Containment Spray Recirculation Following Loss of Secondary Coolant, Revision 0
ML13311A577
Person / Time
Site: San Onofre 
Issue date: 05/20/1982
From:
Southern California Edison Co
To:
Shared Package
ML13311A465 List:
References
SO1-1.2-1.22, NUDOCS 8205240494
Download: ML13311A577 (3)


Text

501-1.2-1.22 CONTAINMENT SPRAY RECIRCULATION REV 0 FOLLOWING LOSS OF SECONDARY COOLANT ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED EMERGENCY INSTRUCTION SO1-1.2-1.22 CONTATINMENT SPRAY RECIRCULATION FOLLOWING LOSS OF SECONDARY COOLANT I.

PURPOSE:

The purpose of this procedure is to provide containment spray if containment pressure remains high after the RWST is exhausted. This event would most likely occur with a loss of secondary coolant inside containment with the need to continually feed auxiliary feedwater.

8205240494 820520 PDR ADOCK 05000206 1 of 3 P

PDR

FOLLOWING LOSS OF SECONDARY COOLANT STE.

ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:

Containment Spray Recirculation must be established before the RWST level reaches 7'.

1 Start SI Recirculation Pumps:

a.

Start both SI recirculation pumps AND run for two minutes against Tose discharge valves.

2 Verify Salt hater Cocling:

a. One saltwater cooling
a. Place aux salt water pump breaker - CLOSED.

pump in service.

3 Verify Component Cooling To Rec rcuIation Heat Exchanger:

a.

Two CCW pump breakers

a. Manually start pumps CLOSED.

as necessary.

b. Open recirculation
b. Locally trip open heat exchanger CCW CV 737 A, AND B.

valves CV 737 A, AND B.

4 Reduce Containment Spray Flow:

a. Override and close CV 517
a. Locally trip closed AND CV 518.

CV 517 AND CV 518.

2 of 3

501-1.2-1.22 CONTANMENT SPRAY RECIRCULATION REV 0 FLOING LOSS OF SCDAYCOOLANT 0 SEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 5

Verify Spray Flow:

a. Spray flow indicator

-LESS THAN 600 GPM.

b. One refueling water
b. Manually start a pump breaker -

CLOSED.

refueling water pump.

6 Establish Recirculation Flow:

a. Open Si recirculation Dump disharge MCV 866 A AND 7

Isclate RwST:

a. Close MOV 883.
a. Manually close MOV 883.

8 SubseQuent Action:

a. Continue with instruction in erfect.

-END H. E. MORGAN MANAGER, STATION OPERATIONS 3 of 3