Inservice Inspection Summary Report
ML082180656
Person / Time
Site: Kewaunee 
Issue date: 07/29/2008
From: Gerald Bichof
Dominion, Dominion Energy Kewaunee
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
08-0332
Download: ML082180656 (122)


Text

Dominion Energy Kewaunee, Inc.

5000 Dominion Boulevard, Glen Allen, VA 23060 ominion July 29, 2008 ATTN: Document Control Desk Serial No. 08-0332 U. S. Nuclear Regulatory Commission LIC/GR/R0 Washington, DC 20555-0001 Docket No.: 50-305 License No.: DPR-43 DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION 2008 INSERVICE INSPECTION

SUMMARY

REPORT As required by American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Section Xl, 10 CFR 50.55a, and Wisconsin Administrative Code, Department of Commerce, Comm 41.55(3), various inservice inspection (ISI) examinations were performed during the 2008 refueling outage at the Kewaunee Power Station (KPS). The refueling outage took place from March 29, 2008 through May 9, 2008. This letter transmits the Inservice Inspection Summary Report as required by paragraph IWA-6230 of ASME Section XI.

Two separate ASME Section Xl inservice inspection programs are implemented at KPS.

One program is for pressure retaining piping/vessels and component supports, and the other program is for the metal containment.

The 2008 refueling outage inservice inspections met the requirements of these two distinct inspection programs as identified below:

a. Class 1, Class 2, and Class 3 component inspections were performed for the first inspection outage of the second period of the fourth interval. These inspections met the requirements of ASME Boiler and Pressure Vessel Code Section Xl, 1998 Edition, 2000 Addenda with implementation in accordance with the KPS Fourth Ten-Year Inservice Inspection (ISI) Program 2004-2014.
b. Class MC component inspections were performed for the first inspection outage of the first period of the second interval. These inspections met the requirements of ASME Boiler and Pressure Vessel Code Section Xl, 2001 Edition, 2003 Addenda with implementation in accordance with the KPS Second Ten-Year Inservice Inspection (ISI) Class MC Program 2006-2016.

The following examinations and tests were performed for Class 1, Class 2, and Class 3 components and their supports:

Reactor vessel closure head bare metal Reactor vessel closure head studs, nuts and washers

  • Reactor vessel threads in flange A

Serial No. 08-0332 Page 2 of 4

" Steam generator nozzle inner radius and integrally welded attachment

" Pressurizer nozzle inner radius and pressurizer heater penetrations Reactor coolant pump main flange bolting and Number 1 seal housing bolting Reactor coolant pump 1 B casing interior and flange surface

" Class 1, Class 2, and Class 3 piping and component supports,and hangers

" Class 1 valves

" Class 1 and Class 2 steam generator primary manway bolting, pressurizer manway bolting, flange bolting, and valve bonnet bolting

" Class 2 preservice examination of auxiliary feedwater piping and supports

  • Class 2 safety injection pumps integrally welded attachments and casing weld Class 1 system leakage test
  • Class 2 and Class 3 system leakage tests The following items were examined for the Class MC reactor building containment vessel:

Accessible surface areas

" Moisture barriers

" Bolted connections In addition, the following examinations were conducted in excess of ASME Boiler and Pressure Vessel Code Section Xl, 1998 Edition, 2000 Addenda requirements:

Nuclear Regulatory Commission Bulletin 2003-02, "Leakage From Reactor Vessel Lower Head Penetrations and Reactor Coolant Pressure Boundary Integrity," dated August 21, 2003

" MRP-139, "Materials Reliability Program Primary System Piping Butt Weld Inspection and Evaluation Guideline" MRP-146, "Materials Reliability Program Management of Thermal Fatigue in Normally Stagnant Non-Isolable Reactor Coolant System Branch Lines" MRP-192, "Materials Reliability Program Assessment of RHR Mixing Tee Thermal Fatigue in PWR Plants" Hydraulic snubbers were examined as required by KPS Technical Specification 4.14, "Testing and Surveillance of Shock Suppressors (Snubbers)."

Serial No. 08-0332 Page 3 of 4 Documentation summarizing the inservice inspection activities performed during the KPS 2008 refueling outage and associated results is provided in attachments 1-8 of this letter.

The final reports for these examinations are maintained in the Quality Assurance/Quality Control Records Vault at KPS.

Additionally, during the 2006 refueling outage, an NIS-2 form for 6-inch valve SI-303B (work order 05-003831) was completed. This NIS-2 form was subsequently submitted in the 2006 ISI summary report for KPS (Letter No.06-748, dated January 8, 2007).

This NIS-2 form incorrectly listed the SI-303B. valve body to bonnet as being seal welded to correct boric acid leakage. A review of data during the 2008 refueling outage determined that SI-303B was not seal welded. Rather, the valve bonnet gasket was replaced. Per ASME Boiler and Pressure Vessel Code Section XI, 1998 Edition 2000, Addenda Section IWA-4120(b)(5),

gasket replacement is exempt from repair/replacement activities.

Therefore, an NIS-2 form was not required to be submitted for this repair activity.

The next refueling outage at KPS is tentatively scheduled for the fall of 2009.

If you have questions or require additional information, please contact Mr. Craig Sly at 804-273-2784.

Very truly yours, Gerald T. Bischof Vice President - Nuclear Engineering

Serial No. 08-0332 Page 4 of 4 Attachments:

1. Summary of Recordable Indications (RIs) and Disposition
2. Summary of Class 1 and Class 2 Repair/Replacement Activities for Components 1-Inch in Diameter or Smaller
3. "Form NIS-1 Owner's Report for Inservice Inspections," Class 1, Class 2, and Class 3, Components for Fourth Ten-Year Interval
4. "Form NIS-1 Owner's Report for Inservice Inspections," Class MC Components, Second Ten-Year Interval
5. "Form NIS-2 Owner's Report for Repair/Replacement Activities" (44 Total)
6. Examination Summary, Class 1, Class 2, and Class 3 Inservice Inspection Program, Fourth Ten-Year Interval
7. Examination Summary, Class MC Inservice Inspection Program, Second Ten-Year Interval
8. Summary of Examinations that were Limited by Geometric, Metallurgical, or Design/Access Restrictions and Associated Data Sheets (30 Total)

Commitments made by this letter: NONE cc:

Regional Administrator, Region III U. S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Mr. Peter S. Tam Sr. Project Manager U.S. Nuclear Regulatory Commission One White Flint North, Mail Stop 08-H4A 11555 Rockville Pike Rockville, MD 20852-2738 NRC Senior Resident Inspector Kewaunee Power Station

Serial No. 08-0332 ATTACHMENT I 2008 INSERVICE INSPECTION

SUMMARY

REPORT

SUMMARY

OF RECORDABLE INDICATIONS (RIs) AND DISPOSITION KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Serial No. 08-0332 Page 1 of 2 Attachment I

SUMMARY

OF RECORDABLE INDICATIONS (Ris) AND DISPOSITION Type or Location of Examination No. of RIs Recordable Indication (RI)

Method (Description)

1. Reactor Building Containment Vessel General Visual 2 (Plate Moisture Barriers)
2. Reactor Building V--3 1 (Penetration No. 18 Blind Containment Vessel Flange Bolting)
3. Reactor Coolant Pump 1A Integrally Welded Liquid Penetrant 2 (Rounded Indications)

Attachment

4. Piping Supports and Visual (VT-3) 10 (Supports)

Hangers

5. Valve Bonnet Bolting Visual (VT-3) 3 (Valves)
6. System Leakage Visual (VT-2) 60 (Items)

Pressure Tests Dispositioning of Class 1, Class 2, and Class 3 indications has been completed in accordance with the rules of American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Section Xl, 1998 Edition, 2000 Addenda for Fourth Ten-Year Interval examinations.

Dispositioning of Class MC components has been completed in accordance with the rules of ASME Boiler and Pressure Vessel Code Section Xl, 2001 Edition, 2003 Addenda for Second Ten-Year Interval examinations.

Applicable codes, standards, and engineering criteria were used to disposition indications associated with the non-code-required examinations. Recordable indications for Class 1, Class 2, Class 3, and Class MC components have been summarized with their disposition as noted below:

1. General visual indications were recorded consisting of separation in the moisture barriers of two plates (62 and 67). The moisture barriers were repaired, reexamined and accepted.
2. VT-3 indications were recorded consisting of damaged threads on six bolts associated with Penetration No. 18 (Refueling Transfer Canal Blind Flange). The six bolts were evaluated and accepted by Engineering; repaired; reexamined by VT-1 (as required Code of Federal Regulations 10 CFR 50.55a(b)(2)(ix)(G) and (H)), and accepted.
3. Two rounded indications (0.175" and 0.200") were recorded on reactor coolant pump 1A integrally welded attachment RCP-CS2 during performance of liquid penetrant examination.

The two rounded indications were acceptable per ASME Boiler and Pressure Vessel Code Section XI, 1998 Edition 2000 Addenda, Table IWB-3514-2.

Serial No. 08-0332 Page 2 of 2

4. Visual (VT-3) indications were recorded on component and piping supports and hangers (10 supports). Theýe indications were (1) evaluated and accepted, or (2) repaired, reexamined, and accepted by KPS Engineering or ISI personnel.

All dispositioned indications were reviewed by the Authorized Nuclear Inservice Inspector.

5. Visual (VT-3) indications were recorded on valve bonnet bolting (three valves). These indications were repaired and/or reexamined and accepted by KPS ISI personnel and reviewed by the Authorized Nuclear Inservice Inspector.
6. Visual (VT-2) indications were recorded during system leakage pressure tests (60 items). These indications were (1) evaluated and accepted, or (2) repaired, reexamined, and accepted by KPS Engineering or ISI personnel. All dispositioned indications were reviewed by the Authorized Nuclear Inservice Inspector.

