PALO VERDE NUCLEAR GENERATING STATION UNITS 1, 2 AND 3 2005 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT USNRC Docket No. STN 50-528/529/530 RCTSAI 1566 IL
- i -!
-"r Digitally siged by Kutner, Kevin W(Z58001)
Date: 04/14/2 1 :38:22 Reason: I arn te ufthor of is dcumernt Prepared by:
Location. PVNGS DlpUsiy sinadby SunqmmtJr Pam.
16012)
NMX:
rw1542,0 16:0s 58 RPon: I Ih ewed IN. docwnt Reviewed by: LdisRm PWv`GS Dig" signed by. Gaf
, JoM PZ3U4%
Date' 0421r20M 1744.04 Reason: I are spipyhig libh documuent Approved by:
- Pv~s
TABLE OF CONTENTS SECTION PAGE INTRODUCTION.........................................................................................................................................5 BIBLIOGRAPHY..........................................................................................................................................6 APPENDIX A SOURCE TERMS AND EFFLUENT AND WASTE DISPOSAL REPORTS......................... 7 APPENDIX B METEOROLOGY..................................................................... 63 APPENDIX C DOSE CALCULATIONS....................................................................
86 APPENDIX D OFFSITE DOSE CALCULATION MANUAL Revision 20................................................... 95 LIST OF TABLES TABLE PAGE I
Evaporation Pond Data.15 2
Batch Release Data.
15 3
Units 1, 2 & 3 Gaseous Effluents Average Lower Limit Of Detection.16 4
Unit 1 Gaseous Effluents - Summation Of All Releases.17 5
Unit 1 Gaseous Effluents - Ground Level Releases - Continuous - Fission Gases and lodines..................... 18 6
Unit 1 Gaseous Effluents - Ground Level Releases - Continuous - Particulates.19 7
Unit 1 Gaseous Effluents - Ground Level Releases - Batch - Fission Gases and lodines.............................. 20 8
Unit 1 Gaseous Effluents - Ground Level Releases - Batch - Particulates.21 9
Unit 1 Gaseous Effluents - Continuous and Batch - Fission Gases and lodines.22 10 Unit 1 Gaseous Effluents - Continuous and Batch - Particulates.23 11 Unit I Radiation Doses At And Beyond The Site Boundary.24 2
A LIST OF TABLES TABLE PAGE 12 Unit 2 Gaseous Effluents - Summation Of All Releases........................................
............................ 25 13 Unit 2 Gaseous Effluents - Ground Level Releases - Continuous - Fission Gases and lodines..................... 26 14 Unit 2 Gaseous Effluents - Ground Level Releases - Continuous - Particulates...................
......................... 27 15 Unit 2 Gaseous Effluents - Ground Level Releases - Batch - Fission Gases and lodines.............................. 28 16 Unit 2 Gaseous Effluents - Ground Level Releases - Batch - Particulates.............................
........................ 29 17 Unit 2 Gaseous Effluents - Continuous and Batch - Fission Gases and lodines...................
......................... 30 18 Unit 2 Gaseous Effluents - Continuous and Batch - Particulates.................................................................... 31 19 Unit 2 Radiation Doses At And Beyond The Site Boundary....................................................................
32 20 Unit 3 Gaseous Effluents - Summation Of All Releases.......................................
............................. 33 21 Unit 3 Gaseous Effluents - Ground Level Releases - Continuous - Fission Gases and lodines..................... 34 22 Unit 3 Gaseous Effluents - Ground Level Releases - Continuous - Particulates...................
......................... 35 23 Unit 3 Gaseous Effluents - Ground Level Releases - Batch - Fission Gases and lodines.............................. 36 24 Unit 3 Gaseous Effluents - Ground Level Releases - Batch - Particulates..............................
....................... 37 25 Unit 3 Gaseous Effluents - Continuous and Batch - Fission Gases and lodines............................................ 38 26 Unit 3 Gaseous Effluents - Continuous and Batch - Particulates.................................................................... 39 27 Unit 3 Radiation Doses At And Beyond The Site Boundary....................................................................
40 3
LIST OF TABLES TABLE PAGE 28 Units 1, 2, and 3 Gaseous Effluents - Continuous - Fission Gases and lodines - Total By Quarter.........
...... 41 29 Units 1, 2, and 3 Gaseous Effluents - Continuous - Particulates - Total By Quarter....................................... 42 30 Units 1, 2, and 3 Gaseous Effluents - Batch - Fission Gases and lodines - Total By Quarter...........
............. 43 31 Units 1, 2, and 3 Gaseous Effluents - Batch - Particulates - Total By Quarter................................................ 44 32 Units 1, 2, and 3 Gaseous Effluents - Continuous and Batch - Fission Gases and lodines - Total By Quarter 45 33 Units 1, 2, and 3 Gaseous Effluents - Continuous and Batch - Particulates - Total By Quarter...................... 46 34 Units 1, 2 and 3 Gaseous Effluents-Continuous - Fission Gases and Iodine -Total By Unit......................... 47 35 Units 1, 2 and 3 Gaseous Effluents-Continuous - Particulates - Total By Unit............................................... 48 36 Units 1, 2 and 3 Gaseous Effluents-Batch - Fission Gases and Iodine - Total By Unit.................................. 49 37 Units 1, 2 and 3 Gaseous Effluents-Batch - Particulates - Total By Unit........................................................ 50 38 Units 1, 2 and 3 Gaseous Effluents-Continuous and Batch - Fission Gases and Iodine - Total By Unit........ 51 39 Units 1, 2 and 3 Gaseous Effluents - Continuous and Batch - Particulates - Total By Unit............................. 52 40 Estimation of Total Percent Error........................................................................... 53 41 Effluent Monitoring Instrumentation Out Of Service Greater Than 30 Days.....................
.............................. 54 42 Solid Waste Summary..........................................................................
55 43 Doses To Special Locations For 2005.......................................................................... 89 44 Integrated Population Dose for 2005..........................................................................
90 45 Summary of Individual Doses for 2005..........................................................................
94 4
INTRODUCTION This report summarizes effluent and waste disposal source term data, meteorological data and doses from radioactive effluents for the Palo Verde Nuclear Generating Station (PVNGS) for the period of January through December 2005. The data presented meets the reporting requirements of Regulatory Guide 1.21 (Revision 1, June 1974) of the U.S. Nuclear Regulatory Commission and the PVNGS Technical Specifications.
BIBLIOGRAPHY U.S. Nuclear Regulatory Commission, Regulatory Guide 1.21, "Measuring, Evaluating, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants," Revision 1,1974.
U.S. Nuclear Regulatory Commission, Regulatory Guide 1.23 (Safety Guide 23), "Onsite Meteorological Programs," 1972.
U.S. Nuclear Regulatory Commission, NUREG/CR-2919, "XOQDOQ: Computer Program for the Meteorological Evaluation of Routine Effluent Releases at Nuclear Power Stations," 1982.
U.S. Nuclear Regulatory Commission, NUREG-0579, "Users Guide to GASPAR Code," June 1980.
U.S. Nuclear Regulatory Commission, Regulatory Guide 1.109, "Calculations of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purpose of Evaluating Compliance with 10 CFR 50, Appendix I," Revision 1, 1977.
U.S. Nuclear Regulatory Commission, NUREG-0172, "Age-specific Radiation Dose Commitment Factors for a One-Year Chronic Intake," 1977.
U.S. Nuclear Regulatory Commission, NUREG-0133, "Preparation of Radiological Effluent Technical Specifications for Nuclear Power Plants," 1978.
"Technical Specifications, Palo Verde Nuclear Generating Station, Unit No. 1, Docket No. 50-528, Appendix "A" to License No. NPF-41".
"Technical Specifications, Palo Verde Nuclear Generating Station, Unit No. 2, Docket No. 50-529, Appendix "A" to License No. NPF-51".
"Technical Specifications, Palo Verde Nuclear Generating Station, Unit No. 3, Docket No. 50-530, Appendix "A" to License No. NPF-74".
Bechtel Power Corp., "Cooling Tower Blowdown System Solar Evaporation Pond," Sept. 1980.
Generation Engineering, "Geotechnical Exploration for Evaporation Pond #2," Oct. 1986 Letter No. 212-00789-WFQ/RHM, "1989 PVNGS Evaporation Pan Data," Jan. 1989.
Offsite Dose Calculation Manual Palo Verde Nuclear Generating Station Units 1, 2 and 3, Rev. 20.
APPENDIX A SOURCE TERMS AND EFFLUENT AND WASTE DISPOSAL REPORTS 7
Supplemental Information 1.0 REGULATORY LIMITS 1.1 Liquid Releases 1.1.1 PVNGS ODCM Requirement 3.2 The concentration of radioactive material discharged from secondary system liquid waste to the circulating water system shall be limited to:
5.OE-07 giCi/ml for the principal gamma emitters (except Ce-144) 3.OE-06 gCi/ml for Ce-144 1.OE-06 giCi/ml for 1-131.
1.OE-03 giCi/ml for H-3 The concentration of radioactive material discharged from secondary system liquid waste to the onsite evaporation ponds shall be limited to:
2.OE-06 j+/-Ci/ml for Cs-1 34 2.OE-06 gCi/ml for Cs-137 The concentrations specified in 10 CFR Part 20.1001-20.2402, Appendix B, Table 2, Column 2, for all other isotopes 1.1.2 PVNGS ODCM Requirement 4.4 The dose or dose commitment to a MEMBER OF THE PUBLIC from radioactive materials in liquid effluents released, from each reactor unit, to areas at and beyond the SITE BOUNDARY shall be limited:
- a.
During any calendar quarter to less than or equal to 1.5 mrems to the total body and to less than or equal to 5 mrems to any organ, and
- b.
During any calendar year to less than or equal to 3 mrems to the total body and to less than or equal to 10 mrems to any organ.
1.2 Gaseous Releases 1.2.1 PVNGS ODCM Requirement 3.1 The dose rate due to radioactive materials released in gaseous effluents from the site shall be limited to the following:
- a.
For noble gases: Less than or equal to 500 mrems/yr to the total body and less than or equal to 3000 mremslyr to the skin, and
- b.
For 1-131 and 1-133, for tritium, and for all radionuclides in particulate form with half-lives greater than 8 days: Less than or equal to 1500 mrems/yr to any organ.
1.2.2 PVNGS ODCM Requirement 4.1 The air dose due to noble gases released in gaseous effluents, from each reactor unit, to areas at and beyond the SITE BOUNDARY shall be limited to the following:
- a.
During any calendar quarter: Less than or equal to 5 mrads for gamma radiation and less than or equal to 10 mrads for beta radiation and,
- b.
During any calendar year: Less than or equal to 10 mrads for gamma radiation and less than or equal to 20 mrads for beta radiation.
1.2.3 PVNGS ODCM Requirement 4.2 The dose to a MEMBER OF THE PUBLIC from iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released, from each reactor unit, to areas at and beyond the SITE BOUNDARY shall be limited to the following:
- a.
During any calendar quarter: Less than or equal to 7.5 mrems to any organ and,
- b.
During any calendar year: Less than or equal to 15 mrems to any organ.
1.2.4 PVNGS ODCM Requirement 4.3 The GASEOUS RADWASTE SYSTEM and the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected gaseous effluent air doses due to gaseous effluent releases, from each reactor unit, from the site, when averaged over 31 days, would exceed 0.2 mrad for gamma radiation and 0.4 mrad for beta radiation. The VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected doses due to gaseous effluent releases, from each reactor unit, to areas at and beyond the SITE BOUNDARY when averaged over 31 days, would exceed 0.3 mrem to any organ of a MEMBER OF THE PUBLIC.
1.3 Total Dose 1.3.1 PVNGS ODCM Requirement 5.1 The annual (calendar year) dose or dose commitment to any MEMBER OF THE PUBLIC due to releases of radioactivity and to direct radiation from uranium fuel cycle sources shall be limited to less than or equal to 25 mrems to the total body or any organ, except the thyroid, which shall be limited to less than or equal to 75 mrems.
2.0 MAXIMUM PERMISSIBLE CONCENTRATIONS Air: Release Concentrations are limited to dose rate limits described in section 1.2.1 of this report.
3.0 AVERAGE ENERGY The average energy (E) of the radionuclide mixture in releases of fission and activation gases is not applicable to PVNGS.
4.0 MEASUREMENTS AND APPROXIMATIONS OF TOTAL RADIOACTIVITY IN GASEOUS EFFLUENTS For continuous releases, sampling is in accordance with PVNGS ODCM Table 3-1.
Particulate and iodine radionuclides are sampled continuously at the Plant Vent and Fuel Building exhaust points. The particulate filters and charcoal cartridges are exchanged for analysis at least four times per month. Noble gas and tritium are sampled at least once per 31 days. The hourly average Radiation Monitoring System (RMS) effluent monitor readings are used, when available, to account for increases and decreases in noble gas concentrations between noble gas grab samples. The tritium concentration is assumed constant between sampling periods.
For batch releases, sampling is also in accordance with PVNGS ODCM Table 3-1. For containment purges, the noble gas concentration may be adjusted to account for decreases or increases in concentration during the purge using RMS readings. The volume of air released during the purge is determined using the exhaust fan rated flow rate. For Waste Gas Decay Tank releases, the volume released is corrected to standard pressure.
Effective January 1, 2004, Containment Purge release permits are updated by removing the permit pre-release particulate and iodine activity. This eliminates double accounting for the Containment Purge particulate and iodine activity at the Plant Vent but allows the particulate and iodine activity to be included in the Containment Purge pre-release dose projection.
The Lower Limit of Detection (LLD) of a measurement system is defined in Table 3 - 1 of the PVNGS ODCM. An average LLD for each radionuclide is provided in Table 3.
5.0 BATCH RELEASES 5.1 Gaseous.
Batch release durations are presented in Table 2.
5.2 Liquid None.
6.0 ABNORMAL RELEASES None.
7.0 OFFSITE DOSE CALCULATION MANUAL AND PROCESS CONTROL PROGRAM (PCP) REVISIONS 7.1 ODCM, Revision 20, effective August 31, 2005, contains changes associated with the implementation of the Radioactive Environmental Monitoring Program (REMP).
The ODCM revision is included as Appendix D.
7.2 There were no revisions to the Process Control Program (PCP).
8.0 EFFLUENTS AND SOLID WASTES 8.1 Gaseous Effluents Gaseous effluent information is presented in Table 1 through Table 41. Included in these tables are summaries of the effluents and estimated total error.
8.2 Liquid Effluents There were no liquid effluent releases beyond the Site Boundary from PVNGS.
8.3 Solid Waste Solid waste shipments are summarized in Table 42.
9.0 MISCELLANEOUS INFORMATION 9.1 EVAPORATION PONDS Releases made to the Evaporation Ponds are limited to the concentrations specified in PVNGS ODCM Requirement 3.2. The Evaporation Ponds were monitored in accordance with PVNGS ODCM Requirement 6.1.
The average historical evaporation is approximately 12 inches, per pond, for each of the first and fourth quarters, and 33 inches, per pond, for each of the second and third quarters. This equates to 3.09E+11 cc evaporated from Pond One for each of the first and fourth quarters and 8.50E+11 cc evaporated from Pond One for each of the second and third quarters. The amount evaporated from Pond Two is 2.89E+11 cc for each of the first and fourth quarters and 7.96E+11 cc for each of the second and third quarters. Using a site boundary X/Q of 5.OE-05 sec/m 3 for the evaporation ponds and equation 4-3 from the ODCM, the dose from the evaporation ponds to a hypothetical individual at the site boundary, for all pathways, is summarized in Table 1.
9.2 RADIATION MONITORING SYSTEM SETPOINT VERIFICATION Current effluent monitor noble gas channel alert alarm setpoints are based on an assumed one per cent failed fuel source term. The current setpoints are more conservative than setpoints calculated using the actual noble gas source term presented in Table 38.
9.3 RCS RADIOIODINE (TRM T5.0.600)
There were no cases where primary coolant specific activity exceeded the Technical Specification 3.4.17 limits during the reporting period.
9.4 INDEPENDENT SPENT FUEL STORAGE INSTALLATION (ISFSI)
There are no radioactive effluents from the NAC-UMS System. Direct dose at the Site Boundary is reported in the Annual Radiological Environmental Operating Report.
9.5 MAJOR CHANGES TO THE RADIOACTIVE WASTE SYSTEMS (liquid, gaseous, and solid).
Licensee-initiated major changes to the radioactive waste systems (liquid, gaseous, and solid) are submitted as part of the FSAR update (TRM T5.0.500.4.a).
9.6 REPORT ADDENDUM None.
10.0 DISCUSSION 10.1 Unit One Unit One operated with a refueling outage (UIR12) from October 8, 2005 to Dec 24, 2005.
Additional Maintenance outages:
U1M12B, 2-9-05 to 2-19-05 U1M12C, 3-18-05 to 3-21-05 U1MI2D, 8-12-05 to 8-28-05.
l Estimated number of fuel defects (source: INPO, CDE)
I Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 0
1 1 1 7 1
1 1 1 1 1 1 1 1 1 n/a 01 10.2 Unit Two Unit Two operated with a refueling outage (U2R12) from April 2, 2005 to May 20, 2005.
Additional Maintenance outages:
U2Ml 3A, 8-22-05 to 8-26-05 U2MI3B, 10-11-05 to 10-20-05.
I Estimated number of fuel defects (source: INPO, CDE)
Jan I Feb Mar Apr I May I Jun I Jul I Aug I Sep I Oct I Nov Decl 0 l 0 l 0 l n/a I n/a I 0 l 0 l 0 l 0 l 0 l 0 0 o I 10.3 Unit Three Unit Three operated without a refueling outage.
Maintenance outages:
U3M12A, 5-23-05 to 6-24-05 U3Ml2B, 7-6-05 to 7-13-05 U3M12C, 10-2-05 to 10-7-05 U3M12D, 10-11-05 to 10-21-05 Estimated number of fuel defects (source: INPO, CDE)
Jan Feb Mar Apr May Jun Jul l Aug Sep Oct Nov Dec 0
1 0
1 0
0 0
0 0
10.4 General PVNGS does not have a liquid release pathway. Removal of tritium is performed by operation of the Boric Acid Concentrator (BAC) in the release mode.
Comparison of PVNGS annual tritium curies released to other utilities should be made only after summing both liquid and gaseous tritium curies released.
10.5 Summary Dose for 2005 was primarily due to the release of tritium. Tritium production is approximately 1000 curies per Reactor Unit per year. In order to control plant tritium concentrations, tritium releases should match tritium production. For 2005, PVNGS released a total of 2050 curies of tritium (see. Table 39).
Total dose from releases from all three Units for the year 2005 were less than year 2004 mainly due to 70 less curies of tritium being released.
Table 1: Evaporation Pond Data Evaporation Pond 1 Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year Historical volume of 3.09E+11 8.50E+11 8.50E+11 3.09E+11 water evaporated (ml)
Tritium Concentration 1.12E-06 1.21 E-06 1.60E-06 2.04E-06 (uCi/cc)
Tritium Curies 3.46E-01 1.03E+00 1.36E+00 6.30E-01 3.36E+00 Evaporation Pond 2 Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year Historical volume of 2.89E+11 7.96E+11 7.96E+11 2.89E+11 water evaporated (ml)
Tritium Concentration 1.63E-06 1.74E-06 1.69E-06 1.76E-06 (uCi/cc)
Tritium curies 4.72E-01 1.38E+00 1.34E+00 5.1OE-01 3.71 E+O0 Dose (mRem)
Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year Pond 1 4.80E-03 1.43E-02 1.89E-02 8.73E-03 4.67E-02 Pond 2 6.55E-03 1.92E-02 1.86E-02 7.07E-03 5.14E-02 Total 1.13E-02 3.34E-02 3.75E-02 1.58E-02 9.81 E-02 Table 2: Batch Release Data All times are in hours Unit 1 Unit 2 Unit 3 January - June Number of batch releases 32 43 35 Total time period for batch releases 598.60 1912.39 1530.36 Maximum time period for a batch release 130.98 168.00 168.00 Average time period for a batch release 18.71 44.47 43.72 Minimum time period for a batch release 1.03 0.02 0.40 July - December Number of batch releases 61 28 33 Total time period for batch releases 3718.07 429.45 964.08 Maximum time period for a batch release 168.00 129.65 168.00 Average time period for a batch release 60.95 15.34 29.21 Minimum time period for a batch release 0.03 1.11 0.54 January - December Number of batch releases 93 71 68 Total time period for batch releases 4316.68 2341.83 2494.44 Maximum time period for a batch release 168.00 168.00 168.00 Average time period for a batch release 46.42 32.98 36.68 Minimum time period for a batch release 0.03 0.02 0.40 15 PVNGS ARERR 2005
Table 3:
Units 1, 2&3 Gaseous Effluents Average Lower Limit Of Detection RCi/cc Nuclide Continuous Batch Nuclide Continuous Batch Antimony-122 2.20E-13 1.90E-11 Argon-41 4.50E-08 4.50E-08 Antimony-124 8.40E-14 1.70E-11 Krypton-85 7.40E-06 7.40E-06 Barium-140 3.40E-13 5.70E-11 Krypton-85m 2.20E-08 2.20E-08 Bromine-82 3.30E-13 1.40E-11 Krypton-87 5.70E-08 5.70E-08 Cerium-141 8.70E-14 3.1OE-11 Krypton-88 7.40E-08 7.40E-08 Cerium-144 3.60E-13 6.50E-11 Xenon-125 2.20E-08 2.20E-08 Cesium-134 1.OOE-13 2.60E-11 Xenon-127 2.1OE-08 2.1 OE-08 Cesium-137 8.1OE-14 1.70E-11 Xenon-131m 9.1OE-07 9.10E-07 Cesium-138 5.20E-10 7.30E-10 Xenon-133 6.30E-08 6.30E-08 Chromium-51 6.90E-1 3 1.40E-10 Xenon-133m 1.90E-07 1.90E-07 Cobalt-58 8.50E-14 1.70E-11 Xenon-135 2.OOE-08 2.OOE-08 Cobalt-60 1.OOE-13 1.90E-11 Xenon-135m 8.90E-08 8.90E-08 Iron-59 1.70E-13 3.20E-11 Xenon-138 2.OOE-07 2.OOE-07 Lanthanum-140 2.80E-13 2.10E-11 lodine-131 8.00E-14 7.OOE-12 Manganese-54 8.30E-14 1.70E-11 lodine-1 32 6.60E-12 1.90E-11 Molybdenum-99 2.40E-13 2.80E-11 Iodine-133 4.70E-13 1.1OE-11 Niobium-95 8.70E-14 1.80E-11 iodine-134 5.90E-11 8.20E-11 Rubidium-88 1.90E-08 1.90E-08 Iodine-135 7.OOE-12 5.50E-11 Ruthenium-103 7.40E-14 1.50E-11 Strontium-89 2.15E-15 (1)
Strontium-90 5.60E-16 (1)
Tellurium-123m 6.60E-14 1.50E-11 Tritium 3.80E-07 3.80E-07 Zinc-65 1.90E-13 3.80E-11 Zirconium-95 1.80E-13 4.1OE-11 Gross Alpha 3.60E-15 (1)
(1) Not required for batch releases.
Table 4:
Unit I Gaseous Effluents - Summation Of All Releases l
Unit Quarter I Quarter 2 [ Quarter 3 Quarter 4 Total For l
Est. Total Error
__Year
% (1)
A. Fission & activation gases
- 1. Total release Ci 2.08E+00 1.22E-01 4.27E+00 2.87E+01 3.52E+01 3.54E+01
- 2. Average release rate for period giCi/sec 2.67E-01 1.55E-02 5.37E-01 3.61 E+00 1.12E+00
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
B. Iodine 131
- 1. Total Iodine 131 Ci 2.02E-06 1.23E-06 1.73E-06 1.55E-04 1.60E-04 3.32E+01
- 2. Average release rate for period tiCi/sec 2.60E-07 1.56E-07 2.18E-47 1.95E-05 5.07E-06
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
C. Particulates
- 1. Particulates with half-lives >8 days Ci 3.1 OE-06 7.37E-07 9.60E-07 3.01 E-03 3.02E-03 3.43E+01
- 2. Average release rate for period jiCi/sec 3.98E-07 9.37E-08 1.21 E-07 3.79E-04 9.57E-05
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
- 4. Gross Alpha radioactivity Ci
< LLD
< LLD
< LLD
< LLD
- 1. Total release Ci 3.08E+02 1.39E+01 3.66E+02 1.38E+02 8.26E+02 3.85E+01
- 2. Average release rate for period gCi/sec 3.96E+01 1.77E+00 4.60E+01 1.74E+01 2.62E+01
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
(1) Estimated total error methodology is presented in Table 40.
