MONTHYEARCP-202400034, (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 1)2024-01-29029 January 2024 (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 1) CP-202300201, (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 0)2023-05-0404 May 2023 (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 0) CP-202200144, (CPNPP) - Core Operating Limits Report (Colr), Unit 1 Cycle 23, (ERX-22-001, Revision 0)2022-04-25025 April 2022 (CPNPP) - Core Operating Limits Report (Colr), Unit 1 Cycle 23, (ERX-22-001, Revision 0) CP-202200128, Core Operating Limits Report Unit 2 Cycle 20, (ERX-21-001, Revision 1)2022-03-28028 March 2022 Core Operating Limits Report Unit 2 Cycle 20, (ERX-21-001, Revision 1) CP-202100682, (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 20, (ERX-21-001, Revision 0)2021-10-19019 October 2021 (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 20, (ERX-21-001, Revision 0) CP-202100062, (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 19, (ERX-20-001, Revision 1)2021-02-0909 February 2021 (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 19, (ERX-20-001, Revision 1) CP-202000589, Core Operating Limits Report (Colr), Unit 1 Cycle 22, (ERX-20-002, Revision 0)2020-10-26026 October 2020 Core Operating Limits Report (Colr), Unit 1 Cycle 22, (ERX-20-002, Revision 0) CP-202000283, Submittal of Core Operating Limits Report (Colr), Unit 2 Cycle 19, (ERX-20-001, Revision 0)2020-04-29029 April 2020 Submittal of Core Operating Limits Report (Colr), Unit 2 Cycle 19, (ERX-20-001, Revision 0) CP-201800883, Core Operating Limits Report, Cycle 18, Revision 02018-12-18018 December 2018 Core Operating Limits Report, Cycle 18, Revision 0 CP-201700977, Core Operating Limits Report, Rev. 12017-12-12012 December 2017 Core Operating Limits Report, Rev. 1 CP-201700932, Core Operating Limits Report2017-11-15015 November 2017 Core Operating Limits Report CP-201700308, Core Operating Limits Report for Cycle 17, Prepared Per Technical Specification 5.6.52017-05-0202 May 2017 Core Operating Limits Report for Cycle 17, Prepared Per Technical Specification 5.6.5 CP-201600686, Core Operating Limits Report Revision 1, Unit 2, Cycle 162016-07-25025 July 2016 Core Operating Limits Report Revision 1, Unit 2, Cycle 16 CP-201600503, Unit 1, Submittal of Revision 0 of Cycle 19 Core Operating Limits Report2016-05-19019 May 2016 Unit 1, Submittal of Revision 0 of Cycle 19 Core Operating Limits Report CP-201500957, Core Operating Limits Report, Cycle 16, Revision 02015-10-19019 October 2015 Core Operating Limits Report, Cycle 16, Revision 0 CP-201401227, Cycle 15 Core Operating Limits Report, Revision 12014-10-21021 October 2014 Cycle 15 Core Operating Limits Report, Revision 1 CP-201400397, Core Operating Limits Report, Cycle 152014-04-0808 April 2014 Core Operating Limits Report, Cycle 15 CP-201300480, Cycle 17 Core Operating Limits Report, Revision 02013-03-25025 March 2013 Cycle 17 Core Operating Limits Report, Revision 0 CP-201300297, Core Operating Limits Report2013-03-18018 March 2013 Core Operating Limits Report CP-201201386, Core Operating Limits Report, Unit 2, Cycle 142012-11-15015 November 2012 Core Operating Limits Report, Unit 2, Cycle 14 CP-201201209, Core Operating Limits Report2012-10-22022 October 2012 Core Operating Limits Report CP-201101450, Core Operating Limits Report2011-10-13013 October 2011 Core Operating Limits Report CP-201100528, Cycle 13 Core Operating Limits Report, March 20112011-04-28028 April 2011 Cycle 13 Core Operating Limits Report, March 2011 CP-201000740, Core Operating Limits Report for Unit 1, Cycle 15, Revision 1 and Unit 2, Cycle 12, Revision 12010-05-19019 May 2010 Core Operating Limits Report for Unit 1, Cycle 15, Revision 1 and Unit 2, Cycle 12, Revision 1 CP-201000611, Submittal of Core Operating Limits Reports2010-04-22022 April 2010 Submittal of Core Operating Limits Reports CP-200900472, Submittal of Annual Report of Changes in Peak Cladding Temperature2009-03-31031 March 2009 Submittal of Annual Report of Changes in Peak Cladding Temperature CP-200900126, Cycle 14 Startup Report2009-01-19019 January 2009 Cycle 14 Startup Report CP-200900069, Thirteenth Refueling Outage (1RF13) Steam Generator 180 Day Report2009-01-0707 January 2009 Thirteenth Refueling Outage (1RF13) Steam Generator 180 Day Report CP-200801523, Core Operating Limits Report2008-10-28028 October 2008 Core Operating Limits Report CP-200800809, Submittal of Core Operating Limits Reports2008-06-0909 June 2008 Submittal of Core Operating Limits Reports CP-200800514, Cycle 11, Core Operating Limits Reports2008-04-22022 April 2008 Cycle 11, Core Operating Limits Reports CPSES-200701324, Supplement to License Amendment Request (LAR) 07-003 Revision to Technical Specification 3.1, Reactivity Control Systems, 3.2, Power Distribution Limits, 3.3, Instrumentation, and 5.6.5 B, Core Operating Limits2007-08-16016 August 2007 Supplement to License Amendment Request (LAR) 07-003 Revision to Technical Specification 