Serial No. 08-0332 ATTACHMENT 2 2008 INSERVICE INSPECTION

SUMMARY

REPORT

SUMMARY

OF CLASS 1 AND CLASS 2 REPAIR/REPLACEMENT ACTIVITIES FOR COMPONENTS I-INCH IN DIAMETER OR SMALLER KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Serial No. 08-0332 Page 1 of 1

SUMMARY

OF CLASS 1 AND CLASS 2 REPAIR/REPLACEMENT ACTIVITIES OF COMPONENTS 1 INCH IN DIAMETER OR SMALLER The following summarizes the repairs and replacements performed following the 2006 refueling outage and during the 2008 refueling outage by grinding, buffing, filing, cutting, or welding on the Class 1 and Class 2 pressure boundaries. These repairs and replacements are in addition to those itemized on the attached forms, "NIS-2 Owner's Report for Repair/Replacement Activity."

Component Class Reference Repair/Replacement Method Drawing 1" valve PR-33A 2

XK-100-10 Welding in replacement 1" valve 1" valve PR-33B 2

XK-100-10 Welding in replacement 1" valve 3/4" valve RHR-4A-1 2

XK-100-18 Welding in new 3/4" valve 3/4" valve RHR-4B-1 2

XK-100-18 Welding in new 3/4" valve 3/4" valve RHR-44 2

XK-100-18 Welding in replacement 3/4" valve 3/4" valve SI-102A 2

XK-100-28 Welding in replacement 3/4" valve 3/4" valve RHR-331 2

XK-100-29 Welding in replacement 3/4" valve 3/4" valve CVC-13 2

XK-1 00-35 Welding in replacement 3/4" valve 1" valve HG-303 2

XK-100-36 Welding in replacement 1" valve 3/8" rupture disc RC-440-3 Welding in replacement 3/8" and 2 flow control orifices 1

XK-1 00-44 rupture disc and 2 new flow control orifices 3/8" rupture disc RC-441-3 Welding in replacement 3/8" and 2 flow control orifices 1

XK-100-44 rupture disc and 2 new flow control orifices

Serial No. 08-0332 ATTACHMENT 3 2008 INSERVICE INSPECTION

SUMMARY

REPORT "FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS" CLASS 1, CLASS 2, AND CLASS 3 COMPONENTS FOURTH TEN-YEAR INTERVAL KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Page 1 of 6 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Reactor Vessel RV Replacement Reactor Vessel Closure Head Pressurizer PZR Steam Generator SG-1A Steam Generator SG-1B Excess Letdown Heat Exchanger AHEL-1A Excess Letdown Heat Exchanger AHEL-IB MANUFACTURER OR INSTALLER MANUFACTURER OR INSTALLER SERIAL NO.

STATE OR PROVINCE NO.

NATIONAL BOARD NO.

Combustion Engineering Mitsubishi Heavy Industries Westinghouse Westinghouse/

Ansaldo Energia Milano Westinghouse/

Ansaldo Energia Milano CE69202 B-VH-N06 1151 1141/0202 1142/0201 U11480 U11480 U11402 U11400 U11401 21010 5845 68-23 68-28/151 68-29/150 Sentry Sentry 3996-5E 3996-6E U11407 U11408 364 365 Class 1 Piping Reactor Coolant Pump RCP-1A Texas Pipe Bending Westinghouse 1A-1-618J871-GO1

Page 2 of 6 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER-DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - NIA
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Reactor Coolant Pump RCP-1B Residual Heat Exchanger ALIRS1-1A Residual Heat Exchanger AIHRS2-1B Regenerative Heat Exchanger ARG Letdown Heat Exchanger AHLD Seal Water Injection Filter AFSI-1A Class 2 Piping MANUFACTURER OR INSTALLER Westinghouse Joseph Oat and Sons Joseph Oat and Sons Joseph Oat and Sons Atlas Commercial Filters MANUFACTURER OR INSTALLER SERIAL NO.

1B-2-618J871-G02 STATE OR NATIONAL PROVINCE NO.

BOARD NO.

1817-IE 1817-IF 1831-13 1206 101072 U11046 U11424 U11409 U11410 U11411 U11405 344 345 413 414 415 1031 1172 Texas Pipe Bending

Page 3 of 6 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Residual Heat Removal Pump APRH1-IA Residual Heat Removal Pump APRH2-1B Refueling Water Storage Tank Auxiliary Feedwater Pump APFM-1A Motor Driven Auxiliary Feedwater Pump APFM-1B Motor Driven Auxiliary Feedwater Pump APFT Turbine Driven Class 3 Piping MANUFACTURER OR INSTALLER Byron Jackson Byron Jackson General American Transportation Company MANUFACTURER OR INSTALLER SERIAL NO.

STATE OR PROVINCE NO.

NATIONAL BOARD NO.

681N0277 681NO276 C-8297/1969 Pacific Pump Pacific Pump Pacific Pump Texas Pipe Bending 46573 46574 46575

Page 4 of 6 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Safety Injection Pump APSI-1A Safety Injection Pump APSI-1B Accumulator Tank ACC-1A Accumulator Tank ACC-1B Containment Spray Pump APCS-1A Containment Spray Pump APCS-1B Containment Spray Pump APCS-1A Gland Seal Cooler Containment Spray Pump APCS-1B Gland Seal Cooler Spent Fuel Pool Heat Exchanger AHSF MANUFACTURER OR INSTALLER Bingham Pump Bingham Pump Wyatt Wyatt Ingersoll Rand Ingersoll Rand MANUFACTURER OR INSTALLER SERIAL NO.

STATE OR PROVINCE NO.

NATIONAL BOARD NO.

290696 290697 H-5645-69 H-5644-69 0670-74 0670-75 49486938 6080694 U11397 U11398 Helliflow Helliflow Struther Wells 1-68-06-1519 U11445

Page 5 of 6 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Main Steam Moisture Separator Spent Fuel Pool Pump APSF-lA Spent Fuel Pool Pump APSF-lB Service Water Pump Strainer ASSW-1A1 Service Water Pump Strainer ASSW-1A2 Service Water Pump Strainer ASSW-1B1 Service Water Pump Strainer ASSW-1B2 Component Cooling Surge Tank ATCS Control Room Air Conditioning Unit 1A Coil MANUFACTURER OR INSTALLER Wright Austin Gould Pumps Gould Pumps S.P. Kinney Engineers S.P. Kinney Engineers S.P. Kinney Engineers S.P. Kinney Engineers Sharpsville Steel Trane Company MANUFACTURER OR INSTALLER SERIAL NO.

STATE OR PROVINCE NO.

X.R.

NATIONAL BOARD NO.

\\6008 6230 786A519.1 786A519.2 2278 2279 2280 2281 714 U11421 714 KIH202002

Page 6 of 6 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER - DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HWY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -

COMPONENT OR APPURTENANCE Control Room Air Conditioning Unit lB Coil Control Room Air Conditioning Expansion Tank 1A Control Room Air Conditioning Expansion Tank 1B Reactor Coolant Pump RCPC-1B Lube Oil Cooler MANUFACTURER OR INSTALLER Trane Company MANUFACTURER OR INSTALLER SERIAL NO.

K1H1202003 STATE OR NATIONAL PROVINCE NO.

BOARD NO.

ITT Bell and Gossett ITT Bell and Gossett Senior Engineering Company 116013 1357901

FORM NIS-1 (Back)

8.

Examination Dates:

August 29, 2007 to May 10, 2008

9.

Inspection Period Identification:

10.

Inspection Interval Identification:

11.

Applicable Edition of Section XI:

12.

Date/Revision of Inspection Plan:

2nd 4th 1998 Addenda:

2000 January 11, 2007 Rev. 2

13.

Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan.

Reference Tab C

14.

Abstract of Results of Examinations and Tests.

Reference Tab B and Tab F

15.

Abstract of Corrective Measures.

Reference Tab B and Tab F Utilization of ASME Boiler and Pressure Vessel Code Section XI Code Case: N-460 and N-566-2.

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (If applicable):

Not Applicable Expiration Date:

Not Applicable Date:

hi link, 4, 2008 Signed:

Dominion-Kewaunee By: /0*14Q C, Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of W/.a*

'.01Co514 and employed by 115'e C i of (n0, VeCr*H-have inspected the components described in this Owner's Report during the period 29,jtio*

-00,7 to

/o,0p,91WZ-01 8

, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

C 1 a 6&...,7(j o'r~ffCommissions A/N8 /,/9Z,"21/A.0W/

4/e013/

Inspector's Signature National Board, State, Province, and Endorsements Date:

/_/

-tA1C 2"

20 09

Serial No. 08-0332 ATTACHMENT 4 2008 INSERVICE INSPECTION

SUMMARY

REPORT "FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS" CLASS MC COMPONENTS SECOND TEN-YEAR INTERVAL KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1. OWNER-DOMINION ENERGY KEWAUNEE, INC.

N490 HIGHWAY 42 KEWAUNEE, WISCONSIN 54216-9511

2. PLANT - KEWAUNEE POWER STATION, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -

MANUFACTURER COMPONENT OR MANUFACTURER OR INSTALLER STATE OR NATIONAL APPURTENANCE OR INSTALLER SERIAL NO.

PROVINCE NO.

BOARD NO.

Reactor Building Chicago Bridge C4454 U11423 Containment Vessel and Iron Company Personnel Airlock Chicago Bridge C4454 U11423 and Iron Company

FORM NIS-1 (Back)

8. Examination Dates:

March 29, 2008 to May 9, 2008

9. Inspection Period Identification:
10. Inspection Interval Identification:
11.

Applicable Edition of Section XI:

12.

Date/Revision of Inspection Plan:

1st 2nd 2001.

Addenda:

2003 May 29, 2007 Revision: 2

13.

Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan.

Reference Tab C

14.

Abstract of Results of Examinations and Tests.

Reference Tab B and Tab F

15.

Abstract of Corrective Measures.

Reference Tab B and Tab F We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (If applicable):

Not Applicable Expiration Date:

Not Applicable Date:

1&1\\ -a 2008 Signed:

Dominion-Kewaunee By:

6'. /.

Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of (V /-*o Ml/

and employed by

,,ss c 7-of cOV,-'c ri cr have inspected the components described in this Owner's Report during the period 29 4 ftkc.H z60oa to 9 /i'iy zoos

, and state that to the best of my knowledge and belief, the Owner has perforned examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected wi O.L

  • '*Commissions ANB //6z-A, 8,.t*, A/

Inspector's Signat ure National Board, State, Province, and Endorsements Date:

2 7 A

2A0 20 09

Serial No. 08-0332 ATTACHMENT 5 2008 INSERVICE INSPECTION

SUMMARY

REPORT "FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITIES" (44 TOTAL)

KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energqy Kewaunee, Inc.

