ML12040A073

From kanterella
Jump to navigation Jump to search

0000-0101-7647-R3, Columbia Generating Station Plant-Specific Responses Required by Numac Prnm Retrofit Plus Option III Stability Trip Function Topical Report, (NEDC-3241 OP-A)
ML12040A073
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 10/31/2011
From:
GE-Hitachi Nuclear Energy Americas
To:
Office of Nuclear Reactor Regulation
References
NEDC-32410P-A 0000-0101-7647-R3, DRF Section 0000-0101-7647-R4
Download: ML12040A073 (29)


Text

LICENSE AMENDMENT REQUEST TO CHANGE TECHNICAL SPECIFICATIONS IN SUPPORT OF PRNM AND ARTS / MELLLA IMPLEMENTATION - Attachment 8 0000-0101-7647-R3 Columbia Generating Station Plant-Specific Responses Required by NUMAC PRNM Retrofit Plus Option III Stability Trip Function Topical Report (NEDC-3241 OP-A)

October 2011 (non-proprietary version)

GE Hitachi Nuclear Energy 44,610 HITACHI 0000-0101 -7647-R3 DRF Section 0000-0101-7647-R4 October 2011 Non-ProprietaryInformation - Class I (Public)

Columbia Generating Station Plant-Specific Responses Required By NUMAC PRNM Retrofit Plus Option III Stability Trip Function Topical Report (NEDC-3241OP-A)

Copyright 2011 GE-HitachiNuclear Energy Americas LLC All Rights Reserved

0000-0101-7647-R3 INFORMATION NOTICE This is a non-proprietary version of the document 0000-0101-7647-R3, which has the proprietary information removed. Portions of the document that have been removed are indicated by an open and closed bracket as shown here ((

IMPORTANT NOTICE REGARDING CONTENTS OF THIS REPORT Please Read Carefully The design, engineering, and other information contained in this document is furnished for the purpose of supporting the Columbia Generating Station license amendment request for an extended power uprate in proceedings before the U.S. Nuclear Regulatory Commission. The only undertakings of GEH with respect to information in this document are contained in the contracts between GEH and its customers or participating utilities, and nothing contained in this document shall be construed as changing that contract. The use of this information by anyone for any purpose other than that for which it is intended is not authorized; and with respect to any unauthorized use, GEH makes no representation or warranty, and assumes no liability as to the completeness, accuracy, or usefulness of the information contained in this document.

i

0000-0101-7647-R3 Table of Contents Columbia Specific Responses Required by NUMAC PRNM Retrofit 1-19 Topical Report , Columbia NUMAC PRNM LTR Deviations A1-A5 ii

0000-0101-7647-R3 The section numbers and Utility Actions Required listed below are from the NUMAC PRNM Retrofit Plus Option III Stability Trip Function Topical Report NEDC-3241OP-A including Supplement 1.

Section No. Utility Action Required Response 2.3.2 Option III Stability Implementation Not a required specific LTR response Confirm that the actual plant Option III The CGS Option III implementation is in configuration is included in the variations accordance with the LTR Requirements of covered in the Power Range Neutron Monitor section 2.3.2.

(PRNM) Licensing Topical Report (LTR)

[NEDC-3241 OP-A, Volumes I & 2 and Supplement 1].

2.3.4 Plant Unique or Plant-Specific Aspects The actual, current plant configuration and the Confirm that the actual plant configuration is proposed replacement PRNM are included in included in the variations covered in the Power the PRNM LTR as follows: (Applicable LTR Range Neutron Monitor (PRNM) Licensing sections are listed.)

Topical Report (LTR) [NEDC-3241OP-A, Volumes I & 2 and Supplement 1], and the Current Proposed configuration alternative(s) being applied for the APRM 2.3.3.1.1.2 2.3.3.1.2.1 replacement PRNM are covered by the PRNM RBM 2.3.3.2.1.1 2.3.3.2.2.1 LTR. Document in the plant-specific licensing Flow Unit 2.3.3.3.1.2 2.3.3.3.2.2 submittal for the PRNM project the actual, Rod Control 2.3.3.4.1.2 2.3.3.4.2.2 current plant configuration of the replacement Panel Interface 2.3.3.6.1.1 2.3.3.6.2.1 PRNM, and document confirmation that the PRNM LTR covers those. For any changes to the plant operator's panel, document in the submittal the human factors review actions that Human Factors Engineering is part of the CGS were taken to confirm compatibility with design process consistent with NUREG-0700..

existing plant commitments and procedures. See discussion on Human Factors Evaluation in the License Amendment Request (LAR).

The actual PRNMS System to be installed at CGS contains three deviations from the system design as described in the LTR. Justifications for these deviations are provided as Enclosure 1.

3.4 System Functions As part of the plant-specificlicensing submittal, the utility should document the following: 1 The current flow channel configuration I) The pre-modification flow channel consists of eight flow transmitters (LTR configuration, and any changes planned Section 3.2.3.1.1). Thus, the current (normally changes will be either adding two configuration meets the requirements channels to reach four or no change described in LTR Section 3.2.3.2.2.

planned)

NOTE: If transmitters are added, the requirements on the added transmitters should be:

I

0000-0101-7647-R3 Section No. Utility Action Required Response

" Non-safety related, but qualified environmentally and seismically to operate in the application environment.

" Mounted with structures equivalent or better than those for the currently installed channels.

  • Cabling routed to achieve separation to the extent feasible using existing cableways and routes.
2) APRM trips currently applied at the plant are listed below along with changes
2) Document the APRM trips currently planned. The "post-modification" trips will applied at the plant. If different from those be the same as those identified in the LTR.

documented in the PRNM LTR, document plans to change to those in the LTR.

" "Inop" Retained, except the logic is modified slightly (same as described in LTR paragraph 3.2.10).

  • "Fixed Neutron Flux-High" is modified to "Neutron Flux-High" (as described in LTR paragraph 3.2.5).
  • "Flow Biased Simulated Thermal Power-High" is modified to Simulated Thermal Power-High" (as described in LTR paragraph 3.2.5).
  • "APRM Neutron Flux - High (Setdown) is retained as described in LTR paragraphs 3.2.4 and 8.3.1.4.
  • Add 2-Out-of-4 Voter as described in LTR paragraphs 3.2.2 and 8.3.2.4.
3) ARTS will be implemented concurrently
3) Document the current status related to with the PRNM and is part of this submittal ARTS and the planned post modification status as:

" ARTS currently implemented, and retained in the PRNM

  • ARTS will be implemented concurrently with the PRNM (reference ARTS submittal)

" ARTS not implemented and will not be implemented with the PRNM

" ARTS not applicable 4.4.1.11 Regulatory Requirements of the Replacement A review of the CGS requirements confirms that System - System Design the regulatory requirements addressed in the LTR encompass the related CGS requirements.

This section identifies requirements that are Regulatory and licensing requirements are expected to encompass most specific plant evaluated in the CGS Digital I&C-ISG-06 commitments relative to the PRNM replacement Compliance document (NEDC-33685P).

project, but may not be complete and some may I 2

0000-0101-7647-R3 Section No. Utility Action Required Response not apply to all plants. Therefore, the utility must confirm that the requirements identified here address all of those identified in the plant commitments. The plant-specific licensing submittal should identify the specific requirements applicable for the plant, confirm that any clarifications included here apply to the plant, and document the specific requirements that the replacement PRNM is intended to meet for the plant.