3.1, Reactivity Control Systems, 3.2, Power Distribution Limits, 3.3, Instrumentation, and 5.6.5 B, Core Operating Limits CPSES-200700605, License Amendment Request (LAR) 07-003, Revision to Technical Specifications 3.1, Reactivity Control Systems, 3.2, Power Distribution Limits, 3.3, Instrumentation, & 5.6.5b, Core Operating Limits Report2007-04-10010 April 2007 License Amendment Request (LAR) 07-003, Revision to Technical Specifications 3.1, Reactivity Control Systems, 3.2, Power Distribution Limits, 3.3, Instrumentation, & 5.6.5b, Core Operating Limits Report CPSES-200700691, Core Operating Limits Report, Cycle 132007-04-0404 April 2007 Core Operating Limits Report, Cycle 13 CPSES-200602137, Submittal of Unit 2, Cycle 10 Core Operating Limits Report2006-10-25025 October 2006 Submittal of Unit 2, Cycle 10 Core Operating Limits Report CPSES-200502312, Submittal of Rev. 0 to Cycle 12 Core Operating Limits Report2005-11-0202 November 2005 Submittal of Rev. 0 to Cycle 12 Core Operating Limits Report CPSES-200401176, Revision 1 to the Core Operating Limits Reports2004-04-21021 April 2004 Revision 1 to the Core Operating Limits Reports CPSES-200302202, Cycle 8 Core Operating Limits Report2003-10-14014 October 2003 Cycle 8 Core Operating Limits Report CPSES-200203517, Cycle 10 Core Operating Limits Report2002-10-10010 October 2002 Cycle 10 Core Operating Limits Report 2024-01-29
[Table view] Category:Letter type:CP
MONTHYEARCP-202400030, License Renewal Application Revision 0 - Supplement 3, Revision 12024-01-31031 January 2024 License Renewal Application Revision 0 - Supplement 3, Revision 1 CP-202400034, (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 1)2024-01-29029 January 2024 (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 1) CP-202300575, (Cpnpp), License Amendment Request to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems and Components for Nuclear Power Reactors Supplement 22023-12-13013 December 2023 (Cpnpp), License Amendment Request to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems and Components for Nuclear Power Reactors Supplement 2 CP-202300566, (Cpnpp), Special Report 1-SR-23-001-00, Inoperable Post Accident Monitoring Instrumentation2023-12-12012 December 2023 (Cpnpp), Special Report 1-SR-23-001-00, Inoperable Post Accident Monitoring Instrumentation CP-202300494, License Renewal Application Revision 0, Supplement 32023-12-0606 December 2023 License Renewal Application Revision 0, Supplement 3 CP-202300349, License Amendment Request (Lar) 23-004 Technical Specifications (TS) 3.9.3, Nuclear Instrumentation2023-11-20020 November 2023 License Amendment Request (Lar) 23-004 Technical Specifications (TS) 3.9.3, Nuclear Instrumentation CP-202300416, Supplemental Information to Facilitate Acceptance of Licensee Amendment Request 23-002, Application Regarding GDC-5 Shared System Requirements2023-10-12012 October 2023 Supplemental Information to Facilitate Acceptance of Licensee Amendment Request 23-002, Application Regarding GDC-5 Shared System Requirements CP-202300432, Response to Request for Additional Information Regarding the Safety Review of the License Renewal Application - Set 42023-10-0404 October 2023 Response to Request for Additional Information Regarding the Safety Review of the License Renewal Application - Set 4 CP-202300442, (CPNPP) - Request to Use Later Code Edition for Inservice Inspection (ISI) Program2023-09-15015 September 2023 (CPNPP) - Request to Use Later Code Edition for Inservice Inspection (ISI) Program CP-202300391, (CPNPP) - Request for Exemption from 10 CFR 50.71(e)(4) Final Safety Analysis Update Schedule2023-08-24024 August 2023 (CPNPP) - Request for Exemption from 10 CFR 50.71(e)(4) Final Safety Analysis Update Schedule CP-202300411, (Cpnpp), Inservice Inspection (ISI) Owner'S Activity Reports (OAR-1 Forms) for Unit 2 Refueling Outage 20 (2RF20)2023-08-17017 August 2023 (Cpnpp), Inservice Inspection (ISI) Owner'S Activity Reports (OAR-1 Forms) for Unit 2 Refueling Outage 20 (2RF20) CP-202300361, (CPNPP) - Unit 2 Refueling Outage 20 (2RF20) Steam Generator 180 Day Report2023-08-17017 August 2023 (CPNPP) - Unit 2 Refueling Outage 20 (2RF20) Steam Generator 180 Day Report CP-202300401, 10CFR50.59 Evaluation Summary Report 024, 10CFR72.48 Evaluation Summary Report 009, and Commitment Material Change Evaluation Report 0182023-08-15015 August 2023 10CFR50.59 Evaluation Summary Report 024, 10CFR72.48 Evaluation Summary Report 009, and Commitment Material Change Evaluation Report 018 CP-202300358, (Cpnpp), Transmittal of Electronic Licensing Basis Documents Including Certified FSAR Amendment 1122023-08-0101 August 2023 (Cpnpp), Transmittal of Electronic Licensing Basis Documents Including Certified FSAR Amendment 112 CP-202300322, Response to Requests for Additional Information Regarding Review of the License Renewal Application Sets 2 and 32023-07-27027 July 2023 Response to Requests for Additional Information Regarding Review of the License Renewal Application