ML090720892
ML090720892 | |
Person / Time | |
---|---|
Site: | Columbia ![]() |
Issue date: | 02/27/2009 |
From: | Energy Northwest |
To: | Office of Nuclear Reactor Regulation |
References | |
GO2-09-043 | |
Download: ML090720892 (50) | |
Text
ý AffNORTýý Z5ý T Columbia Generating Station Radioactive Effluent Release Report January through December 2008 m- m.R'
REFERENCES:
10 CFR 50.36a(a)(2) 10 CFR 72.44(d)(3)
CGS Technical Specification
5.6.2 ISFSI
Technical Specification 5.4.c Columbia Generating Station Radioactive Effluent Release Report January through December 2008 Energy Northwest Submitted February 2009 Table of Contents
1.0 INTRODUCTION
....................................................................................
1 2.0 LIQUID EFFLUENTS
..............................................................................
1 3.0 GASEOUS EFFLUENTS
......................................................................
1 Gaseous Effluent Tables ........................................................................
4 Table 3-0 10 CFR Part 50 Appendix I Dose Compliance
.............
4 Table 3-1 Main Plant Vent Releases..............................
5 Table 3-2 Turbine Building Releases ..............................................
7 Table 3-3 Radwaste Building Releases ..........................
9 Table 3-4 Summation of Releases ...............................................
11 Table 3-5 Gaseous Purges and Vents .........................................
12 Table 3-6 Lower Limits of Detection
.................................
13 4.0 SOLID RADW ASTE ..............................................................................
14 Solid Radwaste Information required by the Offsite Dose Calculation Manual. 14 C lass A ..............................................
..........................
.........
14 C lass B ....................................................................................
..15 C lass C .......................................
............................................
15 Solid Radwaste Information required by NRC Regulatory Guide 1.21 ...........
16 Solid waste shipped offsite for burial or disposal (not irradiated fuel) .........
16 Irradiated Fuel Shipments (Disposition)
............................................
18 5.0 METEOROLOGICAL DATA ...............................................................
19 Joint Frequency Distribution Tables for 2008 .........................................
20 Table 5-1 1st Quarter Average, 33 Ft Above Ground Level (AGL) ..........
20 Table 5-2 1st Quarter Average, 245 Ft AGL .......................................
22 Table 5-3 2nd Quarter Average, 33 Ft AGL ...................................
24 Table 5-4 2nd Quarter Average, 245 Ft AGL ...................................
26 Table 5-5 3rd Quarter Average, 33 Ft AGL ......................
28 Table 5-6 3rd Quarter Average, 245 Ft AGL .......................................
30 Table 5-7 4th Quarter Average, 33 Ft AGL ......................
32 Table 5-8 4th Quarter Average, 245 Ft AGL .....................
34 Table 5-9 Year 2008, 33 Ft AGL ..............................
36 Table 5-10 Year 2008, 245 Ft AGL ..................................................
38 Columbia Generating Station i 2008 Radioactive Effluent Report 6.0 DOSE ASSESSMENT
-- IMPACT ON MAN .....................
40 Dose Tables ...................................................................................
42 Table 6-1 Summary of Doses from Gaseous Effluents
......................
42 Table 6-2 50-Mile Population Dose from Gaseous Effluents
...............
45 7.0 REVISIONS TO THE ODCM .................................................................
46 8.0 REVISIONS TO THE PROCESS CONTROL PROGRAM (PCP) ..........
46 9.0 NEW OR DELETED LOCATIONS FOR DOSE ASSESSMENTS AND/OR ENVIRONMENTAL MONITORING LOCATIONS
..................
46 10.0 MAJOR CHANGES TO RADIOACTIVE LIQUID, GASEOUS, AND SOLID WASTE TREATMENT SYSTEMS .............................................
46 Columbia Generating Station ii 2008 Radioactive Effluent Report
1.0 Introduction
This report has been prepared in compliance with 10 CFR 50.36a(a)(2), 10 CFR 72.44(d)(3), Independent Spent Fuel Storage Installation (ISFSI) Technical Specification 5.4.c, and Columbia Generating Station Technical Specification 5.6.2.It includes a summary of the quantities of radioactive liquid and gaseous effluents and solid radwaste released from Columbia Generating Station during calendar year 2008. Effluent data is summarized on a quarterly basis.2.0 Liquid Effluents No planned releases of contaminated liquids from the liquid radwaste processing system were discharged to the Columbia River from Columbia Generating Station during calendar year 2008. The last planned discharge took place in 1998. There were no known releases of liquid effluents to ground or groundwater.
3.0 Gaseous
Effluents The gaseous radwaste effluents from Columbia Generating Station were released from three (3) release points: Main Plant Vent-- mixed mode release Turbine Building -- ground level release Radwaste Building -- ground level release The gaseous source terms from each release point are listed in Tables 3-1, 3-2, and 3-3. The activation gas argon-41 is included in these tables under fission gases to allow a match with the fission and activation gas totals of Table 3-4. Table 3-4 provides a summation of the total activity released, the average release rate, gross alpha radioactivity, and the estimated total error associated with the measurements of radioactivity in the gaseous effluents.
Radioactivity measurements for gaseous effluent releases are performed for fission and activation gases by collecting the samples in a Marinelli beaker and analyzing them using gamma spectroscopy.
Air is analyzed for tritium by collection of water vapor on a desiccant with subsequent distillation and liquid scintillation counting.Particulates and iodines are sampled continuously and the sample media (particulate filters and charcoal cartridges) are analyzed weekly using gamma spectroscopy.
Each quarter a chemical separation process is used to isolate strontium from the composite particulate filters and quantification is accomplished with liquid scintillation detection.
The average energy per disintegration of fission and activation gases is not included in this report as it is not required by Technical Specifications and is not used for gaseous effluent release rate limit calculations.
When a radioisotope is not positively identified at levels greater than the Minimum Detectable Activity (MDA), a value of zero is used for release concentrations and offsite dose assessments.
Table 3-6 contains the Lower Limit of Detection (LLD)values corresponding to the sampling methods and analytical instruments used for each principal radioisotope.
Columbia Generating Station 1 2008 Radioactive Effluent Report Dose calculations were performed for releases using the NRC GASPAR II computer program and parameters as defined in the Offsite Dose Calculation Manual (ODCM). Desert sigmas were not used in gaseous plume growth calculations.
Throughout this report, the term 'dose' is used as defined in NRC Regulatory Guide 1.109-1977.
Quarterly and annual doses to the potentially highest-exposed Member of the Public at and beyond the site boundary were calculated.
In addition, quarterly and annual doses were calculated at actual resident locations identified in the annual land use census. ODCM limits are based on Part 20 and Appendix I to Part 50 of Title 10 of the Code of Federal Regulations.
The threshold for air dose applies to fission and activation gases and is ten (10)millirad for beta and five (5) millirad for gamma quarterly and twenty (20) millirad for beta and ten (10) millirad for gamma annually.
The threshold for organ dose applies to iodine, tritium, and particulates with half-lives greater than eight days and is seven and a half (7.5) millirem quarterly and fifteen (15) millirem annually.
For fission and activation gases the dose rate limits are less than or equal to 500 mrem per year to the whole body and less than or equal to 3000 mrem per year to the skin. For iodines, particulates, and tritium the dose rate limit is less than or equal to 1500 mrem/year to any organ.Dose calculations were also conducted for Members of the Public within the site boundary.
The results are discussed and tabulated in Section 6.0.The Kootenai building is located approximately 0.75 miles from the Reactor building.
Within this building are the Emergency Operations Facility (EOF) and a backup chemistry laboratory.
During 2005, the laboratory liquid release path was physically blocked and the liquid release monitor deactivated.
The release path for the fume hood within the laboratory contains a high-efficiency particulate air (HEPA) filter and was monitored for radioactive releases even though no radiochemical work was routinely performed in this laboratory.
In August of 2008, the fume hood and heating, ventilation, and air conditioning (HVAC) ducting was surveyed and radiological controls removed. No evidence of gaseous or liquid release of licensed radioactive material was noted in 2008 and no further routine effluent release monitoring is planned.It is estimated that approximately 1.76E-03 Curies of tritium were released through unmonitored vents of the heating steam system within and outside the main power block (Turbine, Radwaste, Reactor, and General Services buildings).
Twelve spent fuel storage containers (SFSC) were added to the ISFSI facility in calendar year 2008 (between February and May). A total of twenty seven (27)SFSCs were in place in the ISFSI facility at the end of 2008. The SFSCs are performing as designed; consequently, there are no effluents from this facility.Columbia Generating Station 2 2008 Radioactive Effluent Report In July, a Seal Steam relief valve lifted for 4.7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> before being reseated and resulted in 0.0239 Curies of activity being released to the atmosphere.
This amounted to 0.05% of the quarterly releases and 0.02% of the activity released during the year.There were no incidents of effluent monitor inoperability greater than 30 days.Columbia Generating Station 3 2008 Radioactive Effluent Report Columbia Generating Station 3 2008 Radioactive Effluent Report ý Gaseous Effluent Tables Table 3-0 10 CFR Part 50 Appendix I Dose Compliance Report Period: January -- December 2008 I 1st Quarter 12nd Quarter 3rd Quarter I4th Quarter I Year* I Noble Gas Gamma Air Dose (mrad) 1.52E-03 1.41E-03 2.31E-03 2.59E-03 7.46E-03 ODCM Limit 5 5 5 5 10% of Limit 3.04E-02 2.82E-02 4.62E-02 5.18E-02 7.46E-02 Beta Air Dose (mrad) 5.35E-04 4.98E-04 9.64E-04 9.14E-04 2.78E-03 ODCM Limit 10 10 10 10 20% of Limit 5.35E-03 4.98E-03 9.64E-03 9.14E-03 1.39E-02 Iodine-131, Iodine-133, Tritium, and Particulates with half-lives greater than eight days.Organ Dose (mrem) 2.54E-03 2.46E-03 7.02E-03 6.05E-03 1.44E-02 ODCM Limit 7.5 7.5 7.5 7.5 15% of Limit 3.39E-02 3.27E-02 9.36E-02 8.07E-02 9.61E-02* Calculated quarterly doses cannot be directly compared to the annual doses.Each above listed quarterly dose is the highest calculated dose based on a number of variables.
Variables that make comparison difficult include location, meteorological data (quarterly joint frequency distribution (JFD) tables vs. annual JFD tables), receptor age, target organ, and characteristics of the emitted radionuclides.
Columbia Generating Station 4 2008 Radioactive Effluent Report Table 3-1 Main Plant Vent Releases Fission Gases and lodines Report Period: January -- December 2008________ I (Cn) arde Q4th j (i Quarter Quarter Quarter Quarter Year Nuclides Released (Ci) (Ci) (Ci) (Ci) (Ci)A. Fission gases krypton- 85 <MDA <MDA <MDA <MDA <MDA krypton-85m
<MDA <MDA <MDA <MDA <MDA krypton-87
<MDA <MDA <MDA <MDA <MDA krypton-88
<MDA <MDA <MDA <MDA <MDA xenon-133
<MDA <MDA <MDA <MDA <MDA xenon- 133m <MDA <MDA <MDA <MDA <MDA xenon- 135 <MDA <MDA 8.80E+00 <MDA 8.80E+00 xenon- 135m <MDA <MDA <MDA <MDA <MDA xenon-138
<MDA <MDA <MDA <MDA <MDA Others argon-41 1.47E+01 1.33E+01 2.43E+01 3.03E+01 8.25E+01 Total for period* 1.47E+01 1.33E+01 3.31E+01 3.03E+01 9.13E+01 B. lodines iodine-131
<MDA <MDA 4.80E-06 <MDA 4.80E-06 iodine-132
<MDA' <MDA <MDA <MDA <MDA iodine-133
<MDA <MDA <MDA <MDA <MDA iodine-134
<MDA <MDA <MDA <MDA <MDA iodine-135
<MDA <MDA <MDA <MDA <MDA Total for period
- O.OOE+00 O.OOE+00 4.80E-06 O.OOE+00 4.80E-06 MDA = Less than the "a posteriori" minimal detectable activity (microcuries per unit mass or volume).* MDA values are not included in the totals.Columbia Generating Station 5 2008 Radioactive Effluent Report Table 3-1 Main Plant Vent Releases (Continued)
Particulates and Tritium Report Period: January--
December 2008 _ _ 4th.1 st 2nd 3rd 4th Quarter Quarter Quarter Quarter Year Nuclides Released (Ci) (Ci) (Ci) (Ci) (Ci)C. Particulates
_ ....strontium-89 5.81E-07 6.51E-07 1.32E-06 1.12E-06 3.67E-06 strontium-90
<MDA <MDA <MDA <MDA <MDA cesium-134
<MDA <MDA <MDA <MDA <MDA cesium-137
<MDA <MDA <MDA <MDA <MDA barium-lanthanum-140
<MDA <MDA <MDA <MDA <MDA silver- 110m <MDA <MDA <MDA <MDA <MDA cerium-141
<MDA <MDA <MDA <MDA <MDA cerium-144