(2) See Table 11 for percent of ODCM Requirement limits.
zC)
Co m
0 0
01 N
cn
Table 5:
Unit I Gaseous Effluents - Ground Level Releases - Continuous - Fission Gases and lodines Relieased Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total
- 1. Fission gases Ar-41 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
<LLD Kr-85 Ci
< LLD
< LLD
<LLD
< LLD
< LLD Kr-85m Ci
< LLD
< LLD 2.64E-02
< LLD 2.64E-02 Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
<LLD
<LLD
< LLD Kr-89 Ci
< LLD
<LLD
<LLD
< LLD
<LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD
<LLD Xe-131m Ci
< LLD
< LLD
<LLD
< LLD
< LLD Xe-1 33 Ci 1.61 E+00
< LLD 3.29E+00 1.66E+01 2.15E+01 Xe-133m Ci
< LLD
< LLD
<LLD
< LLD
< LLD Xe-135 Ci
< LLD
<LLD
< LLD
< LLD
< LLD Xe-1 35m Ci
<LLD
< LLD
< LLD
< LLD
< LLD Xe-137 Ci
< LLD
<LLD
< LLD
' LLD
< LLD
< LLD
< LLD
' LLD
< LLD total Ci 1.61 E+00
< LLD 3.31 E+00 1.66E+01 2.16E+01
- 2. lodines 1-131 Ci 2.02E-06 1.23E-06 1.73E-06 3.91 E-05 4.41 E-05 1-132 Ci
< LLD
< LLD
< LLD
< LLD
<LLD 1-133 Ci
< LLD
< LLD
<LLD
< LLD
< LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
< LLD
' LLD
< LLD total Ci 2.02E-06 1.23E-06 1.73E-06 3.91 E-05 4.41 E-05 18 PVNGS ARERR 2005
Table 6:
Unit I Gaseous Effluents - Ground Level Releases - Continuous - Particulates Nuclides Released Unit Quarter I Quarter 2 Quarter 3 Quarter 4 Year total 3.Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci 2.70E-06
< LLD
< LLD 7.56E-05 7.83E-05 Co-60 Ci
< LLD
< LLD
< LLD 2.36E-05 2.36E-05 Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 1.25E-06 1.25E-06 Mo-99 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD 1.10E-05 1.10E-05 Os-191 Ci
< LLD 7.37E-07
< LLD 3.17E-06 3.91 E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD 9.49E-07 1.34E-06 2.29E-06 Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 3.98E-07
< LLD 7.68E-09 1.45E-07 5.50E-07 Sr-90 Ci
< LLD
< LLD 2.72E-09 5.12E-08 5.39E-08 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD 3.08E-06 3.08E-06 total Ci 3.1 OE-06 7.37E-07 9.60E-07 1.19E-04 1.24E-04 4.Tritium H-3 Ci 1.49E+01 1.39E+01l 1.40E+01 1.55E+01 5.82E+01 19 PVNGS ARERR 2005
Table 7:
Unit I Gaseous Effluents - Ground Level Releases - Batch - Fission Gases and lodines Nuclides Released Unit Quarter I Quarter 2 Quarter 3 Quarter 4 l Year total
- 1. Fission gases Ar-41 Ci 1.12E-01 1.19E-01 1.60E-01 2.35E-01 6.26E-01 Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
<LLD 7.24E-01 3.31 E+0O 4.03E+00 Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
< LLD
<LLD
< LLD
< LLD
< LLD Kr-89 Ci
<LLD
<LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD
<LLD Xe-131m Ci
< LLD
< LLD
< LLD 4.99E-02 4.99E-02 Xe-1 33 Ci 3.42E-01 2.64E-03 6.57E-02 8.46E+00 8.87E+00 Xe-1 33m Ci
< LLD
< LLD
< LLD 8.09E-03 8.09E-03 Xe-135 Ci 7.62E-03
< LLD 8.06E-05
< LLD 7.70E-03 Xe-135m Ci
< LLD
< LLD
< LLD
<LLD
< LLD Xe-137 Ci
< LLD
< LLD
< LLD
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 4.62E-01 1.22E-01 9.50E-01 1.21 E+01 1.36E+01
- 2. todines 1-131 Ci
< LLD
< LLD
< LLD 1.16E-04 1.16E-04 1-132 Ci
< LLD
<LLD
< LLD 7.07E-05 7.07E-05 1-133 Ci
< LLD
<LLD
<LLD
< LLD
< LLD 1-134 Ci
< LLD
<LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
< LLD
<LLD
< LLD total Ci
< LLD
< LLD
< LLD 1.87E-04 1.87E-04 20 PVNGS ARERR 2005
Table 8:
Unit I Gaseous Effluents - Ground Level Releases - Batch - Particulates Nuclides Released Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.66E-06 3.66E-06 Co-58 Ci
< LLD
< LLD
< LLD 1.25E-03 1.25E-03 Co-60 Ci
< LLD
< LLD
< LLD 6.28E-04 6.28E-04 Cr-51 Ci
< LLD
< LLD
< LLD 2.20E-04 2.20E-04 Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 1.80E-05 1.80E-05 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD 3.66E-05 3.66E-05 La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.70E-05 3.70E-05 Mo-99 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD 4.29E-04 4.29E-04 Os-191 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD 7.44E-06 7.44E-06 Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci Note 1 Note 1 Note 1 Note 1 Note 1 Sr-90 Ci Note I Note 1 Note 1 Note 1 Note 1 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD 2.63E-04 2.63E-04 total Ci
< LLD
< LLD
< LLD 2.89E-03 2.89E-03 4.Tritium H-3 Ci 2.93E+02 8.05E-03 3.52E+02 1.22E+02 7.67E+02 Note 1 - Not required for batch releases 21 PVNGS ARERR 2005
Table 9:
Unit I Gaseous Effluents - Continuous and Batch - Fission Gases and lodines Nuclides Released lUnit I Quarter I I Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 1. Fission gases Ar-41 Ci 1.12E-01 1.19E-01 1.60E-01 2.35E-01 6.26E-01 Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
< LLD 7.24E-01 3.31E+00 4.03E+00 Kr-85m Ci
< LLD
< LLD 2.64E-02
< LLD 2.64E-02 Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
<LLD
< LLD
< LLD
< LLD
< LLD Kr-89 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD
<LLD Xe-1 31 m Ci
< LLD
<LLD
<LLD 4.99E-02 4.99E-02 Xe-133 Ci 1.96E+00 2.64E-03 3.35E+00 2.51E+01 3.04E+01 Xe-1 33m Ci
<LLD
< LLD
< LLD 8.09E-03 8.09E-03 Xe-135 Ci 7.62E-03
<LLD 8.06E-05
< LLD 7.70E-03 Xe-135m Ci
< LLD
< LLD
<LLD
< LLD
<LLD Xe-137 Ci
< LLD
'LLD
< LLD
< LLD
<LLD
< LLD
< LLD
< LLD
< LLD total Ci 2.08E+00 1.22E-01 4.27E+00 2.87E+01 3.52E+01
- 2. lodines 1-131 Ci 2.02E-06 1.23E-06 1.73E-06 1.55E-04 1.60E-04 1-132 Ci
< LLD
< LLD
< LLD 7.07E-05 7.07E-05 1-133 Ci
< LLD
< LLD
< LLD
<LLD
< LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
<LLD
< LLD
<LLD total Ci 2.02E-06 1.23E-06 1.73E-06 2.26E-04 2.31 E-04 22 PVNGS ARERR 2005
Table 10:
Unit I Gaseous Effluents - Continuous and Batch - Particulates Nuclides Released I Unit I Quarter 1 l Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.66E-06 3.66E-06 Co-58 Ci 2.70E-06
< LLD
< LLD 1.33E-03 1.33E-03 Co-60 Ci
< LLD
< LLD
< LLD 6.51E-04 6.51 E-04 Cr-51 Ci
< LLD
< LLD
< LLD 2.20E-04 2.20E-04 Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-1 37 Ci
< LLD
< LLD
< LLD 1.80E-05 1.80E-05 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD 3.66E-05 3.66E-05 La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.83E-05 3.83E-05 Mo-99 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD 4.40E-04 4.40E-04 Os-191 Ci
< LLD 7.37E-07
< LLD 3.17E-06 3.91 E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD 9.49E-07 1.34E-06 2.29E-06 Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-1 24 Ci
< LLD
< LLD
< LLD 7.44E-06 7.44E-06 Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 3.98E-07
< LLD 7.68E-09 1.45E-07 5.50E-07 Sr-90 Ci
< LLD
< LLD 2.72E-09 5.12E-08 5.39E-08 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD 2.66E-04 2.66E-04 total Ci 3.1 OE-06 7.37E-07 9.60E-07 3.01 E-03 3.02E-03 total > 8 days Ci 3.1OE-06 7.37E-07 9.60E-07 3.01E-03 3.02E-03 4.Tritium H-3 Ci 3.08E+02 1.39E+01 3.66E+02 1.38E+02 8.26E+02 23 PVNGS ARERR 2005
Table 11:
Unit 1 Radiation Doses At And Beyond The Site Boundary Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total Gamma Air Dose mrad 4.93E-04 3.13E-04 7.68E-04 3.14E-03 4.71 E-03 ODCM Req 4.1 Limit mrad 5.OOE+OO 5.OOE+OO 5.00E+00 5.OOE+00 1.OOE+01
% ODCM Limit 9.86E-03 6.26E-03 1.54E-02 6.28E-02 4.71 E-02 Beta Air Dose mrad 6.89E-04 1.1 E-04 1.56E-03 9.50E-03 1.19E-02 ODCM Req 4.1 Limit mrad 1.OOE+01 1.OOE+01 1.OOE+01 1.OOE+01 2.OOE+01
% ODCM Limit 6.89E-03 1.11E-03 1.56E-02 9.50E-02 5.95E-02 Maximum Organ Dose mrem 1.10E-01 5.01 E-03 1.31E-01 5.32E-02 3.OOE-01 (excluding skin)
Age Teen Teen Teen Teen Teen Organ Thyroid Thyroid Thyroid Lung Lung ODCM Req. 4.2 Limit mrem 7.50E+00 7.50E+00 7.50E+00 7.50E+00 1.50E+01
% ODCM Limit 1.47E+00 6.68E-02 1.75E+00 7.09E-01 2.OOE+OO Calculations are based on parameters and methodologies of the ODCM using historical meteorology. Dose is calculated to a hypothetical individual. In contrast, Appendix C dose calculations are based on concurrent meteorology, a real individual, and only the actual pathways present.
CA Table 12:
Unit 2 Gaseous Effluents - Summation Of All Releases Unit j Quarter 1 Quarter 2 Quarter 3 Quarter 4 YoteaFor (Est Total)Error A. Fission & activation gases
- 1. Total release Ci 3.59E-01 3.60E+00 5.31 E-01 1.29E-01 4.62E+00 3.54E+01
- 2. Average release rate for period g+/-Ci/sec 4.62E-02 4.58E-01 6.68E-02 1.62E-02 1.46E-01
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
B. Iodine 131
- 1. Total Iodine 131 Ci
< LLD 1.07E-04
< LLD
< LLD 1.07E-04 3.32E+01
- 2. Average release rate for period
,uCUsec
< LLD 1.36E-05
< LLD
< LLD 3.39E-06
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
C. Particulates
- 1. Particulates with half-lives > 8 days Ci 3.34E-06 5.27E-05 6.1 OE-09 9.17E-08 5.62E-05 3.43E+01
- 2. Average release rate for period p.Ci/sec 4.30E-07 6.71 E-06 7.67E-10 1.15E-08 1.78E-06
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
- 4. Gross Alpha radioactivity Ci
< LLD LLD
<LLD LLD
- 1. Total release Ci 2.97E+02 1.89E+02 2.03E+01 1.12E+02 6.18E+02 3.85E+01
- 2. Average release rate for period jiCi/sec 3.82E+01 2.40E+01 2.55E+00 1.41 E+01 1.96E+01
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
(1) Estimated total error methodology is presented in Table 40.
(2) See Table 19 for percent of ODCM Requirement limits.
-u z
Co m
rn3 0
0 dl
Table 13:
Unit 2 Gaseous Effluents - Ground Level Releases - Continuous - Fission Gases and lodines Nuclides Released I Unit I Quarter I I Quarter 2 l Quarter 3 l Quarter 4 Year total
- 1. Fission gases Ar-41 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-87 Ci
< LLD
< LLD
< LLD
<LLD
< LLD Kr-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-89 Ci
< LLD
<LLD
<LLD
<LLD
<LLD Kr-90 Ci
< LLD
< LLD
<LLD
< LLD
<LLD Xe-131m Ci
< LLD
< LLD
< LLD
< LLD
< LLD
<LLD
< LLD Xe-133m Ci
< LLD
< LLD
< LLD Xe-135 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-1 35m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-137 Ci
< LLD
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD total Ci
< LLD
< LLD
< LLD
< LLD
< LLD
- 2. lodines 1-131 Ci
< LLD 1.07E-04
< LLD
< LLD 1.07E-04 1-132 Ci
< LLD 1.57E-03
< LLD
< LLD 1.57E-03 1-133 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
< LLD
<LLD
< LLD total Ci
< LLD 1.68E-03 26 PVNGS ARERR 2005
Table 14:
Unit 2 Gaseous Effluents - Ground Level Releases - Continuous - Particulates Nuclides Released I Unit I Quarter 1 lQuarter 2 lQuarter 3 l Quarter 4 lYear total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci
< LLD 5.16E-05
< LLD
< LLD 5.16E-05 Co-60 Ci 3.34E-06
< LLD
< LLD
< LLD 3.34E-06 Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Os-191 Ci
< LLD 1.15E-06
< LLD
< LLD 1.15E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
<.LLD LLD
<LLD
<LLD
<LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 6.10E-09 9.17E-08 9.78E-08 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 3.34E-06 5.27E-05 6.1 OE-09 9.17E-08 5.62E-05
Table 15:
Unit 2 Gaseous Effluents - Ground Level Releases - Batch - Fission Gases and lodines Nuclides Released Unit Quarter 1 l Quarter 2 l Quarter 3 Quarter 4 l Year total
- 1. Fission gases Ar-41 Ci 2.22E-01 8.39E-02 5.31 E-01 1.28E-01 9.66E-01 Kr-83m Ci
<LLD
<LLD
< LLD
<LLD
<LLD Kr-85 Ci
< LLD 1.60E-03
< LLD
< LLD 1.60E-03 Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
<LLD
< LLD
< LLD
< LLD
< LLD Kr-89 Ci
<LLD
<LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-1 31 m Ci
<LLD 2.86E-03
< LLD
< LLD 2.86E-03 Xe-133 Ci 1.34E-01 3.51 E+00
< LLD 8.36E-04 3.65E+00 Xe-133m Ci
< LLD 4.69E-04
< LLD
< LLD 4.69E-04 Xe-1 35 Ci 2.1OE-03
<LLD
< LLD
< LLD 2.10E-03 Xe-137 Ci
< LLD
<LLD
< LLD
< LLD
< LLD Xe-1 35m Ci
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
'LLD total Ci 3.59E-01 3.60E+00 5.31 E-01 1.29E-01 4.62E+00
- 2. lodines 1-131 Ci
<LLD
<LLD
<LLD
<LLD
<LLD 1-132 Ci
<LLD
<LLD
< LLD
< LLD
< LLD 1-133 Ci
< LLD
<LLD
<LLD
<LLD
<LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
< LLD
<LLD
< LLD total Ci
<LLD
< LLD
< LLD
< LLD
Table 16:
Unit 2 Gaseous Effluents - Ground Level Releases - Batch - Particulates Nuclides Released I Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
<LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cs-138 Ci
<LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Os-191 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
<LLD
<LLD
< LLD
<LLD
<LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci Note 1 Note I Note 1 Note 1 Note 1 Sr-90 Ci Note 1 Note I Note 1 Note 1 Note 1 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD total Ci
< LLD
< LLD
< LLD
< LLD
< LLD
- 4. Tritium H-3 Ci 2.69E+02 1.63E+02 1.92E-02 1.02E+02 5.33E+02 Note 1 - Not required for batch releases 29 PVNGS ARERR 2005
Table 17:
Unit 2 Gaseous Effluents - Continuous and Batch - Fission Gases and lodines Nuclides Released I Unit I Quarter1 Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 1. Fission gases Ar-41 Ci 2.22E-01 8.39E-02 5.31 E-01 1.28E-01 9.66E-01 Kr-83m Ci
< LLD
<LLD
<LLD
< LLD
< LLD 1.60E-03
< LLD
< LLD 1.60E-03 Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
<LLD Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
< LLD
< LLD
< LLD
<LLD
< LLD Kr-89 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-1 31 m Ci
< LLD 2.86E-03
<LLD
< LLD 2.86E-03 Xe-133 Ci 1.34E-01 3.51 E+00
< LLD 8.36E-04 3.65E+00 Xe-133m Ci
< LLD 4.69E-04
< LLD
< LLD 4.69E-04 Xe-1 35 Ci 2.1OE-03
< LLD
< LLD
< LLD 2.10E-03 Xe-135m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-137 Ci
< LLD
< LLD
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 3.59E-01 3.60E+00 5.31 E-01 1.29E-01 4.62E+00
- 2. lodines 1-131 Ci
< LLD 1.07E-04
< LLD
< LLD 1.07E-04 1-132 Ci
< LLD 1.57E-03
< LLD
< LLD 1.57E-03 1-133 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
< LLD
< LLD
<LLD total Ci
< LLD 1.68E-03
< LLD
< LLD 1.68E-03 30 PVNGS ARERR 2005
Table 18:
Unit 2 Gaseous Effluents - Continuous and Batch - Particulates Nuclides Released Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci
< LLD 5.16E-05
< LLD
< LLD 5.16E-05 Co-60 Ci 3.34E-06
< LLD
< LLD
< LLD 3.34E-06 Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cs-138 Ci
<LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Os-191 Ci
< LLD 1.15E-06
< LLD
< LLD 1.15E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 6.1OE-09 9.17E-08 9.78E-08 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 3.34E-06 5.27E-05 6.1 OE-09 9.17E-08 5.62E-05 total > 8 days Ci 3.34E-06 5.27E-05 6.1OE-09 9.17E-08 5.62E-05
Table 19:
Unit 2 Radiation Doses At And Beyond The Site Boundary l
Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total Gamma Air Dose mad 5.99E-04 5.71E-04 1.40E-03 3.37E-04 2.90E-03 ODCM Req 4.1 Limit mrad 5.OOE+00 5.OOE+OO 5.OOE+OO 5.OOE+00 1.OOE+01
% ODCM Limit 1.20E-02 1.14E-02 2.80E-02 6.74E-03 2.90E-02 Beta Air Dose mrad 2.47E-04 1.12E-03 4.92E-04 1.19E-04 1.98E-03 ODCM Req 4.1 Limit mrad 1.OOE+01 1.OOE+01 1.OOE+01 1.OOE+01 2.OOE+01
% ODCM Limit I2.47E-03 1.12E-02 4.92E-03 1.19E-03 9.90E-03 Maximum Organ Dose mrem 1.07E-01 6.90E-02 7.27E-03 4.03E-02 2.23E-01 (excluding skin)
Age Teen Teen Teen Teen Teen Organ Lung Thyroid W Body W Body Thyroid ODCM Req. 4.2 Limit mrem 7.50E+00 7.50E+00 7.50E+00 7.50E+00 1.50E+01
% ODCM Limit 1.43E+00 9.20E-01 9.69E-02 5.37E-01 1.49E+OO Calculations are based on parameters and methodologies of the ODCM using historical meteorology. Dose is calculated to a hypothetical individual. In contrast, Appendix C dose calculations are based on concurrent meteorology, a real individual, and only the actual pathways present.
Table 20:
Unit 3 Gaseous Effluents - Summation Of All Releases WA Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Total For Est. Total Error A. Fission & activation gases
- 1. Total release Ci 8.71E-02 2.74E-01 8.81E-01 1.69E-01 1.41E+00 3.54E+01
- 2. Average release rate for period ILCi/sec 1.12E-02 3.48E-02 1.11E-01 2.13E-02 4.47E-02
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
B. Iodine 131
- 1. Total Iodine 131 Ci
< LLD 5.64E-07
< LLD
< LLD 5.64E-07 3.32E+01
- 2. Average release rate for period gCi/sec
< LLD 7.17E-08
< LLD
< LLD 1.79E-08
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
C. Particulates
- 1. Particulates with half-lives > 8 days Ci 1.32E-08 8.66E-06
< LLD
< LLD 8.67E-06 3.43E+01
- 2. Average release rate for period iLCi/sec 1.69E-09 1.10E-06
< LLD
< LLD 2.75E-07
- 3. Percent of ODCM Requirement limit NA (2)
NA (2)
NA (2)
NA (2)
NA (2)
- 4. Gross Alpha radioactivity Ci
< LLD
< LLD
< LLD
< LLD
- 1. Total release Ci 1.20E+01 3.84E+02 1.51E+01 2.OOE+02 6.11E+02 3.85E+01
- 2. Average release rate for period l iiCi/sec 1.54E+00 4.88E+01 1.90E+00 2.52E+01 l 1.94E+01
- 3. Percent of ODCM Requirement limit
{ NA (2)
NA (2)
NA (2)
NA (2)
INA (2)
(1) Estimated total error methodology is presented in Table 40.
(2) See Table 27 for percent of ODCM Requirement limits.