Date 04/23/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit Nd6 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW06-010467
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 23 Class 2 CONTAINMENT SPRAY Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped ICS-H8 ITT GRINNELL VALVE CO.

NA NA NA 1971 CORRECTED N

7. Description of Work CORRECT CLASS 2 INTERNAL CONTAINMENT SPRAY SYSTEM 6" HYDRAULIC SNUBBER ICS-H8 DUE TO OIL LEAK.
8. Tests conducted Hydrostatic DJ Pneumatic Dl Other n

Pressure Nominal Operating Pressure D1 deg. F Exempt psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 04/23/2008 Name of Component:

ICS-H8 Work Order Number: KW06-010467 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed e61 3SXOwner or Owne s

Designeeate,

20T08 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period a7cTi-0.

to 9*4)M!08, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

-'Q a4,w Commissions NB 11622,1, N, BA WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date __*__

20 0,

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Ener-gy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Enerqy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 06 Class 2 MAIN STEAM AND STEAM DUMP Date 05/23/2008 Sheet 1 of 2r Unit No. 1 Work Order KW06-001100 Type Code Sym. Stamp NA Authorization No.

Not Applicable Expiration Date Not Applicable

5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component C

SD-3A Name of I

Manufacturer FISHER CONTROLS CO.

  • anufacturer Serial No.

4950741 National Board No.

NA Other Year ID Built SD022-001 1969 Corrected, Removed, or

. Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT BY REPAIRING SEAT LEAKAGE ON CLASS 2 MAIN AUXILIARY STEAM AND STEAM DUMP SYSTEM 6" VALVE SD-3A AND PERFORMING DEFECT REMOVAL AND WELD REPAIR ON VALVE BODY.
8. Tests conducted Hydrostatic D

Other ED Pneumatic D

Pressure 975 psi Nominal Operating Pressure El Test Temp.

541 deg. F Exempt 1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

SD-3A Work Order Number: KW06-001 100 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed B&.1,L e

4 W

r

  • 5yaMJ Date 20 0a Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 70or7'o6 to 9n'0ro8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622, 1, N, B,A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date 9W51.v"

,20 ____

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1

1. Owner Dominion Enerqy Kewaunee, Inc.

Date 08/09/2007 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW06-001102
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee. Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 23 Class 2 CONTAINMENT SPRAY Expiration Date Not Applicable
5. (a) Applicable Construction Code B16.5-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

ICS-4A Name of Manufacturer TRW MISSION MANUFACTURING Manufacturer Serial No.

47571 National Board No.

NA Other Year ID Built 1CS004-003 1970 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

_;;_I

7. Description of Work INSTALL STAINLESS STEEL BONNET.

NUT ON CLASS 2 CONTAINMENT SPRAY SYSTEM 6" VALVE ICS-4A VALVE

8. Tests conducted Hydrostatic Pneumatic D Other

-]

Pressure

.Nominal Operating Pressure D

Exempt sL deg. F psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 08/09/2007 Name of Component:

ICS-4A Work Order Number: KW06-001102 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed

-&W)*V**' Date 1,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period o"ocl-o4 to c'M&YOS, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

I a4VtW4 64--.7t u Commissions NBl1622,1, N,B,A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date 9 -7we

,20

-00

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05104/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511-Sheet

.1 of 2.

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee. Wisconsin 54216-9511 Work Order KW06-012110
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 34 Class 1 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component RHR-32A Name of Manufacturer ROCKWELL INTERNATIONAL Manufacturer Serial No.

NF National Board No.

NA Other Year ID Built AC103-008 1967 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT CLASS 1 RESIDUAL HEAT REMOVAL VALVE RHR-32 DUE TO LEAKAGE.

SYSTEM 1/2" SWAGELOCK FITTING DOWNSTREAM OF 3/4"

8. Tests conducted Hydrostatic D]

Other -l Pneumatic 1-1 Nominal Operating Pressure E

Pressure 106 psi Test Temp.

87 deg. F Exempt LI

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/04/2008 Name of Component:

RHR-32A Work Order Number: KW06-012110 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed

,4 Date 2 0,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period a*7ocr06 to 9?,*1Y1oa, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

40, a, 7L*s*

Commissions NB 11622,1, N, B, A WIS 100131 IInspector's Signature

__J National Board, State, Province, and Endorsements Date 9r.4ZN'*

20 _

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/20/2008 N490 Highway 42. Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW06-012122
3. Work Performed By Dominion Enerqy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not Applicable
5. (a) Applicable Construction Code NA (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

RCP-113 Name of Manufacturer WESTINGHOUSE Manufacturer Serial No.

2-618J871 -G02 National Board No.

NA Other ID 04125 Year Built 1970 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description. of Work INSTALL REPLACEMENT REACTOR COOLANT SYSTEM REACTOR COOLANT PUMP 1B.
8. Tests conducted Hydrostatic Other El I-1 Pneumatic 1

Nominal Operating Pressure E-Pressure 2235 psi Test Temp.

546 deg. F Exempt

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/20/2008 Name of Component:

RCP-11B Work Order Number: KW06-012122 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed 7%4W**,

Date L

A

,20 o.

Owner or Owner's Designee, Tire CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period ;*7 o06o0 to Q900'8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622,1, N, B, A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date 9 -_og_

20 0_8

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/28/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW06-012125
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

FE-459 Name of Manufacturer VICKERY SIMMS INC.

Manufacturer Serial No.

National Board No.

Other ID Year Built Corrected, Removed, or Installed ASME Code Stamped NF NA 27040 1970 CORRECTED N

t

7. Description of Work CORRECT BY REPLACING GASKETS AND CHANGING FLOW ELEMENT DIRECTION ON CLASS 1 REACTOR COOLANT SYSTEM 3" FLOW ELEMENT FE-459. REPLACE 4 FLANGE STUDS AND 8 FLANGE NUTS.
8. Tests conducted Hydrostatic D]

Other El Pneumatic F]

Nominal Operating Pressure El Pressure 2235 psi Test Temp.

546 deg. F Exempt I1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/28/2008 Name of Component:

FE-459 Work Order Number: KW06-012125 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable S ig ned )U

ý

  • -Date LinG 20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period d74Cr-(>

to 9Mr'

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Q

!I-L/- nLJ Commissions NB 11622,1, N, B,A WIS 100131 Inspector's Signature J

National Board, State, Province, and Endorsements Date 9 7',ej 2

'20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 04/25/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW06-012139
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 34 Class 1 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

RHR-2A Name of Manufacturer VELAN VALVE CORPORATION Manufacturer Serial No.

GX0068 National Board No.

NA Other Year ID Built AC104-002 1972 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT GUIDE/DISC BINDING ON CLASS 1 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-2A.
8. Tests conducted Hydrostatic D

Other D Pneumatic L]

Pressure 143 psi Nominal Operating Pressure El Test Temp.

83 deg. F Exempt 1]

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 04/25/2008 Name of Component:

RHR-2A Work Order Number: KW06-012139 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signe

&WwDate20 0

Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 017o&

to 9 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB11622,1,N,B,A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9.76*Gv-

,20

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/28/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW06-014045
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SEC. III-CL.1 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component (ii*)

CVC-201A Name of Manufacturer KEROTEST MANUFACTURING Manufacturer Serial No.

ASG5-27 National Board No.

NA Other Year ID Built CS002-006 1989 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL REPLACEMENT CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-201A AND CONNECTING 2" SOCKET WELDS.
8. Tests conducted Hydrostatic Other D El Pneumatic 1

Nominal Operating Pressure E

Pressure 2235 psi Test Temp.

112 deg. F Exempt

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/28/2008 Name of Component:

CVC-201A Work Order Number: KW06-014045 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed f*,**A' 0

1*

t Date

& &02Lf2..

20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province'of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 0 C/'0"o0 to 9'IMY-08, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4-1t L~y~Commissions NB 11622,1, N, BA WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date Of

    • 46,

,20 CS

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1

1. Owner Dominion Energy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Ener-gy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Date 05/23/2008 Sheet

.1, of 2. -

Unit No. 1 Work Order KW07-000332 Type Code Sym. Stamp NA Authorization No.

Not Applicable

4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not Apl
5. (a) Applicable Construction Code ANSI B16.34 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda plicable
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped PR-1B FLOWSERVE CORP.

NBRAV-266 NA RC018-002 2003 CORRECTED N

7. Description of Work CORRECT BY LAPPING SEAT AND REPACKING DUE TO SEAT LEAKAGE CLASS 1 REACTOR COOLANT SYSTEM 3" VALVE PR-1 B.
8. Tests conducted Hydrostatic Other R

Pneumatic

-l Pressure 2235 psi Nominal Operating Pressure E

Test Temp.

546 deg. F Exempt

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

PR-1iB Work Order Number: KW07-000332 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed-

?44, M11LAA

,P Date f W 1

,20 08 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period d70cro06 to 9^4'YOS, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

C U4?tu?1J Commissions NB11622,1,N,B,A WIS100131 Inspectors Signature National Board, State, Province, and Endorsements Date q -'1gJ-"

20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

N490 Higqhway 42, Kewauriee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Energy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Date 05/01/2008 Sheet 1 of 2 Unit No. 1 Work Order KW07-001434 Type Code Sym. Stamp NA Authorization No. Not Applicable Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

CVC-2 Name of Manufacturer ANCHOR VALVE CO.

Manufacturer Serial No.

NF National Board No.

NA Other Year 1D Built CS034-001 1970 Corrected, Removed, or Installed ASME Code Stamped CORRECTED N

7. Description of Work CORRECT BODY TO BONNET LEAK ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 4" VALVE CVC-2 DUE TO BORIC ACID LEAKAGE.
8. Tests conducted Hydrostatic

[l Pneumatic D Other L Pressure 20 psi Nominal Opperating Pressure 1-7 Test Temp.