4.4.2.2.1.4 Regulatory Requirements for the Replacement The PRNM control room electronics are System -Eouinment Oualification - Temnerature qualified for continuous operation under the and Humidity following temperature conditions: 5 to 50 'C [41 to 122 *F]. The CGS control room temperature Plant-specific action will confirm that the range is: 40 - 104 °F (72-78 °F normal). The maximum control room temperatures plus design process includes actions to confirm that mounting panel temperature rise, allowing for the PRNM equipment, as installed in the plant, heat load of the PRNM equipment, does not is qualified for the environmental limits, exceed the temperatures presented in the PRNM including temperature rise measurements.

LTR, and that control room humidity is maintained within the limits stated in the PRNM The PRNM control room electronics are LTR. This evaluation will normally be qualified for continuous operation under the accomplished by determining the operating following relative humidity conditions: 10 to temperature of the current equipment which will 90% (non-condensing). The CGS relative be used as a bounding value because the heat humidity requirement for control room load of the replacement system is less than the equipment is: 10 - 60%, which is within the current system while the panel structure, and range for which the PRNM equipment is thus cooling, remains essentially the same. qualified. The qualification results have been Documentation of the above action, including documented in a plant unique "Qualification the specific method used for the required Summary."

confirmation should be included inplant-sDecific licensing submittals.

4.4.2.2.2.4 Regulatory Requirements for the Replacement The PRNM control room electronics are System -Equipment Qualification - Pressure qualified for continuous operation under the Plant-specific action will confirm that the following pressure conditions: 13 - 16 psia. The maximum control room pressure does not CGS normal ambient atmospheric pressure is exceed the limits presented in the PRNM LTR. approximately 14.43 psia (nominally 14.0-15.0 Any pressure differential from inside to outside psia), and is within these limits. The the mounting panel assumed to be negligible qualification results have been documented in a since the panels are not sealed and there is no plant unique "Qualification Summary."

forced cooling or ventilation. Documentation of this action and the required confirmation should be included in plant-specific licensing submittals.

4.4.2.2.3.4 Regulatory Requirements for the Replacement The PRNM control room electronics are System -Equipment Qualification -Radiation qualified for continuous operation under the Plant-specific action will confirm that the following conditions: Dose Rate < 0.001 Rads maximum control room radiation levels do not (carbon)/hr and Total Integrated Dose (TID) <

exceed the limits presented in the PRNM LTR. 1000 Rads (carbon). The CGS control room Documentation of this action and the required dose rates and Total Integrated Dose (TID) over confirmation should be included in plant- 40 years are within the qualified ranges. The specific licensing submittals. qualification results have been documented in a 3

0000-0101-7647-R3 Section No. Utility Action Required Response plant unique "Qualification Summary."

4.4.2.3.4 Regulatory Requirements for the Replacement Evaluations to confirm that the maximum System -Seismic Qualification seismic accelerations at the mounting locations Plant-specific action or analysis will confirm of the equipment do not exceed qualification that the maximum seismic accelerations at the limits of the equipment are completed as part of mounting locations of the equipment (control the CGS normal design change process.

room floor acceleration plus panel The seismic qualification results have been amplification) for both OBE and SSE spectrums documented in "Qualification Summary do not exceed the limits stated in the PRNM LTR. Documentation of this action and the required confirmation should be included in plant-specific licensing submittals.

4.4.2.4.4 Regulatory Requirements for the Replacement System -EMI Qualification The utility should establish or document practices to control emission sources, maintain good grounding practices and maintain equipment and cable separation.

1) Controlling Emissions 1.) Controlling Emissions a) Portable Transceivers (walkie-talkies): a) The qualification levels used for the Establish practices to prevent operation NUMAC PRNM system exceed those of portable transceivers in close expected to result from portable proximity of equipment sensitive to such transceivers, even if such transceivers are emissions. (NOTE: The qualification operated immediately adjacent to NUMAC levels used for the NUMAC PRNM equipment. CGS generally prohibits exceed those expected to result from operation of portable transceivers near portable transceivers, even if such sensitive equipment, and if warranted, transceivers are operated immediately requires positioning of warning signs at adjacent to the NUMAC equipment.) critical locations throughout the plant.

Placements of warning signs were evaluated as part of this modification process.

b) The qualification levels used for the b) ARC Welding: Establish practices to NUMAC PRNM system minimize the assure that ARC welding activities do not likelihood of detrimental effects due to ARC occur in the vicinity of equipment welding as long as reasonable ARC welding sensitive to such emissions, particularly control and shielding practices are used.

during times when the potentially ARC welding is only performed at CGS sensitive equipment is required to be with specific work orders and directions, operational for plant safety. (NOTE: The and is known to have the potential to affect qualification levels used for NUMAC operation of I&C equipment at a number of PRNM minimize the likelihood of locations in the plant. Therefore, ARC detrimental effects due to ARC welding welding activity is only performed when any as long as reasonable ARC welding potential effect on I&C equipment is control and shielding practices are used.) tolerable relative to plant operation.

c) EMI emissions from the new PRNM c) Limit Emissions from New Equipment: equipment were evaluated as part of the Establish practices for new equipment normal design modification process and plant modifications to assure that described in CGS procedures.

they either do not produce unacceptable levels of emissions, or installation 4

0000-0101-7647-R3 Section No. Utility Action Required Response shielding, filters, grounding or other methods prevent such emissions from reaching other potentially sensitive equipment. These practices should address both radiated emissions and conducted emissions, particularly conducted emissions on power lines and power distribution systems. Related to power distribution, both the effects of new equipment injecting noise on the power system and the power system conducting noise to the connected equipment should be addressed. (NOTE:

For the qualification of the PRNM equipment includes emissions testing.)

2) Grounding Practices 2) The PRNM system equipment is being Existing Grounding System: The installed in place of existing Neutron specific details and effectiveness of the Monitoring System (NMS) electronics. The original grounding system in BWRs replacement system will interface with the varied significantly. As part of the same cables and wiring at the panel modification process, identify any interfaces as the current system, including known or likely problem areas based on ground bus connections. No problems have previous experience and include in the been identified with the current NMS related modification program either an to grounding or grounding practices. The evaluation step to determine if problems original installation included specific actually exist, or include corrective grounding practices designed to minimize action as part of the modification. performance problems. The replacement (NOTE: The PRNM equipment is being PRNM system is less sensitive to grounding installed in place of existing PRM issues than is the current system and includes electronics which is generally more specific actions in the wiring inside the panel sensitive to EMI than the NUMAC to maximize shielding and grounding equipment. As long as the plant has effectiveness.

experienced no significant problems with the PRM, no problems are anticipated with the PRNM provided grounding is done in a comparable manner.)

Grounding Practices for New Modifications: New plant modifications process should include a specific evaluation of grounding methods to be used to assure both that the new equipment is installed in a way equivalent to the conditions used in the qualification. (NOTE: NUMAC PRNM equipment qualification is performed in a panel assembly comparable to that used in the plant.)

