Frequency 1.4 1.4 Frequency EXAMPLES EXAMPLE 1.4-1 (continued)
If the interval as specified by SR 3.0.2 is exceeded while the unit is not in a MODE or other specified condition in the Applicability of the LCO for which performance'of the SR is required then SR 3.0.4 becomes applicable.
The Surveillance must be performed within the Frequency requirements of SR 3.0.2, as modified by SR 3.0.3, prior to entry into the MODE or other specified condition or the LCO is considered not met (in accordance with SR 3.0.1) and LCO 3.0.4 becomes applicable.
Failure to do so would result in a violation of SR 3.0.4.
EXAMPLE 1.4-2 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY Verify flow is within limits.
Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after
Ž 25% RTP AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter Example 1.4-2 has two Frequencies.
The first is a one time performance Frequency, and the second is of the type shown in Example 1.4-1.
The logical connector "AND" indicates that both Frequency requirements must be met.
Each time reactor power is increased from a power level < 25% RTP to
> 25% RTP, the Surveillance must be performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
The use of "once" indicates a single performance will satisfy the specified Frequency (assuming no other Frequencies are connected by "AND").
This type of Frequency does not qualify for the extension allowed by SR 3.0.2.
(conti nued)
GRAND GULF 1.0-26 Amendment No.
4-2-4, 175
LCO Applicability 3.0 3.0 LIMITING CONDITION FOR OPERATION (LCO)
APPLICABILITY LCO 3.0.1 LCOs shall be met during the MODES or other specified conditions in the Applicability, except as provided in LCO 3.0.2, LCO 3.0.7, and LCO 3.0.8.
LCO 3.0.2 Upon discovery of a failure to meet an LCO, the Required Actions of the associated Conditions shall be met, except as provided in LCO 3.0.5 and LCO 3.0.6.
If the LCO is met or is no longer applicable prior to expiration of the specified Completion Time(s),
completion of the Required Action(s) is not required, unless otherwise stated.
LCO 3.0.3 When an LCO is not met and the associated ACTIONS are not
- met, an associated ACTION is not provided, or if directed by the associated ACTIONS, the unit shall be placed in a MODE or other specified condition in which the LCO is not applicable.
Action shall be initiated within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to place the unit, as applicable, in:
- a.
MODE 2 within 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />;
- b.
MODE 3 within 13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br />; and
- c.
MODE 4 within 37 hours4.282407e-4 days <br />0.0103 hours <br />6.117725e-5 weeks <br />1.40785e-5 months <br />.
Exceptions to this Specification are stated in the individual Specifications.
Where corrective measures are completed that permit operation in accordance with the LCO or ACTIONS, completion of the actions required by LCO 3.0.3 is not required.
LCO 3.0.3 is only applicable in MODES 1, 2, and 3.
LCO 3.0.4 When an LCO is not met, entry.into a MODE or other specified condition in the Applicability shall only be made:
- a.
When the associated ACTIONS to be entered permit continued operation in the MODE or other specified condition in the Applicability for an unlimited period of time; (continued)
GRAND GULF 3.0-1 Amendment No.
4-74-,
175
LCO Applicability 3.0 3.0 LCO APPLICABILITY LCO 3.0.4 (continued)
- b.
After performance of a risk assessment addressing inoperable systems and components, consideration of the results, determination of the acceptability of entering the MODE or other specified condition in the Applicability, and establishment of risk management
- actions, if appropriate; exceptions to this Specification are stated in the individual Specifications, or
- c.
When an allowance is stated in the individual value, parameter, or other Specification.
-This Specification shall not prevent changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
LCO 3.0.5 Equipment removed from service or declared inoperable to comply with ACTIONS may be returned to service under administrative control solely to perform testing required to demonstrate its OPERABILITY or the OPERABILITY of other equipment.
This is an exception to LCO 3.0.2 for the system returned to service under administrative control to perform the testing required to demonstrate OPERABILITY.
LCO 3.0.6 When a supported system LCO is not met solely due to a support system LCO not being met, the Conditions and Required Actions associated with this supported system are not required to be entered.
Only the support system LCO ACTIONS are required to be entered.
This is an exception to LCO 3.0.2 for the supported system.
In this event, an evaluation shall be performed in accordance with Specification 5.5.10, "Safety Function Determination Program (SFDP)."
If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.
When a support system's Required Action directs a supported system to be declared inoperable or directs entry into Conditions and Required Actions for a supported system, the applicable Conditions and Required Actions shall be entered in accordance with LCO 3.0.2.
(continued)
GRAND GULF 3.0-2 Amendment No.
4-4-2, 175
SR Applicability 3.0 3.0 SR APPLICABILITY (continued)
SR 3.0.4 Entry into a MODE or other specified condition in the Applicability of an LCO shall only be made when the LCO's Surveillances have been met within their specified Frequency, except as provided by SR 3.0.3.