84 deg. F Exempt r:

9. Remarks NOT APPLI8CABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/01/2008 Name of Component:

CVC-2 Work Order Number: KW07-001434 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable SignedA e6 kwzzaa

&6n-,'

Date b t

,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period a"7Oc4O, to cfO, YOS, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

  • Z X,,,=tu Lu7L*t
  • .7w¶ Commissions NB 11622,l, N, B, A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date 9 -7&6;'

20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Enerqy-Kewaune N490 Higqhway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 33 Class 2 SAFETY INJECTION Date 05/28/2008 Sheet 1 of 2 Unit - No. 1..

Work Order KW07-001461 Type Code Sym. Stamp NA Authorization No.

Not Applicable Expiration Date Not Applicable

5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section X1 Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

RSI-H99 Name of Manufacturer ITT GRINNELL VALVE COMPANY Manufacturer Serial No.

NA National Board No.

NA Other ID NA Year Built 1967 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL REPLACEMENT CLASS 2 SAFETY INJECTION SYSTEM 2" HYDRAULIC SNUBBER RSI-H99.
8. Tests conducted Hydrostatic D

Other Dl Pneumatic Pressure Nominal Operating Pressure Exempt Es deg. F psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/28/2008 Name of Component:

RSI-H99 Work Order Number: KW07-001461 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed t04n 1

A0 4

7 yrlW71' Date

,20 0 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 70cr'd, to %*)`G, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

El) t a,

Commissions NB 11622,1, N, B, A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date c' 4Ojed" 20 (96

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/04/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Hi-ghway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-004994
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 34 Class 1 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SECTION VIII (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component C)

RHR-32A-3 Name of Manufacturer BS&B SAFETY SYSTEMS Manufacturer Serial No.

NA National Board No.

NA Other Year ID Built AC125-015 1997 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL REPLACEMENT CLASS 1 RESIDUAL HEAT REMOVAL SYSTEM 1/2" RUPTURE DISC RHR-32A-3.
8. Tests conducted Hydrostatic Other D1 D-1 Pneumatic Nominal Operating Pressure E

Pressure 106 psi Test Temp.

87 deg. F Exempt 1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/04/2008 Name of Component:

RHR-32A-3 Work Order Number: KW07-004994 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed t4O*f t

t Date 2T

,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period "o? 'O6 to 9MISY0'8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

aIIx 6/1 Commissions NB 11622,1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date

'?44','v 20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy Kewaunee, Inc.

Date 05/28/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-005006
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME 111-1968 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped PR-3A CROSBY, ASHTON GAGE NF NA RC008-001 1972 CORRECTED N

COMPANY

7. Description of Work CORRECT BY REPAIRING CLASS 1 REACTOR COOLANT SYSTEM 6" VALVE PR-3A DUE TO EQUIPMENT RELIABILTY CONCERNS.
8. Tests conducted Hydrostatic Other Pneumatic r--

Nominal Operating Pressure El Pressure 2235 psi Test Temp.

546 deg. F Exempt r-

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/28/2008 Name of Component:

PR-3A Work Order Number: KW07-005006 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed Date

  • E L

,20 L

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 2 70TO(

to 9"4,06'*., and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

C!IZI)a-mi L2& nwU Commissions -NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 49rVe'

,20 CIS

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/20/2008 N490 Hi-ghway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-007979
3. Work Performed By Dominion Ener-gy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component FE-27016 Name of Manufacturer SIEMANS WATER TECHNOLOGY Manufacturer Serial No.

N-6057 National Board No.

NA Other ID NA Year Built 2007 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" AND 1/2" PIPING, WELDS. VALVES AND FLANGES FOR 3" VENTURI SYSTEM FOR FLOW ELEMENT FE-27016.
8. Tests conducted Hydrostatic D

Other D Pneumatic Nominal Operating Pressure 1-7 Pressure 1560 psi Test Temp.

81 deg. F Exempt 1-1

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/20/2008 Name of Component:

FE-27016 Work Order Number: KW07-007979 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed Dt 7

  • '/,U'/tf.A* Date "7

,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owners Report during the period 6ocT'06 to 9/V*J'O

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

)

C (4,7(-"

Commissions NB 11622, 1, N, B,A WIS 100131 Inspector's Signature Date TT71hNe "

,20 08 National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy Kewaunee, Inc.

Date 05/08/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-007980
3. Work Performed By Dominion Enerqy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component

()

FDW-H239 Name of Manufacturer DOMINION ENERGY Manufacturer Serial No.

NA National Board No.

NA Other ID NA Year Built 2008 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" PIPE SUPPORT FDW-H239.
8. Tests conducted Hydrostatic El]

Other Li Pneumatic Pressure Nominal Operating Pressure psi Test Temp.

Li deg. F Exempt

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/08/2008 Name of Component:

FDW-H239 Work Order Number: KW07-007980 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed An o C*:*~y

  • 'Y*

(U,/1.R Dte

'7

,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period Q70crO0 to ?,X+118, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

&------4,,ed L7C*e.4(...4.

Commissions NB 11622,1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9,..OAI.F

,20 C8

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/08/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-007980
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

FDW-H240 Name of Manufacturer DOMINION ENERGY Manufacturer Serial No.

NA National Board No.

NA Other ID NA Year Built 2008 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" PIPE SUPPORT FDW-H240.
8. Tests conducted Hydrostatic E]

Other 1 Pneumatic Pressure Nominal Operating Pressure psi Test Temp.

D Exempt Es deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/08/2008 Name of Component:

FDW-H240 Work Order Number: KW07-007980 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed A &,J,*'i.A420410.,

6 d,, Date A2 20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period

) VrM6 to 9

,*YO 8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

  • Q t,,W.*-"

Commissions NB 11622,1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9'

,,IAIVE'

,20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enermy Kewaunee, Inc.

Date 05/23/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-007980
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SEC. I11-1989 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped AFW-2A SPX PROCESS EQUIPMENT 0720-142-154-1-1 NA F032-001 2007 INSTALLED N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-2A AND 3" PIPING WELDS.
8. Tests conducted Hydrostatic Other Pneumatic 1

Nominal Operating Pressure Pressure 1560 psi Test Temp.'

81 deg. F Exempt I--

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

AFW-2A Work Order Number: KW07-007980 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable S ig ned Aono22aw&

L/,

z**

'L'I D a te Lmv

,20 _V__

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period Q 70.e"0 to q'lIt'o8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Q Inse7W Commissions NB11622,1, N,B,A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date 4.4ZAl" 20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/23/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511.

Sheet.

1' of 2-

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-007980
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B1 6.34 CLASS 900 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped AFW-3A WILLIAM POWELL 89954 NA F025-001 1992 INSTALLED N

COMPANY

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-3A, 3" FLOW RESTRICTION AND 3" PIPING WELDS.
8. Tests conducted Hydrostatic r--

Pneumatic E-Nominal Operating Pressure Exempt D Other l Pressure 1560 psi Test Temp.

B1 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

AFW-3A Work Order Number: KW07-007980 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed A*7 a

Ja/

E 4/Aflj 6 'ut.,l* Date 20 0 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period X7o0010 to __,__O_.,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/I InspectorsSin ur-Commissions NB 11622,o1, N, B,tA WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9.nwv

,20 L9

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy Kewaunee, Inc.

Date 05/23/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of.2.

2. Plant Kewaunee Power Station Unit No. 1 N490 Hi-ghway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-007980
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SEC. III 1989 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

AFW-10A Name of Manufacturer National Manufacturer Serial No.

Board No.

SPX PROCESS EQUIPMENT 0720-142154-2-1 NA Other ID F033-001 Year Built 2007 Corrected, Removed, or Installed ASME Code Stamped INSTALLED N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-10A AND 3" PIPING WELDS.
8. Tests conducted Hydrostatic Other LI

--]

Pneumatic F]

Pressure 1560 psi Nominal Operating Pressure M

Test Temp.

81 deg. F Exempt r-

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

AFW-10A Work Order Number: KW07-007980 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed

&0YW,

  • Date L

1 20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period o706-06' to %"91ft4CO8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

eCommissions NB 11622,S1, N, B, A PWIS 100131 IeInspector's Signature National Board, State, Province, and Endorsements Date 94?Ar

,20 O_

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Energy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Date 05/27/2008 Sheet 1 of 2 Unit No. 1 Work Order KW07-007980 Type Code Sym. Stamp NA Authorization No.

Not Applicable Expiration Date Not Applicable

5. (a) Applicable Construction Code ASME SECTION III CL2 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

AFW-40A Name of Manufacturer KEROTEST MANUFACTURING Manufacturer Serial No.

ASN6-21 National Board No.

NA Other ID NA Year Built 1989 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 1 1/2" VALVE AFW-40A AND 1 1/2" PIPING WELDS.
8. Tests conducted Hydrostatic D

Other L]

Pneumatic Pressure 1560 psi Nominal Operating Pressure Test Temp.

81 deg. F Exempt 1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/27/2008 Name of Component:

AFW-40A Work Order Number: KW07-007980 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed 29.4*

1 1 k&D

_b*"*LO/ZA evvi?26)lq

.A. Date 20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period Q7OCTOM to 9M/W01

, and state that to the best of my knowledge and belief, the Owner-has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4w 6,u-7 Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date_ _

20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/23/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-008253
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 36 Class 1
  • REACTOR COOLANT Expiration Date Not Applicable
5. (a) Applicable Construction Code B16.5-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component i

PR-2B Name of Manufacturer MASONEILAN INTERNATIONAL Manufacturer Serial No.

H-20693-5-1 National Board No.

NA Other Year ID Built RC012-001 1969 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT DUE TO SEAT LEAKAGE ON CLASS 1 REACTOR COOLANT SYSTEM 3" VALVE PR-2B BY REPLACING INTERNALS AND REPACKING VALVE.
8. Tests conducted Hydrostatic D

Other D Pneumatic Nominal Operating Pressure

[*

Pressure 2235 psi Test Temp.

546 deg. F Exempt r-

9. Remarks NOT APPLICABLE.

I Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

PR-2B Work Order Number: KW07-008253 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed 4*a &T/1P.W1 rAl.

66Mlu a

4, Date j

,20 09 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 67

-OC(. to 9^0*'0O8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

(=

).n Commissions NB 11622,1, N, B, A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date 7.7Vv6 20 Oe

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enermy Kewaunee, Inc.