3) Equipment and Cable Separation
3) Equipment and Cable Separation The original NMS cable installation
a. Cabling: Establish cabling practices to requirements met this objective. The assure that signal cables with the replacement PRNM system uses the same potential to be "receivers" are kept cable routes and paths at comparable energy 5

0000-0101-7647-R3 Section No. Utility Action Required Response separate from cables that are sources of levels where feasible. Because no specific noise. (NOTE: The original PRM cable problem has been identified in the current installation requirements met this system, no special action is necessary for the objective. The replacement PRNM PRNM modification. The existing system uses the same cable routes and paths, so cabling complies with applicable CGS cable unless some specific problem has been routing and separation requirements.

identified in the current system, no Additionally, the modification process is special action should be necessary for performed in accordance with the existing the PRNM modification.) separation criteria.

b. Equipment: Establish equipment separation and shielding practices for the installation of new equipment to simulate that equipment's qualification condition, both relative to susceptibility and emissions. (NOTE: The original PRM cabinet design met this objective.

The replacement PRNM uses the same mounting cabinet, and used an equivalent mounting assembly for qualification. No special action should be necessary for the PRNM modification.)

The plant-specific licensing submittals should identify the practices that are in place or will be applied for the PRNM modification to address each of the above items.

6.6 System Failure Analysis The utility must confirm applicability of the failure analysis conclusions contained in the PRNM LTR by the following actions:

PRNMLTRby he ollwin acion: I. The CGS Technical Specification (TS)

1. Confirm that the events definedinin Apendies EPRIFSurveillanceS.eThC e ehical fon Requirements for thetS)

Reactor Report No. NP-2230 or in Appendices F Protection System (RPS) are based on and G of Reference 11 of the PRNM LTR, Reference 11 of the PRNM LTR as encompass the events that are analyzed for discussed in the CGS Technical the plant; Specification Bases (Section 3.3.1.1, Reactor Protection System Instrumentation).

Therefore, the Reference I I failure analysis is applicable to CGS. The overall redundancy and diversity of sensors available to provide trip signals in the RPS meets NRC-approved licensing basis requirements.

2. Confirm that the configuration implemented 2. The proposed PRNM configuration is by the plant is within the limits described in included among the configurations the LTR; and described in the PRNM LTR, as itemized under Section 2.3.4 above. The proposed configuration is being designed by GEH and is within the limits described in the LTR.

6

0000-0101-7647-R3 Section No. Utility Action Required Response

3. Prepare a plant-specific IOCFR50.59 3. The requirements of 10CFR50.59 will be evaluation of the modification per the applied to the PRNMS modification in applicable plant procedures. accordance with applicable plant procedures.

should be These confirmations and conclusions documented in the plant-specific licensing submittals for the PRNM modification.

[Reference 11 of the LTR is NEDC-30851P-A, "Technical Specification Improvement Analysis for BWR Reactor Protection System", Licensing Topical Report, GE Nuclear Energy, Class III (proprietary), dated March 1988.]

7.6 Impact on UFSAR Applicable sections of the FSAR are reviewed The plant-specific action required for FSAR and appropriate revisions of those sections are updates will vary between plants. In all cases, prepared and approved as part of the normal however, existing FSAR documents should be design process. Following implementation of reviewed to identify areas that have descriptions the design modification and closure of the specific to the current PRNM using the general design package, the FSAR revisions are guidance of Sections 7.2 through 7.5 of the included in the updated FSAR as part of the PRNM LTR to identify potential areas impacted. periodic 10 CFR 50.7 1(e) FSAR update The utility should include in the plant-specific submittal.

licensing submittal a statement of the plans for updating the plant FSAR for the PRNM project.

8.3.1.4 APRM-Related RPS Trip Functions - Functions Covered by Technical Specifications I. Delete the APRM Downscale function, if 1. CGS does not have an "APRM Downscale" currently used, from the RPS RPS Trip Function Technical Instrumentation "function" table, the related Specifications.

surveillance requirements, and, if applicable, the related setpoint, and related descriptions in the bases sections.

2. Delete the APRM Flow-biased Neutron Flux Upscale function, if currently used, 2. CGS currently uses a "Flow Biased from the RPS Instrumentation "function" Simulated Thermal Power-High," RPS trip table, the related surveillance requirements, "Simulated Thermal Power-High".

and, if applicable, the related setpoint, and related descriptions in the bases sections. The "Fixed Neutron Flux-High" is retained Replace these with the corresponding entries for the APRM Simulated Thermal as "Neutron Flux-High".

Power - High and the APRM Neutron Flux

- High functions. Perform analysis necessary to establish setpoints for added trips. 3. The current APRM Neutron Flux - High

3. Add the APRM Neutron Flux - High (Setdown) function is retained (Setdown) function, if not currently used, to the RPS Instrumentation "function" table, add the related surveillance requirements, and, if applicable, the related setpoints, and related descriptions in the bases sections.

7

0000-0101-7647-R3 Section No. Utility Action Required Response Perform analysis necessary to establish setpoints for added trips.

8.3.2.4 APRM-Related RPS Trip Functions - Minimum Number of Operable APRM Channels

1. The PRNM modification and the proposed I For the 4-APRM channel replacement Technical Specifications and Bases change configuration, revise the RPS implement the changes as described in the Instrumentation "function" table to show 3 PRNM LTR for a "larger core" plant. CGS APRM channels, shared by both trip Technical Specifications do not include systems for each APRM function shown notes related to APRMs that call for (after any additions or deletions per PRNM removal of shorting links or references to LTR Paragraph 8.3.1.4). Add a "2-out-of-4 special conditions related to loss of all Voter" function with two channels under LPRMs from the "other" APRM.

the "minimum operable channels". For Therefore, no related note changes are plants with Technical Specifications that required.

include a footnote calling for removing shorting links, remove the references to the Revised RPS functions to indicate that the footnote related to APRM (retain references required number channels per a trip system for SRM and IRM) and delete any is 3 APRM channels.

references to APRM channels in the footnote. For smaller core plants, delete the "2-out-of-4 Voter" function with two notes for and references to special channels under the "minimum operable conditions related to loss of all LPRMs channels" has been added as Function 2.e.

from the "other" APRM.

2. Review action statements to see if changes 2. Action statement changes in the proposed are required. If the improvements Technical Specifications change are documented in Reference 11 have not been consistent with the PRNM LTR described implemented, then changes will likely be changes for plants with Improved Technical required to implement the 12-hour and 6- Specifications. CGS had previously hour operation times discussed above for switched to the IST format.

fewer than the minimum required channels.

If Improved Technical Specifications (IST) are applied to the plant, action statements remain unchanged.

3. Revise the Bases section as needed to 3. The proposed Technical Specifications replace the descriptions of the current 6- or Bases changes include revisions to the 8-APRM channel systems and bypass descriptions of the architecture, consistent capability with a corresponding description with the PRNM LTR.

of the 4-APRM system, 2-out-of-4 Voter channels (2 per RPS system), and allowed one APRM bypass total.

8.3.3.4 APRM-Related RPS Trip Functions -

Applicable Modes of Operation

1) APRM Neutron Flux - High (Setdown) 1) Technical Specifications and Bases changes Change Technical Specifications are consistent with the PRNM LTR.

"applicable modes" entry, if required, to be Mode 2 (startup). Delete references to actions and surveillance requirements associated with other modes. Delete any references to notes associated with "non-coincidence" mode and correct notes as required. Revise Bases descriptions as required.

8

0000-0101-7647-R3 Section No. Utility Action Required Response

2) APRM Simulated Thermal Power - High 2) The Flow Biased Simulated Thermal Power -

Retain as is unless this function is being High Technical Specification is retained added to replace the APRM Flow-biased however, the name is changed to "APRM Neutron Flux Trip. In that case, add Simulated Thermal Power - High," consistent requirement for operation in Mode 1 (RUN) with the PRNM LTR.

and add or modify Bases descriptions as required.