-u z
G)
N K)
CD C)3 0n
Table 21:
Unit 3 Gaseous Effluents - Ground Level Releases - Continuous - Fission Gases and lodines Nuclides Released I Unit I Quarter 1 l Quarter 2 l Quarter 3 l Quarter 4 Year total
- 1. Fission gases Ar-41 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-83m Ci
< LLD
< LLD
<LLD
<LLD
<LLD Kr-85 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
< LLD
<LLD
<LLD
< LLD
< LLD Kr-89 Ci
<LLD
< LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
<LLD
<LLD
<LLD Xe-131m Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Xe-133m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-135 Ci
< LLD
< LLD
< LLD
<LLD
< LLD Xe-1 35m Ci
< LLD
<LLD
<LLD
< LLD
<LLD Xe-137 Ci
< LLD
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD total Ci
< LLD LLD
< LLD
' LLD
< LLD
- 2. lodines 1-131 Ci
< LLD 5.64E-07
< LLD
< LLD 5.64E-07 1-132 Ci
< LLD
<LLD
< LLD
< LLD
< LLD 1-133 Ci
< LLD
<LLD
<LLD
<LLD
<LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
< LLD
< LLD
< LLD total Ci
< LLD 5.64E-07
< LLD
< LLD 5.64E-07 34 PVNGS ARERR 2005
Table 22:
Unit 3 Gaseous Effluents - Ground Level Releases - Continuous - Particulates Nuclides Released I Unit I Quarter 1 Quarter 2 l Quarter 3 l Quarter 4 Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci
< LLD 3.80E-06
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
<LLD
<LLD
<LLD
<LLD
<LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD OS-191 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 5.20E-09 6.96E-08
< LLD
< LLD 7.48E-08 Sr-90 Ci 7.77E-10 1.04E-08
< LLD
< LLD 1.12E-08 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 5.97E-09 3.88E-06
< LLD
< LLD 3.88E-06
Table 23:
Unit 3 Gaseous Effluents - Ground Level Releases - Batch - Fission Gases and lodines Nuclides Released Unit I Quarter 1 Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 1. Fission gases Ar-41 Ci 8.71E-02 2.56E-01 8.81E-01 1.69E-01 1.39E+00 Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-87 Ci
< LLD
<LLD
< LLD
< LLD
< LLD Kr-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-89 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-131m Ci
< LLD 1.08E-04
< LLD
<LLD 1.08E-04 Xe-133 Ci
< LLD 1.77E-02 4.15E-04
< LLD 1.81E-02 Xe-1 33m Ci
< LLD 3.32E-04
<LLD
< LLD 3.32E-04 Xe-1 35 Ci
< LLD 1.25E-05
< LLD
< LLD 1.25E-05 Xe-1 35m Ci
< LLD
<LLD
<LLD
< LLD
< LLD Xe-137 Ci
<LLD
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 8.71 E-02 2.74E-01 8.81 E-01 1.69E-01 1.41 E+00
- 2. lodines 1-131 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-132 Ci
< LLD
< LLD
<LLD
< LLD
<LLD 1-133 Ci
< LLD
<LLD
<LLD
<LLD
<LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
<LLD
<LLD
<LLD
<LLD total Ci
< LLD
<LLD
<LLD
< LLD
Table 24:
Unit 3 Gaseous Effluents - Ground Level Releases - Batch - Particulates Nuclides Released I Unit I Quarter I I Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD 6.41E-05 3.65E-05 1.01E-04 Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci
< LLD 4.79E-06
< LLD
< LLD
' LLD
< LLD
< LLD
< LLD Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-1 37 Ci 7.19E-09
< LLD
< LLD
< LLD 7.19E-09 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
<LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Os-191 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci Note I Note I Note 1 Note I Note 1 Sr-90 Ci Note I Note 1 Note 1 Note 1 Note 1 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 7.19E-09 4.79E-06 6.41E-05 3.65E-05 1.05E-04
- 4. Tritium H-3 Ci 1.95E-02 3.68E+02 2.77E-02 1.97E+02 5.64E+02 Note I - Not required for batch releases 37 PVNGS ARERR 2005
Table 25:
Unit 3 Gaseous Effluents - Continuous and Batch - Fission Gases and lodines Nuclides Released Unit I Quarter 1 Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 1. Fission gases Ar-41 Ci 8.71 E-02 2.56E-01 8.81 E-01 1.69E-01 1.39E+00 Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
< LLD
<LLD
< LLD
< LLD
< LLD Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
<LLD Kr-87 Ci
< LLD
<LLD
<LLD
< LLD
< LLD
< LLD
<LLD
< LLD
< LLD
<LLD Kr-90 Ci
< LLD
<LLD
< LLD
< LLD
<LLD Xe-131m Ci
< LLD 1.08E-04
< LLD
< LLD 1.08E-04 Xe-1 33 Ci
< LLD 1.77E-02 4.15E-04
< LLD 1.81 E-02 Xe-1 33m Ci
< LLD 3.32E-04
< LLD
< LLD 3.32E-04 Xe-1 35 Ci
< LLD 1.25E-05
< LLD
<LLD 1.25E-05 Xe-135m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-137 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
<LLD total Ci 8.71 E-02 2.74E-01 8.81 E-01 1.69E-01 1.41 E+00
- 2. lodines 1-131 Ci
< LLD 5.64E-07
< LLD
< LLD 5.64E-07 1-132 Ci
< LLD
<LLD
< LLD
< LLD
< LLD 1-133 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-134 Ci
< LLD
<LLD
< LLD
< LLD
< LLD 1-135 Ci
<LLD
< LLD
< LLD
< LLD
< LLD total Ci
< LLD 5.64E-07
< LLD
< LLD 5.64E-07 38 PVNGS ARERR 2005
Table 26:
Unit 3 Gaseous Effluents - Continuous and Batch - Particulates Nuclides Released Unit Quarter I I Quarter 2 Quarter 3 Quarter 4 Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD 6.41 E-05 3.65E-05 1.01E-04 Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci
< LLD 8.58E-06
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-I 37 Ci 7.19E-09
< LLD
< LLD
< LLD 7.19E-09 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Os-191 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 5.20E-09 6.96E-08
< LLD
< LLD 7.48E-08 Sr-90 Ci 7.77E-10 1.04E-08
< LLD
< LLD 1.12E-08 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 1.32E-08 8.66E-06 6.41 E-05 3.65E-05 1.09E-04 total > 8 days Ci 1.32E-08 8.66E-06
< LLD
< LLD 8.68E-06
Table 27:
Unit 3 Radiation Doses At And Beyond The Site Boundary Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total Gamma Air Dose mrad 2.29E-04 6.74E-04 2.31 E-03 4.44E-04 3.66E-03 ODCM Req 4.1 Limit mrad 5.OOE+00 5.OOE+00 5.OOE+00 5.OOE+00 1.OOE+01
% ODCM Limit 4.58E-03 1.35E-02 4.62E-02 8.88E-03 3.66E-02 Beta Air Dose mrad 8.07E-05 2.43E-04 8.16E-04 1.56E-04 1.30E-03 ODCM Req 4.1 Limit mrad 1.OOE+01 1.OOE+01 1.OOE+01 1.OOE+01 2.OOE+01
% ODCM Limit 8.07E-04 2.43E-03 8.16E-03 1.56E-03 6.50E-03 Maximum Organ Dose mrem 4.29E-03 1.38E-01 5.41 E-03 7.17E-02 2.19E-01 (excluding skin)
Age Teen Teen Teen Teen Teen Organ W Body Thyroid (1)
(1)
Thyroid ODCM Req. 4.2 Limit mrem 7.50E+00 7.50E+00 7.50E+00 7.50E+00 1.50E+01
% ODCM Limit 5.72E-02 1.84E+00 7.21 E-02 9.56E-01 1.46E+OO Calculations are based on parameters and methodologies of the ODCM using historical meteorology. Dose is calculated to a hypothetical individual. In contrast, Appendix C dose calculations are based on concurrent meteorology, a real individual, and only the actual pathways present.
Note 1 - All organs except Bone 40 PVNGS ARERR 2005
Table 28:
Units 1,.2, and 3 Gaseous Effluents - Continuous - Fission Gases and lodines -
Total By Quarter Nuclides Released I Unit I Quarter 1 l Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 1. Fission gases Ar-41 Ci c LLD
< LLD
< LLD
< LLD
< LLD Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
< LLD
<LLD
< LLD
<LLD
<LLD Kr-85m Ci
< LLD
< LLD 2.64E-02
< LLD 2.64E-02 Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
<LLD
<LLD
<LLD
<LLD
<LLD Kr-89 Ci
< LLD
<LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-131 m Ci
< LLD
< LLD
< LLD
<LLD
< LLD 3.29E+00 1.66E+01 2.15E+01 Xe-133m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-135 Ci
< LLD
< LLD
<LLD
< LLD
< LLD Xe-1 35m Ci
< LLD
<LLD
< LLD
< LLD
< LLD Xe-137 Ci
<LLD
< LLD
< LLD
< LLD
<LLD Xe-138 Ci
< LLD
<LLD
< LLD
< LLD
< LLD total Ci 1.61 E+00
< LLD 3.31E+00 1.66E+01 2.16E+01
- 2. lodines 1-131 Ci 2.02E-06 1.08E-04 1.73E-06 3.91 E-05 1.51 E-04 1-132 Ci
< LLD 1.57E-03
<LLD
< LLD 1.57E-03 1-133 Ci
< LLD
<LLD
<LLD
< LLD
< LLD 1-134 Ci
<LLD
<LLD
< LLD
< LLD
< LLD 1-135 Ci
< LLD
< LLD
< LLD
<LLD
< LLD total Ci 2.02E-06 1.68E-03 1.73E-06 3.91 E-05 1.72E-03 41 PVNGS ARERR 2005
Table 29:
Units 1, 2, and 3 Gaseous Effluents - Continuous - Particulates -
Total By Quarter Nuclides Released Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 1 Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci 2.70E-06 5.54E-05
< LLD 7.56E-05 1.34E-04 Co-60 Ci 3.34E-06
< LLD
< LLD 2.36E-05 2.69E-05 Cr-51 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-1 37 Ci
<LLD
<LLD
<LLD
<LLD
<LLD Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 1.25E-06 1.25E-06 Mo-99 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD 1.10E-05 1.10E-05 Os-191 Ci
< LLD i.88E-06
< LLD 3.17E-06 5.06E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD 9.49E-07 1.34E-06 2.29E-06 Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 4.03E-07 6.96E-08 7.68E-09 1.45E-07 6.25E-07 Sr-90 Ci 7.77E-10 1.04E-08 8.81 E-09 1.43E-07 1.63E-07 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD 3.08E-06 3.08E-06 total Ci 6.44E-06 5.73E-05 9.66E-07 1.19E-04 1.84E-04
Table 30:
Units 1, 2, and 3 Gaseous Effluents - Batch - Fission Gases and lodines -
Total By Quarter Nuclides Released Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total
- 1. Fission gases Ar-41 Ci 4.21 E-01 4.59E-01 1.57E+00 5.32E-01 2.98E+00 Kr-83m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-85 Ci 7.32E-04 1.60E-03 7.24E-01 3.31 E+00 4.03E+00 Kr-85m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-87 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
< LLD
< LLD
<LLD
< LLD
< LLD Kr-89 Ci
<LLD
<LLD
<LLD
<LLD
<LLD Kr-90 Ci
< LLD cLLD
< LLD
< LLD
< LLD Xe-131m Ci
<LLD 2.97E-03
< LLD 4.99E-02 5.29E-02 Xe-133 Ci 4.76E-01 3.53E+00 6.62E-02 8.46E+00 1.25E+01 Xe-1 33m Ci
< LLD 8.02E-04
< LLD 8.09E-03 8.89E-03 Xe-135 Ci 9.72E-03 1.25E-05 8.06E-05
< LLD 9.81 E-03 Xe-135m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Xe-137 Ci
< LLD
< LLD
< LLD
<LLD
< LLD
< LLD
<LLD C LLD c LLD total Ci 9.08E-01 4.0OE+00 2.36E+00 1.24E+01 1.96E+01
- 2. lodines 1-131 Ci
< LLD
<LLD
< LLD 1.16E-04 1.16E-04 1-132 Ci
< LLD
< LLD
< LLD 7.07E-05 7.07E-05 1-133 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-134 Ci
< LLD
< LLD
<LLD
< LLD
<LLD 1-135 Ci
< LLD
< LLD
<LLD
< LLD
<LLD total Ci
< LLD
< LLD
< LLD 1.87E-04 1.87E-04 43 PVNGS ARERR 2005
Table 31:
Units 1, 2, and 3 Gaseous Effluents - Batch - Particulates -
Total By Quarter Nuclides Released Unit Quarter1 T Quarter 2 1 Quarter 3 Quarter 4 Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD 6.41E-05 3.65E-05 1.01E-04 Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.66E-06 3.66E-06 Co-58 Ci
< LLD 4.79E-06
< LLD 1.25E-03 1.26E-03 Co-60 Ci
< LLD
< LLD
< LLD 6.28E-04 6.28E-04 Cr-51 Ci
< LLD
< LLD
< LLD 2.20E-04 2.20E-04 Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Cs-1 37 Ci 7.19E-09
< LLD
< LLD 1.80E-05 1.80E-05 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD 3.66E-05 3.66E-05 La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.70E-05 3.70E-05 Mo-99 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD 4.29E-04 4.29E-04 Os-191 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD 7.44E-06 7.44E-06 Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci Note 1 Note 1 Note 1 Note I Note 1 Sr-90 Ci Note I Note 1 Note 1 Note 1 Note 1 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD 2.63E-04 2.63E-04 total Ci 7.19E-09 4.79E-06 6.41 E-05 2.93E-03 3.OOE-03
- 4. Tritium H-3 Ci 5.62E+02 5.30E+02 3.52E+02 4.20E+02 1.87E+03 Note I - Not required for batch releases 44 PVNGS ARERR 2005
Table 32:
Units 1, 2, and 3 Gaseous Effluents - Continuous and Batch - Fission Gases and lodines -
Total By Quarter Nuclides Released Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total
- 1. Fission gases Ar-41 Ci 4.21E-01 4.59E-01 1.57E+00 5.32E-01 2.98E+00 Kr-83m Ci
< LLD
< LLD
< LLD
<LLD
< LLD Kr-85 Ci 7.32E-04 1.60E-03 7.24E-01 3.31 E+00 4.03E+00 Kr-85m Ci
< LLD
< LLD 2.64E-02
< LLD 2.64E-02 Kr-87 Ci
< LLD
'LLD
< LLD
< LLD
< LLD Kr-88 Ci
<LLD
<LLD
< LLD
< LLD
< LLD Kr-89 Ci
<LLD c LLD
<LLD
<LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
<LLD
< LLD Xe-131m Ci
< LLD 2.97E-03
< LLD 4.99E-02 5.29E-02 Xe-133 Ci 2.09E+00 3.53E+00 3.35E+00 2.51 E+O1 3.41 E+01 Xe-133m Ci
< LLD 8.02E-04
< LLD 8.09E-03 8.89E-03 Xe-135 Ci 9.72E-03 1.25E-05 8.06E-05
< LLD 9.81 E-03 Xe-135m Ci
<LLD
< LLD
< LLD
<LLD
< LLD Xe-137 Ci
< LLD
< LLD
< LLD
<LLD
< LLD
< LLD
<LLD
< LLD
< LLD total Ci 2.52E+00 4.OOE+00 5.68E+00 2.90E+01 4.12E+01
- 2. lodines 1-131 Ci 2.02E-06 1.08E-04 1.73E-06 1.55E-04 2.68E-04 1-132 Ci
< LLD 1.57E-03
< LLD 7.07E-05 1.64E-03 1-133 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 1-134 Ci
< LLD
<LLD
<LLD c LLD
< LLD 1-135 Ci
<LLD
<LLD
< LLD
< LLD
< LLD total Ci 2.02E-06 1.68E-03 1.73E-06 2.26E44 1.91 E-03 45 PVNGS ARERR 2005
Table 33:
Units 1, 2, and 3 Gaseous Effluents - Continuous and Batch - Particulates -
Total By Quarter Nuclides Released Unit I Quarter 1 l Quarter 2 l Quarter 3 l Quarter 4 l Year total
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD 6.41 E-05 3.65E-05 1.01E-04 Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.66E-06 3.66E-06 Co-58 Ci 2.70E-06 6.02E-05
< LLD 1.33E-03 1.39E-03 Co-60 Ci 3.34E-06
< LLD
< LLD 6.51E-04 6.55E-04 Cr-51 Ci
< LLD
< LLD
< LLD 2.20E-04 2.20E-04 Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 1.80E-05 1.80E-05 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD 3.66E-05 3.66E-05 La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD 3.83E-05 3.83E-05 Mo-99 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci
< LLD
< LLD
< LLD 4.40E-04 4.40E-04 Os-191 Ci
< LLD 1.88E-06
< LLD 3.17E-06 5.06E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD 9.49E-07 1.34E-06 2.29E-06 Sb-122 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD 7.44E-06 7.44E-06 Se-75 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 4.03E-07 6.96E-08 7.68E-09 1.45E-07 6.25E-07 Sr-90 Ci 7.77E-10 1.04E-08 8.81 E-09 1.43E-07 1.63E-07 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci
< LLD
< LLD
< LLD 2.66E-04 2.66E-04 total Ci 6.45E-06 6.21 E-05 6.51 E-05 3.05E-03 3.18E-03 total > 8 days Ci 6.45E-06 6.21 E-05 9.66E-07 3.01E-03 3.08E-03
Table 34:
Units 1, 2 and 3 Gaseous Effluents-Continuous - Fission Gases and Iodine -
Total By Unit Nuclides Released l Unit l Unit 1 1 Unit 2 1 Unit 3 Total Units
.112 and 3
- 1. Fission gases Ar-41 Ci
< LLD
<LLD
< LLD
< LLD Kr-83m Ci
< LLD
<LLD
< LLD
<LLD Kr-85 Ci
< LLD
< LLD
< LLD
< LLD Kr-85m Ci 2.64E-02
< LLD
< LLD 2.64E-02 Kr-87 Ci
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
< LLD
< LLD
< LLD
< LLD Kr-89 Ci
< LLD
<LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD Xe-131m Ci
<LLD
< LLD
< LLD
< LLD
< LLD 2.15E+01 Xe-i 33m Ci
<LLD
<LLD
<LLD
<LLD Xe-1335 Ci
< LLD
< LLD
< LLD
< LLD Xe-135m Ci
< LLD
< LLD
< LLD
< LLD Xe-1337 Ci
< LLD
<LLD
< LLD
< LLD
< LLD
< LLD
<LLD total Ci 2.16E+01
< LLD
< LLD 2.16E+01
- 2. lodines 1-131 Ci 4.41 E-05 1.07E-04 5.64E-07 1.51 E-04 1-132 Ci
< LLD 1.57E-03
<LLD 1.57E-03 1-133 Ci
<LLD
< LLD
< LLD
< LLD 1-134 Ci
<LLD
< LLD
< LLD
< LLD 1-135 Ci
<LLD
< LLD
< LLD
< LLD total Ci 4.41 E-05 1.68E-03 5.64E-07 1.72E-03 47 PVNGS ARERR 2005
Table 35:
Units 1,2 and 3 Gaseous Effluents-Continuous - Particulates -
Total By Unit Nuclides Released Unit l Unit 1 1 Unit 2 l
Unit 3 Total Units 2
1 and3
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD Br-82 Ci
<LLD
< LLD
<LLD
<LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD Ce-141 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Co-58 Ci 7.83E-05 5.16E-05 3.80E-06 1.34E-04 Co-60 Ci 2.36E-05 3.34E-06
< LLD 2.69E-05 Cr-51 Ci
< LLD
< LLD
< LLD
< LLD Cs-134 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Cs-138 Ci
< LLD
< LLD
< LLD
< LLD Fe-59 Ci
< LLD
< LLD
< LLD
< LLD La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci 1.10E-05
< LLD
< LLD 1.10E-05 Os-191 Ci 3.91 E-06 1.15E-06
< LLD 5.06E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD Ru-1 03 Ci 2.29E-06
< LLD
< LLD 2.29E-06 Sb-122 Ci
< LLD
< LLD
< LLD
< LLD Sb-124 Ci
< LLD
< LLD
< LLD
< LLD Se-75 Ci
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 5.50E-07
< LLD 7.48E-08 6.25E-07 Sr-90 Ci 5.39E-08 9.78E-08 1.12E-08 1.63E-07 Te-123m Ci
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD Zr-95 Ci 3.08E-06
< LLD
< LLD 3.08E-06 total Ci 1.24E-04 5.62E-05 3.88E-06 1.84E-04
Table 36:
Units 1, 2 and 3 Gaseous Effluents-Batch - Fission Gases and Iodine -
Total By Unit Nuclides Released 1 Unit l Unit I I
Unit 2 1 Unit 3 l Total Units
_ _ _ _ _ 1
_ _ 1.
1.2 a n d 3
- 1. Fission gases Ar-41 Ci 6.26E-01 9.66E-01 1.39E+00 2.98E+00 Kr-83m Ci
< LLD
< LLD
< LLD
< LLD Kr-85 Ci 4.03E+00 1.60E-03
< LLD 4.03E+00 Kr-85m Ci
< LLD
<LLD
< LLD
< LLD Kr-87 Ci
< LLD
<LLD
< LLD
<LLD Kr-88 Ci
< LLD
< LLD
< LLD
< LLD Kr-89 Ci
< LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
< LLD
< LLD
< LLD Xe-131m Ci 4.99E-02 2.86E-03 1.08E-04 5.29E-02 Xe-1 33 Ci 8.87E+00 3.65E+00 1.81 E-02 1.25E+01 Xe-1 33m Ci 8.09E-03 4.69E-04 3.32E-04 8.89E-03 Xe-1 35 Ci 7.70E-03 2.10E-03 1.25E-05 9.81 E-03 Xe-1 35m Ci
< LLD
< LLD
< LLD
< LLD Xe-137 Ci
< LLD
<LLD
< LLD
< LLD
< LLD
< LLD
< LLD total Ci 1.36E+01 4.62E+00 1.41 E+00 1.96E+01
- 2. lodines 1-131 Ci 1.16E-04
< LLD
< LLD 1.16E-04 1-132 Ci 7.07E-05
< LLD
< LLD 7.07E-05 1-133 Ci
< LLD
<LLD
< LLD
< LLD 1-134 Ci
< LLD
< LLD
< LLD
< LLD 1-135 Ci
<LLD
< LLD
< LLD
< LLD total Ci 1.87E-04
< LLD
<LLD 1.87E-04 49 PVNGS ARERR 2005
Table 37:
Units 1, 2 and 3 Gaseous Effluents-Batch - Particulates -
Total By Unit Nuclides Released 1 Unit Unit 1 I Unit 2 1 Unit 3 Total Units 1,2 and 3
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
< LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD 1.01E-04 1.01E-04 Ce-141 Ci c LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 3.66E-06 Co-58 Ci 1.25E-03
< LLD 4.79E-06 1.26E-03 Co-60 Ci 6.28E-04
< LLD
< LLD 6.28E-04 Cr-51 Ci 2.20E-04
< LLD
< LLD 2.20E-04 Cs-134 Ci
< LLD
< LLD
< LLD
< LLD Cs-1 37 Ci 1.80E-05
< LLD 7.19E-09 1.80E-05 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD 3.66E-05 La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci 4.29E-04
< LLD
< LLD 4.29E-04 Os-191 Ci
< LLD
< LLD
< LLD
< LLD Rb-88 Ci
< LLD
< LLD
< LLD
< LLD Ru-103 Ci
< LLD
< LLD
< LLD
< LLD Sb-122 Ci
< LLD
< LLD
< LLD
< LLD Sb-124 Ci 7.44E-06
< LLD
< LLD 7.44E-06 Se-75 Ci
< LLD
< LLD
< LLD
< LLD Sr-89 Ci Note I Note 1 Note 1 Note 1 Sr-90 Ci Note I Note 1 Note 1 Note 1 Te-123m Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Zr-95 Ci 2.63E-04
< LLD
< LLD 2.63E-04 total Ci 2.89E-03
< LLD 1.05E-04 3.OOE-03
- 4. Tritium H-3 Ci 7.67E+02 5.33E+02 5.64E+02 1.87E+03 Note 1 - Not required for batch releases 50 PVNGS ARERR 2005
Table 38:
Units 1,2 and 3 Gaseous Effluents-Continuous and Batch - Fission Gases and Iodine -
Total By Unit Nuclides Released Unit Unit I I Unit 2 1 Unit 3 l Total Units U1
.2 and 3
- 1. Fission gases Ar-41 Ci 6.26E-01 9.66E-01 1.39E+00 2.98E+00 Kr-83m Ci
< LLD
< LLD
< LLD
< LLD Kr-85 Ci 4.03E+00 1.60E-03
< LLD 4.03E+00 Kr-85m Ci 2.64E-02
< LLD
< LLD 2.64E-02 Kr-87 Ci
< LLD
< LLD
< LLD
< LLD Kr-88 Ci
< LLD
'LLD
< LLD
< LLD Kr-89 Ci
< LLD
< LLD
< LLD
< LLD Kr-90 Ci
< LLD
<LLD
< LLD
< LLD Xe-131 m Ci 4.99E-02 2.86E-03 1.08E-04 5.29E-02 Xe-133 Ci 3.04E+01 3.65E+00 1.81 E-02 3.41 E+01 Xe-13 3m Ci 8.09E-03 4.69E-04 3.32E-04 8.89E-03 Xe-1 35 Ci 7.70E-03 2.10E-03 1.25E-05 9.81 E-03 Xe-1 35m Ci
< LLD
< LLD
< LLD
< LLD Xe-137 Ci
<LLD
< LLD
< LLD
<LLD Xe-138 Ci
<LLD
< LLD
< LLD
< LLD total Ci 3.52E+01 4.62E+00 1.41 E+00 4.12E+01
- 2. lodines 1-131 Ci 1.60E-04 1.07E-04 5.64E-07 2.68E-04 1-132 Ci 7.07E-05 1.57E-03
< LLD 1.64E-03 1-133 Ci
<LLD
< LLD 1-134 Ci
<LLD
< LLD
<LLD
< LLD 1-135 Ci
<LLD
< LLD
< LLD
< LLD total Ci 2.31 E-04 1.68E-03 5.64E-07 1.91 E-03 51 PVNGS ARERR 2005
Table 39:
Units 1, 2 and 3 Gaseous Effluents - Continuous and Batch - Particulates -
Total By Unit Nuclides Released l Unit l Unit I l
Unit 2 1 Unit 3 Total Units
_ _ I _ _ _
1, 2 a n d 3
- 3. Particulates Ag-110m Ci
< LLD
< LLD
< LLD
<LLD Ba-140 Ci
< LLD
< LLD
< LLD
< LLD Br-82 Ci
< LLD
< LLD 1.01 E-04 1.01E-04 Ce-141 Ci
< LLD
< LLD
< LLD
< LLD Ce-144 Ci
< LLD
< LLD
< LLD
< LLD
< LLD 3.66E-06 Co-58 Ci 1.33E-03 5.16E-05 8.58E-06 1.39E-03 Co-60 Ci 6.51 E-04 3.34E-06
< LLD 6.55E-04 Cr-51 Ci 2.20E-04
< LLD
< LLD 2.20E-04 Cs-134 Ci
< LLD
< LLD
< LLD
< LLD 7.19E-09 1.80E-05 Cs-138 Ci
< LLD
< LLD
< LLD
< LLD Fe-59 Ci 3.66E-05
< LLD
< LLD 3.66E-05 La-140 Ci
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD
< LLD Nb-95 Ci 4.40E-04
< LLD
< LLD 4.40E-04 Os-191 Ci 3.91E-06 1.15E-06
< LLD 5.06E-06 Rb-88 Ci
< LLD
< LLD
< LLD
< LLD Ru-1 03 Ci 2.29E-06
< LLD
< LLD 2.29E-06 Sb-122 Ci
< LLD
< LLD
< LLD
< LLD Sb-124 Ci 7.44E-06
< LLD
< LLD 7.44E-06 Se-75 Ci
< LLD
< LLD
< LLD
< LLD Sr-89 Ci 5.50E-07
< LLD 7.48E-08 6.25E-07 Sr-90 Ci 5.39E-08 9.78E-08 1.12E-08 1.63E-07 Te-123m Ci
< LLD
< LLD
< LLD
< LLD Zn-65 Ci
< LLD
< LLD
< LLD
< LLD Zr-95 Ci 2.66E-04
< LLD
< LLD 2.66E-04 total Ci 3.02E-03 5.62E-05 1.09E-04 3.18E-03 total > 8 days Ci 3.02E-03 5.62E-05 8.68E-06 3.08E-03
Table 40:
Estimation of Total Percent Error The estimated total error is calculated as follows:
Total Percent Error = (E1 2 + E2 2 + E3+
... + En2 )1/2 Where En = Percent error associated with each contributing parameter.