Date 05/04/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No.1 1 N490 Higqhway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-012232
3. Work Performed By Dominion Ener-gy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 33 Class 2 SAFETY INJECTION Expiration Date Not Applicable
5. (a) Applicable Construction Code B16.5-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

SI-351B Name of Manufacturer CRANE CO.

Manufacturer National Serial No.

Board No.

546CAK116878B NA N

Other Year ID Built AC020-004 1972 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT SEAT LEAKAGE OF CLASS 2 SAFETY INJECTION SYSTEM 12" VALVE SI-351B BY REMOVING 0.037" METAL ON VALVE DISC AND REPLACING GASKET.
8. Tests conducted Hydrostatic 0

Other MI Pneumatic LI Pressure 100 psi Nominal Operating Pressure El Exempt 1-Test Temp.

80 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/04/2008 Name of Component:

SI-351B Work Order Number: KW07-012232 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed p.

j

(/*

    • /,C2.CJ

/late 20 0 Owner or Owner's Designee, Title 2008 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period o70crO6 to 7?1i9n'OS, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

a,,"Zýu "

Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date-9

/'

20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 10/29/2007 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1-of. 2.

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW07-013140
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not Applicable
5. (a) Applicable Construction Code B16.5-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

PS-1B Name of Manufacturer MASONEILAN INTERNATIONAL Manufacturer Serial No.

National Board No.

Other Year ID Built RC013-001 1970 Corrected, Removed, or Installed ASME Code Stamped H-20694-1-2 NA INSTALLED N

7. Description of Work DISASSEMBLE AND REBUILD CLASS 1 REACTOR COOLANT SYSTEM 3" VALVE PS-1iB WITH A REPLACEMENT GASKET AND INSTALLATION OF REPLACEMENT STAINLESS STEEL 8 VALVE BONNET STUDS AND 8 VALVE BONNET NUTS.
8. Tests conducted Hydrostatic Other Pneumatic LI Pressure 2236 psi Nominal Operating Pressure El Test Temp.

547 deg. F Exempt 1

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 10/29/2007 Name of Component:

PS-iB Work Order Number: KW07-013140 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed 7'J4 a

JAi&/d9UW)

Date k ]

20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period QR77-"

to q,9^Yo6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB11622,1,N,B,A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date 9.-q,,v" 20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Ener-gy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Energy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Date 03/06/2008 Sheet 1 of 2 Unit No. 1 Work Order KW07-013314 Type Code Sym. Stamp NA Authorization No.

Not Applicable Expiration Date Not Applicable

5. (a) Applicable Construction Code SEC.III-CL2 1980 ADD (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

APSS-1B Name of Manufacturer GREER HYDRAULICS Manufacturer Serial No.

GH1-10235 National Board No.

569 Other ID 162-936 Year Built 1981 Corrected, Removed, or Installed CORRECTED ASME Code Stamped Y

7. Description of Work CORRECT BY REPAIRING PIPE PLUG BORIC ACID LEAK ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1 B SUCTION STABILIZER 3" FLANGE.
8. Tests conducted Hydrostatic D

Other n

Pneumatic 1

Pressure 25 psi Nominal Operating Pressure M

Exempt s

Test Temp.

100 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 03/06/2008 Name of Component:

APSS-11B Work Order Number: KW07-013314 CERTIFICATE OF COMPLIANCE I certify that the statements made in the-report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed Date 20 08 Ownev oOnr D T

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owners Report during the period 270cro 6 to q mrYoS, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

(

a&.Q*-

Commissions NB 11622,1, N, B, A WIS 100131 Inspectors Signature National Board, State, Province, and Endorsements Date

'.,70A1157

.20 _

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/20/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 -of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100322618
3. Work Performed By Dominion Ener-gy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ED Built Installed Stamped FE-27017 SIEMANS WATER N-6058 NA NA 2007 INSTALLED N

TECHNOLOGIES

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" AND 1/2" PIPING, WELDS, VALVES AND FLANGES FOR 3" VENTURI SYSTEM FOR FLOW ELEMENT FE-27017.
8. Tests conducted Hydrostatic j

Other R

Pneumatic 1

Pressure 660 psi Nominal Operating Pressure E'

Test Temp.

77 deg. F Exempt [1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/20/2008 Name of Component:

FE-27017 Work Order Number: KW100322618 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed ;JA-tA Date "1

.20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 0'706'0' to 9M,9lbO

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB11622,1,N,BA WIS 100131 Inspectors Signature

__J National Board, State, Province, and Endorsements Date 9' ýj*'A6' 20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/08/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100322641
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

FDW-H235 Name of Manufacturer DOMINION ENERGY Manufacturer Serial No.

NA National Board No.

NA Other Year ID Built NA 2008 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER.SYSTEM 3" PIPE SUPPORT FDW-H235.
8. Tests conducted Hydrostatic E]

Pneumatic D Other LI Pressure Nominal Operating Pressure 11 Exempt Es deg. F psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/08/2008 Name of Component:

FDW-H235 Work Order Number: KW100322641 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to therequirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed 6

dOwner or Date De20gnee Tl0 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period t7o7MO4 to Q

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

6 4d,*t.&'7r'*n c

_Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 90/ 4V,7 g?

,20

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Energy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Date 05/08/2008 Sheet 1 of 2 Unit No.1 Work Order KW100322641 Type Code Sym. Stamp NA Authorization No.

Not Applicable Expiration Date Not Applicable

5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O)

FDW-H236 Name of Manufacturer DOMINION ENERGY Manufacturer Serial No.

NA National Board No.

NA Other ID NA Year Built 2008 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" PIPE SUPPORT FDW-H236.
8. Tests conducted Hydrostatic Pneumatic D]

Other

--1 Pressure Nominal Operating Pressure E]

Exempt E]

deg. F psi Test Temp.

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/08/2008 Name of Component:

FDW-H236 Work Order Number: KW100322641 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed

//

J_

&V0212&WA'L Date 20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 070crTO(

to 9Mftroe, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 11622,1, N, B,A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9-.7Z4M65

,20 (0

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy Kewaunee, Inc.

Date 05/08/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2.

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100322641
3. Work Performed By Dominion Enerqy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

FDW-H238 Name of Manufacturer DOMINION ENERGY Manufacturer Serial No.

NA National Board No.

NA Other ID NA Year Built 2008 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" PIPE SUPPORT FDW-H238.
8. Tests conducted Hydrostatic D

Other D Pneumatic Pressure Nominal Operating Pressure psi Test Temp.

i"i Exempt deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/08/2008 Name of Component:

FDW-H238 Work Order Number: KVV100322641 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed Date KW

"]

,20 0, Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period R7/00.016 to ef W19PI013, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

3ZZ (

t&2(##j 5-fl--

4*

Commissions NB 11622,1,N,B,A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date Ct.,/-- /'e

,20 e L3

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Energy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Date 05/23/2008 Sheet 1 of 2 Unit No. 1 Work Order KW100322641 Type Code Sym. Stamp NA Authorization No.

Not Applicable Expiration Date Not Applicable

5. (a) Applicable Construction Code ASME SECT. III 1989 (c) Applicable Section X1 Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped AFW-2B SPX PROCESS EQUIPMENT 0720-14254-1-2 NA F032-002 2007 INSTALLED N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-2B AND 3" PIPING WELDS.
8. Tests conducted Hydrostatic

-]

Other

['-

Pneumatic Pressure 660 psi Nominal Operating Pressure Test Temp.

77 deg. F Exempt

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

AFW-2B Work Order Number: KW100322641 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed f~

i'/3

-AlIJ Mrno,*

AA, J IW?1.

Date

,20,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period d7"06'06 to 90MtY08, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal~injury or property damage or a loss of any kind arising from or connected with this inspection.

C Commissions NB 11622,1,N, B,A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 6 -'v,'

20 498

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Energy-Kewaune N490 Highway 42, Kewaunee, Wisconsin 54216-9511
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Date 05/23/2008 Sheet 1 of 2-Unit No. 1 Work Order KW100322641 Type Code Sym. Stamp NA Authorization No. Not Applicable Expiration Date Not Applicable
5. (a) Applicable Construction Code B16.34 CLASS 900 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

AFW-3B Name of Manufacturer WILLIAM POWELL COMPANY Manufacturer Serial No.

89954-1 National Board No.

NA Other ED F025-002 Year Built 1992 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-3B, 3" FLOW RESTRICTION AND 3" PIPING WELDS.
8. Tests conducted Hydrostatic Other Li n

Pneumatic []

Nomir P

Pressure 660 psi al Operating Pressure 17 Test Temp.

77 deg. F Exempt El

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

AFW-3B Work Order Number: KW100322641 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed

&wf LV/..

('/,*

Date 200_

Owner or Owner's Designee, fitle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period Q7O-rO6 to 9^0r96, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

s npe?

S tCommissions NB 11622,1,BN,rB,A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9 -7V#4 "

,20

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/23/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Hi-ghway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100322641
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SEC. 111-1989 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O_*

AFW-10B Name of Manufacturer National Manufacturer Serial No.

Board No.

SPX PROCESS EQUIPMENT 0720-142154-2-2 NA Other ID F033-002 Year Built 2007 Corrected, Removed, or Installed ASME Code Stamped INSTALLED N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-10B AND 3" PIPING WELDS.
8. Tests conducted Hydrostatic D

Other -1 Pneumatic

]

Nominal Operating Pressure Ei Pressure 660 psi Test Temp.

77 deg. F Exempt

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/23/2008 Name of Component:

AFW-10B Work Order Number: KW100322641 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable SignedA*.

A 4024*-4 W-41 Date,4-1&

,20

_Q.

Owner or Owner's Designee, Title V

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period aX7=7TO6 to 9

-n'O6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

QIns&4,Ur Commissions NB 11622,a1, N, B, A WIS 100131 Inspectors Signature -- /National Board, State, Province, and Endorsements Date 9,,'ri t4"

,20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/27/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1' N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100322641
3. Work Performed By Dominion Ener-gy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SECTION III CL2 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

AFW-40B Name of Manufacturer KEROTEST MANUFACTURING Manufacturer Serial No.

ASN1-19 National Board No.

