MONTHYEARML0525601182005-08-26026 August 2005 Draft RAI Re. Proposed Amendment on Alternative Source Term Project stage: Draft RAI ML0531203762005-11-0202 November 2005 Response to Request for Additional Information - License Amendment Request No. 315, Application of Alternative Source Term. (Non-Proprietary Version) Project stage: Response to RAI ML0531203242005-12-0505 December 2005 Amergen Energy Company LLC, Request for Withholding Information from Public Disclosure for Oyster Creek Generating Station Project stage: Withholding Request Acceptance ML0633204782006-11-28028 November 2006 E-mail, Miller, NRR, to Distel, Exelon, Draft Request for Additional Information, Oyster Creek AST LAR Project stage: Draft RAI ML0633302152006-12-19019 December 2006 RAI, License Amendment Request for Application of the Alternate Source Term Methodology Project stage: RAI ML0634501852006-12-21021 December 2006 Summary of Meeting with Amergen Energy Company, LL, to Discuss Alternative Source Term License Amendment Request Project stage: Meeting ML0703101012007-01-24024 January 2007 Response to Request for Additional Information - License Amendment Request No. 315, Application of Alternative Source Term Project stage: Response to RAI ML0703603302007-02-0202 February 2007 Response to Request for Additional Information - License Amendment Request No. 315, Application of Alternative Source Term. Project stage: Response to RAI ML0705204592007-02-0909 February 2007 E-mail, Miller, NRR, to Distel, Exelon, Oyster Creek AST Project stage: Other ML0708508202007-03-15015 March 2007 Calculation No. C-1302-826-E310-018, Revision 0, Oyster Creek Offsite Atmospheric Dispersion (X/Q) for Alternative Source Terms (Ast). Project stage: Other ML0708508162007-03-16016 March 2007 Additional Information - License Amendment Request No. 315, Application of Alternative Source Term Project stage: Request ML0706505142007-03-21021 March 2007 Clarification of Response to Request for Additional Information Regarding License Amendment Request for Application of the Alternate Source Term Methodology Project stage: RAI ML0709200672007-03-23023 March 2007 Additional Information - License Amendment Request No. 315, Application of Alternative Source Term Project stage: Request ML0708803932007-03-28028 March 2007 Additional Information - License Amendment Request No. 315, Application of Alternative Source Term. Project stage: Request ML0710800192007-04-26026 April 2007 License Amendment Application of Alternate Source Term Methodology Project stage: Acceptance Review ML0711703892007-04-26026 April 2007 Technical Specifications Application of Alternate Source Term Methodology Project stage: Other ML0713102132007-05-0404 May 2007 Additional Information - License Amendment Request No. 315, Application of Alternative Source Term. Project stage: Request 2007-02-02
[Table View] |
|
---|
Category:Letter
MONTHYEARML23342A1162024-01-0909 January 2024 Independent Spent Fuel Storage Installation Security Inspection Plan L-23-019, Proof of Financial Protection 10 CFR 140.152023-12-18018 December 2023 Proof of Financial Protection 10 CFR 140.15 IR 05000219/20230022023-11-0909 November 2023 EA-23-076 Oyster Creek Nuclear Generating Station - Notice of Violation and Proposed Imposition of Civil Penalty - $43,750 - NRC Inspection Report No. 05000219/2023002 ML23286A1552023-10-13013 October 2023 Defueled Safety Analysis Report (DSAR) ML23249A1212023-09-0606 September 2023 NRC Inspection Report 05000219/2023002, Apparent Violation (EA-23-076) ML23242A1162023-08-30030 August 2023 Biennial 10 CFR 50.59 and 10 CFR 72.48 Change Summary Report January 1, 2021 Through December 31, 2022 ML23214A2472023-08-22022 August 2023 NRC Inspection Report 05000219/2023002 IR 05000219/20230012023-05-31031 May 2023 NRC Inspection Report No. 05000219/2023001 IR 07200015/20234012023-05-16016 May 2023 NRC Independent