When an LCO is not met due to Surveillances not having been met, entry into a MODE or other specified condition in the Applicability shall only be made in accordance with LCO 3.0.4.
This provision shall not prevent entry into MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
GRAND GULF 3.0-5 Amendment No.
4-2-9, 175
PAM Instrumentation 3.3.3.1 3.3 INSTRUMENTATION 3.3.3.1 Post Accident Monitoring (PAM)
Instrumentation LCO 3.3.3.1 APPLICABILITY:
The PAM instrumentation for each Function in Table 3.3.3.1-1 shall be OPERABLE.
MODES 1 and 2.
ACTIONS
NOTE-------------------------------------
Separate Condition entry is allowed for each Function.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more Functions A.1 Restore required 30 days with one required channel to OPERABLE channel inoperable, status.
B.
Required Action and B.1 Initiate action to Immediately associated Completion prepare and submit a Time of Condition A Special Report.
not met.
C.
One or more Functions C.1 Restore one required 7 days with two required channel to OPERABLE channels inoperable, status.
(continued)
GRAND GULF 3.3-19 Amendment No.
4-2-4, 175
Remote Shutdown System 3.3.3.2 3.3 INSTRUMENTATION 3.3.3.2 Remote Shutdown System LCO 3.3.3.2 APPLICABILITY:
The Remote Shutdown System Functions shall be OPERABLE.
MODES 1 and 2.
ACTIONS
i -----------------------------
NOTE----------------------------------
Separate Condition entry is allowed for each Function.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more required A.1 Restore required 30 days Functions inoperable.
Function to OPERABLE status.
B.
Required Action and B.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.3.2.1 Perform CHANNEL CHECK for each required 31 days instrumentation channel that is normally energized.
(continued)
GRAND GULF 3.3-23 Amendment No.
1-24, 175
RCS Leakage Detection Instrumentation 3.4.7 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.7 RCS Leakage Detection Instrumentation LCO 3.4.7 The following RCS leakage detection instrumentation shall be OPERABLE:
- a.
Drywell floor drain sump monitoring system;
- b.
One channel of either drywell atmospheric particulate or atmospheric gaseous monitoring system; and
- c.
Drywell air cooler condensate flow rate monitoring system.
APPLICABILITY:
MODES 1, 2,
and 3.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
Drywell floor drain A.1 Restore drywell 30 days sump monitoring floor drain sump system inoperable, monitoring system to OPERABLE status.
B.
Required drywell B.A Analyze grab samples Once per 12 atmospheric of drywell hours monitoring system atmosphere.
(continued)
GRAND GULF 3.4-16 R Amendment No.4-4-2, 175
RCS Specific Activity 3.4.8 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.8 RCS Specific Activity LCO
3.4.8 APPLICABILITY
The DOSE EQUIVALENT 1-131 specific activity of the reactor coolant shall be
- 0.2 piCi/gm.
MODE 1, MODES 2 and 3 with any main steam line not isolated.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME,
NOTE------------
A.
Reactor coolant LCO 3.0.4.c is applicable.
specific activity
> 0.2 pCi/gm and
- 4.0 jtCi/gm DOSE A.1 Determine DOSE Once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> EQUIVALENT 1-131.
EQUIVALENT 1-131.
AND A.2 Restore DOSE 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> EQUIVALENT 1-131 to within limits.
B.
Required Action and B.1 Determine DOSE Once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> associated Completion EQUIVALENT 1-131.
Time of Condition A not met.
AND OR B.2.1 Isolate all main 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> steam lines.
Reactor coolant specific activity OR
> 4.0 pCi/gm DOSE EQUIVALENT 1-131.
B.2.2.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND B.2.2.2 Be in MODE 4.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> GRAND GULF 3.4-19 Amendment No.
1-2-4, 175
RHR Shutdown Cooling System-Hot Shutdown 3.4.9 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.9 Residual Heat Removal (RHR)
Shutdown Cooling System-Hot Shutdown LCO 3.4.9 Two RHR shutdown cooling subsystems shall be OPERABLE,
- and, with no recirculation pump in operation, at least one RHR shutdown cooling subsystem shall be in operation.
NOTES-------------------------
- 1.
Both RHR shutdown cooling subsystems and recirculation pumps may not be in operation for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> per 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period.
- 2.
One RHR shutdown cooling subsystem may be inoperable for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for performance of Surveillances.
APPLICABILITY:
MOOE 3 with reactor steam dome pressure less than the RHR cut in permissive pressure.
ACTIONS NOTE---------------------------------
Separate Condition entry is allowed for each RHR shutdown cooling subsystem.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or two RHR A.1 Initiate action to Immediately shutdown cooling restore RHR shutdown subsystems inoperable, cooling subsystem(s) to OPERABLE status.
AND (continued)
GRAND GULF 3.4-21 Amendment No.
