Emergency Response Data System Changes
ML14034A247
Person / Time
Site: Mcguire
Issue date: 01/09/2014
From: Capps S
Duke Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML14034A247 (7)


Text

t DUKE ENERGY. McGuire Nuclear Station Duke Energy 12700 Hagers Ferry Road Huntersville, NC 28078 0: 980.875.4000 January 9, 2014 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001

SUBJECT:

Duke Energy Carolinas, LLC McGuire Nuclear Station, Unit 2 Docket No. 50-370 Emergency Response Data System Changes By letter dated May 16, 2013, the NRC staff issued approved License Amendment No. 269 to Renewed Facility Operating License NPF-9 and Amendment No. 249 to Renewed Facility Operating License NPF-1 7 for McGuire Nuclear Station (MNS) Units 1 and 2 respectively. The license amendments were approved to support the implementation of a measurement uncertainty recapture (MUR) power uprate on MNS Units 1 and 2.

Subsequent to the implementation of the MUR power uprate on MNS Unit 2, MUR related Data Point Library (DPL) changes were implemented on the Emergency Response Data System (ERDS) on December 10, 2013. Pursuant to the requirements of 10CFR50 Appendix E, Section VI.3.a, Enclosure 1 provides these ERDS DPL changes. The NRC DPL information for MNS Unit 2 should be revised per the four sheets in Enclosure 1. The MUR power uprate has not yet been implemented on MNS Unit 1. Therefore, the DPL information for Unit 1 will not require revision at this time.

All ERDS communication protocols, messages, quality codes, and formats are unaffected by the MUR power uprate on MNS Unit 2 or the ERDS changes provided in the Enclosure to this letter.

Therefore, there is no requirement for prior notification per 10CFR50 Appendix E, Section VI.3.b.

Questions regarding this submittal should be directed to Jeff Robertson, McGuire Regulatory Affairs at (980) 875-4499.

Steven D. Capp Enclosure www.duke-energy.com

U.S. Nuclear Regulatory Commission January 9, 2014 Page 2 cc: Victor M. McCree Regional Administrator U. S. Nuclear Regulatory commission, Region II Marquis One Tower 245 Peachtree Center Ave., NE, Suite 1200 Atlanta, Georgia 30303-1257 John Zeiler Senior NRC Resident Inspector U. S. Nuclear Regulatory Commission McGuire Nuclear Station Jason Paige (Addressee Only)

NRC Project Manager U. S. Nuclear Regulatory Commission 11555 Rockville Pike Mail Stop 0-8 G9A Rockville, MD 20852-2738

Enclosure 1 MUR Related MNS Unit 2 ERDS DPL Changes

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 1/9/2014 REACTOR UNIT: MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: MN FD FL 1A POINT ID: M2P1412 PLANT SPEC POINT DESC: 2A STEAM GENERATOR TOTAL FEEDWATER FLOW 1 GENERIC/COND DESC: STM GEN A MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 5.15 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 3 HOW PROCESSED: Dir. from flow (DP), Temp and Pressure SENSOR LOCATIONS: ASME nozzle Current Prodac ALARM/TRIP Hi: - Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY CUT- N/A OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP: Y REF_ LEG: N/A UNIQUE SYSTEM DESC: Performance point calculated feedwater flow using delta P across ASME nozzle, temperature, and pressure of feedwater. 1 or 2 channel performance points. Minimum instr. range = 0" of minimum range =>

minimum forced flow readinq of 0 MLB/HR.

point xref: 10.1

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 1/9/2014 REACTOR UNIT: MC2 DATA FEEDER: U2OAC NRC ERDS PARAMETER: MN FD FL 26 POINT ID: M2P1414 PLANT SPEC POINT DESC: 2B STEAM GENERATOR TOTAL FEEDWATER FLOW 1 GENERIC/COND DESC: STM GEN B MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 5.15 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 3 HOW PROCESSED: Dir. from flow (DP), Temp and Pressure SENSOR LOCATIONS: ASME nozzle Current Prodac ALARM/TRIP Hi: - Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY CUT- N/A OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP: Y REF_ LEG: N/A UNIQUE SYSTEM DESC: Performance point calculated feedwater flow using delta P across ASME nozzle, temperature, and pressure of feedwater. 1 or 2 channel performance points. Minimum instr. range = 0" of minimum range =>

minimum forced flow readinQ of 0 MLB/HR.

point xref: 10.1

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 1/9/2014 REACTOR UNIT: MC2 DATA FEEDER: U2 OAC NRC ERDS PARAMETER: MN FD FL 3C POINT ID: M2P1416 PLANT SPEC POINT DESC: 2C STEAM GENERATOR TOTAL FEEDWATER FLOW 1 GENERIC/COND DESC: STM GEN C MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 5.15 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 3 HOW PROCESSED: Dir. from flow (DP), Temp and Pressure SENSOR LOCATIONS: ASME nozzle Current Prodac ALARM/TRIP Hi: - Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY CUT- N/A OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP: Y REF_ LEG: N/A UNIQUE SYSTEM DESC: Performance point calculated feedwater flow using delta P across ASME nozzle, temperature, and pressure of feedwater. 1 or 2 channel performance points. Minimum instr. range = 0" of minimum range =>

minimum forced flow readinq of 0 MLB/HR.

10.1 point xref" pointxref:10.1

A. -

McGuire Nuclear Station Emergency Response Data System (ERDS) Implementation PWR DATA POINT REFERENCE FILE DATE: 1/9/2014 REACTOR UNIT: MC2 DATA FEEDER: U2OAC NRC ERDS PARAMETER: MN FD FL 4D POINT ID: M2P1418 PLANT SPEC POINT DESC: 2D STEAM GENERATOR TOTAL FEEDWATER FLOW 1 GENERIC/COND DESC: STM GEN D MAIN FEEDWATER FLOW ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MLB/HR ENGR UNITS CONVERSION: N/A MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 5.15 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES: N/A PROC OR SENS: P NUMBER OF SENSORS: 3 HOW PROCESSED: Dir. from flow (DP), Temp and Pressure SENSOR LOCATIONS: ASME nozzle Current Prodac ALARM/TRIP Hi: - Lo: -

SETPOINTS:

NI DETECTOR POWER SUPPLY CUT- N/A OFF POWER LEVEL:

NI DETECTOR POWER SUPPLY N/A TURNON POWER LEVEL:

INSTRUMENT FAILURE MODE: LOW TEMPERATURE COMPENSATION FOR DP: Y REF_ LEG: N/A UNIQUE SYSTEM DESC: Performance point calculated feedwater flow using delta P across ASME nozzle, temperature, and pressure of feedwater. 1 or 2 channel performance points. Minimum instr. range = 0" of minimum range =>

minimum forced flow readina of 0 MLB/HR.

point xref: 10.1