3) APRM Neutron Flux - High 3) The Fixed Neutron Flux - High Technical Retain as is unless this function is being Specification and Bases is retained however, the added to replace the APRM Flow-biased name is changed to "APRM Neutron Flux -

Neutron Flux Trip. In that case, add High," consistent with the PRNM LTR.

requirement for operation in Mode 1 (RUN) and add or modify Bases descriptions as required.

4) APRM Inop Trip 4) The current CGS Technical Specifications Delete any requirements for operation in require this Function, only in Modes I and 2.

modes other than Mode 1 and Mode 2 (RUN and STARTUP). Revise the Bases descriptions as needed.

8.3.4.1.4 APRM-Related RPS Trip Functions - Channel Checks/ Instrument Checks a) For plants without Channel Check a) The CGS Technical Specifications currently requirements, add once per 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or once include a once-per-shift Channel Check per day Channel Check or Instrument requirement for the APRM Functions Check requirement for the three APRM (except for Inop). The APRM Function flux based functions. No Channel Check Channel Check requirements are maintained requirements are added for APRM Inop at once perof12the remainder hours, RPS consistent Technical with the Secains. the rps Technical function. Plants with once per 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or Specification and Bases changes for the once per shift requirements may change them to once per day. Channel Check SR are consistent with the PRNM LTR.

b) For plants with 4 full recirculation flow b) CGS currently has 8 flow transmitters.

channels and with Technical Specifications Associated surveillances have been included that call for daily or other channel check in those for the APRM Simulated Thermal requirements for flow comparisons under Power - High, and the OPRM Upscale APRM Flow Biased Simulated Thermal Functions (the latter because of the OPRM Power Trip, delete those requirements. trip enable function). The proposed Move any note reference related to Technical Specification and Bases changes verification of flow signals to Channel for the recirculation flow related SRs are Functional Test entry. consistent with the PRNM LTR but with some expansion to clarify that the recirculation flow functions also support the OPRM Upscale Function trip enable.

9

0000-0101-7647-R3 Section No. I Utility Action Required I Response 8.3.4.2.4 APRM-Related RPS Trip Functions - Channel Functional Tests a) Delete existing channel functional test a) The proposed Technical Specification and requirements and replace with a Bases changes related to Channel requirement for a Channel Functional Test Functional Tests are consistent with the frequency of each 184 days (6 months) PRNM LTR.

[delete any specific requirement related to startup or shutdown except for the APRM Neutron Flux - High (Setdown) function as noted in Paragraph 8.3.4.2.2(1) of the PRNM LTR. Add a notation that both the APRM channels and the 2-out-of-4 Voter channels are to be included in the Channel Functional Test.

b) Add a notation for the APRM Simulated b) The proposed Technical Specification and Thermal Power - High function that the Bases changes to Channel Functional Tests test shall include the recirculation flow for the APRM Functions include a input processing, excluding the flow notation, applicable to the Simulated transmitters. Thermal Power - High (Function 2.b) and the OPRM Upscale (Function 2.f),

CAUTION: Plants that have not implemented consistent with the PRNM LTR the APRM surveillance improvements of requirements, that the SR includes the Reference II of the PRNM LTR, or those that recirculation flow input processing, have continued to use a weekly surveillance of excluding the flow transmitters. However, scram contactors, may need to implement or the PRNM LTR includes this notation only modify surveillance actions to continue to in the Bases. For the CGS Technical provide a once per week functional test of scram Specification, the Channel Functional Test contactors. (Prior to changes defined in has been added as SR 3.3.1.1.16 and has Reference 11, the weekly APRM functional test been expanded from that in the LTR to also also provides a weekly test of all automatic apply to the OPRM Upscale Function (to scram contactors.) cover OPRM Upscale trip enable).

The functional test procedure will be established to test all of the hardware required to produce the trip functions, but not to directly re-test software-only (firmware-only) logic. The APRM automatic self-test function monitors the integrity of the EPROMs storing all of the firmware so that if a hardware fault results in a "change" to the firmware (software), that fault will be detected by the self-test logic. The continued operation of the self-test procedures is monitored by the built-in "watch-dog timer" function, so if for some unforeseen reason the self-test function (lowest priority in the instrument logic) stops running, that failure also will be detected automatically. To provide further assurance that the self-test function continues to operate, a step will be included in the APRM Channel Check surveillance to confirm that self-test is still running.

10

0000-0101-7647-R3 Section No. Utility Action Required Response 8.3.4.3.4 APRM-Related RPS Trip Functions - Channel Calibrations a) Replace current calibration interval with a) The proposed Technical Specification and either 18 or 24 months except for APRM Bases changes related to Channel Inop. Retain Inop requirement as is (i.e., no Calibration for the APRM Functions requirement for calibration). include a 24-month interval, with no calibration required for the Inop Function, consistent with the PRNM LTR.

b) Delete any requirement for flow calibration b) Consistent with the PRNM LTR and calibration of the 6 second time requirements, the proposed Technical constant separate from overall calibration of Specification and Bases changes add a the APRM Simulated Thermal Power notation applicable to the Channel Upscale Trip. Calibration for the APRM Simulated Thermal Power - High and OPRM Upscale Functions to include requirements for calibration of the recirculation flow transmitter and flow processing function.

However, the PRNM LTR includes this notation only in the Bases. For the CGS Technical Specification, the notation has been included in the Channel Calibration SR (Table 3.3.1.1-1), and has been expanded from that in the LTR to also apply to the OPRM Upscale Function (to cover OPRM Upscale trip enable).

c) Replace every 3 day frequency for c) The current CGS Technical Specifications calibration of APRM power against thermal include a "weekly" frequency for the power with a 7 day frequency if applicable. verification of APRM power versus calculated plant thermal power so no change in that frequency is required to be consistent with the PRNM LTR.

d) The proposed Technical Specification Bases d) Revise Bases text as required.

changes related to Channel Calibrations are consistent with the PRNM LTR.

+ t 8.3.4.4.4 APRM-Related RPS Trip Functions - Response The proposed Technical Specification and Bases Time Testing changes related to Response Time Testing (3.3.1.1.15 and Table 3.3.1.1-1) are consistent Delete response time testing requirement from with the justification in the PRNM LTR Technical Specifications or plant procedures, as Supplement 1.

applicable, for the APRM functions. Replace it Consistent with the PRNM LTRs, the only with a response time testing requirement for the APRM Function to which the SR will apply is 2-out-of-4 Voter "pseudo" function, to include Function 2.e (voter). However, while the the output solid-state relays of the voter channel PRNM LTRs justified reduced response time through the final RPS trip channel contactors. testing frequency for Function 2.e, no technical specification markups were included to Frequency of response time testing shall be implement an "n" greater than 4 (the total determined using four 2-out-of-4 Voter number of voter channels). Therefore, a note is channels, but tests may alternate use of 2-out-of- added to the CGS SR 3.3.1.1.15 to define that 4 Voter outputs provided each APRM/RPS "n=8" for Function 2.e.

interfacing relay is tested at least once per eight refueling cycles (based on a maximum 24 month The PRNM LTR Supplement 1 justified cycle), and each RPS scram contactor is tested at response time testing at a rate that tested one II

0000-0101-7647-R3 Section No. Utility Action Required Response least once per four refueling cycles. Each 2-out- RPS Interface relay every plant operating cycle, of-4 Voter output shall be tested at no less than with tests using the APRM output for one cycle half the frequency of the tests of the APRM/RPS and the OPRM output for the next cycle. This interface relays. Tests shall alternate such that yields a testing rate once per 8 operating cycles one logic train for each RPS trip system is tested for each RPS interface relay and once per every every two cycles. 16 operating cycles for the APRM or OPRM output.