--4-2-,
175
ECCS-Operating 3.5.1 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS)
AND REACTOR CORE ISOLATION COOLING (RCIC)
SYSTEM 3.5.1 ECCS-Operating LCO 3.5.1 Each ECCS injection/spray subsystem and the Automatic Depressurization System (ADS) function of eight safety/relief valves shall be OPERABLE.
NOTE----------------------------
Low pressure coolant injection (LPCI) subsystems may be considered OPERABLE during alignment and operation for decay heat removal with reactor steam dome pressure less than the residual heat removal cut in permissive pressure in MODE 3, if capable of being manually realigned and not otherwise inoperable.
APPLICABILITY:
MODE 1, MODES 2 and 3, except ADS valves are-not required to be OPERABLE with reactor steam dome pressure
- 150 psig.
ACTIONS NOTE----------------------------------
LCO 3.0.4.b is not applicable to HPCS.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One low pressure ECCS A.1 Restore low pressure 7 days injection/spray ECCS injection/spray subsystem inoperable, subsystem to OPERABLE status.
(continued)
GRAND GULF 3.5-1 Amendment No.
4-64, 175
ECCS-Operating 3.5.1 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME B.
High Pressure Core B.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Spray (HPCS)
System administrative means inoperable.
RCIC System is OPERABLE when RCIC is required to be OPERABLE.
AND B.2 Restore HPCS System 14 days to OPERABLE status.
(continued)
GRAND GULF 3.5 -1 a Amendment No.
175 1
RCIC System 3.5.3 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS)
AND REACTOR CORE ISOLATION COOLING (RCIC)
SYSTEM 3.5.3 RCIC System LCO
3.5.3 APPLICABILITY
The RCIC System shall be OPERABLE.
MODE 1, MODES 2 and 3 with reactor steam dome pressure > 150 psig.
ACTIONS NOTE --------------------------------------
LCO 3.0.4.b is not applicable to RCIC.
CONDITION REQUIRED ACTION COMPLETION TIME A.
RCIC System A.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable, administrative means High Pressure Core Spray System is OPERABLE.
AND A.2 Restore RCIC System 14 days to OPERABLE status.
B.
Required Action and B.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.
AND B.2 Reduce reactor steam 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> dome pressure to 150 psig.
GRAND GULF 3.5-10 Amendment No.
4-2-0, 175
Primary Containment and Drywell Hydrogen Igniters 3.6.3.2 3.6 CONTAINMENT SYSTEMS 3.6.3.2 Primary Containment and Drywell Hydrogen Igniters LCO 3.6.3.2 APPLICABILITY:
Two divisions of primary containment and drywell hydrogen igniters shall be OPERABLE, each with > 90% of the associated igniter assemblies OPERABLE.
MODES 1 and 2.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
One primary A.1 Restore primary 30 days containment and containment and drywell hydrogen drywell hydrogen igniter division igniter division to inoperable.
OPERABLE status.
B.
Two primary B.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> containment and administrative means drywell hydrogen that the hydrogen igniter divisions control function is inoperable, maintained.
AND B.2 Restore one primary 7 days containment and drywell hydrogen igniter division to OPERABLE status.
(continued)
GRAND GULF 3.6-37 Amendment No.
4-2-4, 175
Drywell Purge System 3.6.3.3 3.6 CONTAINMENT SYSTEMS 3.6.3.3 Drywell Purge System LCO 3.6.3.3 Two drywell purge subsystems shall be OPERABLE.
APPLICABILITY:
MODES 1 and 2.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One drywell purge A.1 Restore drywell purge 30 days subsystem inoperable, subsystem to OPERABLE status.
B.
Two drywell purge B.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> subsystems inoperable, administrative means that the hydrogen control function is maintained.
AND B.2 Restore one drywell 7 days purge subsystem to OPERABLE status.
C.
Required Action and C.1 Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.
GRAND GULF 3.6-40 Amendment No.
4-2-4, 175
AC Sources-Operating 3.8.1 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 AC Sources-Operating LCO 3.8.1 The following AC electrical power sources shall be OPERABLE:
- a.
Two qualified circuits between the offsite transmission network and the onsite Class 1E AC Electric Power Distribution System;
- b.
Three diesel generators (DGs);
and
- c.
Division I and Division 2 automatic load sequencers.
APPLICABILITY:
MODES 1, 2, and 3.
NOTE--------------------------
Division 3 AC electrical power sources are not required to be OPERABLE when High Pressure Core Spray System is inoperable.
ACTIONS
NOTE-----------------------------------
LCO 3.0.4.b is not applicable to DGs.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One required offsite A.1, Perform SR 3.8.1.1 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> circuit inoperable for for OPERABLE required reasons other than offsite circuit.
AND Condition F.
Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter AND (continued)
GRAND GULF 3.8-1 Amendment No.
- 444, 175