Parameters contributing to errors in the measurement of gaseous effluents; process flow rates, sample collection, analytical counting and tank volumes.
The following values (%) were used for error calculations.
Fission & Act gases 1-131 Particulates Tritium 25 25 25 25 Sample counting error 10 10 10 10 Counting system calibration error 5
5 5
5 Counting system source error 20 N/A N/A N/A Temperature/volume correction error 10 10 10 10 Process flow measuring device (1)
N/A 15 15 15 Sample flow measuring device N/A 5
N/A N/A Iodine collection efficiency error N/A N/A 10 N/A Plateout error N/A N/A N/A 20 Bubbler collection efficiency error N/A N/A N/A 2
Sample volume transfer error (pipette)
N/A N/A N/A 2
Sample volume error (graduate)
Note 1 - % of full scale 53 PVNGS ARERR 2005
Table 41:
Effluent Monitoring Instrumentation Out Of Service Greater Than 30 Days Unit Instrument Date span of Cause of inoperability inoperability Explanation NONE 54 PVNGS ARERR 2005
Table 42:
Solid Waste Summary A. Solid Waste Shipped Offsite For Burial Or Disposal (not irradiated fuel) 1.0 Type of Waste Unit Jan-Dec estimated total error %
l.a. Spent resin, filters, evaporator bottoms, etc.
m3 2.50E+01 N/A Ci 1.11E+02 2.50E+01 1.b. Dry compressible waste, contaminated m3 5.44E+02 N/A equipment, etc.
Ci 6.36E-01 2.50E+01 1.c. Irradiated components, control rods, etc.
m3 1.76E+01 N/A Ci 1.45E+01 2.50E+01 1.d. Other (Mixed waste) m3 7.21E+00 N/A Ci 4.40E-03 2.50E+01 Volume and activity for dry compressible waste, contaminated equipment, etc., includes PVNGS waste disposed of after being processed by a volume reduction facility. Volume for waste shipped to the Envirocare Bulk Facility is calculated from waste volume not container disposal volume.
2.0 Principal Radionuclides 2.a Estimate of major nuclide concentrations for spent resins, filters, evaporator bottoms, etc.
Waste Class Nuclide Name Percent Abundance Curies A
Fe-55 3.97E+01 9.22E-01 A
Ni-63 1.90E+01 4.42E-01 A
Co-60 1.37E+01 3.18E-01 A
Cs-137 1.01 E+01 2.35E-01 A
C-14 7.40E+00 1.72E-01 A
H-3 4.43E+00 1.03E-01 A
Sb-125 1.43E+00 3.32E-02 A
Cs-1 34 1.34E+00 3.12E-02 A
Ag-11Om 1.28E+00 2.98E-02 A
Mn-54 6.49E-01 1.51 E-02 A
Co-58 6.11E-01 1.42E-02 A
Ni-59 1.84E-01 4.29E-03 A
Sr-90 6.67E-02 1.55E-03 A
Co-57 6.28E-02 1.46E-03 A
Pu-241 5.25E-02 1.22E-03 A
Sb-124 1.18E-02 2.75E-04 A
Pu-238 8.73E-03 2.03E-04 A
Cm-243 8.26E-03 1.92E-04 A
Ce-144 6.62E-03 1.54E-04 A
Zr-95 6.28E-03 1.46E-04 A
Am-241 5.85E-03 1.36E-04 A
Pu-239 2.84E-03 6.60E-05 A
Sn-113 2.81 E-03 6.54E-05 A
Tc-99 5.38E-04 1.25E-05 A
Nb-95 4.30E-04 1.OOE-05 A
Cm-242 3.15E-04 7.32E-06 Total 2.33E+OO 56 PVNGS ARERR 2005
2.b Estimate of major nuclide concentrations for spent resins, filters, evaporator bottoms, etc.
Waste Class Nuclide Name Percent Abundance Curies B
Ni-63 3.91 E+01 4.OOE+01 B
Fe-55 2.46E+01 2.52E+01 B
Cs-1 37 1.46E+01 1.49E+01 B
Co-60 9.96E+00 1.02E+01 B
Cs-134 8.59E+00 8.79E+OO B
Mn-54 2.09E+00 2.14E+OO B
Sb-125 3.95E-01 4.04E-01 B
C-14 2.73E-01 2.79E-01 B
Co-57 1.54E-01 1.58E-01 B
Co-58 9.87E-02 1.01E-01 B
Sr-90 6.83E-02 6.99E-02 B
Ni-59 4.80E-02 4.91 E-02 B
H-3 4.51 E-02 4.62E-02 B
Pu-241 1.79E-02 1.83E-02 B
Ag-11Om 8.23E-03 8.43E-03 B
Ce-144 4.65E-03 4.76E-03 B
Cm-243 1.47E-03 1.50E-03 B
Pu-238 5.71 E-04 5.85E-04 B
Pu-239 1.24E-04 1.27E-04 B
Am-241 1.20E-04 1.23E-04 B
Tc-99 3.97E-05 4.06E-05 B
Cm-242 3.92E-05 4.O1E-05 Total 1.02E+02 57 PVNGS ARERR 2005
2.c Estimate of major nuclide concentrations for spent resins, filters, evaporator bottoms, etc.
Waste Class Nuclide Name Percent Abundance Curies C
Fe-55 4.80E+01 2.85E+00 C
Ni-63 2.20E+01 1.31 E+00 C
Co-60 1.51 E+01 8.95E-01 C
C-14 1.10E+01 6.53E-01 C
Sb-125 1.56E+00 9.24E-02 C
Mn-54 1.19E+00 7.07E-02 C
Co-58 4.83E-01 2.87E-02 C
Co-57 1.57E-01 9.34E-03 C
Ni-59 1.52E-01 9.04E-03 C
Ag-110m 1.14E-01 6.77E-03 C
Cs-1 37 8.60E-02 5.11E-03 C
H-3 3.67E-02 2.18E-03 C
Zr-95 3.35E-02 1.99E-03 C
Sn-113 2.79E-02 1.66E-03 C
Te-123m 2.69E-02 1.60E-03 C
Cs-1 34 2.61 E-02 1.55E-03 C
Ce-144 1.44E-02 8.55E-04 C
Pu-241 1.04E-02 6.15E-04 C
Sb-124 6.35E-03 3.77E-04 C
Sr-90 5.79E-03 3.44E-04 C
Tc-99 3.67E-04 2.18E-05 C
Cm-243 3.42E-04 2.03E-05 C
Pu-238 1.78E-04 1.06E-05 C
Cm-242 1.46E-04 8.65E-06 C
Am-241 1.05E-04 6.22E-06 C
Fe-59 9.81 E-05 5.83E-06 C
Pu-239 9.68E-05 5.75E-06 C
Nb-95 5.92E-05 3.52E-06 C
Cr-51 6.55E-06 3.89E-07 Total
_ 5.94E+00 58 PVNGS ARERR 2005
2.d Estimate of major nuclide concentrations for dry compressible waste, contaminated equipment, etc.
Waste Class Nuclide Name Percent Abundance Curies A
Fe-55 6.48E+01 4.12E-01 A
Co-58 1.53E+01 9.71 E-02 A
Co-60 5.71 E+OO 3.63E-02 A
Ni-63 5.01 E+OO 3.19E-02 A
Nb-95 2.83E+00 1.80E-02 A
Zr-95 2.39E+00 1.52E-02 A
Cr-51 1.39E+00 8.82E-03 A
Mn-54 7.56E-41 4.81 E-03 A
Fe-59 3.60E-01 2.29E-03 A
Sb-1 25 3.19E-01 2.03E-03 A
H-3 2.70E-01 1.72E-03 A
Sb-124 1.52E-01 9.65E-04 A
Ag-11Om 1.46E-01 9.31 E-04 A
Ru-103 1.41E-01 8.99E-04 A
Sn-113 1.22E-01 7.75E-04 A
Co-57 1.1OE-01 6.99E-04 A
C-14 6.44E-02 4.10E-04 A
Ni-59 3.77E-02 2.40E-04 A
Zn-65 3.33E-02 2.12E-04 A
Pu-241 3.08E-02 1.96E-04 A
Te-123m 2.85E-02 1.81 E-04 A
Ce-144 2.69E-02 1.71 E-04 A
Ce-141 1.63E-02 1.04E-04 A
Hf-181 1.44E-02 9.18E-05 A
Cs-134 5.19E-03 3.30E-05 A
Cs-1 37 4.43E-03 2.82E-05 A
Cm-242 3.52E-03 2.24E-05 A
Sr-89 2.64E-03 1.68E-05 A
Pu-238 7.69E-04 4.89E-06 A
Cm-243 7.40E-04 4.71 E-06 A
Sr-90 6.1OE-04 3.88E-06 A
Am-241 3.62E-04 2.30E-06 A
Pu-239 2.74E-04 1.74E-06 A
Tc-99 7.34E-05 4.67E-07 Total 6.36E-01 59 PVNGS ARERR 2005
2.e Estimate of major nuclide concentrations for irradiated components, control rods, etc.
Waste Class Nuclide Name Percent Abundance Curies A
Co-60 5.09E+01 7.39E+OO A
Fe-55 4.28E+01 6.22E+OO A
Ni-63 4.83E+00 7.01E-01 A
Mn-54 6.55E-01 9.51 E-02 A
Co-58 4.53E-01 6.58E-02 A
H-3 5.84E-02 8.48E-03 A
Zr-95 4.77E-02 6.93E-03 A
Cr-51 4.19E-02 6.08E-03 A
Sb-125 3.86E-02 5.61 E-03 A
C-14 2.78E-02 4.04E-03 A
Ni-59 2.62E-02 3.80E-03 A
Nb-95 1.1 OE-02 1.60E-03 A
Co-57 9.37E-03 1.36E-03 A
Ta-1 82 8.96E-03 1.30E-03 A
Fe-59 8.34E-03 1.21 E-03 A
Sn-113 7.51 E-03 1.09E-03 A
Zn-65 6.80E-03 9.87E-04 A
Ce-144 5.64E-03 8.18E-04 A
Pu-241 2.79E-03 4.05E-04 A
Sb-124 1.92E-03 2.79E-04 A
Te-123m 1.16E-03 1.68E-04 A
Cs-134 5.08E-04 7.37E-05 A
Nb-94 3.79E-04 5.50E-05 A
Sr-90 2.81 E-04 4.08E-05 A
Cm-242 1.51 E-04 2.19E-05 A
Tc-99 1.12E-04 1.63E-05 A
Cm-243 6.45E-05 9.37E-06 A
Pu-238 5.79E-05 8.41 E-06 A
1-129 5.24E-05 7.61 E-06 A
Ru-103 2.93E-05 4.25E-06 A
Pu-239 2.60E-05 3.77E-06 A
Ce-141 2.54E-05 3.68E-06 A
Am-241 2.27E-05 3.29E-06 A
Sr-89 1.07E-05 1.56E-06 A
Sn-117m 2.62E-06 3.80E-07 A
Cs-1 37 8.82E-09 1.28E-09 Total 1.45E+01 60 PVNGS ARERR 2005
2.f Estimate of major nuclide concentrations for Other (mixed waste).
Waste Class Nuclide Name Percent Abundance Curies A
Fe-55 4.04E+01 1.78E-03 A
Co-60 1.66E+01 7.33E-04 A
Ni-63 8.52E+00 3.75E-04 A
Cs-137 6.61 E+00 2.91 E-04 A
C-14 5.43E+00 2.39E-04 A
Pu-241 4.82E+00 2.12E-04 A
Ru-106 4.36E+00 1.92E-04 A
Ce-144 3.52E+00 1.55E-04 A
Ag-11Om 3.32E+00 1.46E-04 A
Cs-1 34 2.91 E+O0 1.28E-04 A
Mn-54 1.28E+00 5.65E-05 A
Sb-125 1.08E+00 4.76E-05 A
Sr-90 3.50E-01 1.54E-05 A
Eu-154 2.91E-01 1.28E-05 A
Pu-238 1.02E-01 4.47E-06 A
Cm-243 7.59E-02 3.34E-06 A
Co-57 6.90E-02 3.04E-06 A
Co-58 6.90E-02 3.04E-06 A
Cm-242 4.32E-02 1.90E-06 A
Pu-239 3.20E-02 1.41 E-06 A
Sn-113 1.79E-02 7.86E-07 A
Am-241 1.60E-02 7.05E-07 A
H-3 1.17E-02 5.15E-07 A
Zr-95 7.79E-03 3.43E-07 A
Te-123m 7.15E-03 3.15E-07 A
Sb-124 2.68E-03 1.18E-07 A
Ni-59 9.93E-04 4.37E-08 A
Nb-95 2.48E-04 1.09E-08 A
Fe-59 8.06E-05 3.55E-09 A
Cr-51 1.27E-05 5.61 E-10 A
Ru-103 5.66E-06 2.49E-10 A
Tc-99 4.18E-06 1.84E-10 A
Hf-181 3.63E-06 1.60E-10 A
Sr-89 1.99E-06 8.75E-11 A
Ce-141 5.81 E-07 2.56E-11 Total I 4.40E-03 61 PVNGS ARERR 2005
3.0 Solid Waste Disposition 3.a Shipments Shipper Mode Of Destination Transportation 3
APS Truck Barnwell, SC 20 APS Truck Envirocare, UT (Bulk) 5 APS Truck Envirocare, UT (Containerized) 1 APS Truck Perma-Fix, FL 3.b Irradiated Fuel Shipments: None 3.c Supplemental Information (This section includes PVNGS and Vendor supplied containers):
Number of Container Type of Waste Container Type Agent 2
132.4 Resin EL-142 None 2
199.4 Resin ES-210 None 1
18.8 Filters Nuhic-55 None 40 7.5 Evaporator Bottoms Drum None 2
98.9 Dry Active Waste CPC 82.2 Box None 6
1031.3 Dry Active Waste Intermodal None 17 1360 Dry Active Waste 20' Sealand None 2
65.8 Irradiated Hardware CPC 38.5 Box None 1
101.9 Irradiated Hardware CPC 68.2 Box None 6
64.9 Irradiated Hardware Tri-Sector None 1
1.2 Mixed Waste Drum None 6
7.5 Mixed Waste Drum None 1
21 Mixed Waste CPC 16.3 Box None 9
98.9 Mixed Waste CPC 82.2 Box None 62 PVNGS ARERR 2005
APPENDIX B METEOROLOGY 63 PVNGS ARERR 2005
JOINT FREQUENCY DISTRIBUTION TABLES The tables presented in this section are results obtained from processing the hourly mete-orological data collected at the Palo Verde Nuclear Generating Station for the period of January - December 2005. The joint frequency distribution (JFD) tables represent the fre-quency, in terms of the number of observations, that a particular wind speed, wind direc-tion, and stability category occurred simultaneously. On a quarterly, semiannual and annual basis, the JFDs were produced for 35-foot wind speed and wind direction by atmo-spheric stability class corresponding to the seven Pasquill stability categories, and for wind speed and wind direction for all stability classes combined. Atmospheric stability was classified per Regulatory Guide 1.23, using the 200-foot to 35-foot temperature difference (delta T).
In accordance with NUREG-01 33, the batch releases for the year were considered as "long term," since the batch releases are sufficiently random in both time of day and dura-tion. Consequently, the JFDs for the batch releases for all quarters are the same as for the continuous releases.
Discussion A summary of 2005 Joint Frequency Distribution (JFD) shows a somewhat typical, but variable year. Of the 8760 hours0.101 days <br />2.433 hours <br />0.0145 weeks <br />0.00333 months <br /> available, only 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of data were lost for a 99.9% data recovery.
The average 35 foot wind speed was 6.4 mph. Distribution of directions was spread over the compass with a predominant direction (3 sectors of 22.5 degrees each) centered on the north. (30.9%) A secondary maximum of three sectors centered on the southwest contained 28.5% of the total. With the northerly directions, the highest frequency occurred at 4.0 mph. Southwesterly flow winds averaged higher speeds with the most frequent speed at 10.0 mph.
Stability class summary:
Overall stable conditions (E,FG) dominated, with extremely stable (G) conditions occurring during 29.2% of the hours.
Stability class E, F, G. (stable categories) 60.6%.
Stability class G. (extremely stable) 29.2%.
Stability class A, B, C, (unstable categories) 21.0%.
Stability class D, (neutral category) 18.4%.
Light northerly flow is most likely for stable conditions, while unstable atmospheres are usually associated with faster southwesterly winds. This distribution is typical of moderate altitude dry climates.
ARIZONA PUBLIC SERVICE CO.
- PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/01/2005 TO 3/31/2005
^.
1ST QRTR.*.
STABILITY CLASS A
STABILITY BASED ON:
DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4.51-5.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
5.51-6.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
6.51-8.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
8.51-11.50 1
0 0
0 0
0 0
0 0
1 1
4 3
0 1
0 11 11.51-14.50 0
0 1
0 0
0 0
0 0
0 0
1 1
0 2
4 9
14.51-20.50 0
1 1
0 0
0 0
0 0
0 3
4 1
0 0
5 15
- 20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 1
1 2
0 0
0 0
0 0
1 4
9 5
0 3
9 35 STABILITY CLASS B
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4.51-5.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
5.51-6.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
6.51-8.50 0
0 1
0 0
0 0
0 1
1 1
1 3
0 0
0 8
8.51-11.50 2
1 1
0 1
0 0
0 0
0 2
3 2
0 0
0 12 11.51-14.50 0
1 0
0 0
0 0
0 0
0 0
1 0
0 0
2 4
14.51-20.50 1
0 0
1 0
0 0
0 0
0 0
1 0
1 0
1 5
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 3
2 2
1 1
0 0
0 1
1 3
6 5
1 0
3 29 STABILITY CLASS C
SPEED (MPH)
N NNE NE ENE B
ESE SE SEE S
WNW NW NNW TOTAL CALM
.76-1.50 0
0 0
0 0
0 0
0 0
0 1.51-2.50 0
0 0
0 0
0 0
0 0
0 2.51-3.50 0
0 0
0 0
0 1
0 0
0 3.51-4.50 0
1 0
0 0
0 0
0 0
0 4.51-5.50 0
1 0
0 1
1 0
1 0
2 5.51-6.50 1
2 1
0 1
0 0
0 2
0 6.51-8.50 2
3 1
0 3
0 0
1 3
0 8.51-11.50 0
1 1
3 1
2 0
0 1
1 11.51-14.50 0
0 0
0 0
0 0
0 0
0 14.51-20.50 1
0 0
4 0
0 0
0 0
0
'20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1 0
0 0
0 0
0 1
1 0
0 0
1 0
a 1
4 2
0 1
0 15 5
4 0
0 0
1 23 5
1 0
1 0
1 18 1
1 1
3 0
0 6
1 0
0 2
0 0
8 0
0 0
0 0
0 0
TOTAL 4
8 3
7 6
3 1
2 6
3 14 10 3
6 2
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/01/Z005 TO 3/31/2005
^
1ST QRTR...
STABILITY CLASS D
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
0 1
1.51-2.50 0
0 2
2 1
0 0
0 0
3 1
1 3
2 1
3 19 2.51-3.50 2
5 5
1 1
1 1
6 2
3 1S 8
16 9
10 5
90 3.51-4.50 12 7
5 2
1 2
2 0
7 9
13 10 10 9
8 12 109 4.51-5.50 6
11 6
2 1
1 1
3 2
5 10 8
5 5
4 S
75 5.51-6.50 3
8 3
5 0
0 1
2 5
9 9
2 2
3 3
3 se 6.51-8.50 6
2 11 7
4 5
5 3
4 6
10 3
2 0
2 1
71 8.51-11.50 0
1 3
3 6
10 4
1 3
2 14 9
3 1
3 0
63 11.51-14.50 1
0 3
4 8
2 0
0 0
0 6
1 0
2 1
0 28 14.51-20.50 0
0 1
5 9
0 0
0 0
0 1
2 0
2 2
1 23
>20.50 0
0 0
2 0
0 0
0 0
0 0
0 0
0 0
0 2
TOTAL 30 34 39 33 31 21 14 15 23 37 79 44 41 33 35 30 539 STABILITY CLASS E
SPEED (MPH)
N NNE NE ENE a
WH NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
1 0
0 0
0 0
0 0
0 1
0 2
1.51-2.50 3
1 0
1 0
0 0
0 0
0 3
0 4
4 7
3 26 2.51-3.50 8
1 0
1 0
1 0
0 1
2 6
3 7
14 12 9
65 3.51-4.50 7
5 1
2 0
1 0
0 1
1 2
7 4
4 16 15 66 4.51-5.50 8
6 1
1 3
0 2
0 3
2 3
1 1
2 4
7 44 5.51-6.50 6
4 7
0 1
0 0
2 5
B 8
7 2
1 0
3 54 6.51-8.50 5
8 7
1 1
1 0
5 7
2 16 7
5 3
5 1
74 8.51-11.50 6
4 4
B 5
5 2
6 0
2 8
4 2
1 3
1 61 11.51-14.50 1
0 0
7 1S 5
2 3
1 1
4 2
4 1
2 1
49 14.51-20.50 0
0 1
0 12 3
0 0
0 0
2 2
4 3
3 0
30
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 44 29 21 21 37 17 6
16 18 lB 52 33 33 33 53 40 471 STABILITY CLASS F
SPEED (MPH)
WN NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 4
1 0
1 2
0 0
0 0
1 0
1 4
6 3
6 29 2.51-3.50 8
1 4
2 2
0 1
0 1
5 1
6 4
20 14 17 66 3.51-4.50 13 a
0 0
0 0
0 0
0 3
4 3
3 5
21 28 80 4.51-5.50 11 2
3 0
0 0
0 0
0 2
6 5
3 3
9 12 56 5.51-6.50 11 5
0 0
0 0
0 0
2 1
11 4
1 0
4 0
47 6.51-8.50 S
4 5
0 1
0 0
0 0
4 5
3 4
2 2
1 36 8.51-11.50 4
1 0
4 1
0 0
0 1
1 12 4
1 1
2 1
33 11.51-14.50 2
1 1
0 0
0 0
0 0
0 1
0 0
0 2
1 8
14.51-20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1 1
.20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 58 15 13 7
6 0
1 0
4 17 40 26 20 37 57 75 376 66 PVNGS ARERR 2005
ARIZONA PUBLIC SERVICE CO.