NA Other ID NA Year Built 1989 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL CLASS 2 AUXILIARY FEEDWATER SYSTEM 1 1/2" VALVE AFW-40B AND 1 1/2" PIPING WELDS.
8. Tests conducted Hydrostatic Other L LI Pneumatic LI Pressure 660 psi Nominal Operating Pressure E-Test Temp.

77 deg. F Exempt [1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/27/2008 Name of Component:

AFW-40B Work Order Number: KW100322641 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed 61y---&Wt--60\\12,tae 20 Q._

Owner or Owner's Designee, Title' CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 6 70oc0O0 to 9? MY08, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Q

') a*ng U4-7t~a-nttzý Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 94 0 mnj-

,20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy Kewaunee, Inc.

Date 05/20/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant
  • Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100328995
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 36 Class 1 REACTOR COOLANT Expiration Date Not Applicable
5. (a) Applicable Construction Code NA (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

RCP-1B Name of Manufacturer WESTINGHOUSE Manufacturer Serial No.

2-618J871-G02 National Board No.

NA Other ID 04125 Year Built 1970 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT BY WELDING REACTOR COOLANT SYSTEM CLASS 1 REACTOR COOLANT PUMP 1B MAIN FLANGE GASKET AREA.
8. Tests conducted Hydrostatic D

Other r-D Pneumatic 1--

Nominal Operating Pressure E-Pressure 2235 psi Test Temp.

546 deg. F Exempt

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/20/2008 Name of Component:

RCP-1 B Work Order Number: KW100328995 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable S ig n ed A

QAQ XU ZM40.C--22 &V140./,0' Date A

.ýý 7

,20 jO

'Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period a67 00"06 to 9 4*fOt, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

a Commissions NB 11622, I, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date q..-,T7zJw e

,20 4

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enerqy Kewaunee, Inc.

Date 05/04/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2..

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100362143
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 34 Class 1

RESIDUAL HEAT REMOVAL Expiration Date Not Applicable

5. (a) Applicable Construction Code ASME SECTION VIII (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped RHR-30B-3 BS&B SAFETY SYSTEMS NA NA NA 1997 INSTALLED N

7. Description of Work INSTALL REPLACEMENT CLASS 1 RESIDUAL HEAT REMOVAL SYSTEM 1/2" RUPTURE DISC RHR-30B-3.
8. Tests conducted Hydrostatic D

Other D Pneumatic D

Nominal Operating Pressure M

Pressure 221 psi Test Temp.

82 deg. F Exempt r-1

9. Remarks NOT APPLICABLE.

)

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/04/2008 Name of Component:

RHR-30B-3 Work Order Number: KW100362143 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed d---LWM/at&_ý_

W2M,6W "W Date l

,2008 Owner or Owner's Designee, ýitle r

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period Q"7o0oo to _________,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

44Ine ctor Commissions NB 11622,B1, N B, A WIS 100131 Inspcto's SgnaureNational Board, State, Province, and Endorsements Date 9 -7"ON6"

,20 O 6

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/15/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2-

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100364153
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code SEC. VIII DIV.1-1975 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Corrected, ASME Name of Name of Manufacturer National Other Year Removed, or Code Component Manufacturer Serial No.

Board No.

ID Built Installed Stamped APD-IA GREER HYDRAULICS GHI-1848 NA 07000 1975 CORRECTED N

7. Description of Work REBUILD CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1A PULSATION DAMPENER.
8. Tests conducted Hydrostatic Other Elr Pneumatic r-Pressure 2245 psi Nominal Operating Pressure El Test Temp.

111 deg. F Exempt 1-]

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/15/2008 Name of Component:

APD-1A Work Order Number: KW100364153 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable SignedA d

J**fl4'Gv 4I2.t7v

_et, '

6W,*

JDate 2

-- 620 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 07OC7'04 to 9

,O6, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

(2---aIII

.,,*.g 4

.L'

-?w Commissions NB 11622, I, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9 -J.',v*

20 0

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 04/26/2008 N490 Hi-ghway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100364544
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component RHR-7B Name of Manufacturer Manufacturer Serial No.

CRANE VALVE COMPANY NF National Board No.

NA Other Year ID Built AC010-006 1972 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT BORIC ACID LEAKAGE ON CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-7B BY REPLACING GASKET. REPLACED 1 FLANGE STUD.
8. Tests conducted Hydrostatic Other D E-Pneumatic Nominal Operating Pressure M

Pressure 144 psi Test Temp.

83 deg. F Exempt 1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 04/26/2008 Name of Component:

RHR-7B Work Order Number: KW100364544 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signedd' Date L

1 20 0-Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period a7o06o0 to 9'/J?*

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

~1IZII~ancs 6~L~~nde(Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9 _.rlwe

,20 O8

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/03/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100368442
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 05B Class 2 AUXILIARY FEEDWATER Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component (9

FDW-H72A Name of Manufacturer ITT GRINNEL COMPANY Manufacturer Serial No.

NA National Board No.

NA Other ID NA Year Built 1967 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

-- I

7. Description of Work CORRECT CLASS 2 - 3" AUXILIARY FEEDWATER SYSTEM SUPPORT FDW-H72A DUE TO BENT SUPPORT ROD.
8. Tests conducted Hydrostatic E'

Other Pneumatic EL Pressure Nominal Operating Pressure psi Test Temp.

Exempts deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/03/2008 Name of Component:

FDW-H72A Work Order Number: KW100368442 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed,AI2J,

/3 O

J 1

&W._ U1 Date J

.20 Owner or Owner's Designee, Tite V

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 01"7MT19-to o/N06Y715, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

1ZI4.m4M62Id-e4 Commissions NB 11622,1, N,B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9-"V*,'

20 __

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

'1. Owner Dominion Enermy Kewaunee, Inc.

Date 05/20/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100370328
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable

'4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable

5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component CVC-10 Name of Manufacturer KEROTEST MFG CORP Manufacturer Serial No.

NV-143 National Board No.

NA Other Year 1]D Built CS100-005 1973 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT BY REPAIRING SEAT LEAK ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-10 INCLUDING REMOVING VALVE BONNET SEAL WELD.
8. Tests conducted Hydrostatic Other El Pneumatic E:

Pressure 2240 psi Nominal Operating Pressure Test Temp.

517 deg. F Exempt 1

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/20/2008 Name of Component:

CVC-10 Work Order Number: KW100370328 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed QW.P&V Date k

i 2006 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period To7'oZ to.9"',oW8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

C4~.Commissions NB11622,, N,B,A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9

&'At7 '

20

'e

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/04/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2,

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100370405
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 34 Class 1 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component RHR-1A Name of Manufacturer VELAN VALVE CORPORATION Manufacturer Serial No.

NF National Board No.

NA Other Year ID Built AC104-001 1972 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work SEAL WELD BODY TO BONNET ON CLASS 1 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-1A DUE TO EVIDENCE OF LEAKAGE.
8. Tests conducted Hydrostatic LI Other El Pneumatic Nominal Operating Pressure Pressure 106 psi Test Temp.

87 deg. F Exempt L-

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/04/2008 Name of Component:

RHR-1A Work Order Number: KW100370405 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed Date 20 0 Owner or Owner's Designee, Title V.

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period a7o"'o6 to c,")o1, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

c----------47(e.¶*

Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date cp4Ivc"

,20 08

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/04/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100373127
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 34 Class 1 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable.Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component RRHR-H2 Name of Manufacturer ITT GRINNELL VALVE COMPANY Manufacturer Serial No.

National Board No.

Other ID Year Built Corrected, Removed, or Installed ASME Code Stamped NA NA NA 1967 CORRECTED N

7. Description of Work CORRECT CLASS 1 RESIDUAL HEAT REMOVAL SYSTEM 8" SUPPORT RRHR-H2 DUE TO LOOSE TENSION ROD AND LOOSE PIPE CLAMP BOLT.
8. Tests conducted Hydrostatic D-Other D1 Pneumatic Pressure Nominal Operating Pressure psi Test Temp.

L Exempt 177 deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/04/2008 Name of Component:

RRHR-H2 Work Order Number: KW100373127 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code-Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed ; A*

6JA

&nd

  • {4Date

,20 Owner or Owner's Designee, Titlev CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 27oclro6 to ___1___8

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB11622,1,N,B,A WIS100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9

20 0 8

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Enermy Kewaunee, Inc.

Date 05/02/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511' Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100373181
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp N/

N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No.

Not Applicable

4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME III CLASS C (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component ARG Name of Manufacturer JOSEPH OAT AND SONS Manufacturer Serial No.

National Board No.

Other ID Year Built Corrected, Removed, or Installed ASME Code Stamped 1831-1B 413 TO 415 00059 1970 CORRECTED Y

7. Description of Work REPAIR CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM REGENERATIVE HEAT EXCHANGER LOOSE NUT ON SUPPORT BRACKET.
8. Tests conducted Hydrostatic D

Other L]

Pneumatic L Pressure Nominal Operating Pressure psi Test Temp.

1]

Exempt El deg. F

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/02/2008 Name of Component:

ARG Work Order Number: KW100373181 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Date 4 T

20 Owner or Owner's Designee, Title V

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period Q 70er--

to 9 /ltw-'oB, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

(=

-III) at4x 6txf 4(w,nt'z1q Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature

-Jg National Board, State, Province, and Endorsements Date 9 4VA"

,20

-9

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee. Inc.

N490 Highway 42, Kewaunee, Wisconsin 54216-9511

2. Plant Kewaunee Power Station N490 Highway 42, Kewaunee, Wisconsin 54216-9511
3. Work Performed By Dominion Enerqy-Kewaune N490 Highway 42, Kewaunee. Wisconsin 54216-9511
4. Identification of System 34 Class 1 RESIDUAL HEAT REMOVAL Date 05/29/2008 Sheet 1 of 2 Unit No. 1 Work Order KW100375143 Type Code Sym. Stamp NA Authorization No. Not Applicable Expiration Date Not Applicable
5. (a) Applicable Construction Code ASME SECTION VIII (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

RHR-32A-3 Name of Manufacturer Manufacturer Serial No.

BS&B SAFETY SYSTEMS NA National Board No.

