - 07:28 I Heater 2A Hi lvl - 03:38 I Time allowed 392 sec-10:10 l
l
- h-r1-r-r,...-;--'T-r---r-r-r-r---r-r-2c34"5r-o-"6r-r-7.--r-r--cr-r=-r-r-r--8*9:;,...r-r--r-,--.r-'r--r-"1-.---<<=iD!
{)3;20 05;00 M:2ll 10:00 11:40 n 50000 DataChart.. Training Load:1962
.. E Shift Loss ofFWH Data 2 1
2 3
4 Description APRM CH.A PWR Total Core Flow Feed Line A Inlet Tem....
Feed Line B Inlet Iem...
Value Units Min PCT 55 MlB/
0 degF 0
degF 0
t 350 r
Data Chart Max 65 Se+004 sao 500
Thunder Sin1ulation Tam Reuort Hone Creek Chris Kittredge, TIHi May 1910:09:58 2016 "E" Shift PRNM" Loss of FWH Description h.**** ***
m
- Rod Select 1439 (Dl) Monitor
- Rod Select 1439 (DI) Monitor 1Rod Select 14-35 (DI) Monitor (00
- 13:05 Select 1435 (Dl)- Monitor 100:13:05 jRODSlLECT
- CO£TINUOUS :oo:l2:47
- 1NSER1 {DI) - Momtor
!ROD SELECT CONTINUOUS
\\INSERT (DI) *Monitor Tnte Ramp Y<es Yes IR.ociseit.14-39 (DI)- iv1:0ito:";oci:T1:55...
False Yes
- R.od Select 14-39 (Di) - M:;ito: ;oo:Il :55
.Ron sEiEcT-coTrNuOlis bcd:; 1:1; True Yes
- INSERT (DI)- Motntor i
lRciD SELECT-CO¢TINUOUS efg*h1 :06
- INSERT (DI) Momtor I
- Rod Selet 22 15 (DI)- Monitor :oo:*ll:OO Select 22-15 (Dl).Monitor !00: 11:00
!RCi6sEi8cTcoN1iNuous !i0.j0.48
!INSERT (Dl) - Monitor 11lokSELECT CO_NTINuous [oo:To:39 INSERT (DT) - Momtor
- Rod Select 384 7 1
Rod Select 38-47 (DI) w Monitor j00:10:31
- w*D**.>*.,
ROD SELECT-COTINUOUS ;00:10:IS INSERT (DI)- Momtor
.ROD SELECT -CONTINUOUS tOO*l0'06
- INSERT (DI) -Monitor False True False Select 38-15 (DI)- Monitor True ROD SELECT* CONTINUOUS
- .00:09:54 False Yes Yes Yes Yes Yes Yes Yes Yes Yes
(Dl}- Monitor
[R.oo sE1Ecr:co]rn\\fuous :oo:o9;44
!INSERT (Dl) Momtor True jRod Select 22-47 (DI)- Monitor ;oo:o9:34
!Rocrseiect 22=47"(n-iF.Moii0*1:
fR:oo*s£LBct-co!'Ir1Nuous*l^_;`a:22
!INSERT (DI) Mm1rtm*
fR.oifsE:i£c1; :co!r1'Nuous1"0.09.15.
!INSERT (DI) "Momtot l................................ ::********).... :**:.. *-
JRod Select 3831 (DI) - Monitor i00:09: 12
>>.'***=
- -'*'*'-+,-*** w-DD-
!Rod Select 38<31 (Dl) -Monitor :00:09:12 lR:oiJ sfiifici; cciN'ri.Nuous*
tiNSERT (Dl) Monitor
- -**,---*******-.-/--*0
!ROD SELECT-CONTINUOUS loo*OS*.54
!INSERT (DI).. Monitor jRODSELECT-CONTINUOUS :00*08*12 (INSERT (DI) Monitor Select 3023 (Dl) -Monitor 100:08;11 False nue False True False
!rue
(""'.
........,,8,..................,.,.