Sets 2 and 3 CP-202300348, (Cpnpp), Transmittal of Revised Emergency Plan (Revision 48)2023-07-18018 July 2023 (Cpnpp), Transmittal of Revised Emergency Plan (Revision 48) CP-202300285, Response to Request for Additional Information Regarding Review of the License Renewal Application - Set 12023-07-12012 July 2023 Response to Request for Additional Information Regarding Review of the License Renewal Application - Set 1 CP-202300262, Response to Request for Confirmation of Information Regarding Review of the License Renewal Application - Set 22023-06-20020 June 2023 Response to Request for Confirmation of Information Regarding Review of the License Renewal Application - Set 2 CP-202300263, Supplemental Information to Facilitate Acceptance of Licensee Amendment Request 23-002, Application Regarding GDC-5 Shared System Requirements2023-06-15015 June 2023 Supplemental Information to Facilitate Acceptance of Licensee Amendment Request 23-002, Application Regarding GDC-5 Shared System Requirements CP-202300248, Response to Request for Additional Information Regarding License Renewal Application - Set 12023-06-13013 June 2023 Response to Request for Additional Information Regarding License Renewal Application - Set 1 CP-202300209, Response to Request for Additional Information - License Renewal Application Environmental Review2023-06-0606 June 2023 Response to Request for Additional Information - License Renewal Application Environmental Review CP-202300207, Revision to Comanche Peak Nuclear Power Plant'S Response to Notice of Violation (NOV) 05000445/2021011-052023-05-25025 May 2023 Revision to Comanche Peak Nuclear Power Plant'S Response to Notice of Violation (NOV) 05000445/2021011-05 CP-202300182, Response to Requests for Confirmation of Information Regarding the Environmental Review of the License Renewal Application2023-05-0808 May 2023 Response to Requests for Confirmation of Information Regarding the Environmental Review of the License Renewal Application CP-202300201, (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 0)2023-05-0404 May 2023 (CPNPP) - Core Operating Limits Report (Colr), Unit 2 Cycle 21, (ERX-23-001, Revision 0) CP-202300160, (Cpnpp), 2022 Annual Radiological Environmental Operating Report2023-04-27027 April 2023 (Cpnpp), 2022 Annual Radiological Environmental Operating Report CP-202300159, (Cpnpp), 2022 Annual Radiological Effluent Release Report2023-04-27027 April 2023 (Cpnpp), 2022 Annual Radiological Effluent Release Report CP-202300165, License Renewal Application Revision 0 - Supplement 22023-04-24024 April 2023 License Renewal Application Revision 0 - Supplement 2 CP-202300175, Submittal of 2022 Annual Environmental Operating Report (Non-Radiological)2023-04-20020 April 2023 Submittal of 2022 Annual Environmental Operating Report (Non-Radiological) CP-202300181, ISFSI, Beaver Valley, Units 1 and 2, ISFSI, Davis-Besse, Unit 1, ISFSI, Perry, Unit 1, ISFSI, Corrected Affidavit for Application for Order Consenting to Transfer of Licenses and Conforming License Amendments2023-04-20020 April 2023 ISFSI, Beaver Valley, Units 1 and 2, ISFSI, Davis-Besse, Unit 1, ISFSI, Perry, Unit 1, ISFSI, Corrected Affidavit for Application for Order Consenting to Transfer of Licenses and Conforming License Amendments CP-202300096, License Amendment Request (LAR) 23-002 Application Regarding GDC-5 Shared Systems Requirements2023-04-20020 April 2023 License Amendment Request (LAR) 23-002 Application Regarding GDC-5 Shared Systems Requirements CP-202300140, Application to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems and Components for Nuclear Power Reactors. LAR 23-0012023-04-19019 April 2023 Application to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems and Components for Nuclear Power Reactors. LAR 23-001 CP-202300157, ISFSI, Beaver Valley, Units 1 and 2, ISFSI, Davis-Besse, Unit 1, ISFSI, Perry, Unit 1, and ISFSI, Application for Order Consenting to Transfer of Licenses and Conforming License Amendments2023-04-14014 April 2023 ISFSI, Beaver Valley, Units 1 and 2, ISFSI, Davis-Besse, Unit 1, ISFSI, Perry, Unit 1, and ISFSI, Application for Order Consenting to Transfer of Licenses and Conforming License Amendments CP-202300135, License Renewal Application Revision 0 - Supplement 12023-04-0606 April 2023 License Renewal Application Revision 0 - Supplement 1 CP-202300144, (CPNPP) - Decommissioning Report2023-03-30030 March 2023 (CPNPP) - Decommissioning Report CP-202300139, (CPNPP) - Property Damage Insurance2023-03-30030 March 2023 (CPNPP) - Property Damage Insurance CP-202300098, (Cpnpp), Annual Report of Changes in Peak Cladding Temperature2023-03-16016 March 2023 (Cpnpp), Annual Report of Changes in Peak Cladding Temperature CP-202200481, Response to Request for Additional Information - Relief Request Application P-1, Inservice Testing (IST)2022-12-0707 December 2022 Response to Request for Additional Information - Relief Request Application P-1, Inservice Testing (IST) CP-202200454, (Cpnpp), Reply