<MDA <MDA <MDA <MDA <MDA cobalt-58
<MDA 2.78E-06 1.29E-05 3.40E-06 1.90E-05 cobalt-60
<MDA 1.1 IE-05 1.49E-05 6.6 1E-06 3.26E-05 iron-59 <MDA <MDA <MDA <MDA <MDA manganese-54
<MDA <MDA 1.OOE-06 <MDA 1.OOE-06 zinc-65 <MDA 7.60E-06 2.57E-05 1.30E-05 4.63E-05 chrome-51
<MDA <MDA <MDA <MDA <MDA antimony-125
<MDA <MDA <MDA <MDA <MDA Total for period* 5.81E-07 2.21E-05 5.58E-05 2.41E-05 1.03E-04 Others with T 1/2 < 8 days arsenic-76
<MDA <MDA <MDA <MDA <MDA bromine-82
<MDA <MDA <MDA <MDA <MDA copper-64
<MDA <MDA <MDA <MDA <MDA molybdenum-99
<MDA' <MDA <MDA <MDA <MDA rhenium-188
<MDA <MDA <MDA <MDA <MDA sodium-24
<MDA <MDA <MDA <MDA <MDA technetium-99m
<MDA 9.01E-05 6.39E-04 2.34E-04 9.63E-04 zinc-69m <MDA <MDA <MDA <MDA <MDA Total with T 1/2 < 8 days* O.OOE+00 9.01E-05 6.39E-04 2.3 4E-04 9.63E-04 D. Tritium I tritium 6.99E-01 I 6.35E-01I 5.76E-01 5.49E-01 12.46E+001 MDA = Less than the "a posteriori" minimal detectable activity (microcuries per unit mass or volume).* MDA values are not included in the totals.Columbia Generating Station 6 2008 Radioactive Effluent Report Table 3-2 Turbine Building Releases Fission Gases and lodines Report Period: January -- December 2008 1 1st 2nd 3rd 4th [Quarter Quarter Quarter Quarter Year Nuclides Released (Ci) (Ci) (Ci) (Ci) j (Ci)A. Fission gases krypton-85
<MDA <MDA <MDA <MDA <MDA krypton-85m
<MDA <MDA <MDA <MDA <MDA krypton-87
<MDA <MDA. <MDA <MDA <MDA krypton-88
<MDA <MDA <MDA <MDA <MDA xenon-133
<MDA <MDA <MDA <MDA <MDA xenon- 133m <MDA <MDA <MDA <MDA <MDA xenon-135
<MDA <MDA <MDA <MDA <MDA xenon- 135m <MDA <MDA <MDA <MDA <MDA xenon-138
<MDA <MDA <MDA <MDA <MDA Others argon-41 <MDA <MDA <MDA <MDA <MDA Total for period
- 0.OOE+00 0.OOE+00 O.OOE+00 O.OOE+00 0.OOE+00 B. lodines iodine-131 3.99E-05 7.75E-05 1.91E-04 8.13E-05 3.89E-04 iodine-132
<MDA <MDA <MDA <MDA <MDA iodine-133 2.07E-04 3.66E-04 1.09E-03 4.41E-04 2.1OE-03 iodine-134
<MDA <MDA <MDA <MDA <MDA iodine-135
<MDA <MDA <MDA <MDA <MDA Total for period
- 2.47E-04 4.43E-04 1.28E-03 5.23E-04 2.49E-03 MDA = Less than the "a posteriori" minimal detectable activity mass or volume).(microcuries per unit* MDA values are not included in the totals.Columbia Generating Station 7 2008 Radioactive Effluent Report Table 3-2 Turbine Building Releases (Continued)
Particulates and Tritium Report Period: January--
December 2008 1st 2nd 3rd 4th Quarter Quarter Quarter Quarter Year Nuclides Released (Ci) (Ci) (Ci) (Ci) (Ci)C. Particulates strontium-89 1.75E-05 1.71E-05 3.06E-05 2.52E-05 9.04E&05 strontium-90
<MDA <MDA <MDA <MDA <MDA cesium- 134 <MDA <MDA <MDA <MDA <MDA cesium-137
<MDA <MDA <MDA <MDA <MDA barium-lanthanum-140 <MDA <MDA <MDA <MDA <MDA cerium-141
<MDA <MDA <MDA <MDA <MDA cerium-144
<MDA <MDA <MDA <MDA <MDA cobalt-58
<MDA <MDA <MDA <MDA <MDA cobalt-60 1.36E-05 2.72E-05 1.49E-04 2.83E-05 2.19E-04 iron-59 <MDA <MDA <MDA <MDA <MDA manganese-54
<MDA <MDA <MDA <MDA <MDA zinc-65 <MDA 5.OOE-05 1.18E-04 1.84E-05 1.87E-04 chrome-51
<MDA <MDA <MDA <MDA <MDA Total for period* 3.1 1E-05 9.43E-05 2.99E-04 7.19E-05 4.96E-04 Others withT 1/2.< 8 days molybdenum-99
<MDA <MDA <MDA <MDA <MDA Total with T 1/2 < 8 days* 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.00E+0O0 D. Tritium tritium 6.05E+00 I 5.87E+00 9.65E+00 I 9.21E+00 1 3.08E+01 MDA = Less than the "a posteriori" minimal detectable activity (microcuries per unit mass or volume).* MDA values are not included in the totals.Columbia Generating Station 8 2008 Radioactive Effluent Report Table 3-3 Radwaste Building Releases Fission Gases and lodines Report Period: January -- December 2008 I 1st 2nd 3rd 4th__ _ Quarter Quarter Quarter Quarter Year Nuclides Released (Ci) (Ci) (Ci) (Ci) (Ci)A. Fission gases krypton-85
<MDA <MDA <MDA <MDA <MDA krypton-85m
<MDA <MDA <MDA <MDA <MDA krypton-87
<MDA <MDA <MDA <MDA <MDA krypton- 88 <MDA <MDA <MDA <MDA <MDA xenon-133
<MDA <MDA <MDA <MDA <MDA xenon- 133m <MDA <MDA <MDA <MDA <MDA xenon-135
<MDA <MDA <MDA <MDA <MDA xenon- 135m <MDA <MDA <MDA <MDA <MDA xenon-138
<MDA <MDA <MDA <MDA <MDA Others argon-41 <MDA <MDA <MDA <MDA <MDA Total for period
- 0.OOE+00 O.OOE+00 0.OOE+00 O.OOE+00 O.OOE+00 B. lodines iodine-131
<MDA <MDA <MDA <MDA <MDA iodine-132
<MDA <MDA <MDA <MDA <MDA iodine-133
<MDA <MDA <MDA <MDA <MDA iodine-134
<MDA <MDA <MDA <MDA <MDA iodine-135
<MDA <MDA <MDA <MDA <MDA Total for period* O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 MDA = Less than the "a posteriori" minimal detectable activity mass or volume).(microcuries per unit* MDA values are not included in the totals.Columbia Generating Station 9 2008 Radioactive Effluent Report Table 3-3 Radwaste Building Releases (Continued)
Particulates and Tritium Report Period: January -- December 2008 I1st T 2nd Q 3rd 4th Quarter Quarter Quarter Quarte Year Nuclides Released .(Ci) (Ci) (Ci) (Ci) 1 (Ci)C. Particulates strontium-89 2.95E-08 6.80E-07 <MDA 1.31E-06 2.02E-06 strontium-90 1.54E-08 <MDA <MDA <MDA 1.54E-08 cesium-134
<MDA <MDA <MDA <MDA <MDA cesium-137
<MDA <MDA <MDA <MDA <MDA barium-lanthanum-140 <MDA <MDA <MDA <MDA <MDA cerium-141
<MDA <MDA <MDA <MDA <MDA cerium-144
<MDA <MDA <MDA <MDA <MDA cobalt-58
<MDA <MDA <MDA <MDA <MDA cobalt-60
<MDA <MDA <MDA 5.99E-07 5.99E-07 iron-59 <MDA <MDA <MDA <MDA <MDA manganese-54
<MDA <MDA <MDA <MDA <MDA zinc-65 <MDA <MDA <MDA <MDA <MDA Total for period* 4.49E-08 6.80E-07 0.OOE+00 1.91E-06 2.63E-06 Others with T 1/2 < 8 days molybdenum-99
<MDA <MDA <MDA <MDA <MDA Total with T 1/2 < 8 days* 0.00E+00 0.00E+00 0.00E+00 0.OOE+00 0.00E+00 D. Tritium I tritium I 2.39E-01 3.53E-01 I 8.50E-01 1.33E-01 1.58E+001 MDA = Less than the "a posteriori" minimal detectable activity (microcuries per unit mass or volume).* MDA values are not included in the totals.Columbia Generating Station 10 2008 Radioactive Effluent Report Table 3-4 Summation of Releases Gaseous Effluents Report Period: January -- December 2008-I I St l 1st 2nd 3rd 4th Total Quarter Quarter Quarter Quarter Year %Error A. Fission and activation gases Total release (Ci) 1.47E+01 1.33E+01 3.31 E+01 3.03E+01 9.13E+01 4.20E+01 Average release rate (pCi/s) 1.87E+00 1.69E+00 4.20E+00 3.85E+00 2.90E+00 Percent of ODCM limit (%)I 5.95E-04 4.78E-04 9.96E-04 1.98E-03 9.48E-04 B. lodines Total 1-131 (Ci) 3.99E-05 7.75E-05 1.95E-04 8.13E-05 3.94E-04 4.60E+01 Average release rate (pCi/s) 5.08E-06 9.85E-06 2.49E-05 1.03E-05 1.25E-05 Percent of ODCM limit (%) 5.03E-05 3.99E-05 1.16E-04 1.43E-04 1.03E-04 C. Particulates Particulates with half-lives
>8 days (Ci) 3.17E-05 1.17E-04 3.54E-04 9.79E-05 6.01E-04 4.50E+01 Average release rate (pCi/s) 4.03E-06 1.49E-05 4.51E-05 1.25E-05 1.91E-05 Percent of ODCM limit (%) 1.06E-05 9.13E-06 4.72E-05 3.09E-05 3.20E-05 Gross alpha radioactivity (Ci)l 8.23E-07 1.89E-05 1.16E-06 1.47E-06 2.23E-05 7.30E+01 D. Tritium Total release (Ci) 6.99E+00 I 6.86E+00 11.11 E+01 9.89E+00 3.48E+01 2.50E+01 Average release rate (pCi/s)I 8.89E-01 I 8.73E-01 11.41 E+00 1 1.26E+00 1.11E+00 Percent of ODCM limit (%) I 3.95E-04 I1.32E-04 I 2.53E-04 I 6.50E-04 3.38E-04 MDA = Less than the "a posteriori" minimal detectable activity (microcuries per unit mass or volume).ODCM release rate limits are based on dose rate. For fission and activation gases the dose rate limits are less than or equal to 500 mrem/year to the whole body and less than or equal to 3000 mrem/year to the skin. For 1-131, particulates, and tritium the dose rate limit is less than or equal to 1500 mrem/year to any organ.The ODCM dose factors and the highest site boundary dispersion value for each period were used in the calculation.
- Measurement errors are sample-specific.
The values reported represent an approximate overall error. The major contributors of this error are measurements associated with sample volume and release point flow rates and estimates of plateout factors.Columbia Generating Station 11 2008 Radioactive Effluent Report Table 3-5 Gaseous Purges and Vents Report Period: January -- December 2008 Columbia Generating Station is a continuous release plant. All purges and vents are discharged through the Standby Gas Treatment System and released through the reactor building stack that is sampled and continuously monitored for radioactive gaseous waste.Columbia Generating Station 12 2008 Radioactive Effluent Report Table 3-6 Lower Limits of Detection Gaseous Effluents Report Period: January--
December 2008 Fission Gases Required LLD T Achieved Analysis Nuclide (pCi/cc) LLD (pCi/cc)krypton-87 1.OOE-04 1.05E-08 krypton-88 1.OOE-04 1.29E-08 xenon-133 1.OOE-04 1.OOE-08 xenon-133m 1.OOE-04 3.25E-08 xenon-135 1.OOE-04 3.77E-09 xenon-138 1.OOE-04 4.48E-08 Iodines iodine-131 1OOE-12 6.04E- 14 iodine-133 1.OOE-10 1.28E- 12 Particulates strontium-89 1.OOE- 11 1. 16E- 14 strontium-90 1.OOE- 11 5.12E- 15 cesium-134 1.OOE-11 5.11E- 14 cesium-137 1.OOE-11 4.70E- 14 molybdenum-99 1.OOE-1 1 9.12E- 13 cerium-141 1.OOE-11 4.88E- 14 cerium-144 1.OOE- 11 1.97E- 13 cobalt-58 1.OOE- 11 4.44E- 14 cobalt-60 1.OOE- 11 7.86E- 14 iron-59 1.OOE-11 1.07E- 13 mangaiese-54 1.O0E-11 4.56E- 14 zinc-65 1.OOE-11 1.01E-13 Gross Alpha 1.OOE-11 9.01E-16 Tritium hydrogen-3 1 .OOE-06 5.85E- 11 t From ODCM Table 6.2.2.1-1 Columbia Generating Station 13 2008 Radioactive Effluent Report Columbia Generating Station 13 2008 Radioactive Effluent Report
4.0 Solid
Radwaste This section of the annual effluent report provides information required by both the Columbia Generating Station Offsite Dose Calculation Manual and by Nuclear Regulatory Commission Regulatory Guide 1.21-1974.
Solid Radwaste Information required by the Offsite Dose Calculation Manual January -- December 2008 Class A 1. Container Volumes 5 GAL PAIL 1 ft3 16 GAL DRUM 2.23 ft3 8 GAL DRUM 1.6 ft3 30 GAL DRUM 4.0 ft3 55 GAL DRUM 7.5 ft3 B-25 Steel Box 96 ft3 B-88 Steel Box 109 ft3 EL-142 Polyethylene HIC 132.4 ft3 B-25 Overpack Steel Box 138 ft3 ES-1 90 Steel Liner 170.2 ft3 EL-190 Polyethylene HIC 174.3 ft3 2. Total Curies 8.03E+02 Ci 3. Principal Radionuclides Fe-55 1.33E+02 1.66E+01 Mn-54 4.03E+01 5.02E+00 Co-58 2.35E+01 2.93E+00 Ni-63 i 1.23E+01 1.53E+00 Cr-51 1.17E+01 1.46E+00 Ag-i 1 Om 3.96E+00 4.93E-01 Fe-59 1.25E+00 1.56E-01 C-14 1.23E+00 1.53E-01 Columbia Generating Station 14 2008 Radioactive Effluent Report Cs-137 9.38E-01 1.17E-01 Ni-59 5.75E-01 7.16E-02 Nb-95 3.13E-01 3.90E-02 Sr-89 2.43E-01 3.03E-02 Zr-95 2.40E-01 2.99E-02.H-3 1.01 E-01 1.25E-02 Co-57 6.57E-02 8.18E-03 Sb-1 25 3.70E-02 4.61 E-03 La-1 40 3.24E-02 4.03E-03 4. Source Resins DAW Irradiated Components Other (Sealed Source & Mixed Waste)8.02E+02 Ci 1.77E+00 Ci 0.00E+00 Ci 1.02E-04 Ci 5. Type of Container All containers shipped as Limited Quantity, LSA, SCO or Radioactive material in IP-1, IP-2, Type A or Type B (including casks) as appropriate.
- 6. Solidification Agent None Class B There were no Class B shipments made during calendar year 2008.Class C There were no Class C shipments made during calendar year 2008.Columbia Generating Station 15 2008 Radioactive Effluent Report Solid Radwaste Information required by NRC Regulatory Guide 1.21 January -- December 2008 Solid waste shipped offsite for burial or disposal (not irradiated fuel).1. Type of Waste Annual Est. Total Waste Stream Unit Cumulative Error %a. Spent. resins, filter sludge, m 1.31 E+02 evaporator bottoms, etc. Ci 8.02E+02 2.5E+01 %b. Dry Active Waste my 7.74E+01 Ci 1.77E+00 2.5E+01%c. Irradiated Components m 0.OOE+00 Ci 0.OOE+00 None d. Other Waste (Sealed Source & m 3.07E+00 mixed waste) Ci 1.02E-04 2.5E+01 %2. Estimate of major nuclide composition (by type of waste)a.Co-60 3.27E+02 4.08E+01 Zn-65 2.45E+02 3.06E+01 Fe-55 1.33E+02 1.66E+01 Mn-54 4.03E+01 5.03E+00 Co-58 2.33E+01 2.91 E+00 Ni-63 1.23E+01 1.53E+00 Cr-51 1.14E+01 1.42E+00 Ag-110m 3.95E+00 4.93E-01 Fe-59 1.25E+00 1.55E-01 C-14 1.23E+00 1.54E-01 Cs-137 9.18E-01 1.14E-01 Ni-59 5.72E-01 7.13E-02 Nb-95 2.99E-01 3.73E-02 Sr-89 2.38E-01 2.96E-02 Zr-95 2.26E-01 2.82E-02 H-3 1.OOE-01 1.25E-02 Co-57 6.57E-02 8.19E-03 La-1 40 3.24E-02 4.04E-03 Columbia Generating Station 16 2008 Radioactive Effluent Report b.Co-60 5.83E-01 3.29E+01 Zn-65 4.76E-01 2.69E+01 Cr-51 3.07E-01 1.73E+01 Co-58 2.32E-01 1.31 E+01 Mn-54 4.98E-02 2.81 E+00 Fe-55 3.33E-02 1.88E+00 Cs-137 1.95E-02 1.1OE+00 Nb-95 1.41 E-02 7.98E-01 Zr-95 1.40E-02 7.90E-01 Sb-125 1.27E-02 7.19E-01 Ni-63 1.07E-02 6.01 E-01 Ag-11Om 6.66E-03 3.76E-01 Sr-89 5.06E-03 2.86E-01 Sb-1 24 4.47E-03 2.52E-01 Ni-59 2.90E-03 1.64E-01 H-3 6.81 E-04 3.84E-02 C-14 2.92E-04 1.65E-02 Sr-90 1.14E-04 6.41 E-03 Irradiated Components None Other Waste Sealed Source & Mixed Waste)Co-60 9.67E-05 9.50E+01 Zn-65 2.60E-06 2.55E+00 Mn-54 1.1OE-06 1.08E+00 Cs-137. 8.22E-07 8.07E-01 Ra-226 3.73E-07 3.66E-01 Co-58 1.18E-07 1.15E-01 Sb-125 1.13E-07 1.11E-01 Na-24 2.51 E-10 2.47E-04 C.d.Columbia Generating Station 17 2008 Radioactive Effluent Report
- 3. Solid Waste Disposition Number of Shipments Mode of TransDortation Destination 19 3*Tractor -Trailer via Public Highway Tractor -Trailer via Public Highway Tractor -Trailer via Public Highway US Ecology, Inc.P.O. Box 638 Hanford Reservation Richland, WA. 99352 Perma-Fix Northwest 2025 Battelle Blvd.Richland, WA 99354 Perma-Fix of Florida 1940 N.W. 67th PI Gainesville, FL 32653 2*(* After processing portions of this shipment may be forwarded for disposal.)