NA Other Year ID Built AC125-015 1997 Corrected, Removed, or Installed INSTALLED ASME Code Stamped N

7. Description of Work INSTALL REPLACEMENT CLASS 1 RESIDUAL HEAT REMOVAL SYSTEM 1/2" RUPTURE DISC RHR-32A-3.
8. Tests conducted Hydrostatic

]

Pneumatic D Other Pressure Nominal Operating Pressure 11 Exempt Es deg. F psi Test Temp.

9. Remarks NOT APPLICABLE.

2 Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/29/2008 Name of Component:

RHR-32A-3 Work Order Number: KW100375143 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this INSTALLED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed T,!W:xZ#V AVV2V &Utrd/y/ate A c

Iae20 Ie Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period Q70crol-to ________,

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

6IZII_.*

Commissions NB 11622,1,N,B,A WIS 100131 Inspector's Signature Date I...

20

_"_,20 6

_S National Board, State, Province, and Endorsements

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/20/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100375164
3. Work Performed By Dominion Ener-gy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section Xl Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

CVC-10 Name of Manufacturer KEROTEST MFG CORP Manufacturer Serial No.

NV-143 National Board No.

NA Other Year ID Built CS100-005 1973 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT SEAT LEAKAGE INCLUDING SEAL WELDING BODY TO BONNET ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-10.
8. Tests conducted Hydrostatic D]

Other I-Pneumatic Nominal Operating Pressure Pressure 2240 psi Test Temp.

571 deg. F Exempt 1

9. Remarks NOT APPLICABLE.

Applicable Manufacturers Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/20/2008 Name of Component:

CVC-10 Work Order Number: KW100375164 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable S ig nedP vo*

_b-T*

/,U Date &

,20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 70c7-067-'O to 9 M006, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Insct Sigatue-Commissions NB 11622,B1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date c

20 __8

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1

1. Owner Dominion Energy Kewaunee, Inc.

Date 05/05/2008 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Sheet 1 of 2

2. Plant Kewaunee Power Station Unit No. 1 N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Work Order KW100375316
3. Work Performed By Dominion Energy-Kewaune Type Code Sym. Stamp NA N490 Highway 42, Kewaunee, Wisconsin 54216-9511 Authorization No. Not Applicable
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL Expiration Date Not Applicable
5. (a) Applicable Construction Code B31.1-1967 (c) Applicable Section XI Code Case NA (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1998 Edition 2000 Addenda
6. Identification of Components Name of Component O

RHR-8A Name of Manufacturer Manufacturer Serial No.

FISHER CONTINENTAL CO. 141550 National Board No.

NA Other Year ED Built AC012-001 1972 Corrected, Removed, or Installed CORRECTED ASME Code Stamped N

7. Description of Work CORRECT BY REPAIRING CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-8A DUE TO BORIC ACID LEAKAGE REPLACED 12 VALVE FLANGE STUDS AND 24 VALVE FLANGE NUTS
8. Tests conducted Hydrostatic Other

-]

Pneumatic l

Nominal Operating Pressure M

Pressure 409 psi Test Temp.

110 deg. F Exempt LI

9. Remarks NOT APPLICABLE.

Applicable Manufacturer's Data Reports to be Attached

NIS-2 (Back)

Sheet 2 of 2 Date: 05/05/2008 Name of Component:

RHR-8A Work Order Number: KW100375316 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this CORRECTED conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NA Certificate of Authorization No.

Not Applicable Expiration Date Not Applicable Signed 1Th a

A f

u t

Date 20 Q Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Insurance Company of CT have inspected the components described in this Owner's Report during the period 2-70,"oT6 to 9'1*Yo8, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

(::II) a,"w 4 WLVlý Commissions NB 11622, 1, N, B, A WIS 100131 Inspector's Signature National Board, State, Province, and Endorsements Date 9 q-abU& 6

,20

Serial No. 08-0332 ATTACHMENT 6 2008 INSERVICE INSPECTION

SUMMARY

REPORT EXAMINATION

SUMMARY

CLASS 1, CLASS 2, AND CLASS 3 INSERVICE INSPECTION PROGRAM FOURTH TEN-YEAR INTERVAL KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION 4TH INTERVAL: 2ND PERIOD: 1ST OUTAGE 2008 EXAMINATION

SUMMARY

INTRODUCTION An Inservice Inspection (ISI) Program (Scheduled and Augmented) was performed at the Kewaunee Power Station from August 29, 2007 through March 27, 2008 (Non Refueling Outage), March 29, 2008 through May 9, 2008 (Closing of GI following Refueling Outage) and May 10, 2008 (following closing of G1) by Kewaunee Power Station and Lambert, MacGill, and Thomas, Inc.(LMT Inc.) examination personnel.

Examinations were performed to satisfy the requirements of:

  • ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda

" United States Nuclear Regulatory Commission Generic Letter 88-05 "Boric Acid Corrosion of Carbon Steel Reactor Coolant Boundary Components in PWR Plants"

" United States Nuclear Regulatory Commission EA-03-009 Revision 1: Issuance of First Revised NRC Order (EA-03-009) Establishing Interim Inspection Requirements For Reactor Pressure Vessel Heads at Pressurized Water Reactors

" Materials Reliability Program MRP-139 Primary System Piping Butt Weld Inspection and Evaluation Guideline e-Materials Reliability Program MRP-146 Management of Thermal Fatigue in Normally Stagnant Non-Isolable Reactor Coolant Branch Lines

" Materials Reliability Program MRP-192 Assessment of RHR Mixing Tee Thermal Fatigue in PWR Plants

" Westinghouse NASL-06-8: Pressurizer Heater Sleeve Cracking The Inservice Inspection Program Plan and Augmented Inspection Program Plan located under Tab C was prepared by Kewaunee Power Station for the 4th Interval: 2nd Period: 1 st Outage as identified in the Kewaunee Power Station Fourth 10-Year Inservice Inspection (ISI) Program 2004 - 2014. Examinations during this Refueling Outage were performed to commence 4th Interval; 2nd Period Examination Requirements of ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda and Kewaunee Power Station Fourth 10-Year Inservice Inspection (ISI) Program 2004-2014.

Page 1 of 4

The following items were examined:

" Reactor Vessel Closure Head Bare Metal

" Reactor Vessel Closure Head Studs, Nuts and Washers

" Reactor Vessel Threads in Flange

" Steam Generator Shell Circumferential Welds

" Steam Generator Tube Sheet To Head Circumferential Weld

" Steam Generator Nozzle Inner Radius and Integrally Welded Attachment

" Pressurizer Nozzle Inner Radius and Pressurizer Heater Penetrations

" Reactor Coolant Pump Main Flange Bolting and No. 1 Seal Housing Bolting

" Class 1, Class 2 and Class 3 Piping and Component Supports and Hangers

" Class 1 Valves

" Class 1 Piping Weld for MRP-139 Generic Guidance For Alloy 600 Management

" Class 1 Piping Welds for MRP-146 Management of Thermal Fatigue in Normally Stagnant Non-Isolable Reactor Coolant Branch Lines

" Class 2 Piping Welds for MRP-192 Assessment of RHR Mixing Tee Thermal Fatigue in PWR Plants

" Class 1 and Class 2 Steam Generator Primary Manway Bolting, Pressurizer Manway Bolting, Flange Bolting and Valve Bonnet Bolting

" Class 2 Preservice of Auxiliary Feedwater Piping and Supports

" Class 2 Safety Injection Pumps Integrally Welded Attachments and Casing Weld

" Class 1 System Leakage Test

" Class 2 and Class 3 System Leakage Tests EXAMINATIONS The examinations performed were in accordance with an approved Inservice Inspection Program Plan located under Tab C of the final report. Examination Procedures were approved prior to the start of examinations and certification documents relative to personnel, equipment and materials were reviewed and determined to be satisfactory.

Some of the arrangements and details of the Kewaunee Power Station Components and Piping Systems were designed and fabricated before ASME Boiler and Pressure Vessel Code Section XI Code requirements were established. Examinations performed were intended to examine 100% of the required surface or volume. In some cases, examinations were limited by geometric, metallurgical or design/access restrictions. In each case, the occurrence and cause of the limitation was documented. In all cases the maximum amount achievable was examined.

Page 2 of 4

Witnessing and surveillance of the examinations were conducted by personnel from: the Nuclear Regulatory Commission and Hartford Steam Boiler Inspection and Insurance Company of CT.

RESULTS Examinations resulted with the following Recordable Indications being noted on the basis of procedure recording criteria, which are generally more restrictive than specified ASME Boiler and Pressure Vessel Code Section XI Acceptance Standards.

Recordable Indications detected during the 2008 Refueling Outage are listed in Table 1 with a brief summary following. Specific data relative to all Recordable Indications and their dispositions by either corrective measures, acceptance by ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda Acceptance Criteria, Repair or Replacement or Evaluation are located in Tab F of the Final Report TABLE 1 TYPE OR LOCATION OF RECORDABLE INDICATION (RI)

  • Component and Piping Supports and Hangers
  • System Leakage Pressure Tests METHOD Surface (PT)

Visual (VT-3)

Visual (VT-3)

Visual (VT-2)

NO. OF RI'S I Integrally Welded Attachment 10 Supports 3 Valves 60 Items

1. 2 Rounded Indications (0.175" and 0.200") were recorded on Reactor Coolant Pump 1A Integrally Welded Attachment RCP-CS2 during performance of Liquid Penetrant Examination. The 2 Rounded Indications were acceptable per ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda Table IWB-3514-2.
2. Visual (VT-3) Indications recorded on Component and Piping Supports and Hangers (10 Supports) were (1) Evaluated and Accepted or (2) Repaired, Reexamined and Accepted by:

Kewaunee Power Station Engineering or Inservice Inspection Personnel and reviewed by the Authorized Nuclear Inservice Inspector.

Page 3 of 4

3. Visual (VT-3) Indications recorded on Valve Bonnet Bolting (3 Valves) were: Repaired and or Reexamined and Accepted by: Kewaunee Power Station Inservice Inspection Personnel and reviewed by the Authorized Nuclear Inservice Inspector.
4. Visual (VT-2) Indications recorded during System Leakage Pressure Tests (60 Items) were:

(1) Evaluated and Accepted or (2) Repaired, Reexamined and Accepted by: Kewaunee Power Station Engineering or Inservice Inspection Personnel and reviewed by the Authorized Nuclear Inservice Inspector.