to a Notice of Violation Transmitted Via NRC Letter from Gregory Werner to Ken Peters Dated 11/01/2022, Comanche Peak Nuclear Power Plant, Units 1 and 2 Integrated Inspection Report 05000445/2022003 .2022-12-0101 December 2022 (Cpnpp), Reply to a Notice of Violation Transmitted Via NRC Letter from Gregory Werner to Ken Peters Dated 11/01/2022, Comanche Peak Nuclear Power Plant, Units 1 and 2 Integrated Inspection Report 05000445/2022003 . CP-202200355, Application to Revise Technical Specifications to Apply the Westinghouse Full Spectrum Loss of Coolant Accident Evaluation Model LAR 22-0022022-11-21021 November 2022 Application to Revise Technical Specifications to Apply the Westinghouse Full Spectrum Loss of Coolant Accident Evaluation Model LAR 22-002 CP-202200380, (CPNPP) - Non-Voluntary License Amendment Request to Revise Technical Specifications 3.2.1, Fq(Z), to Implement Methodology from WCAP-17661, Revision 1, Improved RAOC and CAOC Fq Surveillance Technical Specifications2022-11-21021 November 2022 (CPNPP) - Non-Voluntary License Amendment Request to Revise Technical Specifications 3.2.1, Fq(Z), to Implement Methodology from WCAP-17661, Revision 1, Improved RAOC and CAOC Fq Surveillance Technical Specifications CP-202200450, (CPNPP) - Registration of Dry Spent Fuel Storage Canisters2022-11-16016 November 2022 (CPNPP) - Registration of Dry Spent Fuel Storage Canisters CP-202200435, (Cpnpp), Registration of Dry Spent Fuel Storage Canisters2022-11-0808 November 2022 (Cpnpp), Registration of Dry Spent Fuel Storage Canisters CP-202200419, (CPNPP) - Unit 1 Refueling Outage 22 (1RF22) Steam Generator 180 Day Report2022-11-0303 November 2022 (CPNPP) - Unit 1 Refueling Outage 22 (1RF22) Steam Generator 180 Day Report CP-202200357, (CPNPP) Unit 2 - Response to Request for Additional Information, Fall 2021 (2RF19) Steam Generator Tube Inspection Report2022-09-14014 September 2022 (CPNPP) Unit 2 - Response to Request for Additional Information, Fall 2021 (2RF19) Steam Generator Tube Inspection Report CP-202200358, (CPNPP) - Transmittal of Revised Emergency Plan (Revision 46)2022-09-14014 September 2022 (CPNPP) - Transmittal of Revised Emergency Plan (Revision 46) CP-202200246, Evacuation Time Estimate Analysis2022-08-25025 August 2022 Evacuation Time Estimate Analysis CP-202200306, (CPNPP) - Inservice Inspection (ISI) Owner'S Activity Reports (OAR-1 Forms) for Unit 1 Refueling Outage 22 (1RF22)2022-08-11011 August 2022 (CPNPP) - Inservice Inspection (ISI) Owner'S Activity Reports (OAR-1 Forms) for Unit 1 Refueling Outage 22 (1RF22) CP-202200273, Third Supplement to License Amendment Request (LAR) 20-006 Application to Revise Technical Specifications to Adopt Risk Informed Completion Times, TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative2022-07-20020 July 2022 Third Supplement to License Amendment Request (LAR) 20-006 Application to Revise Technical Specifications to Adopt Risk Informed Completion Times, TSTF-505, Revision 2, Provide Risk-Informed Extended Completion Times - RITSTF Initiative CP-202200276, (CPNPP) - Relief Request Application P-1, Inservice Testing (IST)2022-07-20020 July 2022 (CPNPP) - Relief Request Application P-1, Inservice Testing (IST) CP-202200247, (CPNPP) - 10CFR50.59 Evaluation Summary Report 023, 10CFR72.48 Evaluation Summary Report 008 and Commitment Material Change Evaluation Report 0172022-06-30030 June 2022 (CPNPP) - 10CFR50.59 Evaluation Summary Report 023, 10CFR72.48 Evaluation Summary Report 008 and Commitment Material Change Evaluation Report 017 2024-01-31
[Table view] |
Text
um Mike Blevins Luminant Power Executive Vice President P 0 Box 1002
& Chief Nuclear Officer 6322 North FM 56 Luminant Mike.Blevins@Luminant.com Glen Rose, TX 76043 T 254 897 5209 C 817 559 9085 F 254 897 6652 CP-200800514 Ref. # Tech. Spec. 5.6.5 Log # TXX-08058 April 22, 2008 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555
SUBJECT:
COMANCHE PEAK STEAM ELECTRIC STATION DOCKET NO. 50-446 CORE OPERATING LIMITS REPORTS
Dear Sir or Madam:
Pursuant to Technical Specification 5.6.5, Luminant Generation Company LLC (Luminant Power) hereby submits the Core Operating Limits Reports for Comanche Peak Unit 2, Cycle 11.
This communication contains no new licensing basis commitments regarding Comanche Peak Units 1 and 2. Should you have any questions, please contact Mr. J. D. Seawright at (254) 897-0140.
Sincerely, Luminant Generation Company LLC Mike Blevins By:: _ _ _ _ _
/ Freýl W. Madden Director, Oversight & Regulatory Affairs Enclosure Unit 2, Cycle 11 Core Operating Limits Report (COLR) c- E. E. Collins, Region IV B. K. Singal, NRR Resident Inspectors, Comanche Peak A member of the STARS (Strategic Teaming and Resource Sharing) Alliance..
Callaway - Comanche Peak
- Diablo Canyon Palo Verde - South Texas Project - Wolf Creek
ERX-08-001, Rev. 0 CPNPP UNIT 2 CYCLE 3.1' CORE OPERATING LIMITS REPORT April2008 Prepared: (_
2z 'Date:
Daniel E. Brozak Principal Engineer, Westinghouse El ectricý Co.