Irradiated Fuel Shipments (Disposition)
Number of Shipments None Mode of Transportation N/A Destination N/A Columbia Generating Station 18 2008 Radioactive Effluent Report Columbia Generating Station 18 2008 Radioactive Effluent Report
5.0 Meteorological
Data The meteorological data contained in Tables 5-1 through 5-10 was obtained from the meteorological tower located 2500 feet (762 m) west of Columbia Generating Station. Data was recovered from instruments at the 33-foot (10 meter) and 245-foot (75 meter) levels. The meteorological data is a composite file generated from the automated data recovery systems for the calendar year 2008. Data is archived on the Energy Northwest Local Area Network.Joint data recovery for 2008 was 98.7% from the 33-foot level and 99.1% from the 245-foot level. Redundant wind and temperature sensors are installed at both levels of the meteorological tower. Data from the two systems is mixed to permit maximum data recovery for defined date ranges.The data in Tables 5-1 through 5-8 lists the joint frequency distributions at the 33-foot and 245-foot levels by quarter for 2008. These tables show the total hours at various wind speeds for each sector and stability class. The NRC stability classes A through G and eleven wind speed categories along with the 16 wind direction sectors were used to prepare each joint frequency table. Table 5-9 and 5-10 list the annual joint frequency distributions for those levels for 2008.Wind speed is measured in miles per hour in the following tables and speeds below 1.00 MPH were recorded as calms.Atmospheric factors which affect dispersion and deposition of gaseous effluents as measured on the Hanford Site were snow (30.6 inches total which fell in January, February, and December), total precipitation (5.49 inches), dust or blowing dust (3 days), fog (39 days), and thunderstorms (6 days). No atmospheric smoke was noted on the Hanford Site in'2008.Columbia Generating Station 19 2008 Radioactive Effluent Report Joint Frequency Distribution Tables for 2008 Table 5-1 1st Quarter Average, 33 Ft Above Ground Level (AGL)Joint Frequency Distribution (version 4.0)Sensor Criteria Time Frame Data Recovery Rate Wind Speed: 33 Foot Sensors Startng Date: 111/08 Maximum Hours In Period: 2184 Wind Direction:33 Foot Sensors Ending Date: 3/311/08 Flours Missing: 27 DeltaT: 245 Foot -33 Foot Sensors Flours Used: 2157 Signal Path: Mixed-bba Recovery Rate: 98.8%0 Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 45 6.7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22.4 29.1 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW INW TOTAL 1 2.2 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 2.2 4.5 0 -0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 45 6.7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 134 17.9 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 2 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 2'29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 0 1 0 0 0 0 0 0 0 0 1 3 0 0 0 0 5 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 2 2.2 4.5 3 2 2 0 0 0 0 0 0 0 0 0 0 0 0 0 7 4.5 6.7 5 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 6.7 8.9 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 8.9 11.2 1 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 1 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 0 2 1 1 0 0 0 0 4.17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 1 0 1 2 0 4 22.4 29.1 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 4 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 10 4 3 0 0 0 0 0 0 2 5 3 0 1 2 1 31 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 6 5 6 5 0 0 2 1 2 2 3 3 3 8 5 9 60 2.2 4.5 25 14 7 7 0 1 1 2 12 11 8 8 6 3 9 23 137 45 6.7 14 11 5 0 0 1 1 14 11 15 4 4 4 4 13 13 114 6.7 8.9 3 2 0 .0 0 0 0 7 12 10 3 2 2 7 4 12 64 8.9 11.2 2 2 0 0 0 0 1 3 16 10 4 3 0 5 3 3 52 11.2 13.4 0 1 0 0 0 0 0 2 6 10 11 2 0 3 0 0 35 13.4 17.9 0 6 0 0 0 0 0 0 6 22 19 5. 3 4 4 3 72 17.9 22.4 1 3 0 0 0 0 0 1 0 2 11 3 0 0 3 0 24 224 29.1 0 0 0 0 0 0 0 0 0 1 1 2 2 0 0 0 6 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 1 4 0 0 0 5 4(.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 51 44 18 12 0 2 5 30 65 83 64 33 24 34 41 63 569 Columbia Generating Station 20 2008 Radioactive Effluent Report Table 5-1 Is' Quarter Average, 33 Ft AGL (Continued)
Wmd Speed STABILITY CLASS: E Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 3 3 3 1 3 '2 3 3 1 2 3 6 5 8 3 12 61 2.2 4.5 16 14 7 6 2 1 2 4 14 6 6 7 10 9 23 19 146 4&5 6.7 5 10 1 1 0 1 6 10 22 8 7 3 5 6 26 11 122 6.7 8.9 2 0 3 0 0 0 4 8 24 14 14 3 3 3 15 12 105&.9 11.2 1 2 0 0 0 0 3 6 11 12 11 0 5 0 9 1 61 11.2 13.4 1 1 0 0 0 0 0 12 7 19 12 5 4 5 3 1 70 13.4 17.9 1 5 0 0 0 0 0 2 7 22 23 4 2 4 6 0 76 17.9 22.4 1 6 0 0 0 0 0 0 3 17 5 7 7 0 0 0 46 22.4 29.1 0 0 0 0 0. 0 0 0 1 4 3 1 0 0 0 0 9 29.1 40.3 0 0 0 0 0 0 0 0 0 1 0 2 1 0 0 0 4 4(13 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 30 41 14 8 5 4 18 45 9D 105 84 38 42 35 85 56 700 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 11 4 10 2 1 1 1 3 5 9 6 4 5 8 9 9 88 2.2 4.5 28 22 11 2 1 0 0 7 7 10 12 4 12 12 9 39 176 45 6.7 6 4 7 1 0 0 1 8 11 12 3 4 5 4 13 20 99 6.7 8.9 0 1 1 0 0 0 3 14 19 6 5 2 4 1 8 5 69 8.9 11.2 0 0 0 0 0 0 0 4 5 0 4 1 2 2 1 1 20 11.2 13.4 0 0 0 0 0 0 0 1 4 4 3 0 0 0 0 0 12 13.4 17.9 0 0 0 0 0 0 0 1 3 8 1 0 1 0 1 0 15 17.9 22.4 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4M.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 45 31 29 5 2 1 5 38 55 49 34 15 29 27 41 74 480 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 10 5 9 2 0 0 0 1 4 2 0 2 3 6 5 4 53 2,2 4.5 15 6 12 0 0 0 0 1 11 10 2 1 4 3 8 22 95 45 6.7 6 0 3 0 0 0 0 4 13 3 2 0 1 5 3 14 54 6.7 8.9 0 0 1 0 0 0 0 4 9 0 3 0 0 0 1 0 18 8.9 11.2 0 1 1 0 0 0 0 4 2 0 0 0 1 0 0 0 9 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 31 12 26 2 0 0 0 14 40 15 7 3 9 14 17 40 230 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 30 18 29 10 4 3 6 8 12 15 12 15 16 30 22 35 265 2.2 4.5 87 58 39 15 3 2 3 14 44 37 28 20 32 27 49 103 561 4,5 6.7 36 26 16 2 0 2 8 36 57 38 16 11 15 19 55 58 395 U.7 8.9 6 4 5 0 0 0 7 33 64 30 25 7 9 11 28 29 258 8.9 11.2 4 5 1 0 0 0 4 17 34 22 19 4 8 7 13 5 143 11.2 13.4 1 2 0 0 0 0 0 15 17 33 26 7 4 8 3 1 117 13.4 17.9 1 11 0 0 0 0 0 3 17 54 45 11 6 .8 11 3 170 17.9 22.4 2 9 0 0 0 0 0 1 4 19 16 11 7 1 5 0 75 22.4 29.1 0 0 0 0 0 0 0 0 1 5 8 5 2 0 0 0 21 29,1 40.3 0 0 0 0 0 0 0 0 0 1 0 4 5 *0 0 0 10 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 167 133 90 27 7 7 28 127 250 254 195 95 104 111 186 234 2015 A B C D E F G TOTALS CALM 0 0 0 35 29 51 27 142 Columbia Generating Station 21 2008 Radioactive Effluent Report Table 5-2 1st Quarter Average, 245 Ft AGL Joint Frequency Distribution
(%ersion 4.0)Sensor Criteria rime Frame Data Recovery Rate Wind Speed: 245 Foot Sensors Starting Date: 1/1/08 Maximum Hours In Period: 2184 Wind Direction:
245 Foot Sensors Ending Date: 3/31108 Hours Missing: 27 Delta T: 245 Foot- 33 Foot Sensors Hours Used: 2157 Signal Path: Mixed Recovery Rate: 9118%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4.5 6.7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22A 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 4.5 6.7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13A 17.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17.9 22.4 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 .2 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 0 0 0 1 0 0 0 0 0 0 1 3 0 0 0 0 5 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 1 0 1 1 2 0 2 0 0 0 0 0 0 0 0 0 7 4.5 6.7 0 0 0 1 0 0 1 0 0 0 1 0 0 0 0 0 3 6.7 8.9 1 0 1 1 0 0 0 0 0 1 0 1 0 0 0 0 5 8.9 11.2 0 1 0 0 0 0 0 1 0 1 0 0 0 0 0 0 3 11.2 13A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 2 17.9 22.4 0 0 0 0 0 0 0 0 0 0 1 1 0 0 3 0 5 22.4 29.1 0 0 0 0 0 0 0 0 0 0 2 1 0 0 0 0 3 29.1 40.3 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 2 40.3 90 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 TOTALS 2 1 2 3 2 0 3 1 0 4 6 4 0 0 3 0 31 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 1 3 1 0 2 4 3 5 1 4 3 3 2 2 5 40 2.2 4.5 9 11 6 7 3 1 6 4 10 7 6 8 5 4 8 10 105 4.5 6.7 11 15 4 5 1 2 2 7 9 12 15 7 6 4 7 13 120 6.7 8.9 7 4 5 0 0 0 0 9 9 14 5 4 7 3 4 9 80 8.9 11.2 3 3 0 0 0 0 0 5 5 10 4 2 3 4 5 6 50 11.2 13.4 1 2 0 0 0 0 0 2 9 9 5 4 2 3 4 1 42 13A 17.9 0 4 0 0 0 0 0 2 6 22 23 2 2 6 3 0 70 17.9 22.4 0 1 0 0 0 0 0 0 1 8 17 4 1 4 2 0 38 22A 29.1 0 4 1 0 0 0 0 0 1 2 14 5 1 0 5 0 33 29.1 40.3 0 0 0 0 0 0 0 0 0 0 2 2 4 0 0 0 8 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 2 TOTALS 32 45 19 13 4 5 12 32 55 85 95 41 36 30 40 44 588 Columbia Generating Station 22 2008 Radioactive Effluent Report Table 5-2 1st Quarter Average, 245 Ft AGL (Continued)
Wind Speed Min Max N 1 2.2 1 2.2 4.5 6 4.5 6.7 6 6.7 8.9 4 8.9 11.2 2 11.2 13.4 2 13.4 17.9 1 17.9 22.4 1 22.4 29.1 0 29.1 40.3 0 40.3 90 0 TOTALS 23 STABILITY CLASS: E NNE NE ENE 1 2 3 8 3 3 9 7 1 5 4 0 2 2 0 0 2 1 2 0 0 4 1 0 9 3 0 0 0 *0 0 0 0 40 24 8 E 0 9 0 0 0 0 0 0 0 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0 4 0 2 0 0 2 1 0 3 1 20 7 5 5 3 2 6 8 2 4 11 7 89 2 2 2 8 3 4 5 2 6 10 6 74 1 1 8 11 13 5 4 4 2 15 15 92 0 4 3 8 11 7 3 2 4 16 15 80 0 3 3 5 12 6 4 6 1 12 8 65 0 0 2 18 30 27 8 3 1 12 6 110 0 0 2 5 10 37 10 3 4 11 2 90 0 0 0 2 7 26 8 6 4 4 0 69 0 0 0 2 5 10 5 7 0 0 0 29 0 0 0 0 1 0 0 2 0 0 0 3 10 19 25 64 94 128 57 38 26 94 60 721 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE 1 2.2 2 3 1 2 2.2 4.5 4 8 4 10 4.5 6.7 10 9 16 9 6.7 8.9 11 8 16 3 8.9 11.2 3 1 6 2 11.2 13.4 3 0 1 1 13.4 17.9 1 0 0 0 17.9 22.4 0 0 0 0 22.4 29.1 0 0 0 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 34 29 44 27 E 2 4 3 0 0 0 0 0 0 0 0 9 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 1 1 4 4 0 1 1 2 0 1 26 6 5 11 9 11 7 5 8 5 5 3 105 1 4 7 9 5 5 6 4 2 5 8 103 0 0 6 14 6 7 3 3 2 6 11 96 0 2 7 11 7 3 6 0 6 5 6 65 0 1 1 3 6 3 1 1 0 9 .16 46 0 0 1 5 9 9 3 1 12 4 7 52 0 0 0 1 8 4 1 1 5 3 0 23 0 0 0 0 3 6 1 1 0 1 0 12 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 8 13 34 56 59 45 27 20 34 38 52 529 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 0 3 0 3 2 2 3 1 2 1 1 2 1 0 2 24 2.2 4.5 2 2 1 4 6 1 4 11 3 6 2 5 7 3 1 2 60 4.5 6.7 2 4 5 3 2 0 2 6 7 6 4 3 1 1 2 1 49 6.7 8.9 2 1 4 1 0 1 0 6 6 2 6 1 0 0 1 10 41 8.9 11.2 2 0 1 1 0 0 0 1 6 4 4 0 1 1 2 6 29 11.2 13.4 0 Or 0 1 0 0 0 4 2 2 3 2 0 2 3 6 25 13.4 17.9 0 0 1 0 0 0 0 2 4 2 1 0 0 2 5 2 19.17.9 22.4 0 0 0 0 0 0 0 0 0 1 0 0 0 3 0 0 4 22.4 29.1 