- """'"'*1* i*
... *--....,
,Rod Select30-23 (Dl) Momtor !00:08:10 True
[R:o5 sE:ificT": co.N;iiNoous.. --
1.IN
. SER.1' (D I) M.
- 't 1
00:07;3.5 1
om or
'\\
d:Ji):*t........
!Rod Select 30-39 (DI) Monitor 100:06:34
- Rod sre;;;:*35=3*9* corj:M;nitor foo:o6:34 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
. -*-*"-*-** *œ-- *-***
- .A.CKNOWLED (Dl)- Monitor
- ACKNOWLED (DT) - Monitor
- ... v<>****"'''"''''":""""'O''''''''''''''" "'"''''"**'W.-.-..... *
'RESET-HI LEVEL TRIP-HTR S/TRN A (LO)
!00:03:48 0
,,,,,.,,,,,_,_,,,,.,,.v*w***""'"'"""'="w',-.....,.,.,.,.,..,,... *
. '"' "'-*-WY.
RESET-HTRTRIPHI LEVEL
.QO:OJ:48 0
TRIP-HTR 4/TRN A (LO)
""""'"'"'"'"""*"*""""""'W"""O+O,-mm*"......._"'"'""""'-'"*'-".{*"
- RESET HI LEVEL TRlP-HTR 00:03:48 0
[3/TRN A (LO)
- HTR TRIP
.. HI LEVEL TRIP*
- 00:03:48 1
jHTR 2/TRN A (LO)
!HTR TRIP HI LEVEL TRIP,.
lHTR 1/TRN A (LO)
HTR TR1P-HI LEVEL TRIP
- HTR 6-TRN A (LO)
HTR TRIP-Hl LEVEL TRIP:..
!HTR 5/TRN A (LO)
- H;ii1iiP-HI LBYEL TRIP HTR 4/TRN A (LO)
HTR TRIP-HI LEVEL TRIP
- HTR 3/TRN A (LO)
- HV-.1361A CLOSE-FWH#5
- SHELL SIDE-SHELLMSTRE iSEP A DRN ISLN (DI) -
,Mot1itor
'Ji\\Ll360A CLOSE-FWH#5 SHELL SIDE-SHELL-MSTRE
- SEP B bRN ISLN (DI) "'
Monitor HV M 1362A CLOSE.,FWH #5
'SHELL SIDE-BHELLCROSS AROUND STMISLN (DI)
Monitor HS1365A CLOSE-FWH# 6
,00:03:48 100;03:48
- c 100:03:48 100:03:48
- 00:03:38
'00:03:38
- 00:03:38
- SHELL SIDE-SHELLEXTR
,00:03:38
........ --A**--***********
liV I358A CLOSEFWH #4
,SHELL STDE-.SHBLL-EXT 00:03:38
,STM lSLN (Dl)
- Monitor iV1356A CLOSE STIVI SEAL
'EVAP DRN {DI),. Monitor
.00:03:38
- '** **********B-"**.. -**-*---*--*******-****-**************-********************** ****** **** '""-****
HV.-1357A CLOSE-FWH#3
- SHELL SIDE-SHELL-EXT 00:03;38 STM ISLN (Dl) Monitor
- HS-1365A CLOSE-FWH# 6
HVJ361A CLOSE-FWH #5 SHELL SIDE-SHELL-MSTRE 00:03:38 SEP A DRN ISLN (D f)
HV-1360A CLOSEFWH#5 00:03:38 No No
'True Yes True Yes True Yes Yes Yes Yes 1
No No
. S.HELL SIDESHELLMSTRE
[SEP B DRN ISLN (Dl)
!HV:i 36
.. 2A:-cLcfsJ3:Fw:H#5
.. 1 t.
iSHELL SIDESHELL.;CROSS
!00:03:38 AROUND STM ISLN (DI)
HV1358A CLOSEFWH#4 JSHELL SIDESHELL-.EXT 00:03:38
!StM ISLN (DI)
!HV-1357A CLOSE-FWH #3
'SHELL SIDE-SHELL-EXT
- STM ISLN (DI) tYZ[\\r
- Toggle event 2 No No No No Yes Yes