The PRNM modification includes redundant APRM trip and redundant OPRM trip outputs from each 2-Out-Of-4 Voter channel. One of the OPRM outputs and one of the APRM outputs are connected in series to the coil of one RPS interface relay. The second OPRM output and the second APRM output from the 2-Out-Of-4 Voter channel are connected in series with the coil to a second RPS interface relay. There are 8 total RPS interface relays.

8.3.5.4 APRM-Related RPS Trip Functions - Logic System Functional Testing (LSFT) The CGS Technical Specifications include a SR Revise Technical Specifications to change the for LSFTs for the APRM related functions.

interval for LSFT from 18 months to 24 months These will be deleted, except for the new 2-Out-unless the utility elects to retain the 18-month Of-4 Voter, Function 2.e, the LSFT will be interval for plant scheduling purposes. Delete added. The LSFT requirement for that Function any LSFT requirements associated with the is at a 24-month interval.

APRM channels and move it to the 2-out-of-4 Voter channel. Include testing of the 2-out-of-4 voting logic and any existing LSFTs covering RPS relays.

8.3.6.1 APRM-Related RPS Trip Functions - Setpoints Add to or delete from the appropriate document ARTS is applicable at CGS. CGS has any changed RPS setpoint information. If performed setpoint calculations for the ARTS ARTS is being implemented concurrently with submittal. The results of the ARTS calculations the PRNM modification, either include the were used for the PRNM modification. PRNM related Technical Specifications submittal setpoints and Allowable Values are re-calculated information with the PRNM information in the or confirmed using approved setpoint plant-specific submittal, or reference the ARTS methodology. The Allowable Values for the submittal in the PRNM submittal. In theplant- APRM RPS Functions are included in the specific licensingsubmittal, identify what Technical Specifications or the COLR, changes, if any, are being implemented and comparable to what is currently in the CGS identify the basis or method used for the Technical Specifications and consistent with the calculation of setpoints and where the setpoint PRNM LTR.

information or changes will be recorded.

8.4.1.4 OPRM-Related RPS Trip Functions - Functions An OPRM Upscale Function is added to the Covered by Technical Specifications CGS Technical Specification as an "APRM Function" (Function 2.f) consistent with PRNM Add the OPRM Upscale function as an "APRM LTR Supplement 1, Appendix H. Additions to function" in the RPS Instrumentation "function" the Technical Specification Bases for Function table. Also add the related surveillance 2.f have also been incorporated consistent with requirements and, if applicable, the related the PRNM LTR.

setpoint, and the related descriptions in the bases The PRNM LTR Supplement 1 included some sections. Perform analysis necessary to establish setpoints for the OPRM Upscale trip. additional wording for Function 2.e (voter) to 12

0000-0101-7647-R3 Section No. Utility Action Required Response Add discussions related to the OPRM function address independent voting of the OPRM and in the Bases for the APRM Inop and 2-out-of-4 APRM signals Voter functions.

NOTE: The markups in Appendix H of Supplement 1 to the PRNM LTR show the OPRM Upscale as an APRM sub-function.

However, individual plants may determine that for their particular situation, addition of the OPRM to the RPS Instrumentation table separate from the APRM, or as a separate Technical Specification, better meets their needs. In those cases, the basis elements of the Technical Specifications as shown in this Supplement would remain, but the specific I implementation would be different.

8.4.2.4 OPRM-Related RPS Trip Functions - Minimum A minimum operable channels requirement of Number of Operable OPRM Channels three, shared by both trip systems has been included in the Technical Specification for the For the OPRM functions added (Section 8.4.1),

OPRM Upscale Function (Function 2.). This include in the OPRM Technical Specifications a "minimum operable channels" requirement for addition, as well as addition of Required Action statements and Bases descriptions, is consistent three OPRM channels, shared by both trip with the PRNM LTR and LTR Supplement 1.

systems.

Add the same action statements as for the APRM Neutron Flux - High function for OPRM Upscale function. In addition, add a new action statement for OPRM Upscale function unavailable per Paragraph 8.4.2.2 of the PRNM LTR.

Revise the Bases section as needed to add descriptions of the 4-OPRM system with 2-out-of-4 output Voter channels (2 per RPS Trip System), and allowed one OPRM bypass total.

Regarding the initial monitoring period, the The NRC SER states the OPRM function will be GEH NUMAC OPRM system can be installed monitored during the first fuel cycle to ensure and activated immediately without an initial the OPRM algorithms perform according to the monitoring period because: 1) The operating design specifications. During this monitoring experience of the GEH NUMAC OPRM system period the OPRM trip capabilities would be in general is sufficient, 2) The GEH NUMAC disabled. Upon completion of this initial OPRM system is replacing the current Option III monitoring period, the OPRM trip function OPRM system, and 3) The data received during would be enabled. the initial monitoring period for the currently "armed" and operating digital OPRM system demonstrated that the algorithm was robust and not sensitive to system settings within the range of values described in NEDO-32465-A.

8.4.3.4 OPRM-Related RPS Trip Functions - A Modes of Operation requirement consistent I Applicable Modes of Operation Jwith the PRNM LTR Supplement I has been 13

0000-0101-7647-R3 Section No. Utility Action Required Response included in the Technical Specification along Add the requirement for operation of the OPRM with associated Bases descriptions.

Upscale function in Mode 1 (RUN) when The OPRM operability value has been selected Thermal Power is > 25% RTP, and add Bases to provide the same margin (5%) between the descriptions as required. OPERABILITY requirement and the auto-enable setpoint (see response to 8.4.6.1 below) as the margin included in the PRNM LTR.

The OPRM operable and enabled values are core specific, the actual values used can be the ones specified in the cycle specific COLR.

8.4.4.1.4 OPRM-Related RPS Trip Functions - Channel Check A Channel Check requirement of once per 12 Add once per 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or once per day Channel hours is included for the OPRM Upscale Check or Instrument Check requirements for the Function, consistent with the PRNM LTR OPRM Upscale function. Supplement 1.

8.4.4.2.4 OPRM-Related RPS Trip Functions - Channel Functional Test Add Channel Functional Test requirements with A Channel Functional Test requirement with a a requirement for a test frequency of every 184 test frequency of every 184 days (Table 3.3.1.1-days (6 months), including the 2-out-of-4 Voter 1) has been added as SR 3.3.1.1.16 for the function. OPRM Upscale and 2-Out-Of 4 Voter Functions consistent with the PRNM LTR, Supplement 1.

Note, SR 3.3.1.3 has been removed, including the previously existing OPRM instrumentation section. A second note to SR 3.3.1.1.16 (not included in the PRNM LTR) is included to clarify that the SR also applies to the flow input function, except the transmitters.