ReViewed:
~\ ~
Date: . ...
Somporn Srinilta Prin-cpalý Engineer, Westinghouse Electric Co.
Reviewed: _____ Date:
evin N. Roland Principal Engineer, Westinghouse El .ectric Co.
Approved:
JesBoatwi -Managerr Date:
Westinghouse Engineering Serivices - Texas
DISCLAIMER The information contained in this report was prepared for the specific requirement of Energy Future Holdings Company LP and may not be appropriate for use in situations other than those for which it was specifically prepared. Energy Future Holdings Company LP PROVIDES NO WARRANTY HEREUNDER, EXPRESS OR IMPLIED, OR STATUTORY, OF ANY KIND) OR NATURE WHATSOEVER, REGARDING THIS REPORT OR ITS USE, INCLUDING BUT NOT LIMITED TO ANY WARRANTIES ON MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
By making this report available, Energy Future Holdings Company LP does not authorize its use by others, and any such use is forbidden except with the prior written approval of Energy Future Holdings Company LP. Any such written approval shall itself be deemed to incorporate the disclaimers of liability and disclaimers of warranties provided herein.
In no event shall Energy Future Holdings Company LP have any liability for any incidental or consequential damages of any type in connection with the use, authorized or unauthorized, of this' report or of the information in it.
ii ii ERX-O8-O0l, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 TABLE OF CONTENTS DISCLAIMER...............................................................i TABLE OF CONTENTS.......................................................11 LIST OF TABLES........................................................... iv LIST OF FIGURES.......................................................... v SECTION PAGE 1.0 CORE OPERATING LIMITS REPORT......................................1 2.0 OPERATING LIMITS....................................................2 2.1 SAFETY LIMITS.................................................2 2.2 SHUTDOWN MARGIN...............................................2 2.3 MODERATOR TEMPERATURE COEFFICIENT.......................... 2 2.4 ROD GROUP ALIGNMENT LIMITS...................................3 2.5 SHUTDOWN BANK INSERTION LIMITS.............................. 3 2.6 CONTROL BANK INSERTION LIMITS............................... 4 2.7 PHYSICS TESTS EXCEPTIONS - MODE 2.......................... 4 2.8 HEAT FLUX HOT CHANNEL FACTOR................................ 4 2.9 NUCLEAR ENTHALPY RISE HOT CHANNEL FACTOR....................5 2.10 AXIAL FLUX DIFFERENCE.........................................6 2.11 REACTOR TRIP SYSTEM INSTRUMENTATION.........................6 2.12 RCS PRESSURE, TEMPERATURE, AND FLOW DEPARTURE FROM NUCLEATE BOILING LIMITS..................................... 7 2.13 BORON CONCENTRATION.......................................... 8
3.0 REFERENCES
...........................................................8 iii iii ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 LIST OF TABLES TABLE PAGE 1 FQ(Z) MARGIN DECREASES IN EXCESS OF 2% PER 31 EFPD ....... 9 iv ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 LIST OF FIGURES FIGURE PAGE 1 REACTOR CORE SAFETY LIMITS .............................. 10 2 ROD BANK INSERTION LIMITS VERSUS THERMAL POWER ............. 11 3 K(Z) - NORMALIZED FQ(Z) AS A FUNCTION OF CORE HEIGHT ............................................. 12 4 W(Z) AS A FUNCTION OF CORE HEIGHT -
(150 MWD/MTU) ........................................... 13 5 W(Z) AS A FUNCTION OF CORE HEIGHT -
(5,000 MWD/MTU) ......................................... 14 6 W(Z) AS A FUNCTION OF CORE HEIGHT -
(10,000 MWD/MTU) ........................................ 15 7 W(Z) AS A FUNCTION OF CORE HEIGHT -
(20,000 MWD/MTU) ........................................ 16 8 AXIAL FLUX DIFFERENCE LIMITS AS A FUNCTION OF RATED THERMAL POWER ................................... 17 V ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 1.0 CORE OPERATING LIMITS REPORT This Core Operating Limits Report (COLR) for CPNPP UNIT 2 CYCLE 11 has been prepared in accordance with the requirements of Technical Specification 5.6.5.
The Technical Specifications affected by this report are listed below:
SL 2.1 SAFETY LIMITS LCO 3.1.1 SHUTDOWN MARGIN LCO 3.1.3 MODERATOR TEMPERATURE COEFFICIENT LCO 3.1.4 ROD GROUP ALIGNMENT LIMITS LCO 3.1.5 SHUTDOWN BANK INSERTION LIMITS LCO 3.1.6 CONTROL BANK INSERTION LIMITS LCO 3.1.8 PHYSICS TESTS EXCEPTIONS - MODE 2 LCO 3.2.1.2 HEAT FLUX HOT CHANNEL FACTOR LCO 3.2.2 NUCLEAR ENTHALPY RISE HOT CHANNEL FACTOR LCO 3.2.3.2 AXIAL FLUX DIFFERENCE LCO 3.3.1 REACTOR TRIP SYSTEM INSTRUMENTATION LCO 3.4.1 RCS PRESSURE, TEMPERATURE, AND FLOW DEPARTURE FROM NUCLEATE BOILING LIMITS LCO 3.9.1 BORON CONCENTRATION ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11
- 2.0 OPERATING LIMITS The cycle-specific parameter limits for the specifications listed in Section 1.0 are presented in the following subsections. These limits have been developed using the NRC-approved methodologies specified in Technical Specification 5.6.5b, Items 1, 2, 14, 16, 17, 18 and 21 through 29. These limits have been determined such that all applicable limits of the safety analysis are met.