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 9 7 15 10 11 4 8 33 29 26 21 12 11 13 14 29 252 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 5 5 9 6 5 5 11 7 12 7 5 7 7 5 5 9 110 2.2 4.5 22 29 15 26 24 15 22 31 25 26 21 26 .22 16 25 22 367 4.5 6.7 29 37 32 19 7 5 11 22 33 26 29 21 13 13 24 28 349 6.7 8.9 25 18 30 5 0 2 1 29 40 36 23 13 14 7 26 45 314 8.9 11.2 10 7 9 3 1 0 6 17 30 33 18 11 6 15 28 33 .227 11.2 13.4 6 2 3 3 0 0 4 10 19 29 17 11 9 6 28 31 178 13.4 17.9 2 6 1 0 0 0 0 7 33 65 60 13 6 21 24 15 253 17.9 22.4 1 5 1 0 0 0 0 2 7 27 60 17 5 16 19 2 162 22.4 29.1 0 13 4 0 0 0 0 0 3 13 48 16 8 4 10 0 119 29.1 40.3 0 0 0 0 0 0 0 0 2 5 15 8 11 0 0 0 41 40.3 90 0 0 0 0 0 0 0 0 0 1 0 1 4 0 0 0 6 TOTALS 100 122 104 62 37 27 55 125 204 268 296 144 105 103 189 185 2126 A B C D E F G TOTALS CALM 0 0 0 16 8 2 5 31 Columbia Generating Station 23 2008 Radioactive Effluent Report Table 5-3 2nd Quarter Average, 33 Ft AGL Joint Frequency Distribution (version 40)Sensor Criteria Time Frame Data Recovery Rate Wind Speed: 33 Foot Sensors Startng Date: 411/08 Maximum Hlours In Period: 2184 Wind Direction:33 Foot Sensors Ending Date: 6/30/08 Hours Missing: 75 DdtaT: 245 Foot -33 Foot Sensors Hours Used: 2109 Signal Path: Mixed-aaa Recovery Rate: 96.6%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ,2.2 4.5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4.5 6.7 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 2 6.7 8.9 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 8,9 11.2 2 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 3 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 2 4 0 1 0 0 0 0 .7 17.9 22.4 0 0 0 0 0 0 0 0 1 4 1 1 0 0 4 1 12 22.4 29.1 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 2 29.1 40.3 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 TOTALS 5 0 1 0 0 0 0 0 3 8 3 2 0 0 6 1 29 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 4.5 6.7 2 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 6.7 8.9 3 3 0 0 0 0 0 0 2 0 0 0 0 0 1 1 10 8.9 11.2 3 2 1 1 0 0 0 0 2 4 0 0 1 1 0 0 15 11.2 13.4 0 1 0 0 0 0 0 0 1 .3 0 0 2 0 0 0 7 134 17.9 0 0 0 0 0 0 0 0 4 4 4 2 1 0 3 0 18 17.9 22.4 0 0 0 0 0 0 0 0 0 2 1 3 0 0 2 0 8 22.4 29.1 0 0 0 0 0 0 0 0 0 0 1 1 0 0 3 1 6 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 11 10 1 1 0 0 0 0 9 13 6 6 4 1 9 2 73 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 3 2.2 4.5 4 5 8 1 2 1 *0 0 0 1 1 3 0 1 1 4 32 4.5 6.7 0 6 4 2 0 0 0 0 2 2 5 0 2 1 1 1 26 6.7 8.9 2 3 2 0 0 0 0 1 7 3 3 4 4 2 1 2 34 8.9 11.2 1 2 1 1 0 0 "0 0 5 4 1 4 5 3 1 0 28 11.2 13.4 1 1 0 0 0 0 0 0 3 6 1 2 0 0 3 0 17 13.4 17.9 0 0 0 0 0 0 0 0 1 6 5 4 6 3 3 1 29 17.9 22.4 0 0 0 0 0 0 0 0 0 3 3 5 1 0 4 1 17 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 2 0 0 2 1 5 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 9 17 15 4 2 1 0 1 18 25 19 24 18 11 17 10 191 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 2 3 4 4 2 2 2 2 2 3 2 2 3 2 1 2 38 2.2 4.5 5 10 12 8 7 7 9 20 12 16 8 8 10 6 9 3 150 4.5 6.7 5 9 15 9 7 5 15 35 22 25 10 12 6 8 7 7 197 6.7 8.9 2 7 3 6 0 2 4 18 25 23 8 6 11 3 4 2 125 8.9 11.2 3 2 3 2 1 0 4 7 17 20 7 8 7 4 7 5 97 11.2 13.4 3 2 1 0 0 0 3 2 2 8 4 1 7 3 8 2 46 13.4 17.9 0 1 2 0 0 0 0 0 5 13 14 4 10 7 16 17 89 17.9 22.4 0 0 0 0 0 0 0 0 0 2 2 4 3 1 20 5 37 22.4 29.1 0 0 0 0 0 0 0 0 0 0 *0 1 4 0 8 2 15 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 20 34 40 29 17 16 37 84 86 110 55 46 61 34 81 45 795 Columbia Generating Station 24 2008 Radioactive Effluent Report Table 5-3 2nd Quarter Average, 33 Ft AGL (Continued)
Wind Speed STABILITY CLASS: E Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 0 4 1 0 3 0 4 1 1 1 2 3 1 5 5 32 2.2 4.588 6 2 4 0 3 3 9.10 9 5 5 4 6 12 4 90 45 6.7 4 3 '1 1 0 0 2 5 9 5 7 5 10 7 7 2 68 65.7 8.9 3 3 0 1 0 0 0 7 14 6 8 3 8 7 8 7 75 8.9 11.2 1 0 0 0 0 0 1 6 12 3 2 2 5 14 21 8 75 11.2- 13.4 0 0 1 0 1 0 0 1 8 2 7 3 5 7 18 6 59 13.4 17.9 0 0 0 0 0 0 1 1 1 3 3 6 5 11 22 5 58 17.9 22.4 0 0 0 0 0 0 0 0 0 1 0 1 4 1 6 0 13 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 2 290 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.4a3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 TOTALS 17 12 8 7 1 6 7 33 55 30 33 28 45 54 99 37 472 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NWNNW TOTAL 1 2.2 2 7 1 2 1 0 2 2 2 4 3 2 4 1 3 5 41-2.2 4.5 11 3 3 2 0 1 4 14 12 13 7 5 5 3 5 4 92 45 6.7.2 2 3 1 0 0 1 15 16 13 11 0 5 4 2 7 82 6.7 8.9 1 0 0 2 0 0 1 9 17 2 4 3 1 5 2 2 49 a.9 11.2 0 0 0 0 0 0 2 4 4 3 1 0 0 0 4 0 18 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 4 1a.4 17.9 0 0 0 0 0 0 0 0 0 2 1 0 0 0 0 0 3 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2&1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40L3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 16 12 7 7 1 1 10 44 51 37 27 10 15 17 16 18 289 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW N~W NNW TOTAL 1 2.2 6 8 3 2 0 1 1 5 1 4 4 4 3 3 0 6 51 2.2 4.5 9 14 7 0 0 0 1 9 10 3 3 0 1 0 2 6 65 45 6.7 12 2 9 0 0 0 0 5 6 9 3 0 0 0 2 5 53 6.7 8.9 0 0 3 2 0 0 0 4 10 6 1 0 0 1 1 1 29 8.9 11.2 0 0 0 0 0 0 0 0 1 0 3 0 0 0 1 0 5 11.2 13.4 0 0 0 0 0 0 0 0 1 0 1 0 0 0 0 0 2 1&.4 17.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 211 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 900 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 27 24 22 4 0 1 2 23 29 22 15 4 4 4 6 18 205 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NN*W TOTAL 1 2.2 12 18 12 9 3 6 5 13 6 12 10 10 13 8 10 18 165 2.2 4.5 40 3B 32 15 9 12 17 52 44 42 24 21 20 16 29 21 432 45 6.7 26 26 32 13 7 5 18 60 55 54 36 17 23 20 20 22 434 6.7 8.9 13 16 8 11 0 2 5 39 76 40 24 16 24 18 17 15 324 8.9 11.2 10 6 6 4 1 0 7 17 41 34 14 14 18 22 34 13 241 11.2 13.4 4 4 2 0 1 0 3 3 15 19 13 6 14 14 29 8 135 1&.4 17.9 0 1 2 0 0.0 1 1 13 32 27 17 22 21 44 23 204 17.9 22.4 0 0 0 0 0 0 0 0 1 12 7 14 8 2 36 7 87 22.4 29.1 0 0 0 0 0 0 0 0 0 0 2 5 5 0 14 4 30 2&1 40.3 0 0 0 0 0 0 0 0 0. 0 1 0 0 0 1 0 2 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 105 109 94 52 21 25 56 185 251 245 158 12D 147 121 234 131 2054 A B C D E F G TOTALS CALM 0 0 1 11 12 16 15 55 Columbia Generating Station 25 2008 Radioactive Effluent Report Columbia Generating Station 25 2008 Radioactive Effluent Report Table 5-4 2nd Quarter Average, 245 Ft AGL Joint Frequency Distribution (version 4.0)Sensor Criteria Time Frame Data Recovery Rate Wind Speed: 245 Foot Sensors Starting Date: 4/11/08 Maximum Hours In Period: 2184 Wind Direction:
245 Foot Sensors Ending Date: 6/30/08 Hours Missing: 235 Delta T: 245 Foot -33 Foot Sensors Hours Used: 2149 Signal Path: Mixed Recovery Rate: 98.4%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 4.5 6.7 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 6.7 8.9 0 1 0 0 0 0 0 0 0 0 0 0 0 1 0 1 3 8.9 11.2 2 0 2 0 0 0 0 0 0 0 0 0 0 0 0 0 4 11.2 13.4 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 2 13.4 17.9 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 2 17.9 22.4 0 0 0 0 0 0 0 0 5 0 2 2 0 1 0 0 10 22.4 29.1 0 0 0 0 0 0 0 0 4 1 0 1 0 4 1 1 12 29.1 40.3 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 2 40.3 90 0 0 -0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 2 1 4 0 0 0 0 0 9 2 5 3 0 6 1 3 36 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 1 1 3 0 0 1 0 0 0 0 0 0 0 0 0 1 7 4.5 6.7 0 4 1 3 0 1 0 0 0 0 0 0 0 0 0 1 10 6.7 8.9 4 2 0 0 0 0 0 0 0 1 0 0 0 1 0 0 8 8.9 11.2 2 0 3, 0 0 0 0 0 1 1 1 1 0 1 0 1 11 11.2 13.4 2 0 0 0 0 0 0 0 2 5 1 0 0 0 0 1 11 13.4 17.9 0 1 0 0 0 0 0 0 4 4 2 0 1 0 2 0 14 17.9 22.4 0 0 0 0 0 0 0 0 0 1 1 4 3 1 1 0 11 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 3 0 4 29.1 40.3 0 0 0 0 0 0 0 0 0 0 2 0 0 0 1 0 3 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 9 8 7 3 0 2 0 0 7 12 7 5 .4 4 7 4 79 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 0 2 0 0 0 0 0 0 0 0 0 1 0 1 0 5 2.2 4.5 4 7 1 1 1 0 0 0 0 0 1 1 1 1 2 2 22 4.5 6.7 1 3 1 0 0 0 0 0 0 2 2 1 1 2 0 1 14 6.7 8.9 3 4 2 1 0 0 0 3 4 2 2 1 1 2 2 0 27 8.9 11.2 0 4 2 0 1 0 0 1 6 6 3 0 2 1 0 2 28 11.2 13.4 1 0 1 0 0 0 0 0 1 7 2 2 4 1 0 2 21 13.4 17.9 0 1 0 0 1 0 0 0 4 8 7 4 7 5 3 1 41 17.9 22.4 0 0 0 0 0 0 0 0 0 1 0 5 1 0 1 1 9 22.4 29.1 0 0 0 0 0 0 0 0 1 3 3 2 0 3 3 0 15 29.1 40.3 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 2 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 10 19 9 2 3 0 0 4 16 29 21 16 18 15 13 9 184 Wind Speed .STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 3 2 3 1 4 1 3 2 3 2 2 1 1 0 1 30 2.2 4.5 5 11 5 10 2 11 7 9 11 8 6 6 4 6 4 3 108 4.5 6.7 4 6 10 7 3 5 14 23 15 15 14 8 10 11 6 4 155 6.7 8.9 4 5 8 6 3 7 16 18 23 19 9 13 3 5 6 2 147 8.9 11.2 6 1 3 4 0. 1 8 10 24 21 8 9 9 7 2 2 115 11.2 13.4 1 2 0 1 1 0 3 4 5 14 5 6 4 8 1 1 56 13.4 17.9 3 2 1 0 0 0 3 2 15 7 9 9 8 9 13 3 84 17.9 22.4 0 0 0 0 0 0 0 0 3 6 7 4 5 9 13 1 48 22.4 29.1 0 0 1 0 0 0 0 0 1 2 5 4 6 15 17 2 53 29.1 40.3 0 0 0 0 0 0 0 0 0 0 1 1 2 4 6 0 14 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 24 30 30 31 10 28 52 69 99 95 66 62 52 75 68 19 810 Columbia Generating Station 26 12008 Radioactive Effluent Report Table 5-4 2 nd Quarter Average, 245 Ft AGL (Continued)