SUMMARY

An Inservice Inspection Program Plan was performed at the Kewaunee Power Station from August 29, 2007 through March 27, 2008 (Non Refueling Outage), March 29, 2008 through May 9, 2008 (Closing of GI following Refueling Outage) and May 10, 2008 (following closing of G1). Examinations were performed as scheduled in the Kewaunee Power Station Fourth 10-Year Inservice Inspection (ISI) Program 2004 -2014 to commence examinations for the 4th Interval; 2nd Period. A total of 74 Recordable Indications were detected. All Recordable Indications were corrected or accepted by ASME Boiler and Pressure Vessel Code Section XI 1998 Edition 2000 Addenda Acceptance Criteria, Repair/Replacement or Evaluation requirements Phillip Ef Bukes Date Engineering Programs Inservice Inspection Program Owner Page 4 of 4

Serial No. 08-0332 ATTACHMENT 7 2008 INSERVICE INSPECTION

SUMMARY

REPORT EXAMINATION

SUMMARY

CLASS MC INSERVICE INSPECTION PROGRAM SECOND TEN-YEAR INTERVAL KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION 2ND INTERVAL: 1ST PERIOD: 1ST OUTAGE 2008 EXAMINATION

SUMMARY

INTRODUCTION An Inservice Inspection (ISI) Program for the Class MC Reactor Building Containment Vessel was performed at the Kewaunee Power Station from March 29, 2008 through May 9, 2008 (Closing of GI following Refueling Outage) by Kewaunee Power Station and Lambert, MacGill and Thomas Inc. examination personnel.

Examinations were performed to satisfy the requirements of:

ASME Boiler and Pressure Vessel Code Section XI 2001 Edition 2003 Addenda The Inservice Inspection Program Plan located under Tab C was prepared by Kewaunee Power Station for the 2nd Interval; 1st Period; 1st Outage as identified in the Kewaunee Power Station Second 10-Year Inservice Inspection (ISI) Program 2006-2016. Examinations during this Refueling Outage were performed to commence the 2nd Interval, 1 st Period examination requirements of ASME Boiler and Pressure Vessel Code Section XI 2001 Edition 2003 Addenda and Kewaunee Power Station Second 10-Year Inservice Inspection (ISI) Program 2006-2016.

The following items were examined for the Class MC Reactor Building Containment Vessel:

  • Accessible Surface Areas

" Bolted Connections EXAMINATIONS The examinations performed were in accordance with an approved Inservice Inspection Program Plan located under Tab C of the final report. Examination Procedures were approved prior to the start of examinations and certification documents relative to personnel, equipment and materials were reviewed and determined to be satisfactory.

Page 1 of 3

Some of the arrangements and details of the Kewaunee Power Station Components and Piping Systems were designed and fabricated before ASME Boiler and Pressure Vessel Code Section XI Code requirements were established. Examinations performed were intended to examine 100% of the required surface or volume. In some cases, examinations were limited by. geometric, metallurgical or design/access restrictions. In all cases the maximum amount achievable was examined.

Witnessing and surveillance of the examinations were conducted by: Hartford Steam Boiler Inspection and Insurance Company of CT.

RESULTS Examinations resulted with the following Recordable Indications being noted on the basis of procedure recording criteria, which are generally more restrictive than specified ASME Boiler and Pressure Vessel Code Section XI Acceptance Standards.

The Recordable Indications detected during the 2008 Refueling Outage are listed in Table I with a brief summary following. Specific data relative to the Recordable Indications disposition by acceptance per ASME Boiler and Pressure Vessel Code Section XI 2001 Edition 2003 Addenda Acceptance Criteria, Repair/Replacement or Evaluation is located in Tab F of the Final Report.

TABLE 1 TYPE OR LOCATION OF RECORDABLE INDICATION (R)

METHOD NO. OF RI'S Reactor Building Containment Vessel General Visual 2 Plates Moisture Barriers Reactor Building Containment Vessel VT-3 6 Bolts Penetration No. 18 Blind Flange

1. General Visual Indications consisting of separation in the moisture barriers of 2 Plates (62 and 67). The moisture barriers were repaired under Work Order KW100369624, reexamined and accepted.
2. VT-3 Indications consisting of damaged threads on 6 bolts for Penetration No. 18 Refueling Transfer Canal Blind Flange. The 6 bolts were repaired under Work Order KW100369647, reexamined by VT-1, as required Code of Federal Regulations 1 OCFR50.55a(b)(2)(ix)(G) and (H), and accepted, and evaluated and accepted by Engineering Evaluation.

Page 2 of 3

SUMMARY

An Inservice Inspection Program for the Class MC Reactor Building Containment Vessel was performed at the Kewaunee Power Station from March 29, 2008 through May 9, 2008 (Closing of GI following Refueling Outage). Examinations were performed as scheduled in the Kewaunee Power Station Second 10-Year Inservice Inspection (ISI) Program 2006-2016.

Three (3) Recordable Indications areas were detected. The Recordable Indications were repaired and/or accepted by Kewaunee Power Station Engineering Evaluation per requirements of ASME Boiler and Pressure Vessel Code Section XI 2001 Edition 2003 Addenda Criteria.

Phillip E. Bukes Engineering Programs Inservice Inspection Program Owner

-,020o?

Date Page 3 of 3

Serial No. 08-0332 ATTACHMENT 8 2008 INSERVICE INSPECTION

SUMMARY

REPORT

SUMMARY

OF EXAMINATIONS THAT WERE LIMITED BY GEOMETRIC, METALLURGICAL, OR DESIGN/ACCESS RESTRICTIONS AND ASSOCIATED DATA SHEETS (30 TOTAL)

KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Serial No. 08-0332 Page 1 of 3

SUMMARY

OF EXAMINATIONS THAT WERE LIMITED BY GEOMETRIC, METALLURGICAL, OR DESIGN/ACCESS RESTRICTIONS Year Component Identification Method of

% Recorded as Not Examination Examined and Limitation Replacement Steam Generator 1A 0.09%

2008 Channel Head to Tube Sheet UT Weld SG-W26 Insulation Support Ring Replacement Steam Generator 1A 6.3%

2008 Nozzle Inside Radius Section UT SG-I R26 Integrally Welded Attachment Replacement Steam Generator 1A 0.26%

2008 Shell Circumferential Weld UT SG-W22 Insulation Support Ring 0.43%

Replacement Steam Generator 1A 3 Hand Holes 2008 Shell Circumferential Weld UT 2 - 4" Nozzles SG-W25 1-'2 1/4" Nozzle 4 - 2" Nozzles 50%

Circumferential Weld SI-W249 on 2008 3" Safety Injection UT Tee To Pipe Weld 3 S tConfiguration Nozzle to Safe End Weld 32%

2008 PR-WI DM on 6" Pressurizer UT Nozzle To Safe End Weld Relief Configuration Nozzle to Safe End Weld 63%

2008 PR-W26DM on 6" Pressurizer UT Nozzle To Safe End Weld Relief Configuration 50%

2008 Circumferential Weld ICS-W45 on UT Ve P

8" Containment Spray Valve To Pipe Weld Configuration 50%

2008 Circumferential Weld RHR-W9 on UT 8" Residual Heat Removal Pipe To Valve Weld Configuration 28Circumferential Weld RHR-W31 U9%

2008 Circumferental Weld RHRoWal UT on 8" Residual Heat Removal Rigid Restraint

Serial No. 08-0332 Page 2 of 3 Method of

% Recorded as Not Year Component Identification Examination Examined and Limitation 0.25%

2008 Circumferential Weld RHR-W168 on 10" Residual Heat Removal UT Weld Crown and Elbow Configuration Circumferential Branch 73%

2008 Connection RC-W3BC on 8" UT Branch Connection Weld Reactor Coolant Configuration Nozzle To Safe End Weld 25%

2008 RC-W77DM on Steam Generator UT Nozzle To Safe End Weld 1A Crossover Leg Configuration Circumferential Pipe Weld 50%

2008 AFW-W148 on 3" Auxiliary UT Flange To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 50%

2008 AFW-W151 on 3" Auxiliary UT Pipe To Flange Weld Feedwater Configuration Circumferential Pipe Weld 50%

2008 AFW-W152 on 3" Auxiliary UT Flange To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 50%

2008 AFW-W1 55 on 3" Auxiliary UT Pipe To Flange Weld Feedwater Configuration Circumferential Pipe Weld 32%

2008 AFW-W1 56 on 3" Auxiliary UT Valve To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 15%

2008 AFW-W171 on 3" Auxiliary UT Pipe To Valve Weld Feedwater Configuration Circumferential Pipe Weld 37%

2008 AFW-W172 on 3" Auxiliary UT Valve To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 17%

2008 AFW-W178 on 3" Auxiliary UT Valve To Pipe Weld Feedwater Configuration

Serial No. 08-0332 Page 3 of 3 Year Component Identification Method of

% Recorded as Not Examination Examined and Limitation Circumferential Pipe Weld 13%

2008 AFW-W189 on 3" Auxiliary UT Pipe To Flange Weld Feedwater Configuration Circumferential Pipe Weld 17%

2008 AFW-W1 90 on 3" Auxiliary UT Flange To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 15%

2008 AFW-W191 on 3" Auxiliary UT Pipe To Flange Weld Feedwater Configuration Circumferential Pipe Weld 17%

2008 AFW-W1 92 on 3" Auxiliary UT Flange To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 33%

2008 AFW-W194 on 3" Auxiliary UT Pipe To Flange Weld Feedwater Configuration Circumferential Pipe Weld 15%

2008 AFW-W195 on 3" Auxiliary UT Valve To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 38%

2008 AFW-W196 on 3" Auxiliary UT Flange To Pipe Weld Feedwater Configuration Circumferential Pipe Weld 33%

2008 AFW-W1 97 on 3" Auxiliary UT Pipe To Flange Weld Feedwater Configuration Circumferential Pipe Weld 38%

2008 AFW-W198 on 3" Auxiliary UT Flange To Pipe Weld Feedwater Configuration