2.1 SAFETY LIMITS (SL 2.1) 2.1.1 In MODES 1 and 2, the combination of thermal power, reactor coolant system highest loop average temperature, and pressurizer pressure shall not exceed the safety limits specified in Figure 1.
2.2 SHUTDOWN MARGIN (SDM) (LCO 3.1.1) 2.2.1 The SDM shall be greater than or equal to 1.3% Ak/k in MODE 2 with K... < 1.0, and in MODES 3, 4, and 5.
2.3 MODERATOR TEMPERATURE COEFFICIENT (MTC) (LCO 3.1.3) 2.3.1 The MTC upper and lower limits, respectively, are:
The BOL/ARO/HZP-MTC shall be less positive than +5 pcm/*F.
The EOL/ARO/RTP-MTC shall be less negative than -40 pcm/°F.
2 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 2.3.2 SR 3.1.3.2 The MTC surveillance limit is:
The 300 ppm/ARO/RTP-MTC shall be less negative than or equal to -31 pcm/'F.
The 60 ppm/ARO/RTP-MTC shall be less negative than or equal to -38 pcm/*F.
where: BOL stands for Beginning of Cycle Life ARO stands for All Rods Out HZP stands for Hot Zero THERMAL POWER EOL stands for End of Cycle Life RTP stands for RATED THERMAL POWER 2.4 ROD GROUP ALIGNMENT LIMITS (LCO 3.1.4) 2.4.1 The SDM shall be greater than or equal to 1.3% Ak/k in MODES 1 and 2.
2.5 SHUTDOWN BANK INSERTION LIMITS (LCO 3.1.5) 2.5.1 The shutdown rods shall be fully withdrawn. Fully withdrawn shall be the condition where shutdown rods are at a position within the interval of 218 and 231 steps withdrawn, inclusive.
3 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 2.6 CONTROL BANK INSERTION LIMITS (LCO 3.1.6) 2.6.1 The control banks shall be limited in physical insertion as shown in Figure 2.
2.6.2 The control banks shall always be withdrawn and inserted in the prescribed sequence. For withdrawal, the sequence is control bank A, control bank B, control bank C, and control bank D. The insertion sequence is the reverse of the withdrawal sequence.
2.6.3 A 115 step Tip-to-Tip relationship between each sequential control bank shall be maintained.
2.7 PHYSICS TESTS EXCEPTIONS - MODE 2 (LCO 3.1.8) 2.7.1 The SDM shall be greater than or equal to 1.3% Ak/k in MODE 2 during PHYSICS TESTS.
2.8 HEAT FLUX HOT CHANNEL FACTOR (F. (Z) (LCO 3.2.1.2)
FRTP F
2.8.1 FQ(Z) -- [K(Z)] for P > 0.5 P
IRTP FQ FQ(Z) <_< [K(Z)] for P S 0.5
0.5 where
P = IFHERMAL POWER RATI ED THERMAL POWER 4 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 2.8.2 FFRTP = 2.50 2.8.3 K(Z) is provided in Figure 3.
2.8.4 Elevation and burnup dependent W(Z) values are provided in Figures 4, 5, 6, and 7. The burnup dependent values can be used to interpolate or extrapolate (via a three point fit) the W(Z) at a particular burnup.
2.8.5 SR 3.2.1.2.2 If the two most recent FQ(Z) evaluations show an increase in the expression maximum over Z [ FQC(Z) / K(Z) ],
the burnup dependent values in Table 1 shall be used instead of a constant 2% to increase FQw(Z) per Surveillance Requirement 3.2.1.2.2.a. A constant factor of 2% shall be used for all cycle burnups that are outside the range of Table 1.
2.9 NUCLEAR ENTHALPY RISE HOT CHANNEL FACTOR (FNAHI (LCO 3.2.2),
2.9.1 FNAH 5 F'T'AH [1 + PFA (l-P)]
where: P = THERMAL POWER RATED THERMAL POWER 2.9.2 F TPAH = 1.41 for Region 1-13B and liB Fuel Assemblies FRTPAH = 1.60 for all other Fuel Assembly Regions 2.9.3 PFAH = 0.3 5 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 2.10 AXIAL FLUX DIFFERENCE (AFD) (LCO 3.2.3.2) 2.10.1 The AFD Acceptable Operation Limits are provided in Figure 8.
2.11 REACTOR TRIP SYSTEM (RTS) INSTRUMENTATION (LCO 3.3.1) 2.11.1 The numerical values pertaining to the Overtemperature N-16 reactor trip setpoint are listed below; K, = 1.15 K = 0.0139 I°F K3 = 0.00071 /psig 0
TC0 = indicated loop specific T, at Rated Thermal Power, F P1 Z 2235 psig T, 10 sec T2 5 3 sec f 1 (Aq) = -2.78 - {(q-qb) + 18%} when (q,-q 1 ) 5 -18% RTP
= 0% when -18% RTP < (qt-q,) < +10.0% RTP
= 2.34 {(qt-q,) - 10.0%) when (qt-qb) a +10.0% RTP 6 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 2.12 RCS PRESSURE, TEMPERATURE, AND FLOW DEPARTURE FROM NUCLEATE BOILING (DNB) LIMITS (LCO 3.4.1) 2.12.1 RCS DNB parameters for pressurizer pressure, RCS average temperature, and RCS total flow rate shall be within the surveillance limits specified below:
2.12.2 SR 3.4.1.1 Pressurizer pressure 2 2220 psig (4 channels) 2222 psig (3 channels)
The pressurizer pressure limits correspond to the analytical limit of 2205 psig used in the safety analysis with allowance for measurement uncertainty. These uncertainties are based on the use of control board indications and the number of available channels.