Wind Speed Min Max N 1 2.2 3 2.2 4.5 3 4.5 6.7 2 6.7 8.9 0 8.9 11.2 1 11.2 13.4 0 13.4 17.9 1 17.9 22.4 0 22.4 29.1 0 29.1 40.3 0 40.3 90 0 TOTALS 10 Wind Speed Min Max N 1 2.2 0 2.2 4.5 2 4.5 6.7 6 6.7 8.9 2 8.9 11.2 0 11.2 13.4 0 13A 17.9 0 17.9 22.4 0 22.4 29.1 0 29.1 40.3 0 40.3 90 0 TOTALS 10 STABILITY CLASS: E NNE NE ENE 2 0 2 1 2 2 3 2 1 4 1 0 0 2 0 0 0 0 2 0 0 0 1 1 0 0 0 0 0 0 0 0 0 12 8 6 E 0 0 0 0 0 0 0 0 0 2 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 2 0 0 4 0 1 1 1 0 0 2 18 0 2 0 1 3 6 5 6 3 2 2 39 4 2 4 3 6 3 2 3 5 7 5 53 2 1 4 3 2 6 1 6 12 9 2 53 0 1 2 7 5 6 3 6 9 9 2 53 0 1 2 9 4 5 2 4 9 8 2 46 1 1 2 15 6 8 5 4 17 19 7 88 0 0 0 5 2 4 7 9 28 22 3 82 0 0 0 1 3 1 4 7 20 15 0 51 0 0 0 0 0 1 2 0 1 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 9 8 14 48 31 41 32 46 104 91 25 487 STABILITY CLASS: F NNE NE ENE E 0 1 0 0 1 0 4 1 0 3 2 0 1 2 1 0 0 3 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 2 9 7 2 ESE SE SSE 1 2 2 4 7 1 2 4 6 0 3 3 1 3 7 0 1 3 0 5 1 0 0 0 0 0 0 0 0 0 0 0 0 8 25 23 ESE SE SSE 1 1 0 1 1 2 0 2 6 0 4 2 0 0 3 0 1 2 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 2 9 18 S SSW SW WSW W WNW NW NNW TOTAL 2 1 1 3 1 1 2 2 19 3 10 5 5 5 6 2 1 57 5 6 7 7 5 1 1 6 61 8 3 8 3 5 2 7 2 50'9 5 2 2 1 .4 3 5 45 3 4 0 1 2 5 2 3 25 5 4 2 2 3 6 8 0 36 0 0 2 0 1 2 6 0 11 0 1 0 0 0 0 0 0 1"0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 35 34 27 23 23 27 31 19 305 S SSW SW WSW W WNW NW NNW TOTAL 0 1 1 0 1 1 0 1 16 5 8 4 4 2 5 2 4 46 6 6 4 4 2 0 1 3 56 6 6 7 3 1 1 3 5 59 4 3 1 1 0 2 0 1 21 1 1 0 2 1 0 0 1 10 0 0 1 0 0 2 3 3 14 0 0 0 0 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 22 25 18 14 7 11 10 18 223 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE E 1 2.2 3 1 1 3 1 2.2 4.5 1 4 3 0 0 4.5 6.7 7 4 4 2 5 6.7 8.9 4 8 8 1 0 8.9 11.2 2 1 2 1 0 11.2 13A 0 0 0 1 0 13.4 17.9 0 0 0 2 0 17.9 22A 0 0 0 0 0 22.4 29.1 0 0 0 0 0 29.1 40.3 0 0 0 0 0 40.3 90 0 0 0 0 0 TOTALS 17 18 18 10 6 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE 1 2.2 8 6 6 8 2.2 4.5 16 25 14 17 4.5 6.7 20 20 22 15 6.7 8.9 17 25 21 9 8.9 11.2 13 6 17 5 11.2 13.4 4 2 2 2 13.4 17.9 4 6 1 2 17.9 22.4 0 0 1 1 22.4 29.1 0 0 1 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 82 90 85 59 A B C D E CALM 0 0 0 10 4 E 2 5 9 3 1 2 1 0 0 0 0 23 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 8 4 5 8 5 5 6 5 3 3 6 88 17 17 12 20 29 22 21 18 21 12 13 279 12 22 39 29 35 30 22 21 19 15 20 350 9 24 30 44 33 32 21 16 24 27 12 347 2 12 23 51 41 21 16 18 24 14 13 277 0 6 11 21 35 13 13 15 23 11 11 171 1 9 8 43 30 30 20 23 39 48 14 279 0 0 0 13 10 16 22 19 41 44 5 172 0 0 0 7 10 9 11 13 43 39 3 136 0 0 0 0 0 7 3 2 5 8 0 25 0 0 0 0 0 0 0 0 0 0 0 0 49 94 128 236 228 185 155 150 242 221 97 2124 F G TOTALS 6 5 25 Columbia Generating Station 27 2008 Radioactive Effluent Report Table 5-5 3rd Quarter Average, 33 Ft AGL Joint Frequency Distribution (version 4.0)Sensor Criteria Time Frame Data Recovery Rate Wind Speed: 33 Foot Sensors Stari ng Date: 7/1/08 Maximum Hours In Period: 220 Wind Direction:
33 Foot Sensors Ending Date: 9/30108 Hours Missing: 9 Delta T: .245 Foot -33 Foot Sensors Hours Used: 2199 Signal Path: Mixed-bbb Recovery Rate: 99.6%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W' WNW NW INW TOTAL 1 2.2 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2.2 4.5 3 16 12 7 3 1 0 0 0 0 0 0 0 0 0 0 42 45 6.7 5 16 12 3 1 2 0 2 0 0 0 0 0 0 0 0 41 6.7 8.9 5 7 2 0 1 0 1 1 1 0 0 0 0 0 0 0 18 a9 11.2 1 10 0 2 0 0 2 0 4 0 3 0 3 0 0 0 25 11.2 13.4 1 5 2 0 0 0 2 1 1 5 1 2 0 2 0 1 23 13.4 17.9 0 1 0 0 0 0 1 0 2 4 0 0 0 0 4 0 12 17.9 22.4 0 0 0 0 0 0 0 0 0 1 1 0 2 3 0 0 7 22.4 29.1 0 0 0 0 0 0 0 0 0 0 1 0 0 1 0 1 3 291 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 16 56 28 12 5 3 6 4 8 10 6 2 5 6 5 2 174 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SWWSW W WNW NW NNW TOTAL 1 2.2 2 4 6 5 3 0 0 0 0 0 0 0 0 0 0 0 20 2,2 4.5 8 16 21 12 5 2 2 1 0 1 0 0 1 0 0 1 70 45 6.7 11 6 6 3 0 1 4 3 2 3 1 1 0 0 2 2 45 6.7 8.9 7 2 2 0 0 0 3 3 6 8 4 1 2 0 0 0 38 8.9 11.2 2 0 0 3 0 0 3 7 8 9 2 1 1 1 0 0 37 11.2 13.4 1 1 0 0 0 0 2 2 2 3 1 3 1 1 1 0 18 13.4 17.9 1 0 0 0 0 0 0 1 0 2 4 4 0 0 2 0 14 17.9 22.4 0 0 0 0 0 0 0 0 0 0 1 0 0 0 3 0 4 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 32 29 35 23 8 3 14 17 18 26 13 10 5 2 9 3 247 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW INNW TOTAL 1 2.2 1 4 7 1 4 0 1 1 0 1 2 1 1 0 1 2 27 2.2 4.5 3 7 7 4 2 2 1 10 4 6 4 1 3 2 5 6 67 45 6.7 1 4 3 2 0 1 2 15 9 3 3 2 2 2 3 4 56 6.7 8.9 3 1 2 3 0 1 0 2 8 7 1 1 1 2 2 2 36 8.9 11.2 2 1 0 0 0 0 1 3 6 6 2 4 2 2 1 0 30 11.2 13.4 1 0 1 0 0 0 2 0 0 2 1 1 2 1 4 0 15 13.4 17.9 .0 0 0 0 0 0 0 0 1 2 0 3 3 0 1 1 11 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 3 1 0 1 0 5 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 11 17 20 10 6 4 7 31 28 27 13 16 15 9 18 15 247 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 1 2 6 6 4 5 3 3 1 2 0 3 1 1 1 39 2.2 4.5 6 3 6 4 1 2 4 9 15 8 1 4 5 5 4 6 83 45 6.7 6 2 3 6 1 1 3 11 10 7 0 8 3 1 3 2 67 6.7 8.9 1 3 3 2 1 0 2 9 5 5 4 5 3 3 1 3 50 8.9 11.2 0 0 0 0 0 0 4 6 9 2 2 2 6 2 4 7 44 11.2 13.4 1 0 0 0 0 0 2 0 7 1 2 5 3 1 10 3 35 13.4 17.9 0 0 0 0 0 0 0 1 0 5 3 1 7 2 27 2 48 17.9 22.4 0 0 0 0 0 0 0 0 0 2 1 1 1 0 12 0 17 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 3 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 014 9 14 18 9 7 20 39 49 31 15 26 31 15 65 24 386 Columbia Generating Station 28 2008 Radioactive Effluent Report Table 5-5 3rd Quarter Average, 33 Ft AGL (Continued)
Wind Speed STABILITY CLASS: E Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 2 3 1 2 2 4 0 2 4 6 1 3 3 1 2 3 39 2.2 4.5 7 4 6 5 1 1 7 7 10 5 6 7 2 3 5 13 89 4,5 6.7 3 2 4 2 0 0 4 10 13 3 3 5 *6 5 11 12 83 6.7 8.9 4 1 2 0 0 0 4 9 9 5 1 1 2 8 17 12 75 8.9 11.2 1 0 0 1 0 0 0 3 5 5 1 1 2 10 19 2 50 11.2 13.4 0 0 1 0 0 0 0 1 5 9 1 3 1 10 17 5 53 1&4 17.9 1 0 0 0 0 0 0 1 0 2 1 2 1 8 23 3 42 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 2 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4a3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 18 10 14 10 3 5 15 33 46 35 14 23 18 45 94 50 433 WIhd Speed STABILITY CLASS: F Min Max N NNE NE ENE E ESE SE SSE -S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 3 8 5 2 1 4 6 3 2 1 2 2 1 3 1 44 22 4.5 9 7 11 4 1 0 3 11 14 8 1 2 1 3 5 9 89 4.5 6.7 4 3 3 2 0 0 3 11 10 8 1 0 0 2 6 6 59 6.7 8.9 0 0 0 1 0 0 3 8 9 8 1 2 3 4 5 6 50 a9 11.2 0 0. 0 0 0 0 2 3 2 3 0 0 1 5 6 1 23 11.2 13.4 1 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 3 134 17.9 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 17.9 22.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 4a.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 14 13 22 12 3 1 15 39 38 31 4 6 7 15 25 23 268 Wind Speed STABILITY CLASS: G MbI Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 8 15 19 4 2 3 2 8 2 7 1 0 1 2 4 6 84 2.2 4.5 20 22 28 8 0 0 3 9 17 3 1 1 0 0 2 13 127 4.5 6.7 6 3 15 4 0 0 0 13 17 3 0 1 0 2 3 8 75 6.7 8.9 0 0 2 1 0 0 0 3 4 4 1 0 0 0 2 4 21 8.9 11.2 0 0 0 0 0 0 0 0 4 0 1 0 1 0 0 0 6 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17.9 22.4 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4(13 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 34 40 64 17 2 3 -5 33 44 17 4 2 2 4 11 31 313 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 14 31 43 23 19 12 12 20 12 17 7 6 10 5 11 13 255 2,2 4.5 56 75 91 44 13 8 20 47 60 31 13 15 12 13 21 48 567 45 6.7 36 36 46 22 2 5 16 65 61 27 8 17 11 12 28 34 426 6.7 8.9 20 14 13 7 2 1 13 35 42 37 12 10 11 17 27 27 288 8.9 11.2 6 11 0 6 0 0 12 22 38 25 11 8 16 20 30 10 215 11.2 13.4 5 6 4 0 0 0 8 4 15 22 6 14 7 *15 32 9 147 13.4 17.9 2 1 0 0 0 0 1 3 3 15 8 10 11 10 57 6 127 17.9 22.4 0 0 0 0 0 0 0 0 0 3 3 5 5 3 16 0 35 22.4 29.1 0 0 0 0 0 0 0 0 0 0 1 0 0 1 4 1 7 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 139 174 197 102 36 26 82 196 231 177 69 85 83 96 227 148 2068 A B C D E F G TOTALS CALM 0 4 8 21 15 25 58 131 Columbia Generating Station 29 2008 Radioactive Effluent Report Table 5-6 3rd Quarter Average, 245 Ft AGL Joint Frequency Distribution
(%ersion 4.0)Sensor Criteria lime Frame Data Recovery Rate Wind Speed: 245 Foot Sensors Starting Date: 7/11/08 Maximum Hours In Period: 2208 Wind Direction:
245 Foot Sensors Ending Date: 9130108 Hours Missing: 9 Delta T: 245 Foot -33 Foot Sensors Hours Used: 2199 Signal Path: Mixed Recovery Rate: 99.6%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .2 2.2 4.5 1 8 2 4 0 1 0 0 0 0 0 0 0 0 0 0 16 4.5 6.7 3 15 14 4 1 1 0 0 0 0 0 0 0 0 .0 0 38 6.7 8.9 3 10 9 5 0 2 2 1 0 0 0 0 0 0 0 0 32 8.9 11.2 4 6 3 1 0 0 1 0 1 0 0 0 0 0 0 0 16 11.2 13A 1 4 2 2 1 1 1 0 3 0 1 1 2 0 0 0 19 13A 17.9 0 9 2 0 0 0 3 0 5 4 1 3 1 2 0 1 '31 17.9 22.4 0 0 0. 0 0 0 1 0 0 4 0 0 1 2 1 1 10 22.4 29.1 0 0 0 0 0 0 0 0 0 0 2 1 1 3 0 0 7 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 2 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 1 0 1 TOTALS 12 54 32 16 2 5 8 1 9 8 4 5 5 8 3 2 174 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 2 5 4 1 0 0 0 0 0 0 0 0 0 0 0 13 2.2 4.5 3 8 13 12 6 1 0 1 0. 0 0 0 0 0 0 2 46 4.5 6.7 9 5 14 6 3 2 0 1 0 3 0 1 0 0 1 1 46 6.7 8.9 7 6 3 3 1 0 4 1 6 1 2 1 0 0 0 2 37 8.9 11.2 3 2 3 1 0 0 3 3 6 4 3 1 2 0 0 0 31 11.2 13.4 3 0 0 1 0 1 5 5 3 10 3 0 0 0 0 0 31 13.4 17.9 1 2 0 1 1 1 1 2 1 6 3 8 3 1 1 0 32 17.9 22.4 0 0 0 0 1 0 0 0 0 0 1 2 3 0 0 1 1 8 22A 29.1 0 0 0 0 0 0 0 0 0 0 1 0 0 0 2 1 4 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 27 25 38 28 12 5 13 13 16 25 14 14 5 1 6 7 249 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 5 3 1 3 1 0 1 1 0 1 0 0 2 1 1 21 2.2 4.5 0 3 5 4 3 0 2 2 1 5 4 1 1 1 3 4 39 4.5 6.7 3 4 1 3 0 1 6 5 6 4 3 3 3 3 4 1 50 6.7 8.9 4 4 2 3 1 1 1 11 8 1 3 1 1 1 2 3 47 8.9 11.2 3 0 2 1 0 1 0 1 4 6 4 0 1 1 1 0 25 11.2 13.4 1 0 0 0 2 0 2 2 6 5 4 3 1 1 0 0 27 13.4 17.9 2 1 1 0 0 2 0 1 0 3 0 6 1 4 4 0 25 17.9 22A 0 0 0 0 0 0 0 0 0 1 0 2 2 0 1 1 7 22A 29.1 0 0 0 0 0 0 0 0 0 0 0 1 4 0 1 0 6 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 14 17 14 12 9 6 11 23 26 25 19 17 14 13 17 10 247 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 1 0 3 3 3 2 1 4 1. 2 1. 0 0 1 2 25 2.2 4.5 3 1 2 2 0 1 6 3 12 4 3 3 2 3 3 2 50 4.5 6.7 5 4 4 5 1 1 2 7 9 7 1 4 3 5 3 5 66 6.7 8.9 3 4 1 4 0 1 1 6 11 5 1 4 2 2 1 2 48 8.9 11.2 2 3 2 2 0 0 3 3 4 4 3 3 3 2 1 1 36 11.2 13A 0 1 0 0 2 1 3 4 7 1 5 1 4 1 2 4 36 13.4 17.9 3 1 0 0 0 1 1 1 2 7 4 7 8 2 4 3 44 17.9 22A 0 0 0 0 0 0 0 0 1 4 2 0 7 4 16 1 35 22.4 29.1 0 0 0 0 0 0 0 0 0 .0 3 1 4 3 21 4 36 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 1 0 1 6 0 8 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 17 15 9 16 6 8 18 25 50 33 24 25 33 23 58 24 384 Columbia Generating Station 30 2008 Radioactive Effluent Report Table 5-6 3 rd Quarter Average, 245 Ft AGL (Continued)