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/0/12005 TO 3/31/2005
'-^
1ST QRTR *..
STABILITY CLASS G
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 PEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 5
2 1
0 1
1 0
0 1
0 1
3 3
4 4
4 30 2.51-3.50 26 8
2 0
0 2
2 0
1 0
3 0
6 10 24 30 114 3.51-4.50 52 18 2
0 0
1 0
0 0
0 1
2 4
2 25 59 166 4.51-5.50 58 14 1
0 1
0 0
0 0
1 0
3 3
4 12 31 128 5.51-6.50 35 8
2 0
0 0
0 0
0 0
1 1
0 2
1 15 65 6.51-8.50 33 13 1
0 0
0 0
0 0
1 2
0 0
1 0
14 65 8.51-11.50 16 30 2
0 0
0 0
0 0
1 1
0 0
0 0
8 58 11.51-14.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3 3
14.51-20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 225 93 11 0
2 4
2 0
2 3
9 9
16 23 66 164 629 STABILITY CLASS ALL SPEED (MPH)
N NNE NE ENE e
NW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
1 0
0 0
0 0
0 0
0 2
0 3
1.51-2.50 12 4
3 4
4 1
0 0
1 4
5 5
14 16 15 16 104 2.51-3.50 44 is 11 4
3 4
5 6
5 10 25 17 33 53 60 61 356 3.51-4.50 84 31 8
4 1
4 2
0 8
13 20 22 21 20 70 114 422 4.51-5.50 83 34 11 3
6 2
3 4
5 12 20 17 12 14 30 55 311 5.51-6.50 56 27 13 5
2 0
1 4
14 18 30 18 7
6 9
29 239 6.51-8.50 51 30 26 8
9 6
5 9
15 14 39 18 14 6
9 18 277 8.51-11.50 29 38 11 10 14 17 6
7 5
8 43 25 11 4
9 11 256 11.51-14.50 4
2 5
11 23 7
2 3
1 1
12 6
6 6
7 11 107 14.51-20.50 2
1 3
10 21 3
0 0
0 0
7 9
5 8
5 8
82
- 20.50 0
0 0
2 0
0 0
0 0
0 0
0 0
0 0
0 2
TOTAL 365 182 91 69 83 45 24 33 54 80 201 137 123 133 216 323 2159 TOTAL NUMBER OF OBSERVATIONS:
2160 TOTAL NUMBER OF VALID OBSERVATIONS:
2159 TOTAL NUMBER OF MISSING OBSERVATIONS:
1 PERCENT DATA RECOVERY FOR THIS PERIOD: 100.0 8 MEAN WIND SPEED FOR THIS PERIOD:
6.2 OPW TOTAL NUMBER OF OBSERVATIONS WITH BACKUP DATA:
0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A
B C
D E
F G
1.62 1.34 3.71 24.97 21.82 17.42 29.13 DISTRIBUTION OF WIND DIRECTION VS STABILITY N
NNE NE ENE e
SSW SW WSW WN WN NW NNW CALM A
1 1
2 0
0 0
0 0
0 1
4 9
5 0
3 9
0 B
3 2
2 1
1 0
0 0
1 1
3 6
5 1
0 3
0 C
4 8
3 7
6 3
1 2
6 3
14 10 3
6 2
2 0
D 30 34 39 33 31 21 14 15 23 37 79 44 41 33 35 30 0
E 44 29 21 21 37 17 6
16 18 18 52 33 33 33 53 40 0
F 58 15 13 7
6 0
1 0
4 17 40 26 20 37 57 75 0
0 225 93 11 0
2 4
2 0
2 3
9 9
16 23 66 164 0
TOTAL 365 182 91 69 83 45 24 33 54 80 201 137 123 133 216 323 0
ARIZONA PUBLIC SERVICE CO.
- PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 4/01/2005 TO 6/30/2005 2ND QRTR...
STABILITY CLASS A
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE e
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4.51-5.50 0
0 0
0 0
0 1
1 2
1 0
0 0
0 1
0 6
5.51-6.50 0
0 0
1 0
2 5
6 9
4 1
0 2
0 0
0 30 6.51-8.50 0
0 0
0 1
2 3
6 19 18 22 6
2 0
0 0
79 8.51-11.50 0
0 0
0 0
0 0
5 9
42 46 17 11 1
1 4
136 11.51-14.50 1
0 0
0 1
0 0
1 5
19 33 5
2 a
4 2
81 14.51-20.50 0
0 0
1 0
0 0
0 2
16 30 11 2
6 4
1 73
,20.50 0
0 0
0 1
0 0
0 0
1 4
1 0
0 0
0 7
TOTAL 1
0 0
2 3
4 9
19 46 101 136 40 19 15 10 7
412 STABILITY CLASS B
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM
.76-1.50 0
0 0
1.51-2.50 0
0 0
2.51-3.50 0
0 0
3.51-4.50 0
0 0
4.51-5.50 0
1 0
5.51-6.50 0
0 0
6.51-8.50 1
0 0
8.51-11.50 0
0 0
11.51-14.50 0
0 0
14.51-20.50 0
0 0
.20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 10 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
1 0
1 0
0 0
1 0
0 0
4 0
1 2
3 2
1 1
3 4
1 0
0 23 0
3 2
6 10 12 6
4 5
0 0
0 2
50 0
1 3
5 5
7 4
6 7
2 1
2 0
44 0
0 4
0 1
1 9
14 7
3 1
1 1
42 1
1 0
0 0
0 2
8 3
0 0
0 0
15 1
1 0
0 0
0 0
3 1
0 0
0 0
6 0
0 0
0 0
0 1
0 0
0 0
0 0
1 TOTAL 1
1 0
2 7
12 15 18 25 23 36 26 10 3
3 3
185 STABILITY CLASS C
SPEED (MPH)
N NNE NE ENE e
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 1
0 0
0 1
3.51-4.50 1
0 0
1 2
2 4
4 2
2 1
0 0
0 0
0 19 4.51-5.50 0
0 0
1 3
6 4
8 6
1 3
1 0
0 1
0 34 5.51-6.50 0
1 0
0 3
3 8
7 3
3 2
1 1
1 0
0 33 6.51-8.50 0
0 0
0 0
1 0
1 1
6 3
3 3
2 0
1 21 8.51-11.50 0
0 0
0 1
0 0
0 0
1 7
2 0
1 0
1 13 11.51-14.50 0
0 0
0 0
0 0
0 0
0 1
0 0
2 2
0 5
14.51-20.50 0
0 0
0 0
0 0
0 0
0 1
1 0
1 0
0 3
>20.50 0
0 0
1 0
0 0
0 0
0 0
0 0
0 0
0 1
TOTAL 1
1 0
3 9
12 16 20 12 13 18 8
5 7
3 2
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 4/01/2005 TO 6/30/2005 2ND QRTR...
STABILITY CLASS D
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
2 0
1 3
1 0
1 1
0 0
0 0
1 10 2.51-3.50 1
2 2
1 5
7 7
3 2
3 3
0 2
0 1
0 39 3.51-4.50 0
0 2
2 3
5 5
7 7
4 4
3 1
0 0
0 43 4.51-5.50 0
1 2
0 3
3 5
B 1
3 4
2 3
0 0
1 36 5.51-6.50 0
0 0
1 1
2 5
3 5
2 2
5 3
0 0
0 29 6.51-8.50 0
0 0
0 0
3 1
2 1
4 10 11 2
1 1
1 37 8.51-11.50 0
0 0
0 1
3 1
0 0
3 7
6 2
2 2
0 27 11.S1-14.50 0
0 0
1 2
1 0
0 0
3 7
9 0
2 0
0 25 14.51-20.50 0
0 0
1 2
1 0
0 0
4 13 0
2 0
2 0
25
'20.50 0
0 0
0 0
0 0
0 0
1 3
1 0
0 0
0 5
TOTAL 1
3 6
8 17 26 27 24 16 28 54 37 15 5
6 3
276 STABILITY CLASS E
SPEED (MPH)
N NNE NE ENE e
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 3
0 1
2 1
0 2
0 0
0 0
1 2
1 0
1 14 2.51-3.50 9
4 1
2 2
0 0
1 3
0 1
0 0
2 2
1 28 3.51-4.50 2
0 2
5 1
1 7
1 1
0 2
3 2
0 0
2 29 4.51-5.50 0
0 1
0 1
0 3
1 4
6 4
4 4
1 1
1 31 5.51-6.50 1
0 1
1 1
0 1
2 2
4 2
2 0
0 0
0 17 6.51-8.50 0
0 1
1 1
1 1
0 0
14 21 13 3
2 1
0 59 8.51-11.50 0
0 1
0 1
2 6
0 1
17 30 22 9
1 4
0 94 11.51-14.50 0
0 1
0 2
0 0
0 0
16 16 4
5 1
3 0
48 14.51-20.50 0
0 0
0 2
0 1
0 0
7 4
1 0
1 1
0 17
'20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 15 4
9 11 12 4
21 5
11 64 80 50 25 9
12 5
337 STABILITY CLASS F
SPEED (MPH)
N NNE NE ENE E
ssw sw WSW W
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 3
1 0
1 2
0 0
0 1
2 0
0 0
0 1
2 13 2.51-3.50 4
4 1
5 2
1 2
0 3
2 3
0 5
4 3
1 40 3.51-4.50 2
3 2
1 3
0 1
0 2
6 9
6 6
4 0
4 49 4.51-5.50 0
0 1
0 0
0 0
1 3
2 9
4 6
1 4
4 35 5.51-6.50 1
0 0
0 0
0 0
2 5
9 12 7
2 2
3 0
43 6.51-8.50 1
1 0
1 0
0 0
0 2
12 29 17 8
3 7
0 80 8.51-11.50 0
0 0
0 0
0 1
0 0
17 20 22 2
3 4
0 69 11.51-14.50 0
0 0
0 0
0 0
0 0
2 2
0 1
0 0
0 5
14.51-20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 11 9
4 8
7 1
4 3
16 52 83 56 30 17 22 11 334 69 PVNGS ARERR 2005
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR TNE PERIOD 4/01/2005 TO 6/30/2005
^
2ND QRTR...
STABILITY CLASS 0
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND TNRESNOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 3
4 1
2 1
2 1
0 1
0 2
2.51-3.50 33 15 2
3 4
3 1
4 1
1 2
3.51-4.50 50 11 6
6 0
1 2
3 0
2 5
4.51-5.50 34 17 7
1 2
0 0
3 2
3 2
5.51-6.50 23 11 5
0 2
0 0
0 1
1 3
6.51-8.50 14 9
2 0
0 0
1 0
0 2
14 8.51-11.50 6
6 1
0 0
0 0
0 0
6 3
11.51-14.50 0
2 0
0 0
0 0
0 0
0 0
14.51-20.50 0
0 0
0 0
0 0
0 0
0 0
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
0 2
4 6
2 1
4 5
1 1
4 1
1 3
2 2
0 0
0 0
0 0
0 0
0 0
0 0
0 0
S 7
8 6
S 0
0 0
0 0
0 0
5 30 21 109 27 131 15 98 9
65 7
53 0
22 0
2 0
0 0
0 TOTAL 163 75 24 12 9
6 5
10 5
15 31 10 14 16 31 84 510 STABILITY CLASS ALL SPEED (MPH)
N NNE NE ENE e
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 9
5 2
7 4
3 6
1 2
3 3
2 2
3 6
9 67 2.51-3.50 47 25 6
11 13 11 10 8
9 6
9 4
14 8
13 23 217 3.51-4.50 55 14 12 15 9
10 20 15 13 14 21 13 14 9
8 33 275 4.51-5.50 34 19 11 2
10 11 16 24 22 17 23 15 18 7
13 21 263 5.51-6.50 25 12 6
3 10 9
25 30 37 29 26 21 9
6 8
11 267 6.51-8.50 16 10 3
2 3
10 11 14 30 60 104 59 22 9
11 9
373 8.51-11.50 6
6 2
0 3
9 8
6 11 95 127 76 27 9
12 6
403 11.51-14.50 1
2 1
2 6
1 0
1 5
42 67 21 8
13 9
2 181 14.51-20.50 0
0 0
3 5
1 1
0 2
27 51 14 4
8 7
1 124
>20.50 0
0 0
1 1
0 0
0 0
3 7
2 0
0 0
0 14 TOTAL 193 93 43 46 64 65 97 99 131 296 438 227 118 72 87 115 2184 TOTAL NUMBER OF OBSERVATIONS:
2184 TOTAL NUMBER OF VALID OBSERVATIONS:
2184 TOTAL NUMBER OF MISSING OBSERVATIONS:
0 PERCENT DATA RECOVERY FOR THIS PERIOD: 100.0 I MEAN WIND SPEED FOR THIS PERIOD:
7.5 MPH TOTAL NUMBER OF OBSERVATIONS WITH BACKUP DATA:
0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A
B C
0 E
F G
18.86 8.47 5.95 12.64 15.43 15.29 23.35 DISTRIBUTION OF WIND DIRECTION VS STABILITY N
NNE NE ENE E
WNW NW NNW CALM A
1 0
0 2
3 4
9 19 46 101 136 40 19 15 10 7
B 1
1 0
2 7
12 15 18 25 23 36 26 10 3
3 3
C 1
1 0
3 9
12 16 20 12 13 18 8
5 7
3 2
D 1
3 6
a 17 26 27 24 16 28 54 37 15 5
6 3
E 15 4
9 11 12 4
21 5
11 64 80 50 25 9
12 5
F 11 9
4 8
7 1
4 3
16 52 83 56 30 17 22 11 G
163 75 24 12 9
6 5
10 5
15 31 10 14 16 31 84 TOTAL 193 93 43 46 64 65 97 99 131 296 438 227 118 72 87 115 0
0 0
0 0
0 0
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/01/2005 TO 6/30/2005
^
1ST SEMI STABILITY CLASS A
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4.51-5.50 0
0 0
0 0
0 1
1 2
1 0
0 0
0 1
0 6
5.51-6.50 0
0 0
1 0
2 5
6 9
4 1
0 2
0 0
0 30 6.51-8.50 0
0 0
0 1
2 3
6 19 18 22 6
2 0
0 0
79 8.51-11.50 1
0 0
0 0
0 0
5 9
43 47 21 14 1
2 4
147 11.51-14.50 1
0 1
0 1
0 0
1 5
19 33 6
3 B
6 6
90 14.51-20.50 0
1 1
1 0
0 0
0 2
16 33 15 3
6 4
6 BB
>20.50 0
0 0
0 1
0 0
0 0
1 4
1 0
0 0
0 7
TOTAL 2
1 2
2 3
4 9
19 46 102 140 49 24 15 13 16 447 STABILITY CLASS B
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
1 1
0 1
0 0
0 1
0 0
0 4
4.51-5.50 0
1 0
0 1
2 3
2 4
1 1
3 4
1 0
0 23 5.51-6.50 0
0 0
0 3
2 6
10 12 6
4 5
0 0
0 2
50 6.51-8.50 1
0 1
0 1
3 5
5 8
5 7
B 5
1 2
0 52 8.51-11.50 2
1 1
0 1
4 0
1 1
9 16 10 5
1 1
1 54 11.51-14.50 0
1 0
1 1
0 0
0 0
2 8
4 0
0 0
2 19 14.51-20.50 1
0 0
2 1
0 0
0 0
0 3
2 0
1 0
1 11
,20.50 0
0 0
0 0
0 0
0 0
1 0
0 0
0 0
0 1
TOTAL 4
3 2
3 8
12 15 1B 26 24 39 32 15 4
3 6
214 STABILITY CLASS C
SPEED (MPH)
N NNE NE ENE E
SSW EN WSW W
WNW NW NNW TOTAL CALM
.76-1.50 0
0 0
0 0
1.51-2.50 0
0 0
0 0
2.51-3.50 0
0 0
0 0
3.51-4.50 1
1 0
1 2
4.51-5.50 0
1 0
1 4
5.51-6.50 1
3 1
0 4
6.51-8.50 2
3 1
0 3
8.51-11.50 0
1 1
3 2
11.51-14.50 0
0 0
0 0
14.51-20.50 1
0 0
4 0
>20.50 0
0 0
1 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1 0
0 0
0 0
1 0
0 0
2 2
4 4
2 2
1 0
0 0
0 0
20 7
4 9
6 3
4 1
0 0
2 0
42 3
8 7
5 3
3 5
3 1
1 0
48 1
0 2
4 6
8 7
3 2
0 2
44 2
0 0
1 2
12 3
0 2
0 2
31 0
0 0
0 0
2 1
1 5
2 0
11 0
0 0
0 0
2 1
0 3
0 0
11 0
0 0
0 0
0 0
0 0
0 0
1 TOTAL 5
9 3
10 15 15 17 22 18 16 32 18 8
13 5
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT PREQUENCY DISTRIBUTION FOR THE PERIOD 1/01/2005 TO 6/30/2005 ST SEMI *.*
STABILITY CLASS D
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 PEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED
{MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
0 1
1.51-2.50 0
0 2
4 1
1 3
1 0
4 2
1 3
2 1
4 29 2.51-3.50 3
7 7
2 6
8 8
9 4
6 18 8
16 9
11 5
129 3.51-4.50 12 7
7 4
4 7
7 7
14 13 17 13 11 9
8 12 152 4.51-5.50 6
12 8
2 4
4 6
11 3
8 14 10 8
5 4
6 111 5.51-6.50 3
8 3
6 1
2 6
5 10 11 11 7
5 3
3 3
87 6.51-8.50 6
2 11 7
4 8
6 5
5 10 20 14 4
1 3
2 108 8.51-11.50 0
1 3
3 7
13 5
1 3
5 21 15 5
3 5
0 90 11.51-14.50 1
0 3
5 10 3
0 0
0 3
13 10 0
4 1
0 53 14.51-20.50 0
0 1
6 11 1
0 0
0 4
14 2
2 2
4 1
48
>20.50 0
0 0
2 0
0 0
0 0
1 3
1 0
0 0
0 7
TOTAL 31 37 45 41 48 47 41 39 39 65 133 81 56 36 41 33 815 STABILITY CLASS E
SPEED (MPH)
N NNE NE ENE E
SSW EN WSN W
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
1 0
0 0
0 0
0 0
0 1
0 2
1.51-2.50 6
1 1
3 1
0 2
0 0
0 3
1 6
5 7
4 40 2.51-3.50 17 5
1 3
2 1
0 1
4 2
7 3
7 16 14 10 93 3.51-4.50 9
5 3
7 1
2 7
1 2
1 4
10 6
4 16 17 95 4.51-5.50 8
6 2
1 4
0 5
1 7
8 7
5 5
3 5
8 75 5.51-6.50 7
4 8
1 2
0 1
4 7
12 10 9
2 1
0 3
71 6.51-8.50 5
8 8
2 2
2 1
5 7
16 37 20 8
5 6
1 133 8.51-11.50 6
4 5
8 6
7 8
6 1
19 38 26 11 2
7 1
155 11.51-14.50 1
0 1
7 17 5
2 3
1 17 20 6
9 2
5 1
97 14.51-20.50 0
0 1
0 14 3
1 0
0 7
6 3
4 4
4 0
47
'20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 59 33 30 32 49 21 27 21 29 82 132 83 58 42 65 45 808 STABILITY CLASS F
SPEED (MPH)
N NNE NE EWE S
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 7
2 0
2 4
0 0
0 1
3 0
1 4
6 4
8 42 2.51-3.50 12 5
5 7
4 1
3 0
4 7
4 6
9 24 17 18 126 3.51-4.50 15 3
2 1
3 0
1 0
2 9
13 9
9 9
21 32 129 4.51-5.50 11 2
4 0
0 0
0 1
3 4
15 9
9 4
13 16 91 5.51-6.50 12 5
0 0
0 0
0 2
7 10 23 11 3
2 7
6 90 6.51-8.50 6
5 5
1 1
0 0
0 2
16 33 20 12 5
9 1
116 8.51-11.50 4
1 0
4 1
0 1
0 1
18 32 26 3
4 6
1 102 11.51-14.50 2
1 1
0 0
0 0
0 0
2 3
0 1
0 2
1 13 14.51-20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1 1
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 69 24 17 15 13 1
5 3
20 69 123 82 50 54 79 86 710 72 PVNGS ARERR 2005
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/0112005 TO 6/30/2005 1ST SEMI...
STABILITY CLASS G
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE e
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 9
6 2
2 2
3 1
0 2
0 3
4 3
6 9
9 60 2.51-3.50 59 23 4
3 4
5 3
4 2
1 5
4 12 12 31 51 223 3.51-4.50 102 29 9
6 0
2 2
3 0
2 6
3 B
7 33 86 297 4.51-5.50 92 31 B
1 3
0 0
3 2
4 2
4 4
B 18 46 226 5.51-6.50 SB 19 7
0 2
0 0
0 1
1 4
2 1
5 6
24 130 6.51-8.50 47 22 3
0 0
0 1
0 0
3 16 2
2 1
0 21 119 8.51-11.50 22 36 3
0 0
0 0
0 0
7 4
0 0
0 0
8 80 11.51-14.50 0
2 0
0 0
0 0
0 0
0 0
0 0
0 0
3 5
14.51-20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 388 168 35 12 11 10 7
10 7
18 40 19 30 39 97 248 1139 STABILITY CLASS ALL SPEED IMPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
1 0
0 0
0 0
0 0
0 2
0 3
1.51-2.50 21 9
5 11 B
4 6
1 3
7 B
7 16 19 21 25 171 2.51-3.50 91 40 17 15 16 15 is 14 14 16 34 21 47 61 73 84 573 3.51-4.50 139 45 20 19 10 14 22 15 21 27 41 35 35 29 78 147 697 4.51-5.50 117 53 22 5
16 13 19 29 27 29 43 32 30 21 43 76 574 5.51-6.50 91 39 19 8
12 9
26 34 51 47 56 39 16 12 17 40 506 6.51-8.50 67 40 29 10 12 16 16 23 45 74 143 77 36 15 20 27 650 8.51-11.50 35 44 13 19 17 26 14 13 16 103 170 101 39 13 21 17 659 11.51-14.50 5
4 6
13 29 8
2 4
6 43 79 27 14 19 16 13 288 14.51-20.50 2
1 3
13 26 4
1 0
2 27 58 23 9
16 12 9
206
>20.50 0
0 0
3 1
0 0
0 0
3 7
2 0
0 0
0 16 TOTAL 55B 275 134 115 147 110 121 132 185 376 639 364 241 205 303 438 4343 TOTAL NUMBER OF OBSERVATIONS:
4344 TOTAL NUMBER OF VALID OBSERVATIONS:
4343 TOTAL NUMBER OF MISSING OBSERVATIONS:
1 PERCENT DATA RECOVERY FOR THIS PERIOD: 100.0 %
MEAN WND SPEED FOR THIS PERIOD:
6.9 MPH TOTAL NUMBER OF OBSERVATIONS WIEN BACKUP DATA:
0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A
B C
D E
F C
10.29 4.93 4.94 19.77 19.60 16.35 26.23 DISTRIBUTION OF WIND DIRECTION VS STABILITY N
NNE NE ENE E
WNW NW NNW CALM A
2 1
2 2
3 4
9 19 46 102 140 49 24 15 13 16 0
B 4
3 2
3 9
1 12 5
19 26 24 39 32 15 4
3 6
0 C
5 9
3 10 15 15 17 22 19 16 32 18 8
13 5
4 0
D 31 37 45 41 48 47 41 39 39 65 133 81 56 39 41 33 0
E 59 33 30 32 49 21 27 21 29 82 132 83 58 42 65 45 0
F 69 24 17 15 13 1
5 3
20 69 123 82 50 54 79 86 0
G 388 164 35 12 11 10 7
10 7
18 40 19 30 39 97 248 0
TOTAL 558 275 134 115 147 110 121 132 185 376 639 364 241 205 303 438 0
ARIZONA PUBLIC SERVICE CO.