Spent Fuel Storage Installation Security Inspection Report 07200015/2023401 ML23114A0912023-04-24024 April 2023 Annual Radioactive Effluent Release Report for 2022 ML23114A0872023-04-24024 April 2023 Annual Radioactive Environmental Operating Report for 2022 L-23-004, HDI Annual Occupational Radiation Exposure Data Reports - 20222023-04-24024 April 2023 HDI Annual Occupational Radiation Exposure Data Reports - 2022 L-23-003, Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations2023-03-31031 March 2023 Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations ML23088A0382023-03-29029 March 2023 Stations 1, 2, & 3, Palisades Nuclear Plant, and Big Rock Point - Nuclear Onsite Property Damage Insurance ML22361A1022023-02-24024 February 2023 Reactor Decommissioning Branch Project Management Changes for Some Decommissioning Facilities and Establishment of Backup Project Manager for All Decommissioning Facilities IR 05000219/20220022023-02-0909 February 2023 NRC Inspection Report No. 05000219/2022002 ML23031A3012023-02-0808 February 2023 Discontinuation of Radiological Effluent Monitoring Location in the Sewerage System ML23033A5052023-02-0202 February 2023 First Use Notification of NRC Approved Cask RT-100 ML23025A0112023-01-24024 January 2023 LLRW Late Shipment Investigation Report Per 10 CFR 20, Appendix G ML22347A2732022-12-21021 December 2022 Independent Spent Fuel Storage Installation Security Inspection Plan Dated December 21, 2022 ML22297A1432022-12-15015 December 2022 Part 20 App G Exemption Letter L-22-042, Oyster, Pilgrim, Indian Point, Palisades and Big Rock Point - Proof of Financial Protection 10 CFR 140.152022-12-14014 December 2022 Oyster, Pilgrim, Indian Point, Palisades and Big Rock Point - Proof of Financial Protection 10 CFR 140.15 IR 07200015/20224012022-12-0606 December 2022 NRC Independent Spent Fuel Storage Installation Security Inspection Report 07200015/2022401 (Letter & Enclosure 1) ML22280A0762022-11-0202 November 2022 Us NRC Analysis of Holtec Decommissioning Internationals Funding Status Report for Oyster Creek, Indian Point and Pilgrim Nuclear Power Station ML22276A1762022-10-24024 October 2022 Decommissioning International Proposed Revisions to the Quality Assurance Program Approval Forms for Radioactive Material Packages ML22286A1402022-10-13013 October 2022 NRC Confirmatory Order EA-21-041 IR 05000219/20220012022-08-11011 August 2022 NRC Inspection Report 05000219/2022001 ML22215A1772022-08-0303 August 2022 Decommissioning International (HDI) Proposed Revisions to the Quality Assurance Program Approval Forms for Radioactive Material Packages ML22214A1732022-08-0202 August 2022 Request for Exemption from 10 CFR 20, Appendix G, Section Iii.E ML22207B8382022-07-26026 July 2022 NRC Confirmatory Order EA-21-041 ML22130A6882022-05-10010 May 2022 Late LLRW Shipment Investigation Report Pursuant to 10 CFR 20, Appendix G L-22-026, Occupational Radiation Exposure Data Report - 20212022-04-29029 April 2022 Occupational Radiation Exposure Data Report - 2021 ML22118A6122022-04-28028 April 2022 Annual Radioactive Environmental Operating Report for 2021 ML22118A5822022-04-28028 April 2022 Annual Radioactive Effluent Release Report for 2021 ML22091A1062022-04-0101 April 2022 Nuclear Onsite Property Damage Insurance (10 CFR 50.54(w)(3)) L-22-022, and Indian Point Nuclear Generating Stations 1, 2, & 3 - Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations - Holtec.2022-03-25025 March 2022 and Indian Point Nuclear Generating Stations 1, 2, & 3 - Report on Status of Decommissioning Funding for Reactors and Independent Spent Fuel Storage Installations - Holtec. ML22069A3762022-03-10010 March 2022 Late LLRW Shipment Investigation Report Pursuant to 10 CFR 20, Appendix G ML22032A0582022-03-0808 March 2022 EA-21-139; EA-150: Oyster Creek Nuclear Generating Station - NRC Investigation Report Nos.. 