Wind Speed STABILITY CLASS: E Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 2 2 0 1 2 4 0 2 1 0 2 3 0 1 2 22 2.2 4.5 3 1 0 4 1 1 0 3 4 2 1 5 2 2 3 3 35 4.5 6.7 1 4 3 2 2 0 2 2 2 7 3 3 6 1 7 2 47 6.7 8.9 7 1 0 1 0 1 1 2 6 6 2 0 3 8 6 7 51 8.9 11.2 1 0 1 0 1 0 1 3 3 5 0 2 3 2 13 5 40 11.2 13A 2 0 1 1 1 0 1 0 5 4 1 2 3 3 3 4 31 13.4 17.9 6 1 2 0 0 0 1 5 6 5 7 1 2 12 26 6 80 17.9 22.4 1 0 0 0 0 0 0 0 3 2 10. 2 2 21 31 2 74 22.4 29.1 0 0 1 1 0 0 0 0 1 1 1 3 3 9 35 4 59 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 21 9 10 9 6 4 10 15 32 33 25 20 28 ,58 125 35 440 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 1 0 1 0 1 3 4 2 2 0 2 2 0 1 2 21 2.2 4.5 2 2 2 2 1 1 5 3 3 2 4 1 3 3 0 1 35 4.5 6.7 8 2 1 0 0 2 3 7 3 4 5 1 2 2 3 3 46.6.7 8.9 5 5 2 0 0 0 0 5 8 8 1 2 1 3 2 5 47-8.9 11.2 3 1 3 1 2 0 1 5 7 2 3 0 0 2 3 5 38 11.2 13.4 1 0 0 1 0 0 0 6 4 6 2 0 2 2 5 3 32 13.4 17.9 4 0 1 1 0 0 1. 1 0 3 3 0 1 4 8 10 37 17.9 22.4 2 0 0 1 0 0 0 0 1 0 3 0 0 6 4 4 21 22.4 29.1 1 0 1 0 0 0 0 0 0 0 0 0 0 1 2 0 5 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 26 11 10 7 3 4 13 31 28 27 21 6 11 23 28 33 282 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 1 1 2 4 2. 1 4 3 3 3 2 1 1 0 4 32 2.2 4.5 3 5 3 9 5 2 4 11 8 8 5 3 2 2 0 2 72 4.5 6.7 8 4 5' 12 5 0 1 6 4 8 3 0 0 2 1 5 64 6.7 8.9 6 3 4 4 2 0 1 10 13 2 2 0 1 0 3 7 58 8.9 11.2 12 0 1 5 1 0 1 5 8 1 3 0 1 1 3 11 53 11.2 13.4 6 2 1 0 0 0 0 4 3 3 1 0 0 0 3 9 32 13.4 17.9 4 0 0 0 0 0 0 1 3 0 1 0 1 0 7 10 27 17.9 22A 0. 0 0 2 0 0 0 0 0 0 1 0 0 0 1 0 4 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 39 15 15 34 17 4 8 41 42 25 19 5 6 6 18 48 342 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 3 14 11 11 12 9 10 10 12 7 6 7 6 3 4 11 136 2.2 4.5 15 28 27 37 16 7 17 23 28 21 17 13 10 11 9 14 293 4.5 6.7 37 38 42 32 12 7 14 28 24 33 15 12 14 13 19 17 357 6.7 8.9 35 33 21 20 4 5 10 36 52 23 11 8 8 14 14 26 320 8.9 11.2 28 12 15 11 4 1 10 20 33 22 16 6 10 8 21 22 239 11.2 13.4 14 7 4 5 6 3 12 21 31 29 17 7 12 7 13 20 208 13.4 17.9 20 14 6 2 1 4 7 11 17 28 19 25 17 25 50 30 276 17.9 22.4 3 0 0 3 0 0 1 0 5 12 18 7 12 33 55 10 159 22.4 29.1 1 0 2 1 0 0 0 0 1 1 .7 6 12 16 61 9 117 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 1 1 2 8 0 12 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 TOTALS 156, 146 128 122 55 36 81 149 203 176 126 92 102 132 255 159 2118 A B C D E F G TOTALS CALM 0 2 8 23 8 11 29 81 Columbia Generating Station 31 ' 2008 Radioactive Effluent Report Table 5-7 4th Quarter Average, 33 Ft AGL Joint Frequency Distribution (version 4.0)Sensor Criteria Time Frame Data Recovery Rate WindSpeed:
33 Foot Sensors Startlng Date: 1011/08 Maximum Hours In Period: 2208 Wind Direction:33 Foot Sensors Ending Date: 12131/08 H-ours Missing: 6 DeltaT: 245 Foot -33 Foot Sensors Hours Used: 2202 Signal Path: Mixed-aaa Recovery Rate: 99.7%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4.5 6.7 0- 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 6.7 8.9 0 0 0 0 0 0 0 0 0- 0 0 0 0 0 0 0 0 1.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 1 0 0 0 0 0 0 0 0 0 1 0 0 0 0 2 17.9 22.4 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 22.4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29R1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 0 2 0 0 0 0 0 0 0 0 0 1 0 0 0 0 3 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 2.2 4.5 0 0 0 0 0 0 0 0 0 "0 0 0 0 0 0 0 0 4.5 6.7 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 3 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 134 17.9 1 1 1 0 0 0 0 0 0 0 0 0 1 0 0 1 5 17.9 22.4 0 2 0 0 0 0 0 0 0 0 0 2 0 0 0 1 5 22-4 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 3 3 1 0 0 0 0 0 0 0 0 2 1 0 0 5 15 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 6 0 0 0 0 0 0 0 0 0 0 0 0 0 1 4 11 4.5 6.7 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 5 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 '0 1 0 1 2 8&9 11.2 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 11.2 13.4 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 2 13.4 17.9 1 1 0 0 0 0 0 0 0 0 0 1 0 0 0 4 7 17.9 22.4 1 1 0 0 0 0 0 0 0 0 0 2 0 0 1 0 5 224 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 11 3 0 0 0 0 0 0 1 1 0 3 0 1 2 12 34 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW INW TOTAL 1 2.2 6 9 7 7 7 3 6 4 5 7 3 4 4 4 6 10 92 2.2 4.5 27 15 10 6 1 1 2 13 11 11 2 7 5 8 19 32 170 4.5 6.7 15 5 6 2 0 0 1 19 19 2 3 1 4 4 26 37 144 6.7 8.9 15 4 0 1 0 0 5 7 13 2 2 3 1 3 9 4 69 6&9 11.2 0 6 1 0 0 0 0 6 8 5 0 2 1 3 2 3 37 11.2 13.4 14 0 0 0 0 0 0 1 7 2 1 2 0 1 2 6 36 13.4 17.9 28 3 0 0 0 0 0 0 3 5 3 4 3 0 4 3 56 17.9 22.4 5 6 0 0 0 0 0 0 0 4 2 4 0 0 2 0 23 224 29.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 110 48 24 16 8 4 14 50 66 38 16 27 18 23 71 95 628 Columbia Generating Station 32 2008 Radioactive Effluent Report Table 5-7 4 th Quarter Average, 33 Ft AGL (Continued)
Wind Speed STABILITY CLASS: E Min Max N NNE NE ENE 1 2.2 10 8 6 1 2.2 4.5 14 7 1 2 4.5 6.7 13 2 2 3 6.7 8.9 2 '1 0 1 8.9 11.2 1 1 0 0 11.2 134 2 0 0 0 13.4 17.9 1 0 0 0 17.9 22.4 0 0 0 0 22.4 29.1 0 0 0 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS .43 19 9 7 E 0 0 0 0 0 0 0-0 0 0 0 0 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 2 3 .7 8 11 3 10 9 9 6 13 106 1 5 10 11 6 7 12 10 20 26 33 165 0 4 8 24 9 3 6 5 7 18 29 133 2 12 19 11 5 5 2 4 4 12 9 89 0 1 14 3 2. 2 3 1 2 8 6 44 0 1 2 4 1 6 5 2 2 1 1 27 0 0 2 1 1 11 2 1 0 2 2 23 0 0 0 0 2 6 7 1 0 0 0 16 0 0 0 0 4 0 2 0 0 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 5 26 62 62 41 43 49 33 44 73 93 609 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE E 1 2.2 7 7 8 4 2 2.2 4.5 17 7 4 2 0 4.5 6.7 22 4 2 0 0&.7 8.9 3 2 1 0 0 8.9 11.2 2 0 2 0 0 11.2 13.4 1 0 0 0 0 13.4 17.9 0 0 0 0 0 17.9 22.4 0 0 0 0 0 22.4 29.1 0 0 0 0 0 29.1 40.3 0 0 0 0 0 46.3 90 0 0 0 0 0 TOTALS 52 2D 17 6 2 ESE SE SSE S SSW SW WSW W WNW NW NN1W TOTAL 2 2 4 5 7 5 4 4 8 20 11 100 1 1 12 13 9 9 4 5 6 19 2B 137 0 2 15 14 11 2 2 0 2 5 11 92 0 3 19 8 4 2 0 1 1 9 3 56 0 0 6 5 2 1 2 2 2 1 0 25 0 0 4 2 1 0 0 0 1 4 1 14 0 0 0 0 2 2 0 0 0 0 0 4 0 0 0 0 0 2 0. 0 0 0 0 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 8 60 47 36 23 12 12 20 58 54 430 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE 1 2.2 12 10 5 2 2.2 4.5 25 11 9 0 45 6.7 6 1 1 0 6.7 8.9 2 0 0 0 8.9 11.2 0 0 0 0 11.2 13.4 0 0 0 0 13.4 17.9 0 0 0 0 17.9 22.4 0 0 0 0 22.4 29.1 0 0 0 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 45 22 15 2 E 1 0 0 0 0 0 0 0 0 0 0 1 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 0 5 3 4 3 4 3 6 11 19 89 0 1 12 13 4 7 5 3 7 15 33 145 0 0 6 4 7 0 1 0 1 5 21 53 0 1 5 1 1 0 2 1 1 5 2 21 0 1 5 1 0 0 0 0 0 4 1 12 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 3 33 22 16 10 12 7 15 40 76 320 Wind Speed STABILITY CLASS: ALL Minm Max N NNE NE ENE 1 2.2 35 34 26 14 2.2 4.5 89 40 24 10 45 6.7 60 12 11 5 6.7 8.9 22 7 1 2&.9 11.2 3 7 3 0 11.2 13.4 18 1 0 0 13.4 17.9 31 6 1 0 17.9 22.4 6 10 0 0 22.4 29.1 0 0 0 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 264 117 66 31 E 0 1 0 0 0 0 0 0 0 0 0 11 ESE SE SSE S SSW SW WSW W WNW NW INNW TOTAL 8 11 20 21 29 14 22 20 27 43 54 388 3 9 47 48 30 25 28 23 41 80 130 628 0 7 48 61 29 8 10 9 14 54 102 430 2 21 50 33 12 9 7 7 10 35 19 237 0 2 31 17 10 3 7 4 7 15 10 119 0 1 7 14 4 7 7 2 4 7 8 80 0 0 2 4 8 16 8 5 0 6 10 97 0 0 0 0 6 10 15 1 0 3 1 52 0 0 0 0 4 0 2 0 0 1 1 8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13 51 205 198 132 92 106 71 103 244 335 2039 A B C D E F G TOTALS CALM 0 0 0 39 31 52 41 163 Columbia Generating Station 33 2008 Radioactive Effluent Report Table 5-8 4th Quarter Average, 245 Ft AGL Joint Frequency Distribution4.0)Sensor Criteria Time Frame Data Recovery Rate Wind Speed: 245 Foot Sensors Starting Date: 10/1108 Maximum Hours In Period: 2208 Wind Direction:
245 Foot Sensors Ending Date: 12/31108 Hours Missing: 6 Delta T: 245 Foot -33 Foot Sensors Hours Used: 2202 Signal Path: Mixed Recovery Rate: 99.7%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 4.5 6.7 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13.4 17.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17.9 22.4 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 22.4 29.1 0 1 0 0 0 0 0 0 0 0 0 1 0 0 0 0 2 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 0 2 0 1 0 0 0 0 0 0 0 1 0 0 0 0 4 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 4.5 6.7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6.7 8.9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 8.9 11.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11.2 13.4 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 13.4 17.9 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 17.9 22.4 0 3 1 0 0 0 0 0 0 0 0 0 1 0 0 0 5 22.4 29.1 1 1 0 0 0 0 0 0 0 0 0 2 0 0 0 1 5 29.1 40.3 0 0 0 0 0 0 0. 0 0 0 0 0 0 .0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 3 5 1 0 0 0 0 0 0 0 0 2 1 0 0 3 15 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.2 4.5 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 4.5 6.7 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 3 5 6.7 8.9 5 0 1 0 0 0 0 0 0 0 0 0 0 0 0 2 8 8.9 11.2 1 1 6 0 0 0 0 0 0 0 0 0 0 1 1 0 4 11.2 13.4 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 13.4 17.9 0 2 0 0 0 0 0 0 1 0 0 0 0. 0 0 0 3 17.9 22.4 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 2 3 22.4 29.1 4 0 0 0 0 0 0 0 0 0 0 2 1 0 1 0 8 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 40.3 90 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 TOTALS 11 6 1 0 0 0 0 0 1 1 0 2 1 1 3 8 35 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 3 2 0 3 1 1 2 3 2 0 2 2 2 1 5 2 31 2.2 4.5 14 9 16 13 5 1 3 7 11 7 3 7 5 5 9 17 132 4.5 6.7 20 11 5 2 1 2 1 9 11 4 3 3 4 3 18 22 119 6.7 8.9 10 13 3 2 0 0 2 10 15 7 4 2 3 2 11 21 105 8.9 11.2 6 10 2 0 0 0 2 9 11 5 0 2 0 2 10 11 70 11.2 13.4 9 3 3 0 0 0 0 1 9 11 4 0 0 4 2 4 50 13.4 17.9 16 3 2 1 0 0 0 0 11 5 0 2 2 3 4 9 58 17.9 22.4 16 11 0 0 0 0 0 0 2 3 2 2 4 0 6 1 47 22.4 29.1 1 10 0 0 0 0 0 0 0 5 3 7 0 0 0 2 28 29.1 40.3 0 0 0 0 0 0 0 0 0 1 3 2 1 0 3 0 10 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 95 72 31 21 7 4 10 39 72 48 24 29 21 20 68 89 650 Columbia Generating Station 34 2008 Radioactive Effluent Report Table 5-8 4 th Quarter Average, 245 Ft AGL (Continued)