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 7/01/2005 TO 9/30/2005 3RD QRTR...
STABILITY CLASS A
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEST WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
ESE SE SE S
Wpm NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 1
0 0
0 1
4.S1-5.50 0
0 0
0 0
0 1
0 1
2 1
1 1
0 0
0 7
5.51-6.50 0
0 1
0 0
0 3
3 9
5 8
2 1
1 0
0 33 6.51-8.50 0
0 1
2 5
8 4
9 24 25 34 14 2
0 0
0 120 8.51-11.50 0
0 0
4 5
9 1
1 12 24 34 8
8 1
0 0
107 11.51-14.50 0
0 0
0 3
1 2
1 0
11 21 3
2 3
0 0
47 14.51-20.50 1
0 0
0 1
2 1
0 1
4 B
0 0
0 0
1 19
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 1
0 2
6 14 20 12 14 47 71 106 29 15 5
0 1
342 STABILITY CLASS B
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 1
0 1
1 1
0 0
1 0
0 0
0 0
0 5
4.51-5.50 0
0 1
0 2
1 1
3 5
4 2
3 0
1 0
2 25 5.51-6.50 1
2 0
1 2
3 2
7 15 iB 10 9
1 0
1 1
73 6.51-8.50 0
1 0
5 5
3 1
2 13 14 11 15 1
1 0
0 72 9.51-11.50 0
0 1
0 6
2 0
2 2
2 6
6 1
0 0
0 29 11.51-14.50 0
0 0
0 1
0 0
0 1
1 3
1 0
0 0
0 7
14.51-20.50 0
0 0
0 0
0 0
0 1
0 0
1 0
0 0
0 2
>20.50 0
0 0
0 0
0 0
0 0
1 0
0 0
0 0
0 1
TOTAL 1
3 3
6 17 10 S
14 37 41 32 35 3
2 1
3 213 STABILITY CLASS C
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM
.76-1.50 0
0 1.51-2.50 0
0 2.51-3.50 0
0 3.51-4.50 0
0 4.51-5.50 1
2 5.51-6.50 0
0 6.51- 0.50 0
1 9.51-11.50 0
0 11.51-14.50 0
0 14.51-20.50 0
0
.20.50 0
1 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2 0
1 1
0 2
2 0
0 1
0 0
0 9
0 2
1 0
2 2
11 7
7 1
5 3
3 1
49 1
2 0
0 2
2 6
B 3
4 2
0 0
1 30 5
0 1
5 3
0 2
B 5
6 4
1 0
0 41 0
2 0
1 0
0 0
0 1
1 0
0 0
0 5
0 0
5 0
0 0
0 1
3 0
0 0
0 0
9 0
0 0
0 0
0 1
0 2
0 0
0 0
0 3
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1 TOTAL 1
4 6
8 7
7 a
4 22 26 21 12 11 4
3 2
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 7/01/2005 To 9/30/2005 3RD QRTR...
STABILITY CLASS D
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN NOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
SSW SW WSW WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
2 0
1 1
0 0
1 1
2 0
2 3
0 13 2.51-3.50 1
7 2
3 4
2 4
3 3
0 5
4 1
3 4
2 48 3.51-4.50 7
3 3
4 3
0 3
4 6
7 4
8 3
5 4
2 66 4.51-5.50 4
1 3
4 1
2 3
4 2
1 9
4 5
3 1
3 50 5.51-6.50 2
3 3
1 1
0 1
0 0
0 5
5 2
0 1
0 24 6.51-8.50 1
2 4
2 2
1 3
1 0
0 8
5 5
3 2
2 41 8.51-11.50 0
0 1
6 6
2 0
4 1
1 15 4
3 1
0 1
45 11.51-14.50 1
1 1
0 9
2 0
0 1
3 5
2 2
3 0
0 30 14.51-20.50 1
1 1
1 7
3 2
0 0
5 5
0 0
0 0
1 26
>20.50 0
0 1
0 1
1 0
0 0
0 2
0 0
0 0
0 5
TOTAL 17 19 19 23 34 14 16 16 13 18 59 34 21 20 15 11 348 STABILITY CLASS E
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
2 0
1 1
1 0
0 0
0 3
1 2
4 3
2 20 2.51-3.50 4
3 0
5 1
2 2
0 0
3 2
3 3
5 7
5 45 3.51-4.50 4
4 3
2 1
1 1
0 1
3 6
2 2
6 3
7 46 4.51-5.50 3
1 1
4 1
0 1
1 1
5 3
4 5
3 3
2 38 5.51-6.50 0
3 1
2 1
0 1
2 2
4 5
3 0
2 4
2 32 6.51-8.50 6
5 3
2 4
4 3
2 2
10 12 7
5 3
3 0
71 8.51-11.50 4
3 3
4 5
1 2
1 3
9 35 8
1 4
5 0
88 11.51-14.50 0
0 1
4 8
4 0
2 1
3 12 2
1 0
1 0
39 14.51-20.50 0
0 0
0 15 2
2 0
0 1
0 1
0 0
0 1
22
>20.50 0
0 0
0 1
0 0
0 0
0 0
0 0
0 0
0 1
TOTAL 21 21 12 24 38 15 12 8
10 38 78 31 19 27 29 19 402 STABILITY CLASS F
SPEED (MPH)
N NNE NE ENE E
Wm NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
1 0
0 1
1 0
0 0
0 0
0 3
1.51-2.50 5
1 1
0 0
0 1
0 0
1 2
0 2
1 2
4 20 2.51-3.50 11 2
1 0
0 0
1 1
3 0
8 4
7 5
8 11 62 3.51-4.50 11 3
2 1
2 3
0 0
0 2
11 9
6 5
8 8
71 4.51-5.50 11 6
1 1
0 1
1 0
1 4
6 6
5 4
1 4
52 5.51-6.50 3
2 2
1 0
1 0
0 0
4 6
6 4
5 2
6 42 6.51-8.50 2
1 3
1 2
0 0
1 3
12 14 8
3 3
3 0
56 8.51-11.50 0
0 1
2 0
1 0
0 0
7 18 5
1 1
2 2
40 11.51-14.50 0
0 0
0 0
0 0
1 0
1 0
0 0
0 0
0 2
14.51-20.50 1
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
'20.50 0
0 0
0 0
0 0
0 1
0 0
0 0
0 0
0 1
TOTAL 44 15 11 6
4 7
3 3
9 32 65 38 28 24 26 35 350 75 PVNGS ARERR 2005
ARIZONA PUBLIC SERVICE CO.
- PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 7/01/2005 TO 9/30/2005 3RD QRTR...
STABILITY CLASS G
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED IMPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
B 1
0 1
1.51-2.50 3
1 2
0 0
0 0
0 0
1 1
2 0
3 5
2 20 2.51-3.50 16 7
4 1
2 0
1 1
0 1
2 1
8 4
9 17 74 3.51-4.50 42 18 5
1 1
2 0
0 1
1 1
1 4
4 3
37 121 4.51-5.50 44 14 4
4 0
0 0
0 0
0 3
0 1
9 5
21 105 5.51-6.50 26 12 1
2 1
0 0
0 0
2 3
2 1
0 1
7 58 6.51-8.50 8
2 2
2 0
0 0
0 0
0 1
2 2
2 1
1 23 8.51-11.50 0
2 0
0 0
0 0
0 0
1 0
0 1
0 0
0 4
11.51-14.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
14.51-20.50 0
0 0
0 0
0 0
0 0
1 0
0 0
0 0
0 1
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 139 56 18 10 4
2 1
1 1
7 11 8
17 22 25 85 407 STABILITY CLASS ALL SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
1 0
0 1
1 0
0 0
0 1
0 4
1.51-2.50 8
4 3
3 1
2 2
0 0
3 7
5 4
10 13 8
73 2.51-3.50 32 19 7
9 7
4 8
5 6
4 17 12 19 17 28 35 229 3.51-4.50 64 28 14 10 8
8 6
4 10 16 22 20 17 20 18 54 319 4.51-5.50 63 24 10 15 5
4 9
10 21 23 31 19 22 23 13 33 325 5.51-6.50 32 22 9
9 5
4 9
14 32 41 40 31 10 8
9 17 292 6.51-8.50 17 12 19 14 19 21 14 15 44 69 85 57 22 13 9
3 432 8.51-11.50 4
5 6
18 22 16 3
8 18 44 109 32 1S 7
7 3
317 11.51-14.50 1
1 2
4 26 7
2 4
3 20 44 8
5 6
1 0
134 14.51-20.50 3
1 1
1 23 7
4 0
3 11 1S 2
0 0
0 3
74
>20.50 0
1 1
0 2
1 0
0 1
1 2
0 0
0 0
0 9
TOTAL 224 117 71 83 118 75 57 60 139 233 372 186 114 104 99 156 2208 TOTAL NUMBER OF OBSERVATIONS:
2208 TOTAL NUMBER OF VALID OBSERVATIONS:
2208 TOTAL NUMBER OF MISSING OBSERVATIONS:
0 PERCENT DATA RECOVERY FOR THIS PERIOD: 100.0 8 MEAN WIND SPEED FOR THIS PERIOD:
6.8 MPH TOTAL NUMBER OF OBSERVATIONS WITH BACKUP DATA:
0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A
B C
D S
F G
15.49 9.65 6.61 15.76 18.21 15.85 18.43 DISTRIBUTION OF WIND DIRECTION VS STABILITY N
NNE NE ENE E
WNW NW NNW CALM A
1 0
2 6
14 20 12 14 47 71 106 28 1S 5
0 1
0 B
1 3
3 6
17 10 5
14 37 41 32 35 3
2 1
3 0
C 1
4 6
8 7
7 8
4 22 26 21 12 11 4
3 2
0 D
17 18 19 23 34 14 16 16 13 18 59 34 21 20 1S 11 0
E 21 21 12 24 38 15 12 8
10 38 78 31 19 27 29 19 0
F 44 15 11 6
4 7
3 3
9 32 65 38 28 24 26 35 0
G 139 56 18 10 4
2 1
1 1
7 11 8
17 22 25 85 0
TOTAL 224 117 71 83 118 75 57 60 139 233 372 186 114 104 99 156 0
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 10/01/2005 TO 12/31/2005
^
4TH QRTR STABILITY CLASS A
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 PEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
a 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4.51-5.50 0
0 0
0 0
0 0
0 1
1 0
0 0
0 0
0 2
5.51-6.50 0
0 0
0 0
0 0
2 2
0 0
0 0
1 0
0 5
6.51-8.50 0
0 0
0 0
0 1
0 1
1 0
0 0
0 0
0 3
8.51-11.50 0
0 0
0 3
2 1
0 1
1 2
2 0
0 0
0 12 11.51-14.50 0
1 0
0 3
0 0
0 0
1 5
3 4
1 0
0 18 14.51-20.50 0
1 3
1 4
0 0
0 0
1 2
0 2
2 2
2 20
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 0
2 3
1 10 2
2 2
5 5
9 5
6 4
2 2
60 STABILITY CLASS B
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW 70TAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
1 0
0 0
0 0
0 0
0 1
3.51-4.50 0
1 0
0 0
0 0
1 0
1 0
0 0
0 0
0 3
4.51-5.50 0
0 0
0 0
1 1
2 2
1 0
0 0
0 0
0 7
5.51-6.50 0
0 0
0 0
1 0
1 3
3 0
1 2
0 0
0 11 6.51-8.50 0
0 1
4 1
1 1
1 1
0 2
4 2
0 0
0 18 8.51-11.50 0
1 0
1 6
1 0
1 0
3 2
2 1
1 0
0 19 11.51-14.50 0
0 0
0 3
0 0
0 0
1 2
1 0
0 1
1 9
14.51-20.50 0
0 0
0 1
0 0
0 0
0 2
0 0
0 1
0 4
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 0
2 1
5 11 4
2 7
6 9
8 8
5 1
2 1
72 STABILITY CLASS C
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 1
0 0
1 0
0 0
0 0
0 0
0 0
0 0
0 2
3.51-4.50 0
1 1
2 1
3 2
1 5
1 0
1 0
3 0
0 21 4.51-5.50 2
0 1
2 2
1 2
4 3
7 3
5 3
0 1
0 36 5.51-6.50 3
0 2
6 1
3 0
2 2
3 3
4 0
0 0
1 30 6.51-8.50 1
0 4
7 0
0 0
2 1
0 6
3 1
1 0
0 26 8.51-11.50 0
0 1
5 1
0 0
0 0
1 1
0 1
3 0
1 14 11.51-14.50 1
0 0
0 2
0 0
0 0
0 1
0 0
0 1
0 5
14.51-20.50 0
1 0
1 1
0 0
0 0
0 0
0 0
2 0
0 5
'20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 8
2 9
24 8
7 4
9 11 12 14 13 5
9 2
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 10/01/2005 TO 12831/2005 4TH ORTR...
STABILITY CLASS 0
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW BNW TOTAL CALM 0
.76-1.50 0
0 0
1 0
0 0
0 0
0 0
0 0
0 0
0 1
1.51-2.50 3
2 4
1 5
1 2
4 4
4 5
3 1
3 2
3 47 2.51-3.50 10 2
6 11 5
9 10 8
11 7
6 5
5 12 7
4 liB 3.51-4.50 2
9 12 11 7
3 5
1 10 6
15 B
3 4
4 2
102 4.51-5.50 1
2 9
15 6
2 2
2 9
5 4
6 5
2 1
2 73 5.51-6.50 0
2 4
6 0
1 2
0 6
2 7
1 2
1 1
1 36 6.51-8.50 1
1 4
12 2
2 1
1 0
0 3
3 2
1 1
2 36 8.51-11.50 1
0 1
3 5
0 0
0 2
1 2
0 2
3 0
0 20 11.51-14.50 0
0 0
1 3
0 0
0 1
1 1
2 0
0 1
0 10 14.51-20.50 0
0 0
0 1
1 0
0 1
0 0
0 0
2 0
0 5
'20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 18 18 40 61 34 19 22 16 44 26 43 28 20 28 17 14 448 STABILITY CLASS E
SPEED (MPH)
N NNE NE ENE E
SSW W
SMEW W
WNW NW NNW TOTAL CALM 0
.76-1.50 1
0 0
1 0
0 0
0 1
0 0
0 1
0 0
0 4
1.51-2.50 2
6 2
0 1
1 1
1 1
0 2
1 1
4 3
3 29 2.51-3.50 4
0 3
1 0
1 2
0 1
3 1
0 3
2 4
3 28 3.51-4.50 4
2 4
1 0
0 3
1 0
5 1
2 2
2 2
2 31 4.51-5.50 2
1 0
0 0
0 1
2 0
4 4
3 2
0 1
2 22 5.51-6.50 0
3 2
0 0
0 0
0 1
1 4
2 1
1 2
0 17 6.51-8.50 0
0 0
2 0
2 0
1 1
2 5
4 4
0 2
0 23 8.51-11.50 0
0 0
2 3
0 0
0 0
2 8
4 1
8 4
0 32 11.51-14.50 0
1 0
0 1
1 0
0 0
3 4
1 2
5 6
3 27 14.51-20.50 0
0 0
0 0
0 0
0 0
1 0
0 1
2 1
0 5
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 13 13 11 7
5 5
7 5
5 21 29 17 18 24 25 13 218 STABILITY CLASS P
SPEED (ttPH)
N NNE NE ENE E
WNW NW NMW TOTAL CALM
.76-1.50 0
0 0
0 0
1.51-2.50 7
0 1
3 0
2.51-3.50 10 6
2 3
1 3.51-4.50 7
8 4
0 2
4.51-5.50 5
2 3
2 3
5.51-6.50 1
3 1
0 1
6.51-8.50 0
2 4
0 1
8.51-11.50 1
0 0
0 0
11.51-14.50 1
0 0
0 0
14.51-20.50 0
0 0
0 0
'20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
2 0
0 2
1 0
1 3
2 1
0 1
2 0
1 0
0 2
0 0
0 0
7 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
2 0
4 2
3 6
1 4
3 4
1 2
2 3
3 2
5 4
0 2
0 0
0 0
0 0
0 0
0 0
0 1
0 0
2 3
2 4
26 6
2 6
50 3
7 5
51 1
11 9
49 2
8 2
29 4
4 4
37 1
6 4
14 0
0 0
1 0
0 0
0 0
0 0
0 TOTAL 32 21 15 8
8 4
4 2
2 14 13 18 23 21 40 34 259 78 PVNGS ARERR 2005
ARIZONA PUBLIC SERVICE CO.
- PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 10/01/2005 TO 12f31/2005
^
4TH QRTR...
STABILITY CLASS a
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WmN NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 1
0 0
1 0
0 2
1.51-2.50 13 9
6 1
3 0
2 1
3 3
2 3
2 3
10 17 78 2.51-3.50 50 27 10 7
1 3
2 1
4 2
3 6
9 5
44 64 238 3.51-4.50 116 52 9
5 0
4 1
2 0
0 0
5 2
9 26 61 292 4.51-5.50 BE 54 10 0
1 0
0 0
0 3
2 2
4 5
9 44 222 5.51-6.50 39 20 12 0
0 0
0 0
0 1
1 1
1 1
5 16 105 6.51-8.50 15 11 3
1 0
0 0
0 0
0 1
0 0
1 3
13 48 8.51-11.50 11 5
2 0
0 0
0 0
0 0
0 0
0 0
0 4
22 11.51-14.50 1
0 0
0 0
0 0
0 0
0 0
0 1
0 0
2 4
14.51-20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 333 186 52 14 5
7 5
4 7
9 10 17 19 25 97 221 1011 STABILITY CLASS ALL SPEED (MPH)
N NNE NE ENE E
SSW EW WSW N
WNW NW NNW TOTAL CALM 0
.76-1.50 1
0 0
2 0
0 0
0 1
0 1
0 2
2 0
0 9
1.51-2.50 25 17 13 5
9 2
5 6
8 7
11 7
8 13 17 27 180 2.51-3.50 75 35 21 23 7
13 15 12 16 12 12 14 23 25 57 77 437 3.51-4.50 129 73 30 19 10 12 12 6
16 16 17 20 10 21 39 70 500 4.51-5.50 98 59 23 19 12 6
7 10 16 23 17 17 16 8
23 57 411 5.51-6.50 43 36 21 12 2
5 3
5 14 12 17 12 9
6 16 20 233 6.51-8.50 17 14 16 26 4
5 3
5 4
10 19 19 13 7
10 19 191 8.51-11.50 13 6
4 11 18 3
1 1
3 8
15 10 S
16 10 9
133 11.51-14.50 3
2 0
1 12 1
0 0
1 6
13 7
7 6
9 6
74 14.51-20.50 0
2 3
2 7
1 0
0 1
2 4
0 3
8 4
2 39
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 404 244 131 120 81 48 46 45 80 96 126 106 96 112 185 287 2207 TOTAL NUMBER OF OBSERVATIONS:
2208 TOTAL NUMBER OF VALID OBSERVATIONS:
2207 TOTAL NUMBER OF MISSING OBSERVATIONS:
1 PERCENT DATA RECOVERY FOR THIS PERIOD: 100.0 %
MEAN WIND SPEED FOR THIS PERIOD:
5.2 MPH TOTAL NUMBER OF OBSERVATIONS WITH BACKUP DATA:
0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A
B C
D E
F G
2.72 3.26 6.30 20.30 9.88 11.74 45.81 DISTRIBUTION OF WIND DIRECTION VS STABILITY N
NNE NE ENE E ESE SE 05E S
MNW EN NNW CALM A
0 2
3 1
10 2
2 2
5 S
9 5
6 4
2 2
0 B
0 2
1 5
11 4
2 7
6 9
8 8
5 1
2 1
0 C
8 2
9 24 8
7 4
9 11 12 14 13 5
9 2
2 0
D 18 18 40 61 34 19 22 16 44 26 43 28 20 28 17 14 0
E 13 13 11 7
5 5
7 S
5 21 29 17 18 24 25 13 0
F 32 21 15 8
8 4
4 2
2 14 13 18 23 21 40 34 0
333 186 52 14 5
7 5
4 7
9 10 17 19 25 97 221 0
TOTAL 404 244 131 120 81 48 46 45 80 96 126 106 96 112 185 287 0
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR TNE PERIOD 7/01/2005 TO 12/31/2005 2ND SEMI...
STABILITY CLASS A
STABILITY BASED ON:
DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESNOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 1
0 0
0 1
4.51-5.50 0
0 0
0 0
0 1
0 2
3 1
1 1
0 0
0 9
5.51-6.50 0
0 1
0 0
0 3
5 11 5
8 2
1 2
0 0
38 6.51-8.50 0
0 1
2 5
8 5
9 25 26 34 14 2
0 0
0 131 8.51-11.50 0
0 0
4 8
11 2
1 13 25 36 10 8
1 0
0 119 11.51-14.50 0
1 0
0 6
1 2
1 0
12 26 6
6 4
0 0
65 14.51-20.50 1
1 3
1 5
2 1
0 1
5 10 0
2 2
2 3
39
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 1
2 5
7 24 22 14 16 52 76 115 33 21 9
2 3
402 STABILITY CLASS B
SPEED (MPH)
N NNE NE ENE E
WNW NW NNH TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
1 0
0 0
0 0
0 0
0 1
3.51-4.50 0
1 1
0 1
1 1
1 0
2 0
0 0
0 0
0 8
4.51-5.50 0
0 1
0 2
2 2
5 7
5 2
3 0
1 0
2 32 5.51-6.50 1
2 0
1 2
4 2
8 18 21 10 10 3
0 1
1 84 6.51-8.50 0
1 1
9 6
4 2
3 14 14 13 19 3
1 0
0 90 8.51-11.50 0
1 1
1 12 3
0 3
2 5
8 8
2 1
0 0
47 lI.51-14.50 0
0 0
0 4
0 0
0 1
2 5
2 0
0 1
1 16 14.51-20.50 0
0 0
0 1
0 0
0 1
0 2
1 0
0 1
0 6
>20.50 0
0 0
0 0
0 0
0 0
1 0
0 0
0 0
0 1
TOTAL 1
5 4
11 28 14 7
21 43 50 40 43 8
3 3
4 285 STABILITY CLASS C
SPEED (MPH)
N NNE NE ENE E
55W SW WIN W
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 1
0 0
1 0
0 0
0 0
0 0
0 0
0 0
0 2
3.51-4.50 0
1 1
4 1
4 3
1 7
3 0
1 1
3 0
0 30 4.51-5.50 3
2 1
4 3
1 4
6 14 14 10 6
B 3
4 1
84 5.51-6.50 3
0 3
8 1
3 2
4 8
11 6
6 1
0 0
2 60 6.51-8.50 1
1 9
7 1
5 3
2 3
8 11 9
5 2
0 0
67 8.51-11.50 0
0 1
7 1
1 0
0 0
1 2
1 1
3 0
1 19 11.51-14.50 1
0 0
0 7
0 0
0 0
1 4
0 0
0 1
0 14 14.51-20.50 0
1 0
1 1
0 0
0 1
0 2
0 0
2 0
0 8
>20.50 0
1 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
TOTAL 9
6 15 32 15 14 12 13 33 38 35 25 16 13 5
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 7/01/2005 TO 12/31/2005 2ND SEMI...