1-2021-002 & 1-2021-014 ML22060A2202022-03-0202 March 2022 NRC Office of Investigations Case No. 1-2021-009 ML22049B2452022-02-19019 February 2022 Late Low Level Radwaste Shipment Report Pursuant to 10 CFR 20 Appendix G IR 05000219/20214022022-01-26026 January 2022 EA-21-041: Confirmatory Order Related to Oyster Greek Nuclear Generating Station - NRC Investigation Report I-2020-007; NRC Inspection Report Nos. 05000219/2021402 & 07200015/2021401 ML22025A3422022-01-25025 January 2022 and Big Rock Point - Changes to Site Organization ML22025A2182022-01-25025 January 2022 Late LLRW Shipments Investigation Report Pursuant to 10 CFR 20, Appendix G ML22021B5512022-01-21021 January 2022 Compensatory Measures Not Implemented Per Site'S Physical Security Plan Due to Multiplexer (Mux) Power Supply Failure L-21-134, and Indian Point Nuclear Generating Stations 1, 2, & 3 - Report on Status of Decommissioning Funding for Independent Spent Fuel Storage Installations2021-12-17017 December 2021 and Indian Point Nuclear Generating Stations 1, 2, & 3 - Report on Status of Decommissioning Funding for Independent Spent Fuel Storage Installations ML21349A5192021-12-15015 December 2021 Commitment Change Summary Report ML21285A1912021-11-30030 November 2021 Nrc'S Analysis of Holtec Decommissioning International'S Decommissioning Funding Status Report for Oyster Creek Nuclear Generating Station and Pilgrim Nuclear Power Station, Docket Nos 50-219 and 50-293 IR 05000219/20210032021-11-16016 November 2021 NRC Inspection Report No. 05000219/2021003 L-21-118, Changes to Signature Authority & Addressee for Holtec Decommissioning International, LLC Correspondence Re to Oyster Creek Nuclear Generating Station, Pilgrim Nuclear Power Station, Indian Point Nuclear Generating Units 1, 2, 3, & Palisades2021-11-0909 November 2021 Changes to Signature Authority & Addressee for Holtec Decommissioning International, LLC Correspondence Re to Oyster Creek Nuclear Generating Station, Pilgrim Nuclear Power Station, Indian Point Nuclear Generating Units 1, 2, 3, & Palisades IR 05000219/20214042021-08-26026 August 2021 NRC Independent Spent Fuel Storage Security Inspection Report No. 07200015/2021402 and Security Decommissioning Inspection Report 05000219/2021404 - (Public) 2024-01-09
[Table view] |
Text
March 21, 2007 Mr. Christopher M. Crane President and Chief Executive Officer AmerGen Energy Company, LLC 4300 Winfield Road Warrenville, IL 60555
SUBJECT:
CLARIFICATION OF RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION REGARDING LICENSE AMENDMENT REQUEST FOR APPLICATION OF THE ALTERNATE SOURCE TERM METHODOLOGY (TAC NO. MC6519)
Dear Mr. Crane:
By letter dated March 28, 2005, AmerGen Energy Company, LLC (AmerGen, or the licensee) requested changes to the Facility Operating License for the Oyster Creek Nuclear Generating Station (Oyster Creek). The license amendment request (LAR) would revise the Oyster Creek licensing basis in the area of radiological dose analyses for design-basis accidents using the alternative source terms depicted in Regulatory Guide 1.183, Alternative Radiological Source Terms for Evaluating Design Basis Accidents at Nuclear Power Reactors.
The Nuclear Regulatory Commission (NRC) staff, during review of the submittal, determined that additional information was needed to complete its review. These questions were provided via e-mail in draft form to Mr. David Distel of your staff on November 28, 2006, to ensure that the questions were understandable, the regulatory basis was clear and to determine if the information was previously docketed. Subsequently they were provided in final form by letter dated December 19, 2006. Mr. David Distel of your staff agreed to respond within 45 days from the date of the December 19, 2006 letter (e.g., February 2, 2007).
By letters dated January 24 and February 2, 2007, you provided responses to the questions.