Wind Speed STABILITY CLASS: E Min Max N NNE NE ENE 1 2.2 2 1 2 1 2.2 4.5 8 8 4 1 4.5 6.7 9 8 7 6 6.7 8.9 12 5 5 3 8.9 11.2 5 3 4 4 11.2 13.4 2 3 0 0 13.4 17.9 4 0 2 1 17.9 22.4 4 0 1 0 22.4 29.1 0 0 0 0 29.1 40.3 0 0 0 0 40.3 90 o 0 0 0 TOTALS 46 28 25 16 E 3", 6 3 1 0 0 0 0 0 15 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE 1 2.2 2 1 1 1 2.2 4.5 5 6 8 6 4.5 6.7 11 6 2 5 6.7 8.9 13 5 3 1 8.9 11.2 12 5 2 3 11.2 13.4 5 0 0 1 13.4 17.9 5 1 3 0 17.9 22.4 1 1 4 0 22.4 29.1 0 0 1 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 54 25 24 17 E 0 2 2 3 1 0 0 0 0 0 0 8 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 1 3 0 1 2 0 4 2 1 1 25 3 3 4 12 6 5 3 9 5 7 9 93 2 3 7 11 5 2 0 2 5 13 22 105 0 1 7 7 8 6 3 2 3 7 22 92 1 4 4 10 5 2 1 4 5 4 10 66 0 4 8 9 10 4 1 4 2 9 19 76 0 3 5 11 9 2 4 3 6 7 15 73 0 1 1 5 7 11 4 4 2 3 10 53 0 0 1 2 2 5 6 5 2 3 1 27 0 0 0 1 1 9 8 0 0 1 0 20 0 0 0 0 0 1 0 0 0 0 0 1 7 20 40 68 54 49 30 37 32 55 109 631 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 4 2 2 1 1 3 3 1 0 1 0 23 3 4 9 6 5 2 4 3 1 4 6 74 2 4 13 8 7 5 2 3 4 3 7 84 0 3 10 7 5 2 2' 2 1 6 10 73 0 2 12 9 4 7 1 1 1 6 6 72 0 0 8 8 4 1 2 1 2 7 4 43 0 0 11 7 6 5 0 1 1 8 16 64 0 0 1 4 6 3 1 1 3 5 0 30 0 0 0 0 0 4 0 2 0 4 2 13 0 0 0 0 0 0 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 9 15 66 50 38 32 16 15 13 44 51 477 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 2 1 0 0 1 1 0 0 2 0 0 9 2 6 5 6 4 5 4 4 0 4 5 73 0 2 9 10 5 4 6 4 0 3 .3 69 1 4 6 10 4 6 1 5 2 3 6 70 0 2 4 11 3 1 1 2 3 2 14 55 0 0 4 2 2 3 2 1 0 5 7 33 0 0. 3 6 2 2 0 0 1 3 6 27 0 2 0 2 0 0 0 0 0 3 6 15 0 0 1 0 0 0 0 0 0 2 4 7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0O 5 17 32 47 21 22 .14 16 8 25 51 358 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 8 6 8 3 3 8 5 7 5 7 3 88 9 16 25 35 22 15 18 21 11 24 37 *376 6 10 38 40 21 14 11 13 12 38 57 382 1 10 33 39 24 18 8 12 8 27 63, 350 1 10 29 41 17 10 5 7 12 23 41 267 0 4 21 28 28 12 5 6 8 23 34 204 0 3 19 36 22 9 6 6 11 22 46 226 0 3 2 13 16 16 7 10 5 17 .19 154 0 0 2 2 7 12 18 8 2 10 10 90 0 0 0 1 2 12 11 1 0 4 1 32 0 0 0 0 0 1 0 0 0 0 0 1 25 62 177 238 162 127 94 91 74 195 311 2170 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE 1 2.2 0 1 0 1 2.2 4.5 5 9 5 4 4.5 6.7 4 7 8 3 6.7 8.9 7 6 7 2 8.9 11.2 3 5 2 1 11.2 13.4 2 2 2 1 13.4 17.9 4 0 0 0.17.9 22A 2 0 0 0 22A 29.1 0 0 0 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 27 30 24 12 E 0 5 1 0 1 0 0 0 0 0 0 7 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE 1 2.2 7 5 3 6 2.2 4.5 34 33 33 25 4.5 6.7 .44 33 22 16 6.7 8.9 47 29 19 8 8.9 11.2 27 24 10 8 11.2 13.4 19 8 5 2 13.4 17.9 29 7 7 2 17.9 22.4 23 17 6 0 22.4 29.1 6 12 1 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 236 168 106 67 E 4 18 7 4 2 1 1 0 0 0 0 37 A B C D E F G TOTALS CALM 0 0 0 11 10 7 4 32 Columbia Generating Station 35 2008 Radioactive Effluent Report Columbia Generating Station 35 2008 Radioactive Effluent Report Table 5-9 Year 2008, 33 Ft AGL Joint Frequency Distribution (version 4.0)Sensor Criteria Time Frame Data Recovery Rate WindSpeed:
33 Foot Sensors Starting Date: 1/1/08 Maidmum Hours In Period: 8784 Wind Direction:33 Foot Sensors Ending Date: 12131/08 Hours Missing: 117 DeltaT: 245 Foot -33 Foot Sensors Hours Used: 8667 Signal Path: Mixed Signals Recovery Rate: 98.7%/o Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2,2 4.5 3 16 12 7 3 1 0 0 0 0 0 0 0 0 0 0 42 45 6.7 6 16 12 3 1 2 0 2 0 0 0 0 0 0 1 0 43 6.7 8.9 7 7 2 0 1 0 1 1 1 0 0 0 0 0 0 0 20 8.9 11.2 3 10 1 2 0 0 2 0 4 0 3 0 3 0 0 0 28 11.2 13.4 1 5 2 0 0 0 2 1 1 5 1 2 0 2 0 1 23 13.4 17.9 0 2 0 0 0 0 1 0 4 8 0 2 0 0 4 0 21 17.9 22.4 0 1 0 0 0 0 0 0 1 5 2 1 2 3 4 1 20 22.4 29.1 0 0 0 0 0 0 0 0 0 0 2 0 0 1 1 1 5 29.1 40.3 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 2 40.3 90 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 21 58 29 12 5 3 6 4 11 18 9 5 5 6 11 3 206 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 2 5 6 5 3 0 0 0 0 0 0 0 0 0 0 1 22 2.2 4.5 11 16 21 12 5 2 2 1 0 1 0 0 1 0 0 1 73 45 6.7 14 10 6 3 0 1 4 3 2 3 1 1 0 0 2 4 54 6.7 8.9 10 5 2 0 0 0 3 3 8 8 4 1 2 0 1 1 48 8.9 11.2 5 2 1 4 0 0 3 7 10 13 2 1 2 2 0 0 52 11.2 13.4 2 2 0 0 0 0 2 2 3 6 .1 3 3 1 1 0 26 13.4 17.9 2 1 1 0 0 0 0 1 4 6 9 7 2 0 5 1 39 17.9 22.4 0 2 0 0 0 0 0 0 0 2 2 5 0 0 5 1 17 22.4 29.1 0 0 0 0 0 0 0 0 0 0 1 3 0 0 4 1 9 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 46 43 37 24 8 3 14 17 27 39 20 21 10 3 18 10 340 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 2 4 8 1 4 0 1 1 0 1 2 1 1 1 2 3 32 2.2 4.5 16 14 17 5 4 3 1 10 4 7 5 4 3 3 7 14 117 45 6.7 9 11 7 4 0 1 2 15 11 5 8 2 4 3 4 7 93 6.7 8.9 6 5 4 3 0 1 0 3 15 10 4 5 5 5 3 5 74 8.9 11.2 4 3 1 1 0 0 1 3 11 11 3 8 7 5 2 0 60 11.2 13.4 2 2 1 .0 0 0 2 0 4 8 2 3 2 1 7 0 34 1314 17.9 1 1 0 0 0 0 0 0 2 10 6 9 9 3 4 6 51 17.9 22.4 1 1 0 0 0 0 0 0 0 3 3 11 2 1 8 1 31 22.4 29.1 0 0 0 0 0 0 0 0 0 0 4 2 0 0 2 2 10 29L1 40.3 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 41 41 38 14 8 5 7 32 47 55 37 46 33 22 39 3B 503 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 14 18 19 22 15 9 15 10 12 13 10 9 13 15 13 22 229 2.2 4.5 63 42 35 25 9 11 16 44 50 46 19 27 26 22 41 64 540 45 6.7 40 27 29 17 8 7 20 79 62 49 17 25 17 17 49 59 522 6.7 8.9 21 16 6 9 1 2 11 41 56 40 17 16 17 16 18 21 308 8.9 11.2 5 10 4 2 1 0 9 22 50 37 13 15 14 14 16 18 230 11.2 13.4 18 3 1 0 0 0 5 5 22 21 18 10 10 8 20 11 152 13.4 17.9 28 10 2 0 0 0 0 1 14 45 39 14 23 13 51 25 265 17.9 22.4 6 9 0 0 0 0 0 1 0 10 16 12 4 1 37 5 101 22.4 29.1 0 0 0 0 0 0 0 0 0 1 1 3 6 0 12 2 25 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 1 4 0 1 0 6 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 195 135 96 75 34 29 76 203 266 262 150 132 134 106 258 227 2378 Columbia Generating S~tation 36 2008 Radioactive Effluent Report Table 5-9 Year 2008, 33 Ft AGL (Continued)
Wind Speed STABILITY CLASS: E Mwn Max N NNE NE ENE E 1 2.2 16 14 14 5 5 2.2 4.5 45 31 16 17 3 4,5 6.7 25 17 8 7 0 6.7 8.9 11 5 5 2 0 89 11.2 4 3 0 1 0 11.2 13.4 3 1 2 0 1 13.4 17.9 3 5 0 0 0 17.9 22.4 1 6 0 0 0 22.4 29.1 0 0 0 0 0 29.1 40.3 0 0 0 0 0.4(.3 90 0 0 0 0 0 TOTALS 108 82 45 32 9 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE E 1 2.2 20 21 27 13 6 22 4.5 65 39 29 10 2 45 .6.7 34 13 15 4 0 6.7 8.9 4 3 2 3 0&.9 11.2 2 0 2 0 0 11.2 13.4 2 0 0 0 0 13.4 17.9 0 0 0 0 0 17.9 22.4 0 0 0 0 0 22.4 29.1 0 0 0 0 0 29.1 40.3 0 0 0 0 0 4a3 90 0 0 0 0 0 TOTALS 127 76 75 30 8 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE E 1 2.2 36 38 36 10 3 22 4.5 69 53 56 8 0 45 6.7 30 6 28 4 0 6.7 8.9 2 0 6 3 0&.9 11.2 0 1 1 0 0 11.2 13.4 0 0 0 0 0 13.4 17.9 0 0 0 0 0 17.9 22.4 0 0 0 0 0 224 29.1 0 0 0 0 0 29.1 40.3 0 0 0 0 0 40L3 90 0 0 0 0 0 TOTALS 137 98 127 25 3 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 11 6 16 14 20 8 21 20 19 16 33 238 6 17 30 45 26 24 31 26 38 66 69 490 1 16 33 68 25 20 19 26 25 62 54 406 2 20 43 58 30 28 9 17 22 52 40 344 0 5 29 31 22 16 6 13 26 57 17 230 0 1 16 24 31 26 16 12 24 39 13 209 0 1 6 9 28 38 14 9 23 53 10 199 0 0 0 3 20 11 16 13 1 6 0 77 0 0 0 1 8 3 4 1 0 0 0 17 0 0 0 0 1 0 2 1 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 20 66 173 253 211 174 138 138 178 351 236 2214 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 4 9 15 15 22 15 12 15 18 35 26 273 2 8 44 46 40 29 15 23 24 38 80 494 0 7 49 51 44 17 6 10 12 26 44 332 0 10 50 53 20 12 7 9 11 24 16 224 0 4 17 16 8 6 3 5 9 12 2 86 0 0 5 6 7 3 0 0 5 4 1 33 0 0 1 3 12 4 0 1 0 1 0 22 0 0 0 1 0 .2 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 38 181 191 153 88 43 63 79 140 169 1467 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 5 3 19 10 17 8 10 10 17 20 35 277 0 5 31 51 20 13 7 8 10 27 74 432 0 0 28 40 22 5 2 1 8 13 48 235 0 1 16 24 11 5 2 1 2 9 7 89 0 1 9 8 0 4 0 2 0 5 1 32 0 0 0 1 0 1 0 0 0 0 0 2 0 0 0 1 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 10 103 135 70 36 21 22 37 74 165 1068 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 29 34 61 51 73 43 53 59 70 86 120 1073 25 49 160 196 140 90 84 87 97 179 302 2188 12 49 209 234 148 68 55 58 65 157 216 1685 5 46 157 215 119 70 40 51 56 107 90 1107 0 25 87 130 91 47 33 46 56 92 38 718 0 12 29 61 78 52 34 27 41 71 25 479 0 2 9 37 109 96 46 44 39 118 42 598 0 0 1 5 40 36 45 21 6 60 8 249 0 0 0 1 9 11 12 7 1 19 6 66 0 0 0 0 1 1 4 5 0 2 0 13 0 0 0 0 0 0 0 0 0 0 0 0 71 217 713 930 808 514 406 405 431 891 848 8176 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE E 1 2.2 91 101 110 56 36 2.2 4.5 272 211 186 84 26 45 6.7 158 1W0 105 42 9 6.7 8.9 61 41 27 20 2 89 11.2 23 29 10 10 1 11.2 13.4 28 13 6 0 1 13.4 17.9 34 19 3 0 0 17.9 22.4 8 19 0 0 0 22.4 29.1 0 0 0 0 0 29.1 40.3 0 0 0 0 0 40.3 90 0 0 0 0 0 TOTALS 675 533 447 212 75 A B C D E F G TOTALS CALM 0 4 9 106 87 144 141 491 Columbia Generating Station 37 2008 Radioactive Effluent Report Table 5-10 Year 2008, 245 Ft AGL Joint Frequency Distribution (ersion 4.0)Sensor Criteria rime Frame Data Recovery Rate Wind Speed: 245 Foot Sensors Starting Date: 1/11/08 Maximum Hours In Period: 8784 Wind Direction:
245 Foot Sensors Ending Date: 12/31/08 Hours Missing: 77 Delta T: 245 Foot -33 Foot Sensors Hours Used: 8707 Signal Path: Mixed Recovery Rate: 99.1%Processing:
Instantaneous Wind Speed STABILITY CLASS: A Min Max N NNE NE ENE E ESE. SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 0 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2.2 4.5 1 8 2 5. 0 1 0 0 0 0 0 0 0 0 0 0 17 4.5 6.7 3 15 15 4 1 1 0 0 0 0 0 0 0 0 0 0 39 6.7 8.9 3 11 9 5 0 2 2 1 0 0 0 0 0 1 0 1 35 8.9 11.2 6 6 5 1 0 0 1 0 1 0 0 0 0 0 0 0 20 11.2 13.4 1 4 3 2 1 1 1 0 3 0 1 1 2 0 0 1 21 13.4 17.9 0 9 2 0 0 0 3 .0 5 5 2 3 1 2 0 1 33 17.9 22.4 0 1 0 0 0 0 1 0 5 4 2 2 1 3 1 1 21 22.4 29.1 0 1 0 0 0 0 0 0 4 1. 2 3 1 7 1 1 21 29.1 40.3 0 0 0 0 0 0 0 0 0 0 2 0 0 1 1 0 4 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 TOTALS 14 57 36 17 2 5 8 1 18 10 9 9 5 14 4 5 214 Wind Speed STABILITY CLASS: B Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 1 2 5 4 1 0 0 0 0 0 0 0 0 0 0 0 13 2.2 4.5 5 9 16 13 6 2 0 1 0 0 0 0 0 0 0 3 55 4.5 6.7 9 9 15 9 3 3 0 1 0 3 0 1 0 0 1 2 56 6.7 8.9 11 8 3 3 1 0 4 1 6 2 2 1 0 1 0 4 47 8.9 11.2 5 2 6 1 0 0 3 3 7 5 4 2 2 1 0 1 42 11.2 13.4 6 0 0 1 0 1 5 5 5 15 4 0 0 0 0 1 43 13A 17.9 1 4 0 1 1 1 1 2 5 10 5 8 4 1 3 0 47 17.9 22.4 0 3 1 0 0 0 0 0 0 2 4 8 4 1 2 1 26 22.4 29.1 1 1 0 0 0 0 0 0 0 0 1 3 0 1 5 2 14 29.1 40.3 0 0 0 0 0 0 0 0 0 0 2 1 0 0 2 0 5 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 39 38 46 32 12 7 13 13 23 37 22 24 10 5 13 14 348 Wind Speed STABILITY CLASS: C Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 2 5 5 1 3 1 0 1 1 0 1 0 1 2 2 1 26 2.2 4.5 6 11 7 6 6 0 4 2 1 5 5 2 2 2 5 6 70 4.5 6.7 4 8 2 4 0 1 7 5 6 6 6 4 4 5 5 5 72 6.7 8.9 13 8 6 5 1 1 1 14 12 4 5 3 2 3 4 5 87 8.9 11.2 4 *6 4 1 1 1 0 3 10 13 7 0 3 3 2 2 60 11.2 13.4 2 0. 1 0 2 0 2 2 7 13 6 5 5 2 0 2 49 13.4 17.9 2 4 1 0 1 2 0 1 5 13 7 10 8 9 7 1 71 17.9 22A 0 1 0 0 0 0 0 0 0 2 1 8 3 0 5 4 24 22.4 29.1 4 0 0 0 0 0 0 0 1 3 5 6 5 3 5 0 32 29.1 40.3 0 0 0 0 0 0 0 0 0 0 3 0 0 0 1 1 5 40.3 90 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 TOTALS 37 43 26 17 14 6 14 28 43 59 46 39 33 29 36 27 497 Wind Speed STABILITY CLASS: D Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 6 7 5 10 5 10 9 10 13 5 10 8 6 4 8 10 126 2.2 4.5 31 32 29 32 10 14 22 23 44 26 18 24 16 18 24 32 395 4.5 6.7 40 36 23 19 6 10 19 46 44 38 33 22 23 23 34 44 460 6.7 8.9 24 26 17 12 3 8 19 43 58 45 19 23 15 12 22 34 380 8.9 11.2 17 17 7 6 0 1 13 27 44 40 15 16 15 15 18 20 271 11.2 13.4 11 8 3 1 3 1 6 11 30 35 19 11 10 16 9 10 184 13.4 17.9 22 10 3 1 0 1 4 5 34 41 36 20 20 20 24 15 256 17.9 22.4 16 12 0 0 0 0 0 0 7 21 28 10 17 17 37 3 168 22A 29.1 1 14 2 0 0 0 0 0 2 9 25 17 11 18 43 8 150 29.1 40.3 0 0 0 0 0 0 0 0 0 1 6 6 7 5 15 0 40 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 2 TOTALS 168 162 89 81 27 45 92 165 276 261 209 157 142 148 234 176 2432 Columbia Generating.