STABILITY CLASS D
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
1 0
0 0
0 0
0 0
0 0
0 0
0 1
1.51-2.50 3
2 4
3 5
2 3
4 4
5 6
5 1
5 5
3 60 2.51-3.50 11 9
8 14 9
11 14 11 14 7
11 9
6 15 11 6
166 3.51-4.50 9
12 15 15 10 3
8 5
16 13 19 16 6
9 e
4 168 4.51-5.50 5
3 12 19 7
4 5
6 11 6
13 10 10 5
2 5
123 5.51-6.50 2
5 7
7 1
1 3
0 6
2 12 6
4 1
2 1
60 6.51-8.50 2
3 8
14-4 3
4 2
0 0
11 8
7 4
3 4
77 8.51-11.50 1
0 2
9 11 2
0 4
3 2
17 4
5 4
0 1
65 11.51-14.50 1
1 1
1 12 2
0 0
2 4
6 4
2 3
1 0
40 14.51-20.50 1
1 1
1 B
4 1
0 1
5 5
0 0
2 0
1 31
.20.50 0
0 1
0 1
1 0
0 0
0 2
0 0
0 0
0 5
TOTAL 35 36 59 84 68 33 38 32 57 44 102 62 41 48 32 25 796 STABILITY CLASS E
SPEED (MPH)
N NNE NE ENE B
WNW NW NNW TOTAL CALM 0
.76-1.50 1
0 0
1 0
0 0
0 1
0 0
0 1
0 0
0 4
1.51-2.50 2
8 2
1 2
2 1
1 1
0 5
2 3
8 6
5 49 2.51-3.50 8
3 3
6 1
3 4
0 1
6 3
3 6
7 11 8
73 3.51-4.50 8
6 7
3 1
1 4
1 1
8 7
4 4
8 5
9 77 4.51-5.50 5
2 1
4 1
0 2
3 1
9 7
7 7
3 4
4 60 5.51-6.50 0
6 3
2 1
0 1
2 3
5 9
5 1
3 6
2 49 6.51-8.50 6
5 3
4 4
6 3
3 3
12 17 11 9
3 5
0 94 8.51-11.50 4
3 3
6 B
1 2
1 3
11 43 12 2
12 9
0 120 11.51-14.50 0
1 1
4 9
5 0
2 1
6 16 3
3 5
7 3
66 14.51-20.50 0
0 0
0 1S 2
2 0
0 2
0 1
1 2
1 1
27
'20.50 0
0 0
0 1
0 0
0 0
0 0
0 0
0 0
0 1
TOTAL 34 34 23 31 43 20 19 13 15 59 107 48 37 51 54 32 620 STABILITY CLASS F
SPEED (MPH)
N NNE NE ENE e
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
1 0
0 1
1 0
0 1
1 0
0 S
1.51-2.50 12 1
2 3
0 0
1 0
0 1
4 0
6 4
4 8
46 2.51-3.50 21 9
3 3
1 0
2 3
3 0
10 7
13 11 10 17 112 3.51-4.50 18 11 6
1 4
5 1
0 1
5 12 13 9
a 1S 13 122 4.51-5.50 16 8
4 3
3 3
2 0
2 6
10 7
7 5
12 13 101 5.51-6.50 4
5 3
1 1
1 1
0 0
6 8
9 7
7 10 8
71 6.51-8.50 2
3 7
1 3
0 0
1 3
19 16 13 7
7 7
4 93 8.51-11.50 1
0 1
2 0
1 0
0 0
7 18 7
1 2
8 6
54 11.51-14.50 1
0 0
0 0
0 0
1 0
1 0
0 0
0 0
0 3
14.51-20.50 1
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
>20.50 0
0 0
0 0
0 0
0 1
0 0
0 0
0 0
0 1
TOTAL 76 36 26 14 12 11 7
5 11 46 78 56 51 45 66 69 609 81 PVNGS ARERR 2005
ARIZONA PUBLIC SERVICE CO.
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 7/01/2005 TO 12/31/2005 2ND SEMI...
STABILITY CLASS G
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESNOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
57iW SW WSW N
WNW NW NNW TOTAL CALM
.76-1.50 0
0 0
1.51-2.50 16 10 B
2.51-3.50 66 34 14 3.51-4.50 158 70 14 4.51-5.50 132 68 14 5.51-6.50 65 40 13 6.51-8.50 23 13 5
8.51-11.50 11 7
2 11.51-14.50 1
0 0
14.51-20.50 0
0 0
>20.50 0
0 0
0 1
B 6
4 2
3 0
0 0
0 30 3
3 1
1 1
0 0
0 0
0 0
3 6
0 0
0 0
0 0
0 0
2 3
1 0
0 0
0 0
0 0
0 1
2 2
0 0
0 0
0 0
0 0
3 4
1 0
0 0
0 0
0 0
1 3
3 0
1 0
1 0
1 3
1 2
0 0
0 0
0 0
0 1
1 0
3 5
2 6
15 19 98 7
17 9
53 81 312 6
6 13 29 98 413 2
5 14 14 65 327 3
2 1
6 23 163 2
2 3
4 14 71 0
1 0
0 4
26 0
1 0
0 2
4 0
0 0
0 0
1 0
0 0
0 0
0 TOTAL 472 242 70 24 9
9 6
5 8
16 21 25 36 47 122 306 1418 STABILITY CLASS ALL SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 1
0 0
2 0
1 0
0 2
1 1
0 2
2 1
0 13 1.51-2.50 33 21 16 8
10 4
7 6
8 10 18 12 12 23 30 35 253 2.51-3.50 107 54 28 32 14 17 23 17 22 16 29 26 42 42 85 112 666 3.51-4.50 193 101 44 29 18 20 18 10 26 32 39 40 27 41 S7 124 819 4.51-5.50 161 83 33 34 17 10 16 20 37 46 48 36 38 31 36 90 736 5.51-6.50 75 58 30 21 7
9 12 19 46 53 57 43 19 14 25 37 525 6.51-8.50 34 26 34 40 23 26 17 20 48 79 104 76 35 20 19 22 623 8.51-11.50 17 11 10 29 40 19 4
9 21 52 124 42 20 23 17 12 450 11.51-14.50 4
3 2
5 38 8
2 4
4 26 57 15 12 12 10 6
208 14.51-20.50 3
3 4
3 30 8
4 0
4 13 19 2
3 8
4 5
113
>20.50 0
1 1
0 2
1 0
0 1
1 2
0 0
0 0
0 9
TOTAL 628 361 202 203 199 123 103 105 219 329 498 292 210 216 284 443 4415 TOTAL NUMBER OF OBSERVATIONS:
4416 TOTAL NUMBER OF VALID OBSERVATIONS:
4415 TOTAL NUMBER OF MISSING OBSERVATIONS:
1 PERCENT DATA RECOVERY FOR THIS PERIOD: 100.0 I MEAN WIND SPEED FOR THIS PERIOD:
6.0 MPH TOTAL NUMBER OF OBSERVATIONS WITH BACKUP DATA:
0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A
B C
D E
F G
9.11 6.46 6.46 18.03 14.04 13.79 32.12 DISTRIBUTION OF WIND DIRECTION VS STABILITY E
NNE NE ENE W
WNW NW NNW CALM A
1 2
5 7
24 22 14 16 52 76 115 33 21 9
2 3
B 1
5 4
11 28 14 7
21 43 50 40 43 8
3 3
4 C
9 6
15 32 15 14 12 13 33 38 35 25 16 13 5
4 D
35 36 59 84 68 33 38 32 57 44 102 62 41 48 32 25 E
34 34 23 31 43 20 19 13 15 59 107 48 37 51 54 32 F
76 36 26 14 12 11 7
5 11 46 78 56 51 45 66 69 G
472 242 70 24 9
9 6
5 8
16 21 25 36 47 122 306 TOTAL 628 361 202 203 199 123 103 105 219 329 498 292 210 216 284 443 82 PVNGS ARERR 0
0 0
0 0
0 0
0 2005
ARIZONA PUBLIC SERVICE CO.
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/01/2005 TO 12/31/2005 ANNUAL STABILITY CLASS A
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OP WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (I4PHN N
NNE NE ENE B
ESE SE sse s
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
3.51-4.50 0
0 0
0 0
0 0
0 0
0 0
0 1
0 0
0 1
4.51-5.50 0
0 0
0 0
0 2
1 4
4 1
1 1
0 1
0 15 5.51-6.50 0
0 1
1 0
2 8
11 20 9
9 2
3 2
0 0
68 6.51-8.50 0
0 1
2 6
10 8
15 44 44 56 20 4
0 0
0 210 8.51-11.50 1
0 0
4 a
11 2
6 22 68 83 31 22 2
2 4
266 11.51-14.50 1
1 1
0 7
1 2
2 5
31 59 12 9
12 6
6 155 14.51-20.50 1
2 4
2 5
2 1
0 3
21 43 15 5
8 6
9 127
>20.50 0
0 0
0 1
0 0
0 0
1 4
1 0
0 0
0 7
TOTAL 3
3 7
9 27 26 23 35 98 178 255 82 45 24 15 19 849 STABILITY CLASS B
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 0
0 0
0 0
0 0
1 0
0 0
0 0
0 0
0 1
3.51-4.50 0
1 1
0 1
2 2
1 1
2 0
0 1
0 0
0 12 4.51-5.50 0
1 1
0 3
4 5
7 11 6
3 6
4 2
0 2
55 5.51-6.50 1
2 0
1 5
6 8
18 30 27 14 15 3
0 1
3 134 6.51-8.50 1
1 2
9 7
7 7
8 22 19 20 27 8
2 2
0 142 8.51-11.50 2
2 2
1 13 7
0 4
3 14 24 19 7
2 1
1 101 11.51-14.50 0
1 0
1 5
0 0
0 1
4 13 6
0 0
1 3
35 14.51-20.50 1
0 0
2 2
0 0
0 1
0 5
3 0
1 1
1 17
>20.50 0
0 0
0 0
0 0
0 0
2 0
0 0
0 0
0 2
TOTAL 5
8 6
14 36 26 22 39 69 74 79 75 23 7
6 10 499 STABILITY CLASS C
SPEEW (YPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1.51-2.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2.51-3.50 1
0 0
1 0
0 1
0 0
0 0
0 1
0 0
0 4
3.51-4.50 1
2 1
5 3
6 7
5 9
5 1
1 1
3 0
0 50 4.51-5.50 3
3 1
5 7
8 8
15 20 17 14 7
8 3
6 1
126 5.51-6.50 4
3 4
8 5
6 10 11 13 14 9
13 4
1 1
2 108 6.51-8.50 3
4 10 7
4 6
3 4
7 14 19 16 8
4 0
2 111 8.51-11.50 0
1 2
10 3
3 0
0 1
3 14 4
2 5
0 3
50 11.51-14.50 1
0 0
0 7
0 0
0 0
1 6
1 1
5 3
0 25 14.51-20.50 1
1 0
5 1
0 0
0 1
0 4
1 0
5 0
0 19
>20.50 0
1 0
1 0
0 0
0 0
0 0
0 0
0 0
0 2
TOTAL 14 15 18 42 30 29 29 35 51 54 67 43 24 26 10 8
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/01/2005 TO 12/31/2005 ANNUAL STABILITY CLASS D
STABILITY EASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREOUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
1 0
0 0
0 0
0 0
0 0
0 1
0 2
1.51-2.50 3
2 6
7 6
3 6
5 4
9 8
6 4
7 6
7 89 2.51-3.50 14 16 15 16 15 19 22 20 18 13 29 17 24 24 22 11 295 3.51-4.50 21 19 22 19 14 10 15 12 30 26 36 29 17 18 16 16 320 4.51-5.50 11 15 20 21 11 8
11 17 14 14 27 20 18 10 6
11 234 5.51-6.50 5
13 10 13 2
3 9
5 16 13 23 13 9
4 5
4 147 6.51-8.50 8
5 19 21 8
11 10 7
5 10 31 22 11 5
6 6
185 8.51-11.50 1
1 5
12 18 1S 5
5 6
7 38 19 10 7
5 1
155 11.51-14.50 2
1 4
6 22 5
0 0
2 7
19 14 2
7 2
0 93 14.51-20.50 1
1 2
7 19 S
1 0
1 9
19 2
2 4
4 2
79
'20.50 0
0 1
2 1
1 0
0 0
1 5
1 0
0 0
0 12 TOTAL 66 73 104 125 116 80 79 71 96 109 235 143 97 86 73 58 1611 STABILITY CLASS E
SPEED (MPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 1
0 0
1 0
1 0
0 1
0 0
0 1
0 1
0 6
1.51-2.50 8
9 3
4 3
2 3
1 1
0 8
3 9
13 13 9
89 2.51-3.50 25 8
4 9
3 4
4 1
5 8
10 6
13 23 25 18 166 3.51-4.50 17 11 10 10 2
3 11 2
3 9
11 14 10 12 21 26 172 4.51-5.50 13 8
3 5
5 0
7 4
8 17 14 12 12 6
9 12 135 5.51-6.50 7
10 11 3
3 0
2 6
10 17 19 14 3
4 6
5 120 6.51-8.50 11 13 11 6
6 8
6 8
10 28 54 31 17 8
11 1
227 8.51-11.50 10 7
8 14 14 8
10 7
4 30 81 38 13 14 16 1
275 11.51-14.50 1
1 2
11 26 10 2
5 2
23 36 9
12 7
12 4
163 14.51-20.50 0
0 1
0 29 5
3 0
0 9
6 4
5 6
5 1
74
>20.50 0
0 0
0 1
0 0
0 0
0 0
0 0
0 0
0 1
TOTAL 93 67 53 63 92 41 46 34 44 141 239 131 95 93 119 77 1428 STABILITY CLASS F
SPEED (MPH)
N NNE NE ENE E
WNW MW NNW TOTAL CALM
.76-1.50 0
0 0
0 1.51-2.50 19 3
2 5
2.51-3.50 33 13 8
10 3.51-4.50 33 14 8
2 4.51-5.50 27 10 8
3 5.51-6.50 16 10 3
1 6.51-8.50 8
a 12 2
8.51-11.50 5
1 1
6 11.51-14.50 3
1 1
0 14.51-20.50 1
0 0
0
'20.50 0
0 0
0 0
4 S
7 3
1 4
1 0
0 0
1 0
1 S
3 1
0 1
0 0
0 0
1 222 1
0 1
0 0
0I 3
0 1
2 1
0 1
0 0
0 1
1 0
0 1
1 0
0 5
1 4
4 1
10 10 8
16 B8 7
7 14 13 22 35 27 35 238 3
14 25 22 18 17 36 45 251 5
10 25 16 16 9
25 29 192 7
16 31 20 10 9
17 16 161 5
35 49 33 19 12 16 5
209 1
25 so 33 4
6 14 7
156 0
3 3
0 1
0 2
1 16 0
0 0
0 0
0 0
1 2
1 0
0 0
0 0
0 0
1 TOTAL 145 60 43 29 25 12 12 8
31 115 201 138 101 99 145 155 1319 84 PVNGS ARERR 2005
ARIZONA PUBLIC SERVICE CO. -
PALO VERDE NUCLEAR GENERATING STATION JOINT FREQUENCY DISTRIBUTION FOR THE PERIOD 1/01/2005 TO 12/31/2005 ANNUAL STABILITY CLASS 0
STABILITY BASED ON: DELTA T BETWEEN 200.0 AND 35.0 FEET WIND MEASURED AT:
35.0 FEET WIND THRESHOLD AT:
.75 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 PEET SPEED (NPH)
N NNE NE ENE E
WNW NW NNW TOTAL CALM 0
.76-1.50 0
0 0
0 0
0 0
0 0
0 1
0 0
1 1
0 3
1.51-2.50 24 16 10 3
5 3
3 1
5 4
6 9
5 12 24 28 158 2.51-3.50 125 57 18 11 7
8 6
6 6
4 10 11 29 21 84 132 535 3.51-4.50 260 99 22 12 1
8 3
5 1
3 7
9 14 20 62 184 710 4.51-5.50 224 99 22 5
4 0
0 3
2 7
7 6
9 22 32 111 553 5.51-6.50 123 59 20 2
3 0
0 0
1 4
8 5
3 6
12 47 293 6.51-8.50 70 35 8
3 0
0 1
0 0
3 18 4
4 4
4 35 189 8.51-11.50 33 43 5
0 0
0 0
0 0
8 4
0 1
0 0
12 106 11.51-14.50 1
2 0
0 0
0 0
0 0
0 0
0 1
0 0
5 9
14.51-20.50 0
0 0
0 0
0 0
0 0
1 0
0 0
0 0
0 1
>20.50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
TOTAL 860 410 105 36 20 19 13 15 15 34 61 44 66 86 219 554 2557 STABILITY CLASS ALL SPEED (MPH)
N NNE NE ENS E
WNNW NW NNW TOTAL CALM 0
.76-1.50 1
0 0
2 0
2 0
0 2
1 1
0 2
2 3
0 16 1.51-2.50 54 30 21 19 18 8
13 7
11 17 26 19 28 42 S1 60 424 2.51-3.50 198 94 45 47 30 32 38 31 36 32 63 47 89 103 158 196 1239 3.51-4.50 332 146 64 48 28 34 40 25 47 59 80 75 62 70 135 271 1516 4.51-5.50 278 136 55 39 33 23 35 48 64 75 91 68 68 52 79 166 1310 5.51-6.50 156 97 49 29 19 18 38 53 97 100 113 82 35 26 42 77 1031 6.51-8.50 101 66 63 50 35 42 33 43 93 153 247 153 71 35 39 49 1273 8.51-11.50 52 55 23 47 57 45 18 22 37 155 294 143 58 36 38 29 1109 11.51-14.50 9
7 8
18 67 16 4
8 10 69 136 42 26 31 26 19 496 14.51-20.50 5
4 7
16 56 12 5
0 6
40 77 25 12 24 16 14 319
>20.50 0
1 1
3 3
1 0
0 1
4 9
2 0
0 0
0 25 TOTAL 1186 636 336 318 346 233 224 237 404 705 1137 656 451 421 587 881 8758 TOTAL NUMBER OF OBSERVATIONS:
8760 TOTAL NUMBER OF VALID OBSERVATIONS:
8758 TOTAL NUMBER OF MISSING OBSERVATIONS:
2 PERCENT DATA RECOVERY FOR THIS PERIOD: 100.0 0 MEAN WIND SPEED FOR THIS PERIOD:
6.4 MPH TOTAL NUMBER OF OBSERVATIONS WITH BACKUP DATA:
0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A
B C
D a
F a
9.69 5.70 5.65 18.39 16.31 15.06 29.20 DISTRIBUTION OF WIND DIRECTION VS STABILITY N
NNE NE ENE E
SE S
E SSE S
WNW NW NNW CALM A
3 3
7 9
27 26 23 35 98 178 255 82 45 24 15 19 0
8 5
8 6
14 36 26 22 39 69 74 79 75 23 7
6 10 0
C 14 15 18 42 30 29 29 35 51 54 67 43 24 26 10 8
0 D
66 73 104 125 116 80 79 71 96 109 235 143 97 66 73 58 0
3 93 67 53 63 92 41 46 34 44 141 239 131 95 93 119 77 0
F 145 60 43 29 25 12 12 8
31 115 201 138 101 99 145 155 0
G 860 410 105 36 20 19 13 15 15 34 61 44 66 86 239 554 0
TOTAL 1186 636 336 318 346 233 224 237 404 705 1137 656 451 421 587 881 0
APPENDIX C DOSE CALCULATIONS 86 PVNGS ARERR 2005
GASEOUS EFFLUENT DOSE CALCULATIONS Doses to the maximum individual and the surrounding population resulting from the release of radioactive material in gaseous effluents from the Palo Verde Nuclear Generating Station were cal-culated using the GASPAR computer program. The radionuclides considered in the dose calcula-tions were Tritium, lodine-131, lodine-132, lodine-133, lodine-135, all noble gases, and particulates having a half-life greater than eight days and for which dose factors are contained in NUREG-01 72. Locations selected for individual dose calculations included for each sector, the site boundary, and within five miles, if present, the nearest residence, the nearest garden, and the nearest milk animal. GASPAR implements the radiological dose models of Regulatory Guide 1.109 to determine the radiation exposure to man from four principal atmospheric exposure pathways:
plume, ground deposition, inhalation, and ingestion. Doses to the maximum individual and the population were calculated as a function of age group and pathway for significant body organs.
Table 43 presents the doses on a quarterly, semiannual and annual basis for the Energy Informa-tion Center. An occupancy factor of 1.0 (implying continuous occupancy over the entire year) was considered for the Energy Information Center and the exposure pathways considered to calculate its doses were plume, ground deposition, and inhalation.
Table 44 presents the population dose.
Table 45 summarizes the individual doses and compares the result to PVNGS ODCM Require-ment limits. The site boundary and residence locations for which data are presented represent the highest annual doses.
Based on results obtained by placing TLDs on the site boundary in each sector, the net dose for this reporting period, from direct-radiation, (plume and ground deposition) from all three units was indistinguishable from preoperational values of 8 - 14 gR/hr (17 - 30 mR/Std Qtr).
There were no liquid effluents associated with the operation of this facility.
Dose Calculation Models The GASPAR computer code was used to evaluate the radiological consequences of the routine release of gaseous effluents. GASPAR Implements the dose calculational methodologies of Regu-latory Guide 1.109, Revision 1.
Source terms for each quarter are combined with station-specific demographic data and each quarter's atmospheric diffusion estimates for gaseous dose calculations.
Atmospheric diffusion estimates are generated by the XOQDOQ computer code using onsite meteorological data as input. Additional input to GASPAR includes the following site-specific data:
0 to 5 mile nearest residence, milk animal and garden In each of the 16 compass sectors, based on the 2005 Land Use Census.
0 to 10 mile population distribution based on the State of Arizona - Madcopa County, Offsite Emergency Response Plan for Palo Verde Nuclear Generating Station, December 2005, Survey Information.
The 10 to 50 mile population distribution from the PVNGS UFSAR, Figure 2.1-11.
The population distribution of metropolitan Phoenix greater than 50 miles from PVNGS, based on the 1980 federal census results, is conservatively included in the 40 to 50 mile sectors (NE=123; ENE=140,097; E=621,130; ESE=8,392).
Absolute humidity of 6.0 g/m3 from the PVNGS UFSAR, Table 2.3-16.
The fraction of the year that vegetables are grown (0.667) from the PVNGS ER-OL, Section 2.1.3.4, Table 2.1-8.
The fraction of daily feed derived from pasture while on pasture (0.35) and length of grazing season for milk animals beyond 5 miles (0.75) from the PVNGS ER-OL, Section 2.1.3.4.3.
The fraction of daily feed derived from pasture while on pasture (0.05) and length of grazing season for meat animals (0.25) from the PVNGS ER-OL, Section 2.1.3.4.4.
There were three (3) sectors containing milk animal (goat or cow) locations within five (5) miles. For calculational purposes these milk animals are assumed to be fed 100% on pasture grass during the year.
Other values used for input to GASPAR are default values from Regulatory Guide 1.109, Revision 1.