The NRC staff, upon reviewing the responses, identified certain responses that did not fully address the issues raised by the NRC staff in the original RAIs. Specifically, the responses did not sufficiently address use of the assumption of full mixing credit for mixing/dilution in the secondary containment nor the use of a pressure dependant function for containment main steam isolation valve (MSIV) leakage and did not adequately support the offsite atmospheric dispersion factors used to calculate offsite dose. The clarifications needed were communicated to you in teleconferences on February 9, 2007 and March 5, 2007.
In a teleconference on March 15, 2007, you agreed to provide a revised analysis in which full mixing credit and pressure dependant MSIV leakage is not assumed. Additionally, by letter dated March 16, 2007, you provided revised offsite atmospheric dispersion factors for offsite dose calculation.
In order to complete our review of the LAR, the NRC staff requests that you provide these revised analyses. A submittal date of March 23, 2007 was agreed upon during discussions with your staff.
C. Crane Please note that if you do not respond to this letter within the prescribed response time or provide an acceptable alternate date in writing, we may reject your application for amendment under the provisions of Title 10 of the Code of Federal Regulations, Section 2.108. If you have any questions, I can be reached at (301) 415-2481.
Sincerely,
/ra/
G. Edward Miller, Project Manager Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-219 cc: See next page
C. Crane Please note that if you do not respond to this letter within the prescribed response time or provide an acceptable alternate date in writing, we may reject your application for amendment under the provisions of Title 10 of the Code of Federal Regulations, Section 2.108. If you have any questions, I can be reached at (301) 415-2481.
Sincerely,
/ra/
G. Edward Miller, Project Manager Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-219 cc: See next page DISTRIBUTION:
PUBLIC RidsNrrDorlLpl1-2 RidsNrrPMGMiller RidsOgcMailCenter LPL1-2 R/F RidsNrrLACRaynor RidsAcrsAcnwMailCenter RidsNrrDssSbpb MHart LBrown ADAMS Accession Number: ML070650514 OFFICE LPL1-2/PM LPL1-2/LA LPL1-2/BC NAME GEMiller MOBrien, HChernoff RSola for DATE 3/21/07 3/21/07 3/21/07 OFFICIAL RECORD COPY
Oyster Creek Nuclear Generating Station Site Vice President - Oyster Creek Director - Licensing and Regulatory Affairs Nuclear Generating Station AmerGen Energy Company, LLC AmerGen Energy Company, LLC Correspondence Control P.O. Box 388 P.O. Box 160 Forked River, NJ 08731 Kennett Square, PA 19348 Senior Vice President of Manager Licensing - Oyster Creek Operations Exelon Generation Company, LLC AmerGen Energy Company, LLC Correspondence Control 200 Exelon Way, KSA 3-N P.O. Box 160 Kennett Square, PA 19348 Kennett Square, PA 19348 Kathryn M. Sutton, Esquire Regulatory Assurance Manager Morgan, Lewis, & Bockius LLP Oyster Creek 1111 Pennsylvania Avenue, NW AmerGen Energy Company, LLC Washington, DC 20004 P.O. Box 388 Forked River, NJ 08731 Kent Tosch, Chief New Jersey Department of Assistant General Counsel Environmental Protection AmerGen Energy Company, LLC Bureau of Nuclear Engineering 200 Exelon Way CN 415 Kennett Square, PA 19348 Trenton, NJ 08625 Ron Bellamy, Region I Vice President - Licensing and U.S. Nuclear Regulatory Commission Regulatory Affairs 475 Allendale Road AmerGen Energy Company, LLC King of Prussia, PA 19406-1415 4300 Winfield Road Warrenville, IL 60555 Correspondence Control Desk AmerGen Energy Company, LLC Regional Administrator, Region I 200 Exelon Way, KSA 1--1 U.S. Nuclear Regulatory Commission Kennett Square, PA 19348 475 Allendale Road King of Prussia, PA 19406-1415 Oyster Creek Nuclear Generating Station Plant Manager Mayor of Lacey Township AmerGen Energy Company, LLC 818 West Lacey Road P.O. Box 388 Forked River, NJ 08731 Forked River, NJ 08731 Senior Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 445 Forked River, NJ 08731