Add a "confirm auto-enable region" surveillance on a once per outage basis up to 24 month A "confirm auto-enable region" surveillance intervals.

requirement 3.3.1.1.17, Table 3.3.1.1-1, is added to require confirmation that the OPRM Upscale trip output auto-enable (not bypassed) setpoints remain correct. The SR Bases wording is consistent with the LTR.

The sample Technical Specifications in the LTR include the generic 30% power, and 60% flow values for the auto-enable setpoints as well as the 25% OPRM operable value. The reload stability analysis includes a confirmation that the auto-enable region bounds the part of the power flow map where the plant may be susceptible to an instability event. If this confirmation is not successful, the region boundaries will have to be expanded for that cycle. Similar to the other cycle specific values referenced in the Technical Specifications, the flow and power values defining the auto-enable region boundaries, and 14

0000-0101-7647-R3 Section No. Utility Action Required Response the OPRM operable region are specified in COLR. These values are referenced in the Technical Specifications. Note that the cycle specific auto-enable region boundaries are at least as large as the generic auto-enable region boundaries.

8.4.4.3.4 OPRM-Related RPS Trip Functions - Channel Calibration Add calibration interval requirement of every 24 A Channel Calibration requirement for the months for the OPRM Upscale function. OPRM Upscale Function references the existing 24-month frequency of SR 3.3.1.1.10 PRNM Revise Bases text as required. LTR Supplement 1.

8.4.4.4.4 OPRM-Related RPS Trip Functions - Response Time Testing Modify as necessary the response time testing See response to 8.3.4.4.4. That response also procedure for the 2-out-of-4 Voter function to addresses OPRM. Current CGS Technical include the Voter OPRM output solid-state Specification SR 3.3.1.1.15 is modified to relays as part of the response time tests, address response time testing for APRM and alternating testing of the Voter OPRM output OPRM.

with the Voter APRM output.

8.4.5.4 OPRM-Related RPS Trip Functions - Logic The LSFT (Table 3.3.1.1-1) for the OPRM System Functional Testing (LSFT) Upscale Function is the same as for the APRM, a test of the 2-Out-Of-4 Voter only. Consistent Add requirement for LSFT every refueling with the PRNM LTR Supplement 1, the only cycle, 18 or 24 months at the utility's option change required to implement the OPRM based on which best fits plant scheduling. "LSFT" is the addition of "and OPRM" in the Technical Specification Bases and revision of the related plant procedures to include testing of the OPRM Upscale trip outputs from the 2-Out-Of-4 Voter. The procedure changes will be made as part of the normal modification process.

8.4.6.1 OPRM-Related RPS Trip Functions - Setpoints There are four "sets" of OPRM related setpoints and adjustable parameters: a) OPRM trip auto-Add setpoint information to the appropriate enable (not bypassed) setpoints for STP and document and identify in the plant-specific drive flow; b) period based detection algorithm submittal the basis or method used for the (PBDA) confirmation count and amplitude calculation and where the setpoint information setpoints; c) period based detection algorithm will be recorded. tuning parameters; and d) growth rate algorithm (GRA) and amplitude based algorithm (ABA) setpoints.

The first set, the setpoints for the "auto-enable" region for OPRM, discussed in the Bases for Function 2.f, will be treated as nominal setpoints 15

0000-0101-7647-R3 Section No. Utility Action Required Response with no additional margins added. The deadband for these setpoints is established so that it increases the enabled region once the enabled region is entered. The settings are specified in the COLR from the plant procedures.

The second set, the PBDA trip setpoints, will be established in accordance with the BWROG LTR 32465-A methodology, previously reviewed and approved by the NRC, and will be documented in the COLR.

The third set, the PBDA "tuning" parameter values, will be established in accordance with and controlled by CGS procedures, within the limits established in the BWROG LTRs, or as documented in this submittal.

The fourth set, the GRA and ABA setpoints, consistent with the BWROG submittals, will be established as nominal values only, and controlled by CGS procedures.

8.5.1.4 APRM-Related Control Rod Block Functions - ARTS will be implemented concurrently with Functions Covered by Technical Specifications the PRNM modification at CGS.

If ARTS will be implemented concurrently with CGS Technical Specifications currently do not the PRNM modification, include or reference contain any APRM rod block functions. These those changes in the plant-specificPRNM have been moved to the CGS LCS.

submittal. Implement the applicable portion of the above described changes via modifications to the Technical Specifications and related procedures and documents. In the plant-specific submittal, identify functions currently in the plant Technical Specifications and which, if any, changes are being implemented. For any functions deleted from Technical Specifications, identify where setpoint and surveillance requirements will be documented. NOTE: A utility may choose not to delete some or all of the items identified in the PRNM LTR from the plant Technical Specifications.

8.5.2.4 APRM-Related Control Rod Block Functions - See 8.5.1.4 above. No additional confirmation Minimum Number of Operable Control Rod of action required relative to minimum operable Block Channels channels as shown in the Technical Change the minimum number of APRM Specifications beyond that required by 8.5.1.4 channels to three, if APRM functions are above.

retained in Technical Specifications. No additional action is required relative to minimum The APRM rod block functions are listed in the operable channels beyond that required by LCS. In the LCS, the minimum number of Paragraph 8.5.1.4 of the PRNM LTR. APRM channels is four and will be changed to three.

16

0000-0101-7647-R3 Section No. Utility Action Required Response 8.5.3.4 APRM-Related Control Rod Block Functions - See 8.5.1.4 above. No additional confirmation Applicable Modes of Operation of action required relative to applicable modes No action required relative to modes during of operation as shown in the Technical which the function must be available beyond Specifications beyond that required by 8.5.1.4 that required by Paragraph 8.5.1.4 of the PRNM above.

LTR unless APRM functions are retained in The APRM rod block functions are listed in the Technical Specifications and include operability LCS. There are no operability requirements in requirements for Mode 5. In that case, delete Mode 5 for the APRM rod block functions in the such requirements. LCS, consistent with the PRNM LTRs.

8.5.4.1.4 APRM-Related Control Rod Block Functions - CGS Technical Specifications currently do not Required Surveillances and Calibration - contain any APRM rod block functions, or any Channel Check Channel Check requirements for the RBM rod Delete any requirements for instrument or block functions. Therefore, no change to CGS channel checks related to RBM and, where Technical Specifications is required to applicable, recirculation flow rod block implement the PRNM LTR requirements.

functions (non-ARTS plants), and APRM The LCS currently includes no Channel Check functions. Identify in the plant-specific PRNM requirements for the APRM rod block functions.

submittals if any checks are currently included in Technical Specifications, and confirm that they are being deleted.

8.5.4.2.4 APRM-Related Control Rod Block Functions - CGS Technical Specifications currently do not Required Surveillances and Calibration - contain any APRM rod block functions. The Channel Functional Test Channel Functional Test frequency for the Change Channel Functional Test requirements APRM rod block functions is changed to once to identify a frequency of every 184-days (6 per 184 days in the LCS.

months).

In the plant-specific licensingsubmittal, identify current Technical Specification test frequencies that will be changed to 184 days (6 months).

8.5.4.3.4 APRM-Related Control Rod Block Functions - CGS Technical Specifications currently do not Required Surveillances and Calibration - contain any APRM rod block functions. The Channel Calibrations Channel Calibration frequency for the APRM Change channel calibration requirements to rod block functions is once per 184 days, which identify a frequency of every 24 months. In the is changed to 18 months per the LTR.

plant-specifc licensingsubmittal, identify current Technical Specification test frequencies that will be changed to 24 months.