2.12.3 SR 3.4.1.2 RCS average temperature S 592 'F (4 channels) 5 591 'F (3 channels)
The RCS average temperature limits correspond to the 0
analytical limit of 595.2 F used in the safety analysis with allowance for measurement uncertainty. These uncertainties are based on the use of control board indications and the number of available channels.
7 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 2.12.4 SR 3.4.1.3 The RCS total flow rate shall be Ž 408,000 gpm.
2.12.5 SR 3.4.1.4 The RCS total flow rate based on precision heat balance shall be Ž 408,000 gpm.
The required RCS flow, based on an elbow tap differential pressure instrument measurement prior to MODE 1 after the refueling outage, shall be greater than 327,000 gpm.
2.13 BORON CONCENTRATION (LCO 3.9.1) 2.13.1 The required refueling boron concentration is 2!1899 ppm.
3.0 REFERENCES
Technical Specification 5.6.5.
8 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 Table 1 F, (Z) MARGIN DECREASES IN EXCESS OF 2% PER 31 EFPD Cycle Maximum Decrease Burnup In F, (Z) MARGIN (MWD/MTU) (Percent) 982 2.00 1190 2.65 1398 3.75 1606 4.78 1814 5.21 2022 4.51 2230 3.83 2438 3.21 2647 2.63 2855 2.11 3063 2.00 Note: All Cycle burnups outside the range of the table shall use a constant 2% decrease in FQ(Z) margin for compliance with the 3.2.1.2.2.a Surveillance Requirements. Linear interpolation is acceptable to determine the FQ(Z) margin decrease for cycle burnups which fall between the specified burnups.
9 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 Figure 1 Reactor Core Safety Limits 680-660 ______ ______ _____
660 5 pUnacceptable 640O 0
0.
E 620 620- 100 120 14 600) 0 580 560 0 20 40 60 80 100 120 140 Percent of Rated Thermal Power (3458 MWt) 10 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 FIGURE 2 ROD BANK INSERTION LIMITS VERSUS THERMAL POWER 240
- - (2 .3,28).(79.6,218) 220 200 BANK B 180
,n 160 -- (0,164)-
4J
-,-I
-(00,146) 140 4J BANK C + -+ /II 120 0
H H 100 0
80 BANK D o 60 40 20 0
0 10 20 30 40 50 60 70 80. 90 100 PERCENT OF RATED THERMAL POWER NOTES: 1. Fully withdrawn shall be the condition where control rods are at a position within the interval of 218 and 231 steps withdrawn, inclusive.
- 2. Control Bank A shall be fully withdrawn.
11 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 FIGURE 3 K(Z) - NORMALIZED FQ(Z) AS A FUNCTION OF CORE HEIGHT 1.1 1 11 1 1 1 1 1 ýI I I I I (0.011.0) 6.0,1.0 1.0
-7 71 j, H111 11411, -11 0.9 1 1 2 . 0, 0.925) 0.8 00.7 N 0.6 o 0.5 I
.7; 7 IHF~
- 0.4 0.3 0.2 ... I ......... I ..... I ..... .. 1- 1- - .1- .... - I 0.1 0.0 0
H 1 2 3 4 5 I+rHi+/- Hr 6 7 8 FM H [++I+I 9 10 11 12 BOTTOM CORE HEIGHT (FEET) TOP Axial Axial Axial Axial Node K(Z) Node KI(Z) Node K(Z) Node K(Z) 61 0.9250 53 0.9450 45 0.9650 37 0.9850 60 0.9275 52 0.9475 44 0.9675 36 0.9875 59 0.9300 51 0.9500 43 0.9700 35 0.9900 58 0.9325 50 0.9525 42 0.9725 34 0.9925 57 0.9350 49 0.9550 41 0.9750 33 0.9950 56 0.9375 48 0.9575 40 0.9775 32 0.9975 55 0.9400 47 0.9600 39 0.9800 1 - 31 1.0000 54 0.9425 46 0.9625 38 0.9825 Core Height (ft) = (Node - 1)
- 0.2 12 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 FIGURE 4 W(Z) AS A FUNCTION OF CORE HEIGHT (150 MWD/MTU) 1.450 1.400 1.350 1.300 N
1.250 1.200 1.150 N I I J J
/
S 2N 1.100 1.050 1.000 I I i 0 1 2 3 4 5 6 7 8 9 10 11 12 BOTTOM CORE HEIGHT (FEET) TOP Axial Axial Axial Axial Node W(Z) Node w(Z) Node w(Z) Node w(Z) 58 - 61 --- 44 1.1608 30 1.1672 16 1.0802 57 1.1794 43 1.1624 29 1.1610 15 1.0849 56 1.1791 42 1.1632 28 1.1558 14 1.0887 55 1.1789 41 1.1643 27 1.1509 13 1.0931 54 1.1770 40 1.1685 26 1.1449 12 1.0978 53 1.1718 39 1.1735 25 1.1383 11 1.1023 52 1.1644 38 1.1774 24 1.1313 10 1.1083 51 1.1583 37 1.1832 23 1.1233 9 1.1171.
