Technical Specifications Corrected Page for Amendment Nos. 249 and 229
ML070220219
Person / Time
Site: North Anna  
(NPF-004, NPF-007)
Issue date: 01/19/2007
From:
NRC/NRR/ADRO/DORL/LPLII-1
To:
Lingam, Siva NRR/DORL 415-1564
References
TAC MD2107, TAC MD2108
Download: ML070220219 (1)


Text

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.12 Diesel Fuel Oil Testina Program A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established. The program shall include sampling and testing requirements, and acceptance criteria, all in accordance with applicable ASTM Standards. The purpose of the program is to-establish the following:

a.

Acceptability of new fuel oil for use prior to addition to storage tanks by determining that the fuel oil has:

-1. an API gravity or an absolute specific gravity within

limits,
2. a flash point and kinematic viscosity within limits for ASTM 2D fuel oil, and
3. water and sediment
  • 0.05%.
b.

Within 31 days following addition of the new fuel oil to storage tanks verify that the properties of the new fuel oil, other than those addressed in a. above, are within limits for ASTM 2D fuel oil;

c.

Total particulate concentration of the stored fuel oil is

  • 10 mg/i when tested every 92 days; and
d.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Diesel Fuel Oil Testing Program testing Frequencies.

5.5.13 Technical Specifications (TS)

Bases Control Program This program provides a means for processing changes to the Bases of these Technical Specifications.

a.

Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews.

b.

Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:

1. a change in the TS incorporated in the license; or (continued)

North Anna Units 1 and 2 5.5-12 Amendment Nos. 249, 229 Corrected by letter dated Januarv 19. 2007