Station 38 2008 Radioactive Effluent Report Table 5-10 Year 2008, 245 Ft AGL (Continued)
Wind Speed STABILITY CLASS: E Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL.1 2.2 6 6 6 *6 4 5 9 3 8 2 3 5 9 2 5 6 85 2.2 4.5 20 18 9 10 17 11 10 12 20 13 18 21 19 14 23 21 256 4.5 6.7 18. 24 19 10 7 8 9 15 24 21 12 10 13 17 37 35 279 6.7 8.9 23 15 10 4 1 4 4 21 27 29 19 8 15 25 37 46 288 8.9 11.2 9 5 9 4 2 1 10 12 28 26 15 9 15 20 42 32 239 11.2 13.4 6 3 3 2 2 0 9 13 28 30 16 9 17 15 32 33 218 13.4 17.9 12 5 4 1 1 1 5 14 50 50 44 18 12 36 64 34 351 17.9 22.4 6 4 3 1 0 0 1 3 18 21 62 23 18 55 67 17 299 22.4 29.1 0 9 4 1 0 0 0 1 6 13 33 21 21 35 57 5 206 29.1 40.3 0 0 0 0 0 0 0 0 3 6 20 15 8 1 1 0 54 40.3 90 0 0 0 0 0 0 0 0 0 1 1 0 2 0 0 0 4 TOTALS 100 89 67 39 34 30 57 94 212 212 243 139 149 220 365 229 2279 Wind Speed STABILITY CLASS: F Min Max N NNE NE ENE 1 2.2 4 5 3 4 2.2 4.5 13' 17 14 22 4.5 6.7 35 17 22 16 6.7 8.9 31 19 23 5 8.9 11.2 18 7 14 6 11.2 13.4 9 0 1 3 13A 17.9 10 1 4 1 17.9 22.4 3 1 4 1 22A 29.1 1 0 2 0 29.1 40.3 0 0 0 0 40.3 90 0 0 0 0 TOTALS 124 67 87 58 E 2 8 5 3 3 1 0 0 0 0 0 22 ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 7 8 9 9 8 4 9 5 3 4 5 89 14 21 24 21 28 18 15 19 15 11 11 271 7 15 33 25 22 22 16 14 9 12 24 294 0 6 24 37 22 18 10 11 8 21 28- 266 1 8 31 36 18 15 9 2 13 17 22 220 0 2 18 18 20 6 4 6 9 23 26 146 0 6 14 17 22 19 5 6 23 28 33 189 0 0 1 6 14 12 2 3 16 18 4 85 0 0 0 0 4 10 1 3 1 7 2 31 0 0 0 0 0 1 1 0 0 0 0 2 0 0 0 0 0 0 0 0 0 0 0. 0 29 66 154 169 158 125 72 69 97 141 155 1593 Wind Speed STABILITY CLASS: G Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 4 3 5 6 8 7 5 7 4 7 6 3 4 5 0 7 81 2.2 4.5 11 20 12 17 16 6 15 29 22 28 16 16 15 10 7 13 251 4.5 6.7 21 19 22 20 13 0 7 27 27 25 15 13 7 3 7 12 238 6.7 8.9 19 18 23 8 2 2 9 24 35 14 21 5 7 3 10 28 228 8.9 11.2 19 6 6 8 2 0 3 13 29 11 9 2 4 7 7 32 158 11.2 13A 8 4 3 3 0 0 1 14 8 8 7 6 2 2 11 23 100 13A 17.9 8 0 1 2 0 0 0 9 13 4 5 0 1 5 18 21 87 17.9 22.4 2 0 0 2 0 0 2 0 2 1 1 0 0 3 5 6 24 22.4 29.1 0 0 0 0 0 0 0 1 0 1 0 0 0 0 2 4 8 29.1 40.3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40.3 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TOTALS 92 70 72 66 41 15 42 124 140 97 80 45 40 38 67 146 1175 Wind Speed STABILITY CLASS: ALL Min Max N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 1 2.2 23 30 29 31 23 30 31 30 35 22 24 25 25 16 19 29 422 2.2 4.5 87 115 89 105 63 48 72 91 108 98 .75 78 71 59 70 86 1315 4.5 6.7 130 128 118 82 35 30 57 127 126 115 88 66 61 57 96 122 1438 6.7 8.9 124 105 91 42 11 17 45 128 175 116 84. 50 50 53 94 146 1331 8.9 11.2 78 49 51 27 8 4 38 89 155 113 65 38 41 59 86 109 1010 11.2 13.4 43 19 14 12 9 3 26 63 99 .121 59 36 42 44 75 96 761 13.4 17.9 .55 33 15 6 3 5 19 45 129 145 118 64 52 96 144 105 1034 17.9 22.4 27 22 8 4 0 0 4 4 38 65 110 53 46 95 135 36 647 22.4 29.1 7 25 8 1 0 0 0 2 13 31 76 51 41 65 120 22 462 29.1 40.3 0 0 0 0 0 0 0 0 3 7 34 23 15 7 20 1 110 40.3 90 0 0 0 0 0 0 0 0 0 1 1 1 4 0 1 0 8 TOTALS 574 526 423 310 152 137 292 579 881 834 734 485 448 551 860 752 8538 A B C D E F G TOTALS CALM 0 2 8 60 30 26 43 169 Columbia Generating Station 39 2008 Radioactive Effluent Report 6.0 DOSE ASSESSMENT
-- IMPACT ON MAN Liquid Effluents
-There were no liquid discharges from the radwaste processing system to the Columbia River during calendar year 2008.Gaseous Effluents
-The NRC GASPAR II computer code was used to calculate doses at and beyond the site boundary using quarterly and annual meteorological data and site-specific variables as required and defined in the ODCM. Table 6-1 shows the highest calculated doses at the site boundary and beyond the site boundary.
Table 6-1 also shows the quarterly and annual dose for the nearest and highest exposed resident identified in the land use census. Table 6-2 lists the annual 50-mile dose using values obtained from the ALARA annual integrated population dose summary (person-rem).
Table 6-2 also provides the annual individual doses associated with each pathway. These values were obtained by dividing the ALARA integrated dose (person-rem) by the estimated year 2000 50-mile population (356,993) and converting to mrem.The highest calculated dose to a child living at locations identified in the most recent land use census was 1.06E-03 mrem to the total body, 1.1 3E-03 mrem to the thyroid, and 1.64E-03 mrem to the skin. This location was at 4.59 miles in the East sector.Periodically, Columbia Generating Station offers public tours of selected locations within the site boundary.
Calculations assumed an eight (8) hour per year exposure to the plume, ground shine, and inhalation pathways.
The organ with the highest dose was the thyroid at 7.96E-04 mrem.During 2008, Members of the Public worked at the Industrial Development area in the E and ESE sectors of the owner controlled area. The maximum dose to these individuals was also calculated assuming adult exposure to the plume, inhalation, and ground deposition pathways.The following table shows dose to Members of the Public from gaseous effluents within the site boundary of Columbia Generating Station for the total indicated hours spent at each location.Total Body Thyroid Highest Other Beta Air Gamma Hours Dose Dose Organ Dose Dose Air Dose Location Spent (mrem) (mrem) (mrem) (mrad) (mrad)Tour Visitors 8.00E+00 5.96E-04 7.96E-04 6.30E-04 9.31 E-06 2.49E-05 WNP-4 Whse.2-4 1.04E+03 2.38E-03 3.02E-03 2.78E-03 2.97E-04 7.96E-04 WNP-1 Bldg 121 2.08E+03 4.26E-03 5.05E-03 5.11E-03 5.27E-04 1.42E-03 There was no measurable direct radiation contribution from Columbia Generating Station to the tour visitors or to the workers at the WNP-1 or WNP-4 industrial areas.During the growing season, Columbia Generating Station conducts a five-mile land use census to determine the locations of nearest residents, gardens, and farm animals out to five miles in each sector. No change to land usage was found.Columbia Generating Station 40 2008 Radioactive Effluent Report The following table provides the results of annual dose calculations for the highest dose age group for each identified land use census location from gaseous effluents.
Highest Total Body Thyroid Other Organ Beta Gamma Dose Dose Dose Air Dose Air Dose Age Location (mrem) (mrem) (mrem) (mrad) (mrad) Group Resident (4.47 miles NE) 5.84E-04 6.46E-04 8.38E-04 2.22E-04 5.62E-04 Teen Resident (4.01 miles ENE) 7.06E-04 7.68E-04 9.83E-04 2.46E-04 6.11E-04 Adult Resident (4.59 miles E) 1.08E-03 1.14E-03 1.66E-03 5.33E-04 1.29E-03 Teen Resident (4.24 miles ESE) 8.80E-04 9.73E-04 1.29E-03 3.73E-04 8.76E-04 Teen The highest 'Other Organ' in all cases was the skin.For environmental thermoluminescent dosimeter (TLD) stations at or beyond the site boundary where preoperational (background) data was acquired, no increase in ambient exposure was observed in 2008 from the preoperational values.Columbia Generating Station 41 2008 Radioactive Effluent Report Dose Tables Table 6-1 Summary of Doses from Gaseous Effluents 1. Maximum Air Dose at the Site Boundary (1.2 miles)1st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Cumulative*
Beta air dose (mrad) 5.35E-04 4.98E-04 9.64E-04 9.14E-04 2.78E-03 Gamma air dose (mrad) 1.52E-03 1.41 E-03 2.31 E-03 2.59E-03 7.46E-03 2. Maximum Air Dose Beyond the Site Boundary 1st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Cumulative*
Beta air dose (mrad) 1.46E-04 3.04E-04 5.78E-04 3.15E-04 5.33E-04 Gamma air dose (mrad) 4.14E-04 8.63E-04 1.39E-03 8.93E-04 1.29E-03 3. Maximum Annual Dose at the Site Boundary Y Annual Dose Annual total body dose (mrem) 1.12E-02 Annual skin dose (mrem) 1.36E-02 4. Maximum Annual Dose Beyond the Site Boundary Annual Dose Annual total body dose (mrem) 1.11 E-03 Annual skin dose (mrem) 1 1.54E-03* Rather than the sum of the quarters, these values are based on annual meteorological data and total annual effluents.
Columbia Generating Station 42 2008 Radioactive Effluent Report Table 6-1 Summary of Doses from Gaseous Effluents (Continued)
- 5. Maximum Organ Dose at the Site Boundary (1.2 miles)1 st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Cumulative*
Maximum Organ dose (mrem) 2.54E-03 2.46E-03 7.02E-03 6.05E-03 1.44E-02 6. Maximum Organ Dose Beyond the Site Boundary I st 2nd 3rd 4th Ann ual Quarter Quarter Quarter Quarter Cumulative*
Maximum Organ dose (mrem) 4.88E-04 1.OOE-03 1.76E-03 1.16E-03 1.66E-03 7. Dose to Nearest Residents within 5-Miles in each Sector with Residents 4.47 Miles NE 1 st 2nd 3rd 4th J__Annual Quarter Quarter Quarter Quarter Cu2ltie*Beta Air Dose (mrad) 5.39E-'05 3.57E-05 8.35E-05 5.79E-05 2.22E-04 Gamma Air Dose (mrad) 1.53E-04 1.01 E-04 2.OOE-04 1.64E-04 5.62E-04 Maximum Organ dose (mrem) 2.06E-04 1.53E-04 2.70E-04 2.34E-04 8.38E-04 4.01 Miles ENE 1 st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Cumulative*
Beta Air Dose (mrad) 4.71 E-05 3.67E-05 7.43E-05 1.28E-04 2.46E-04 Gamma Air Dose (mrad) 1.34E-04 1.04E-04 1.50E-04 3.63E-04 6.11 E-04 Maximum Organ dose (mrem) 2.04E-04 1.63E-04 2.50E-04 4.98E-04 9.83E-04 4.59 Miles E 1 st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Cumulative*
Beta Air Dose (mrad) 1.46E-04 6.07E-05 3.53E-04 1.95E-04 5.33E-04 Gamma Air Dose (mrad) 4.14E-04 1.72E-04 8.47E-04 5.52E-04 1.29E-03 Maximum Organ dose (mrem) 4.88E-04 2.26E-04 1.OOE-03 6.46E-04 1.66E-03 Columbia Generating Station 43 2008 Radioactive Effluent Report Table 6-1 Summary of Doses from Gaseous Effluents (Continued)
- 7. Dose to Nearest Residents within 5-Miles in each Sector with Residents (Continued) 4.24 Miles ESE 1 st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Cumulative*
Beta Air Dose (mrad) 1.35E-04 1.52E-04 1.68E-04 7.68E-O5 3.73E-04 Gamma Air Dose (mrad) 3.83E-04 4.31E-04 3.67E-04 2.18E-04 8.76E-04 Maximum Organ dose (mrem) 4.87E-04 4.92E-04 3.36E-04 1.29E-03* Rather than the sum of the quarters, these values are based on annual meteorological data and total annual effluents.
Columbia Generating Station 44 2008 Radioactive Effluent Report Table 6-2 50-Mile Population Dose from Gaseous Effluents A. 50-mile population collective dose Exposure Total Body Max. Organ Pathway (person-rem) (person-rem)
Plume 1.60E-03 1.60E-03 Ground 1.31 E-03 1.31 E-03 Inhalation 1.29E-02 1.63E-02 Vegetables 1.15E-02 1.16E-02 Milk 4.09E-03 6.95E-03 Meat 2.08E-03 2.19E-03 Total 3.35E-02 3.99E-02 B. Average Individual' Exposure Total Body Max. Organ Pathway (mrem) (mrem)Plume 4.48E-06 4.48E-06 Ground 3.67E-06 3.67E-06 Inhalation 3.61 E-05 4.57E-05 Vegetables 3.22E-05 3.25E-05 Milk 1.15E-05 1.95E-05 Meat 5.83E-06 6.13E-06 Total 9.38E-05 1.12E-04* These values are derived by dividing the 50-mile population collective doses by the population within 50 miles of Columbia Generating Station (356,993).
The population estimate is based on the 2000 census conducted by the United States Census Bureau and documented in the Columbia Generating Station Final Safety Analysis Report. The Maximum Organ was the thyroid.Columbia Generating Station 45 2008 Radioactive Effluent Report
7.0 REVISIONS
TO THE ODCM The following revisions were made to the ODCM in 2008 as Amendment 47:* Section 3.1, Tables 3-2, 3-3, and 3-16, and Figure 3-1 revised the site boundary for dose calculation from a circle with radius of 1.21 miles to 1950 meters (approximately 1.212 miles).* Section 6.0.1 -Revised the definition of VENTILATION EXHAUST TREATMENT SYSTEM to be consistent with NUREG-1 302.* Section 6.2.2.5 and RFO 6.2.2.5 were revised by changing the Reactor Building Sump Vent Exhaust Filter System to VENTILATION EXHAUST TREATMENT SYSTEM.* SR 6.2.2.5.2 was revised to require that the VENTILATION EXHAUST TREATMENT SYSTEM comply with RFOs 6.2.2.1 and 6.2.2.3 to remain Operable.* The Bases for RFO 6.2.2.5 was revised to add examples of VENTILATION EXHAUST TREATMENT SYSTEM.8.0 REVISIONS TO THE PROCESS CONTROL PROGRAM (PCP)There were no revisions to the Process Control Program in 2008.9.0 NEW OR DELETED LOCATIONS FOR DOSE ASSESSMENTS AND/OR ENVIRONMENTAL MONITORING LOCATIONS 9.1 No new locations were identified for dose assessments as the 2008 Five-Mile Land Use Census showed no changes.9.2 There were no new locations for environmental monitoring formally adopted into the program based on the 2008 Land Use Census.9.3 No dose assessment or environmental monitoring locations were deleted.There were four TLD and air sample locations established in the fourth quarter of 2008 within the site boundary to monitor the impact of the planned remediation of the DOE 618-11 burial site. These are not associated with the effluent dose assessment program.10.0 MAJOR CHANGES TO RADIOACTIVE LIQUID, GASEOUS, AND SOLID WASTE TREATMENT SYSTEMS No major changes (as defined by ODCM Section 6.4.3) were made to the radioactive waste systems (liquid, gaseous, or solid) during this reporting period.Columbia Generating Station 46 2008 Radioactive Effluent Report