8.5.4.4.4 APRM-Related Control Rod Block Functions - CGS Technical Specifications currently do not Required Surveillances and Calibration - contain any APRM rod block functions.

Response Time Testing Response time testing is not required for these None. functions per the CGS licensing basis.

8.5.5.4 APRM-Related Control Rod Block Functions - CGS Technical Specifications currently do not Required Surveillances and Calibration - Logic contain any APRM rod block functions. Logic System Functional Testing (LSFT) System Functional testing is currently included None. in the LCS at a frequency of 24 months.

8.5.6.1 APRM-Related Control Rod Block Functions - ARTS will be implemented concurrently with Required Surveillances and Calibration - the PRNM modification at CGS.

Setpoints APRM rod block setpoints are based on setpoint Add to or delete from the appropriate document calculations using approved setpoint any changed control rod block setpoint methodology. The actual Allowable Values and information. If ARTS is being implemented setpoints are defined in the LCS. Setpoint 17

0000-0101-7647-R3 Section No. Utility Action Required Response concurrently with the PRNM modification, changes (if any) that will be implemented due to either include the related Technical ARTS/PRNM submittal will be identified.

Specifications submittal information with the PRNM information in the plant-specific submittal, or reference the ARTS submittal in the PRNM submittal. In the plant-specific submittal, identify what changes, if any, are being implemented and identify the basis or method used for calculation of setpoints and where the setpoint information or changes will be recorded.

8.6.2 Shutdown Margin Testing - Refueling Added function 2.e to SR 3.10.8.1. Technical As applicable, revise the Shutdown Margin Specification or Technical Specification Bases Testing - Refueling (or equivalent Technical changes to Specification 3.10.8, Shutdown Specifications) LCO(s), action statements, Margin (SDM) Test - Refueling and its surveillance requirements and Bases as required associated bases were modified consistent with to be consistent with the APRM Technical the APRM Technical Specification changes Specification changes implemented for PRNM. implemented for PRNM.

None Core Operating Limits Report Specification 5.6.3 has been modified to require that the Period Based Detection Algorithm Reporting requirements Section 5.6.3 does not (PBDA) setpoints be included in the COLR to currently address the OPRM. support LCO 3.3.1.1.

9.1.3 Utility Quality Assurance Program Quality assurance requirements for work performed at CGS are defined and described in As part of the plant-specific licensingsubmittal, Energy Northwest "Operational Quality the utility should document the established Assurance Program Description (EN-QA-004)"

program that is applicable to the project (OQAPD), LDN-OQAPD-OQAPD-01.

modification. The submittal should also document for the project what scope is being Note: The OQAPD applies to all activities performed by the utility and what scope is being associated with structures, systems, and supplied by others. For scope supplied by components, which are safety related or others, document the utility actions taken or controlled by 10 CFR 72. The OQAPD also planned to define or establish requirements for applies to transportation packages controlled by the project, to assure those requirements are 10 CFR 71. The OQAPD implements compatible with the plant-specific configuration. 10 CFR 50 Appendix B, 10 CFR 71 Subpart H, Actions taken or planned by the utility to assure and 10 CFR 72 Subpart G. It is implemented by compatibility of the GEH-I quality program with site procedures and instructions.

the utility program should also be documented.

For the PRNM modification, CGS has Utility planned level of participation in the contracted with GEH to include the following overall V&V process for the project should be PRNM scope: 1) design, 2) hardware/ software, documented, along with utility plans for 3) licensing support, 4) training, 5) O&M software configuration management and manuals and design documentation, 6) EMI/RFI provision to support any required changes after qualification of equipment, and 7) PRNMS delivery should be documented. setpoint calculations.

On-site engineering work to incorporate the GEH-provided design information into an Engineering Change (EC) or to provide any supporting, interface design changes will be performed per requirements of applicable CGS 18

0000-0101-7647-R3 Section No. Utility Action Required Response procedures. Modification work to implement the design change will be performed per CGS procedures or CGS-approved contractor procedures. CGS has participated and will continue to participate in appropriate reviews of GEH's design and V&V program for the PRNM modification.

For software delivered in the form of hardware (EPROMs), CGS intends to have GEH maintain post delivery configuration control of the actual source code and handle any changes. CGS will handle any changes in the EPROMs as hardware changes under its applicable hardware modification procedures.

19

0000-0101-7647-R3 Enclosure 1 Columbia NUMAC PRNM LTR Deviations A-i

0000-0101-7647-R3 Columbia NUMAC PRNM LTR Deviations Energy Northwest will be submitting a license application for the implementation of Power Range Neutron Monitor (PRNM) using the Long Term Stability Solution Option III at the Columbia Generating Station. The bases for the license application are the referenced documents in the relevant licensing topical reports (References 1-3).

The PRNM developed for Columbia has three (3) deviations from the referenced documents.

They are summarized in Table 1 and discussed in detail below. The licensing topical reports explicitly allow for plant-to-plant variation of some features. These plant-to-plant variations are not addressed herein, just the one deviation.

Table 1. Columbia NUMAC PRNM LTR Deviations

, ,,,,:Function/ PRNM ,Licensing:, *;I,; i,',i: * ,

"unctin/ PRM Licnsing Columbia Design Justifications, Equipment Basis

a. APRM Upscale / OPRM Upscale OPRM Upscale Improved OPRM Upscale / function voted function voted operating APRM Inop separately from the with the APRM flexibility Function Logic APRM Inop function Inop function
b. Time to Total time to PRNM takes 300 Inconsequential Calculate Flow- calculate STP Trip ms, but the flow biased Trip Setpoint, including transmitter alone Setpoint sensor processing, is may take over 600 600 ins after change Ms.

to flow C. Abnormal Any missing module Any missing Not required by Conditions in a chassis causes an module in a Technical Leading to INOP Trip. chassis causes an Specifications Inoperative alarm but not Status necessarily a trip.

References

1. NEDC-3241OP-A Volume 1, "Nuclear Measurement Analysis and Control Power Range Neutron Monitor (NUMAC PRNM) Retrofit Plus Option III Stability Trip Function,"

October, 1995.

2. NEDC-32410P-A Volume 2 -- Appendices, "Nuclear Measurement Analysis and Control Power Range Neutron Monitor (NUMAC PRNM) Retrofit Plus Option III Stability Trip Function," October, 1995.
3. NEDC-32410P-A Supplement 1, "Nuclear Measurement Analysis and Control Power Range Neutron Monitor (NUMAC PRNM) Retrofit Plus Option III Stability Trip Function,"

November, 1997.

A-2

0000-0101-7647-R3

a. APRM Upscale / OPRM Upscale / APRM Inop Function Logic Licensing Topical Report NEDC-32410P-A Supplement I (Reference 3) Section 8.4.1.3 describes the logic wherein the OPRM Upscale function is voted separately from the APRM Inop function. That is, an APRM Inop in one APRM channel and an OPRM Upscale in another will result in two half-trips in each of the 2-out-of-4 voter channels, but no RPS trips.