50 1.1574 36 1.1868 22 1.1145 8 1.1264 49 1.1591 35 1.1880 21 1.1057 7 1.1343 48 1.1591 34 1.1873 20 1.0983 6 1.1414 47 1.1561 33 1.1847 19 1.0920 5 1.1490 46 1.1537 32 1.1802 18 1.0850 1 - 4 45 1.1558 31 1.1740 17 1.0790 Core Height (ft) = (Node - 1)
- 0.2 13 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 FIGURE 5 W(Z) AS A FUNCTION OF CORE HEIGHT (5,000 MWD/MTU) 1.450 1.400 1.350 I
1.300
-I------
i i F-- 1.250 1.200
/
1.150 ffiAffiLX 1.100 1.050
-l
+ I I~-I~-I-~
1.000 0 1 2 3 4 5 6 7 8 9 10 11 12 BOTTOM CORE HEIGHT (FEET) TOP Axial Axial Axial Axial Node W (Z) Node w(z) Node w(Z) Node w(Z) 58 - 61 --- 44 1.1437 30 1.1281 16 1.0959 57 1.3237 43 1.1516 29 1.1264 15 1.1062 56 1.3102 42 1.1533 28 1.1241 14 1.1203 55 1.2936 41 1.1527 27 1.1207 13 1.1343 54 1.2735 40 1.1498 26 1.1163 12 1.1488 53 1.2504 39 1.1478 25 1.1112 11 1.1618 52 1.2241 38 1.1479 24 1.1054 10 1.1805 51 1.1950 37 1.1482 23 1.0990 9 1. 2093 50 1.1746 36 1.1469 22 1.0926 8 1. 2406 49 1.1621 35 1.1440 21 1.0914 7 1. 2669 48 1.1518 34 1.1401 20 1.0915 6 1.2886 47 1.1424 33 1.1363 19 1.0916 5 1.3071 46 1.1329 32 1.1329 18 1.0914 1 - 4 45 1.1340 31 1.1301 17 1.0917 Core Height (ft) = (Node - 1)
- 0.2 14 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 FIGURE 6 W(Z) AS A FUNCTION OF CORE HEIGHT (10,000 MWD/MTU) 1.450 1.400 1.350 1.300 I I I I i ! i i i 1.250 i i I i 1.200 1.150 I I A.
F---IV 1.100 1.050 IHý 1.000 -fýwl 0 1 2 3 4 5 6 7 8 9 10 11 12 BOTTOM CORE HEIGHT (FEET) TOP Axial Axial Axial Axial Node W(Z) Node w(Z) Node w(Z) Node w(Z) 58 - 61 --- 44 1.1897 30 1.1348 16 1.0689 57 1.2732 43 1.1922 29 1.1317 15 1.0691 56 1.2689 42 1.1900 28 1.1284 14 1.0747 55 1.2628 41 1.1858 27 1.1240 13 1.0868 54 1.2563 40 1.1792 26 1.1185 12 1.0986 53 1.2495 39 1.1719 25 1.1122 11 1.1126 52 1.2420 38 1.1669 24 1.1052 10 1.1276 51 1.2338 37 1.1653 23 1.0977 9 1.1462 50 1.2251 36 1.1634 22 1.0912 8 1.1718 49 1.2160 35 1.1598 21 1.0847 7 1.1927 48 1.2069 34 1.1545 20 1.0773 6 1.2088 47 1.1977 33 1.1485 19 1.0719 5 1.2223 46 1.1879 32 1.1438 18 1.0712 1 - 4 45 1.1870 31 1.1390 17 1.0702 Core Height (ft) = (Node - 1)
- 0.2 15 ERX-08-001, Rev. 0
COLR for CPNPP Unit 2 Cycle 11 FIGURE 7 W(Z) AS A FUNCTION OF CORE HEIGHT (20,000 MWD/MTU) 1.450 1.400 1.350 1.300 1.250 -- ýF 11200 /- 71 1.150 1.100 1.050 I I I I 1.000 0 1 2 3 4 5 6 7 8 9 10 11 12 BOTTOM CORE HEIGHT (FEET) TOP Axial Axial Axial Axial Node W(Z) Node w(Z) Node w(Z) Node w(Z) 58 - 61 44 1.1852 30 1.2037 16 1.0564 57 1.2502 43 1.1903 29 1.1966 15 1.0649 56 1.2492 42 1.1948 28 1.1927 14 1.0747 55 1.2444 41 1.1998 27 1.1861 13 1.0846 54 1.2344 40 1.2074 26 1.1775 12 1.0948 53 1.2232 39 1.2150 25 1.1674 11 1.1051 52 1.2161 38 1.2211 24 1.1556 10 1.1152 51 1.2086 37 1.2287 23 1.1426 9 1.1249 50 1.1980 36 1. 2333 22 1.1285 8 1.1341 49 1.1874 35 1.2348 21 1.1136 7 1.1425 48 1.1808 34 1. 2336 20 1.0983 6 1.1480 47 1.1778 33 1.2296 19 1.0826 5 1.1534 46 1.1799 32 1.2230 18 1.0672 1 - 4 45 1.1822 31 1.2137 17 1.0558 Core Height (ft) = (Node - 1)
COLR for CPNPP Unit 2 Cycle 11 FIGURE 8 AXIAL FLUX DIFFERENCE LIMITS AS A FUNCTION OF RATED THERMAL POWER 100 90 80 70 0
60 so E-4 40 0
u 30 P4, 20 10 0-30 -20 -10 0 10 20 30 40 AXIAL FLUX DIFFERENCE (%)
17 ERX-08-001, Rev. 0