Table 43:
Doses To Special Locations For 2005 ENERGY INFORMATION CENTER LOCATED ONSITE 0.45 MILE S FROM UNIT 1, 0.29 MILE SSE FROM UNIT 2 AND 0.20 MILE ESE FROM UNIT 3 (MREM)
T.BODY 1ST QUARTER ADULT 6.93E-01 TEEN 6.99E-01 CHILD 6.18E-01 INFANT 3.56E-01 2ND QUARTER ADULT 1.95E-01 TEEN 1.96E-01 CHILD 1.73E-01 INFANT 1.OOE-01 1ST SEMI-ANNUAL ADULT 8.87E-01 TEEN 8.94E-01 CHILD 7.91E-01 INFANT 4.56E-01 3RD QUARTER ADULT 2.67E-01 TEEN 2.69E-01 CHILD 2.39E-01 INFANT 1.39E-01 4TH QUARTER ADULT 4.73E-01 TEEN 4.76E-01 CHILD 4.24E-01 INFANT 2.57E-01 2ND SEMI-ANNUAL ADULT 7.41E-01 TEEN 7.45E-01 CHILD 6.63E-01 INFANT 3.96E-01 GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN 6.93E-01 6.98E-01 6.18E-01 3.56E-01 1.95E-01 1.96E-01 1.73E-01 1.00E-01 8.87E-01 8.94E-01 7.91E-01 4.56E-01 2.67E-01 2.69E-01 2.39E-01 1.39E-01 4.73E-01 4.76E-01 4.25E-01 2.57E-01 7.41E-01 7.45E-01 6.64E-01 3.96E-01 1.63E+00 1.64E+00 1.45E+00 8.52E-01 2.66E-03 2.66E-03 2.66E-03 2.66E-03 1.18E-03 1.18E-03 1.18E-03 1.18E-03 3.83E-03 3.83E-03 3.83E-03 3.83E-03 4.36E-03 4.36E-03 4.36E-03 4.36E-03 3.09E-02 3.09E-02 3.09E-02 3.09E-02 3.52E-02 3.53E-02 3.53E-02 3.52E-02 3.91E-02 3.91E-02 3.91E-02 3.91E-02 6.93E-01 6.98E-01 6.18E-01 3.56E-01 1.95E-01 1.96E-01 1.73E-01 1.OOE-01 8.87E-01
- 8. 94E-01 7.91E-01 4.56E-01 2.67E-01 2.69E-01 2.39E-01 1.39E-01 4.73E-01 4.76E-01 4.24E-01 2.57E-01 7.41E-01 7.45E-01 6.63E-01 3.96E-01 1.63E+00 1.64E+00 1.45E+00 8.52E-01 6.93E-01 6.98E-01 6.18E-01
- 3. 56E-01 1.95E-01 1.96E-01 1.73E-01 1.00E-01 9.87E-01
- 8. 94E-01 7.91E-01 4.56E-01 2.67E-01 2.69E-01 2.39E-01
- 1. 39E-01 4.73E-01 4.76E-01 4.24E-01 2.57E-01 7.41E-01 7.45E-01 6.63E-01 3.96E-01 1.63E+00 1.64E+00 1.45E+00
- 8. 52E-01 6.93E-01 6.98E-01 6.18E-01 3.56E-01 1.95E-01 1.97E-01 1.74E-01 1.01E-01 8.88E-01 8.94E-01 7.92E-01 4.57E-01 2.67E-01 2.69E-01 2.39E-01 1.40E-01 4.75E-01 4.78E-01 4.27E-01 2.60E-01 7.43E-01 7.47E-01 6.66E-01 3.99E-01 1.63E+00 1.64E+00 1.46E+00 8.56E-01 6.93E-01 6.98E-01
- 6. 18E-01 3.56E-01 1.95E-01 1.96E-01 1.73E-01 1.00E-01 8.87E-01 8.94E-01 7.91E-01 4.56E-01 2.67E-01 2.69E-01 2.39E-01 1.39E-01 4.79E-01 4.85E-01 4.32E-01 2.62E-01 7.47E-01 7.54E-01 6.71E-01 4.00E-01
- 1. 63E+00 1.65E+00 1.46E+00 9.56E-01 6.95E-01 7.00E-01 6.20E-01 3.58E-01 1.96E-01 1.97E-01 1.74E-01
- 1. 01E-01 8.90E-01 9.97E-01 7.94E-01 4.59E-01 2.71E-01 2.73E-01 2.43E-01 1.42E-01 4.94E-01 4.97E-01 4.44E-01 2.28E-01 7.65E-01 7.70E-01 6.87E-01 3.70E-01 1.66E+00
- 1. 67E+00 1.48E+00 8.29E-01
'i ANNUAL ADULT TEEN CHILD INFANT 1.63E+00 1.64E+00 1.45E+00 9.52E-01 89 PVNGS ARERR 2005
Table 44:
Integrated Population Dose for 2005 JAN -
MAR PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
+
+_-
+__--
__+
4
+
4--___
PLUME 6.01E-04 6.01E-04 l 6.01E-04 6.01E-04 6.01E-04 6.01E-04 6.012-04 1.90E-03 l
.01%
.01%
95.35%
.01%
.01%
.01%
.01% j
.03%
________+
__________+
_________+___ ______+
_________+
+
4_______+__________+
GROUND 2.36E-05 2.36E-05 l 2.36E-05 l 2.36E-05 l 2.36E-05 l 2.36E-05 2.36E-05 l 2.78E-05
.00%
.00%
3.74%
.00%
.00%
.00%
.00%
.00%
_-_--__-+______-_-_+
-+___--_----+___-__--
+__--_-_4
_---+---+-
INHAL 1.34E+00 1.34E+00 2.73E-07 1.34E+00 l 1.34E+00 l 1.34E+00 1.34E+00 l 1.34E+00 22.25%
22.25%
.04%
22.25%
22.25% j 22.25%
22.25%
22.25%
_-+__-__-
-__+
____--+
+
+
_____+
+
__+
VEGET l 4.05E+00 l 4.05E+00 l 5.33E-06 l 4.05Z+00 l 4.05E+00 4.05E+00 l 4.05E+00 l 4.05E+00 l
67.21%
67.21%
.85%
67.21% I 67.21% I 67.21%
67.21% I 67.20% I COW MILK 4.29E-01 l 4.29E-01 8.03E-08 4.29E-01 4.29E-01 4.29E-01 4.29E-01 4.29E-01 I
7.13% I 7.13%
.01%
7.13%
7.13% I 7.13% I 7.13%
7.12%
MEAT 2.05E-01 2.05E-01 4.30E-09 l 2.05E-01 l 2.05E-01 l 2.05E-01 2.05E-01 l 2.05E-01 I
3.40% I 3.40% I
.00% I 3.40S I 3.40% I 3.40%
3.40% I 3.40% I
'TOTAL^
I 6.02E+00 I 6.02E+00 I 6.30E-04 I 6.02E+00 I 6.02E+00 l 6.02E+00 l 6.02E+00 l 6.03E+00 l
_________+__________+__________+__________+__________+__________+__________+__________+__________+
(1)
II I
I I
I I
I I
PER CAPITAl 3.07E-06 I 3.07E-06 l 3.22E-10 l 3.07E-06 l 3.07E-06 l 3.07E-06 I 3.07E-06 I 3.08E-06 I DOSE (REM)I I
I I
I I
I I
I APR - JUN PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
_________+_________+__________+_________+__________+_________+__________+_________+__________+
PLUME 8.99E-04 l 8.99E-04 I 8.99E-04 I 8.99E-04 I 8.99E-04 I 8.99E-04 I 8.99E-04 I 2.81E-03 I
.02%
.02% 1 97.19% 1
.02% 1
.02% 1
.02% 1
.02% 1
.06%
GROUND I 9.94E-06 I 9.94E-06 I 9.94E-06 l 9.94E-06 l 9.94E-06 l 9.94E-06 l 9.94E-06 l 1.17E-05 I I
.00% I
.00% 1 1.07%
.00%
.00% j
.00%
.00% I
.00%
INHAL I 1.09E+00 I 1.09E+00 I 4.57E-06 I 1.09E+00 I 1.09E+00 I 1.09E+00 1.09E+00 1.09E+00 1
25.02% 1 25.02% 1
.49% 1 25.02% 1 25.02% 1 25.03% I 25.02% I 25.01%
VEGET I 2.83E+00 I 2.83E+00 I 1.03E-05 I 2.83E+00 I 2.83E+00 I 2.83E+00 I 2.83E+00 I 2.83E+00 I 1
64.72% 1 64.72% 1 1.12% 1 64.72% 1 64.72% 1 64.72% 1 64.72% 1 64.70% 1 COW MILK I 3.31E-01 I 3.31E-01 l 1.132-06 l 3.31E-01 3.31E-01 I 3.32E-01 I 3.31E-01 I 3.31E-01 I 1
7.59% I 7.59% j
.12%
7.59% I 7.59% I 7.59% I 7.59% 1 7.58%
S HEAT I 1.16E-01 1.16E-01 7.26E-09 1.16E-01 I 1.16E-01 1.16E-01 1.162-01 1.16E-01 1
2.64% I 2.64% I
.00% I 2.64% I 2.64% 1 2.64%
2.64%
2.64%
'TOTAL' I 4.37E+00 I 4.37E+00 I 9.25E-04 l 4.37E+00 l 4.37E+00 l 4.372+00 l 4.37E+00 l 4.37E+00 I
_________+_________+__________+__________+_________+__________+_________+__________+_________+
(1)
I I
I I
I I
I I
I PER CAPITAl 2.23E-06 I 2.23E-06 I 4.72E-10 j 2.23E-06 l 2.23E-06 l 2.23E-06 I 2.23E-06 I 2.23E-06 I DOSE (REM)l I
I I
I I
I I
I
+----------
+
+
+
+
+
+
+
+
Table 44: (continued)
Integrated Population Dose for 2005 JAN - JUN PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
________+_________+__________+_________+__________+_________+__________+__________+_________+
PLUME l 1.50E-03 1.50E-03 l 1.50E-03 1.50E-03 l 1.50E-03 1.50E-03 1.50E-03 l 4.70E-03
.01%
.01%
96.45% I
.Ol I
.01%
..01%
.01%
.05%
GROUND 3.35E-05 3.35E-05 3.35E-05 3.35e-05 I 3.35E-05 I 3.35E-05 I 3.35E-05 I 3.94E-05
.00%
.00%
2.16% I
.00% I
.00% I
.00% I
.00% j
.00%
INHAL l 2.43E+00 2.43E+00 1 4.842-06 1 2.433+00 1 2.43E+00 1 2.44E+00 I 2.43E+00 I 2.43E+00 I
23.42% I 23.42% 1
.31% 1 23.42% 1 23.42% 1 23.42% I 23.42%
23.41%
VEGET l 6.88E+00 I 6.88E+00 1.57E-05 I 6.88E+00 I 6.88E+00 6.88E+00 I 6.88E+00 I 6.88E+00 66.17%
66.17t 1.01%
66.17% I 66.17%
66.16% I 66.17% j 66.15%
COW MILK 7.61E-01 7.61E-01 l 1.21E-06 l 7.61E-01 l 7.61E-01 l 7.61E-01 l 7.61E-01 l 7.61E-01 I
7.32% j 7.32% 1
.08% 1 7.32% 1 7.32% I 7.32% I 7.32% I 7.32%
MEAT l 3.20E-01 l 3.20E-01 l 1.16E-08 l 3.20E-01 l 3.20E-01 3.20E-01 l 3.20E-01 i 3.20E-01 3.08%
3.08%
.00% I 3.08% j 3.08% j 3.08% j 3.08%
3.08%
- TOTAL^ I 1.04E+01 I 1.04E+01 1 1.55E-03 1 1.04E+01 1 1.04E+01 I 1.04E+01 I 1.04E+01 I 1.04E+01 I
_________+__________+__________+__________+__________+__________+__________+__________+__________+
(1)
I I
I I
I I
I I
I PER CAPITAl 5.31E-06 1 5.31E-06 I 7.91E-10 I 5.313-06 I 5.31E-06 I 5.31E-06 I 5.31E-06 1 5.31E-06 DOSE (REM)i I
I I
I I
I I
JUL -
SEP PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
________+__________+__________+_________+_________+__________+__________+_________+__________+
PLUME l 1.14E-03 j 1.143-03 1.14E-03 1.14E-03 1.14E-03 1.14E-03 1.14E-03 I 4.75E-03
.04%
.04%
99.61% I
.04%
.04% I
.04%
.04%
.16%
_________+_________+__________+_________+__________+_________+__________+_________+__________+
GROUND l 4.60E-07 I 4.60E-07 4.60E-07 I 4.60E-07 j 4.60E-07 I 4.60E-07 I 4.60E-07 I 5.33E-07
.00%
.00%
.04% I
.00%
.00% I
.00%
.00%
.00%
INHAL l 7.853-01 J 7.85E-01 7.42E-07 7.85E-01 7.85E-01 7.85E-01 7.85E-01 7.85E-01 I
26.37% I 26.37%
.06%
26.37%
26.37%
26.37%
26.37% I 26.34%
VEGET l 1.85E+00 I 1.85E+00 I 3.16E-06 I 1.85E+00 I 1.853+00 j 1.85E300 I 1.85E+00 1.85E+00 I I
62.33% I 62.33% I
.28%
62.33%
62.33% I 62.33% I 62.33% I 62.26%
+_---------+-------_---____-----_+___-------+-----_----+---___----+-______---+_---------+
COW MILK 2.51E-01 l 2.51E-01 l 6.10E-08 l 2.51E-01 l 2.51E-01 2.51E-01 2.51E-01 2.51E-01 I
8.44% I 8.44% I
.01%
8.44%
8.44% I 8.44%
8.44%
8.43%
MEAT l 8.38E-02 8.38E-02 6.90E-09 8.38E-02 8.38E-02 8.38E-02 8.38E-02 8.38E-02 I
2.82% j 2.82% I
.00%
2.82% I 2.82% j 2.82%
2.82%
2.81%
- TOTAL^
I 2.98E+00 I 2.98E+00 1 1.15E-03 1 2.98E+00 I 2.98E+00 1 2.98E+00 1 2.98E+00 I 2.98E+00 I
_________+__________+__________+__________+__________+__________+__________+__________+__________+
( l)
I I
I I
I I
I I
I PER CAPITAl 1.52E-06 1 1.52E-06 I 5.87E-10 I 1.52E-06 I 1.52E-06 I 1.52E-06 I 1.52E-06 I 1.52E-06 DOSE (REM)I I
I I
II
+-----------------------------+-+
+
+
+
Table 44: (continued)
Integrated Population Dose for 2005 OCT -
DEC PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
________+
__________+
_________+
__________+
__________+
__________+___
______+ __________+
_________+
PLUME 7.17E-03 7.17E-03 7.17E-03 l 7.17E-03 l 7.17E-03 j 7.17E-03 7.17E-03 l 3.32E-02
.12%
.12%
63.70% I
.12%
.12%
.12%
.12%
.57%
GROUND 3.84E-03 l 3.84E-03 l 3.84E-03 l 3.84E-03 l 3.84E-03 l 3.84E-03 l 3.84E-03 l 4.52E-03
.07%
.07%
34.15% I
.07% I
.07%
.07%
.07%
.08%
INHAL 1.14E300 l 1.14E+00 l 7.253-05 l 1.14E+00 l 1.14E+00 1.14E+00 j 1.14E+00 1.13E+00 I
19.60% j 19.60%
.64% I 19.60% I 19.60%
19.63% I 19.69%
19.51% I VEGET 4.11E+00 4.113+00 1.52E-04 l 4.11E+00 l 4.10E+00 l 4.11E+00 4.103+00 4.10E+00 70.90%
70.90%
1.35% I 70.90% I 70.90%
70.88%
70.82% I 70.58%
COW MILK 3.45E-01 3.45E-01 1.63E-05 l 3.45E-01 l 3.45E-01 l 3.46E-01 3.45E-01 3.45E-01 I
5.97% I 5.96% I
.14%
5.97% I 5.97% I 5.97%
5.96% I 5.94% I MEAT 1.93E-01 1.93E-01 l 1.44E-06 l 1.93E-01 1.93E-0l 1.93E-01 l 1.93E-01 j 1.93E-01 I
3.34% I 3.34%
.01%
3.34% I 3.34% I 3.33% I 3.33% I 3.32%
- TOTAL*
I 5.79E+00 I 5.79E+00 l 1.13E-02 l 5.79E+00 I 5.79E+00 I 5.80E+00 I 5.80E+00 I 5.82E+00 I
_________+__________+__________+__________+__________+__________+__________+__________+__________+
(1)
I I
I I
I I
I I
I PER CAPITAl 2.96E-06 I 2.96E-06 I 5.77E-09 I 2.96E-06 I 2.96E-06 I 2.96E-06 l 2.96E-06 l 2.97E-06 I DOSE (REM)I I
I I
I I
I II JUL -
DEC PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
_______+__________+__________+__________+__________+_________+__________+_________+_________+
PLUME 8.31E-03 j 8.31E-03 l 8.31E-03 l 8.31E-03 l 8.31E-03 8.31E-03 l 8.31E-03 l 3.79E-02
.09%
.09%
67.02% I
.09%
.09%
.09% I
.09%
.43% I GROUND l 3.84E-03 l 3.84E-03 l 3.84E-03 l 3.84E-03 3.84E-03 3.84E-03 3.84E-03 j 4.52E-03 l
.04% f
.04%
30.99% I
.04%
.04%
.04%
.04% I
.05S INHAL 1.92E+00 1.92E+00 l 7.32E-05 l 1.92E+00 l 1.92E+00 1.92E+00 1.93E+00 l 1.92E+00 I
21.90% I 21.90% I
.59% I 21.90%
21.90%
21.92% I 21.96%
21.83%
+
_________+
__________+
_________+
+-----------
+ __________+
VEGET j 5.96E+00 5.96E+00 l 1.56E-04 l 5.96E+00 l 5.96E+00 l 5.96E+00 l 5.96E+00 5.96E+00 I
67.99% I 68.00% I 1.25%
67.99% I 67.99% I 67.98%
67.94% I 67.76%
COW MILK 5.97E-01 5.97E-01 I 1.63E-05 5.97E-01 l 5.97E-01 l 5.97E-01 5.97E-01 5.97E-01 6.81%
6.80%
.13%
6.81% I 6.81%
6.811 I 6.80% j 6.78% I MEAT 2.77E-01 2.77E-01 1.44E-06 2.77E-01 2.77E-01 2.77E-01 2.77E-01 2.773-01 I
3.16% I 3.16%
.01%
3.16% I 3.16%
3.16% I 3.16% I 3.15S
- TOTAL*
I 8.77E+00 I 8.77E+00 I 1.24E-02 I 8.76E+00 I 8.76E+00 I 8.77E+00 I 8.773+00 I 8.79E+00 I
_________+__________+__________+__________+__________+__________+__________+__________+__________+
(1)
I I
I I
I I
I II PER CAPITAl 4.48E-06 l 4.48E-06 l 6.33E-09 l 4.47E-06 I 4.47E-06 I 4.48E-06 I 4.48E-06 I 4.49E-06 I DOSE (REM)lI I
I I
I I
I I
+----------
+
+
+
+
4
+
+
+
Table 44: (continued)
Integrated Population Dose for 2005 JAN -
DEC PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN 4______+__________+__________+__________+__________+_______4__+__________+__________+_________+
PLUME j 9.81E-03 j 9.81E-03 j 9.81E-03 j 9.81E-03 l 9.81E-03 9.81E-03 9.81E-03 l 4.27E-02 I
.05% I
.05%
70.30% I
.05%
.05%
.05%
.05% I
.22%
GROUND 3.88E-03 3.88E-03 j 3.88E-03 j 3.88E-03 3.88E-03 3.88E-03 l 3.88E-03 l 4.56E-03 I
.02% I
.02%
27.78%
.02%
.02%
.02%
.02%
.02%
INHAL 4.35E+00 4.35E+00 7.81E-05 l 4.35E+00 l 4.35E+00 l 4.36E+00 4.36E+00 l 4.353+00 22.72%
22.72%
.56%
22.72%
22.72% I 22.73% f 22.75%
22.68%
VEGET 1.28E+01 1.28E+01 1.71E-04 1.28E+01 l 1.28E+01 l 1.28E+01 1.28E+01 1.28E+01 I
67.00%
67.00% I 1.23% I 67.00% I 67.00% I 67.00% I 66.98% I 66.89%
COW MILK 1.36E+00 l 1.36E+00 l 1.76E-05 l 1.36E+00 l 1.36E+00 l 1.36E+00 l 1.36E+00 l 1.36E+00 l
I 7.08% I 7.08%
.13%
7.08% I 7.08% I 7.08%
7.08% I 7.07%
MEAT 5.97E-01 5.97E-01 1.45E-06 l 5.97E-01 l 5.97E-01 l 5.97E-01 l 5.97E-01 5.97E-01 3.12% I 3.12%
.01%
3.12% I 3.12% I 3.12% I 3.12% I 3.11% I
^TOTAL^ I 1.92E+01 I 1.92E+01 l 1.40E-02 l 1.92E+01 l 1.92E+01 l 1.92E+01 I 1.92E+01 I 1.92E+01 I (1)
I I
I I
I I
I I
I PER CAPITAj 9.80E-06 j 9.80E-06 1 7.15E-09 l 9.80E-06 I 9.80E-06 1 9.80E-06 1 9.80E-06 I 9.80E-06 I DOSE (REM)I I
I I
I I
I I
I
_________+__________+_________+__________+_________+__________+_________+__________+_________+
Note 1: Personrem total divided by 50-mile population of 1,959,000 93 PVNGS ARERR 2005
Table 45:
Summary of Individual Doses for 2005 Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Year total Gamma Air Dose mrad 1.01E-03 9.11E-04 2.37E-03 4.78E-03 9.08E-03 ODCM Req. 4.1 Limit mrad 5.OOE+00 5.OOE+00 5.OOE+00 5.OOE+00 1.00E+01
% ODCM Limit 2.02E-02 1.82E-02 4.74E-02 9.56E-02 9.08E-02 Beta Air Dose mrad 8.21 E-04 8.99E-04 1.55E-03 1.23E-02 1.56E-02 ODCM Req. 4.1 Limit mrad 1.00E+01 1.00E+01 1.00E+01 1.00E+01 2.OOE+01
% ODCM Limit 8.21E-03 8.99E-03 1.55E-02 1.23E-01 7.80E-02 Maximum Individual Total Body mrem 6.60E-04 5.89E-04 1.56E-03 2.92E-03 5.73E-03 Skin mrem 1.18E-03 1.1OE-03_l 2.80E-03 8.54E-03_l 1.36E-02 Site Boundary Location Unit 1 miles 1.87 S 1.87 S 1.87 S 1.87 S 1.87 S Unit 2 miles 1.68 S 1.68 S 1.68 S 1.68 S 1.68 S Unit 3 miles 1.46 S 1.46 S 1.46 S 1.46 S 1.46 S Maximum Organ Dose Age Teen Child Child Teen Teen (excluding skin)
Organ Thyroid (3) Thyroid Thyroid (3) Lung Lung mrem 1.42E.01 2.15E-01 1.01E-01 1.68E-01 4.77E-01 ODCM Req. 4.2 Limit mrem 7.50E+00 7.50E+00 7.50E+00 7.50E+00 1.50E+01
% ODCM Limit(')
1%
r.89E+00 2.87E+00 1.35E+00 2.24E+00 3.18E+00 Location Unit 1 miles 2.84 S 1.85 N 2.29 NE 2.84 S 2.84 S Unit 2 miles 2.68 S 2.05 NNE 2.51 NE 2.68 S 2.68 S Unit 3 miles 2.48 S 2.27 NNE 2.73 NNE 2.48 S 2.48 S Organ dose from tritium only for Unit 2 location mrem 1.42E-01 2.12E-01 1.01E-01 1.63E-01 4.70E-01 above Fraction of organ dose from tritium only for Unit 2 100 99 100 97 99 location above (2)
X/Q for Unit 2 location sec/rm 3 5.67E-06 1.16E-06 1.13E-06 8.65E-06 5.56E-06 above ab/0 for Unit 2 location m-2 2.46E-09 3.89E-09 3.17E-09 2.66E-09 1.97E-09 Note 1: ODCM Requirement 5.1 has higher limits than ODCM Requirement 4.2, therefore the percent of limits are more conservative based on ODCM Requirement 4.2 than on ODCM Requirement 5.1.
Note 2: Fraction of dose from tritium varies mainly due to the ratio of tritium to iodine curies released (see Tables 32 and 33) and changes in X/Q and D/Q for each quarter Note 3:AII organs except bone 94 PVNGS ARERR 2005