Designed this way, when an APRM chassis keylock switch is placed in the "INOP" position, the APRM upscale trip signal sent to the 2-out-of-4 voter channels is set to trip. However, the OPRM trip output from that chassis continues to be processed normally. Typically this logic is of no consequence because if an APRM chassis (affecting both the APRM and OPRM channels) is declared inoperable, the APRM bypass can be used to bypass both the APRM and OPRM trips from that channel, which in turn modifies the logic in the 2-out-of-4 voter to be a 2-out-of-3 vote of both the APRM and OPRM trips from the remaining 3 channels. However, if the need to declare a second APRM/OPRM channel inoperable arises when another APRM/OPRM channel is already bypassed (and cannot be returned to service within the allowed out of service time), it is necessary to place the APRM and OPRM outputs from the second channel in the tripped condition to satisfy Technical Specification requirements. If the APRM channel is still sufficiently functional to process trip outputs, placing the keylock switch in the INOP position will force a trip for the APRM channel, but not for the OPRM channel. Other action, such as disconnecting a fiber-optic cable to the 2-out-of-4 voters or removing power from the APRM chassis, is necessary to satisfy the requirement to place the OPRM channel in the tripped condition.

The automatic APRM Inop trip is intended to provide a trip when the APRM channel is known to be incapable of providing a trip based on normal functions. This trip occurs immediately even though the Technical Specification requirements allow a period of time for action. The automatic trip is provided to assure that conditions that may disable the APRM trip function do not go undetected. Since the OPRM trip function is implemented in the same equipment as the APRM trip function, conditions that could disable the APRM trip function would likely disable the OPRM trip function as well.

For the Columbia PRNM, the OPRM Upscale function is combined with the APRM Inop function as the OPRM channel input to be voted. That is, an APRM Inop in one APRM channel and an OPRM Upscale in another will result in RPS trip outputs from all four 2-out-of-4 voter channels. Again this logic is typically of no consequence because if an APRM chassis (affecting both the APRM and OPRM channels) is declared inoperable, the APRM bypass can be used to bypass both the APRM and OPRM trips from that channel, which in turn modifies the logic in the 2-out-of-4 voter to be a 2-out-of-3 vote of both the APRM and OPRM trips from the remaining 3 channels. This design allows using the APRM chassis keylock switch to place APRM and OPRM outputs from a second channel in the tripped condition when another APRM/OPRM channel is already bypassed (and cannot be returned to service within the allowed out of service time) without having to resort to other actions such as disconnecting a fiber-optic cable to the 2-out-of-4 voters or removing power from the APRM chassis.

A-3

0000-0101-7647-R3 For the Columbia PRNM, the Supplement 1 (Reference 3) Bases are changed as follows.

1. Page H-12: change the second paragraph as shown below.

The APRM System is divided into four APRM channels and four 2-out-of-4 voter channels. Each APRM channel provides inputs to each of the four voter channels. The four voter channels are divided into two groups of two each, with each group of two providing inputs to one RPS trip system. The system is designed to allow one APRM channel, but no voter channels, to be bypassed. A trip from any one unbypassed APRM will result in a "half-trip" in all four of the voter channels, but no trip inputs to either RPS trip system. APRM trip -unctians 2.a, 2-ban.n , and 2.@1 arc iatad indapandantly trm r1 Upzala 2ucio

.f. Tharafar, an Puntian 2~a r L.e. ar-2.1 trip t any- twe udnbya...d APRMl channeal will reate in- a full trip inaazl at tal focur vofta ehannall, which in turn raeuita in twe trip input9 inRta cachl RPS tri4p System lagic ch~annal!

(Al, A2, Bl, and B2) . S-1 _Imiarly, a Funtian L2f trip tiram aytaunbm acc APPJI channalas will3 racsult iafultptrm eachat ha au vtr channals. Three of the four APRM channels and all four of the voter channels are required to be OPERABLE to ensure that no single failure will preclude a scram on a valid signal. In addition, to provide adequate coverage of the entire core, consistent with the design bases for the APRM Functions 2.a, 2.b, and 2.c, at least [20] LPRM inputs, with at least [three] LPRM inputs from each of the four axial levels at which the LPRMs are located, must be operable for each APRM channel.

For the OPRM Upscale, Function 2.f, LPRMs are assigned to "cells" of [4] detectors. A minimum of

[later] cells, each with a minimum of [2] LPRMs, must be OPERABLE for the OPRM Upscale Function 2.f to be OPERABLE.

Replaced deleted text with the following:

Since APRM trip Functions 2.a, 2.b, 2.c and 2.f are implemented in the same hardware, these trip Functions are combined with APRM Inop trip Function 2.d. Any Function 2.a, 2.b, 2.c or 2.d trip from any two unbypassed APRM channels will result in a full trip in each of the four voter channels, which in turn results in two trip inputs into each RPS trip system logic channel (Al, A2, B1, and B2). Similarly, any Function 2.d or 2.f trip from any two unbypassed APRM channels will result in a full trip from each of the four voter channels.

A-4

0000-0101-7647-R3

2. Page H-13: For Function 2.e, change the 1st sentence of the 3rd paragraph to the following. "The 2-Out-Of-4 Voter Function votes APRM Functions 2.a, 2.b, and 2.c independently of Function 2.f."
b. Time to Calculate Flow-biased Trip Setpoint Licensing Topical Report NEDC-32410P-A Volume 1 (Reference 1) Section 3.3.2 describes the processing time for calculating flow-biased setpoints as follows.

The Average Power Range Monitor (APRM) Simulated Thermal Power (STP) high trip is the only trip function with a setpoint that is calculated based on recirculation flow. ((

)) The flow transmitters, which are unaffected by a PRNM retrofit, also perform signal processing and their filters have time constants that are adjustable from 0.2 and 2 seconds. Allowing 5 constants to settle on a new value, the response time for the transmitters takes between 1 and 10 seconds. Thus, the response of the recirculation flow system alone exceeds what is described in Reference 1. When combined with the PRNM response, the total time could be as high as just over 10 seconds. For the reasons discussed below, this is inconsequential.

Most importantly, the Safety Analysis does not take credit for the STP high trip in any of the design basis events. Therefore, the conclusions of the Safety Analysis are not called into question in any way.

The Safety Analysis mentions the flow-biased STP trip in the context of protection against transients such as the Loss of Feedwater Heating where therinalpower increasesslowly. In this type of scenario, the thermal power and flow rates change gradually, over tens of seconds. Even if the longest setpoint calculation time is assumed, the setpoint will track closely with the ideal value (i.e., the value based on actual flow rate). Furthermore, when the initial condition is at or near rated power, the STP trip setpoint does not even vary with flow because it is clamped.

In summary, due to processing in the recirculation flow transmitters, the time for the recirculation flow system to calculate the APRM STP trip setpoint is longer than what is stated in Reference 1. However, the performance does not present any safety risks, and is acceptable.

A-5

0000-0101-7647-113

c. Abnormal Conditions Leading to Inoperative Status The way the system is designed meets the Technical Specification Requirements. Specifically, if the channel is found to be inoperative, a limiting condition for operation (LCO) exists, and the Technical Specifications allow time to correct the problem or to place the channel in INOP.

Therefore, it is not necessary to cause an immediate, automatic trip if a module is determined to be missing from the chassis. ((

1]

Reference 1 Section 3.2.10.1 discusses the purpose of the APRM INOP trip, and provides insight. Quoting in part from that section, ((

))

If the system were designed as described in Reference 1 Section 5.3.8.2 and ((

)) This is well beyond the intent of the APRM INOP trip, and is not required by the Technical Specifications. Similar reasoning applies to the RBM. Therefore, the present design is acceptable.

A-6