Frequency 1.4 1.4 Frequency DESCRIPTION criteria.

SR 3.0.4 restrictions would not apply if both the (continued) following conditions are satisfied:

a.

The Surveillance is not required to be performed; and

b.

The Surveillance is not required to be met or, even if required to be met, is not known to be failed.

EXAMPLES The following examples illustrate the various ways that Frequencies are specified.

In these examples, the Applicability of the LCO (LCO not shown) is MODES 1, 2, and 3. The examples do not reflect the potential application of LCO 3.0.4.b.

EXAMPLE 1.4-1 I

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Example 1.4-1 contains the type of SR most often encountered in the Technical Specifications (TS).

The Frequency specifies an interval (12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />) during which the associated Surveillance must be performed at least one time.

Performance of the Surveillance initiates the subsequent interval.

Although the Frequency is stated as 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, an extension of the time interval to 1.25 times the interval specified in the Frequency is allowed by SR 3.0.2 for operational flexibility.

The measurement of this interval continues at all times, even when the SR is not required to be met per SR 3.0.1 (such as when the equipment is inoperable, a variable is outside specified limits, or the unit is outside the Applicability of the LCO):

If the interval specified by SR 3.0.2 is exceeded while the unit is in a MODE or other specified condition in the Applicability of the LCO, and the performance of the Surveillance is not otherwise modified (refer to Examples 1.4-3 and 1.4-4), then SR 3.0.3 becomes applicable.

(continued)

CLINTON 1.0-25 Amendment No.163

LCO Applicability 3.0 3.0 LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY LCO 3.0.1 LCOs shall be met during the MODES or other specified conditions in the Applicability, except as provided in LCO 3.0.2 and LCO 3.0.7.

LCO 3.0.2 Upon discovery of a failure to meet an LCO, the Required Actions of the associated Conditions shall be met, except as provided in LCO 3.0.5 and LCO 3.0.6.

If the LCO is met or is no longer applicable prior to expiration of the specified Completion Time(s), completion of the Required Action(s) is not required, unless otherwise stated.

LCO 3.0.3 When an LCO is not met and the associated ACTIONS are not met, an associated ACTION is not provided, or if directed by the associated ACTIONS, the unit shall be placed in a MODE or other specified condition in which the LCO is not applicable.

Action shall be initiated within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to place the unit, as applicable, in:

a. MODE 2 within 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />;
b. MODE 3 within 13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br />; and
c. MODE 4 within 37 hours4.282407e-4 days <br />0.0103 hours <br />6.117725e-5 weeks <br />1.40785e-5 months <br />.

Exceptions to this Specification are stated in the individual Specifications.

Where corrective measures are completed that permit operation in accordance with the LCO or ACTIONS, completion of the actions required by LCO 3.0.3 is not required.

LCO 3.0.3 is only applicable in MODES 1, 2, and 3.

LCO 3.0.4 When an LCO is not met, entry into a MODE or other specified condition in the Applicability shall only be made:

a. When the associated ACTIONS to be entered permit continued operation in the MODE or other specified condition in the Applicability for an unlimited period of time; (continued)

CLINTON 3.0-1I Amendment No. 163

LCO Applicability 3.0 3.0 LCO APPLICABILITY LCO 3.0.4 (continued)

b. After performance of a risk assessment addressing inoperable systems and components, consideration of the results, determination of the acceptability of entering the MODE or other specified condition in the Applicability, and establishment of risk management actions, if appropriate; exceptions to this Specification are stated in the individual Specifications, or
c. When an allowance is stated in the individual value, parameter, or other Specification.

This specification shall not prevent changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.

I LCO 3.0.5 Equipment removed from service or declared inoperable to comply with ACTIONS may be returned to service under administrative control solely to perform testing required to demonstrate its OPERABILITY or the OPERABILITY of other equipment.

This is an exception to LCO 3.0.2 for the system returned to service under administrative control to perform the testing required to demonstrate OPERABILITY.

LCO 3.0.6 When a supported system LCO is not met solely due to a support system LCO not being met, the Conditions and Required Actions associated with this supported system are not required to be entered.

Only the support system LCO ACTIONS are required to be entered.

This is an exception to LCO 3.0.2 for the supported system.

In this event, additional evaluations and limitations may be required in accordance with Specification 5.5.10, "Safety Function Determination Program (SFDP)."

If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

When a support system's Required Action directs a supported system to be declared inoperable or directs entry into Conditions and Required Actions for a supported system, the applicable Conditions and Required Actions shall be entered in accordance with LCO 3.0.2.

(continued)

CLINTON

3. 0-2 Amendment No.163

SR Applicability 3.0 3.0 SR APPLICABILITY (continued)

SR 3.0.3 (continued)

When the Surveillance is performed within the delay period and the Surveillance is not met, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.

SR 3.0.4 Entry into a MODE or other specified condition in the Applicability of an LCO shall only be made when the LCO's Surveillances have been met within their specified Frequency, except as-provided by SR 3.0.3. When an LCO is not met due to Surveillances not having been met, entry into a MODE or other specified condition in the Applicability shall only be made in accordance with LCO 3.0.4.

This provision shall not prevent entry into MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.

I (continued)

Amendment No. 163 CLINTON

3. 0 -

PAM Instrumentation 3.3.3.1 3.3 INSTRUMENTATION 3.3.3.1 Post Accident Monitoring (PAM) Instrumentation LCO 3.3.3.1 APPLICABILITY:

The PAM instrumentation for each Function in Table 3.3.3.1-1 shall be OPERABLE.

MODES 1 and 2.

ACTIONS


NOTE-------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A.

One or more Functions A.I Restore required 30 days with one required channel to OPERABLE channel inoperable.

status.

B.

Required Action and B.1 Initiate action to Immediately associated Completion prepare and submit a Time of Condition A Special Report.

not met.

C.

One or more Functions C.1 Restore one required 7 days with two required channel to OPERABLE channels inoperable.

status.

(continued)

CLINTON 3.3 -19 Amendment No.163

Remote Shutdown System 3.3.3.2 3.3 INSTRUMENTATION 3.3.3.2 Remote Shutdown System LCO 3.3.3.2 APPLICABILITY:

The Remote Shutdown System Functions shall be OPERABLE.

MODES 1 and 2.

ACTIONS


NOTE--------------------------------------

Separate Condition entry is allowed for each Function.

I CONDITION REQUIRED ACTION COMPLETION TIME A.

One or more required A.1 Restore required 30 days Functions inoperable.

Function to OPERABLE status.

B.

Required Action and B.1 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.3.2.1 Perform CHANNEL CHECK for each required 31 days instrumentation channel that is normally energized.

(continued) 163 CLINTON 3.3 -23 Amendment No.

RCS Leakage Detection Instrumentation 3.4.7 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.7 RCS Leakage Detection Instrumentation LCO 3.4.7 The following RCS leakage detection instrumentation shall be OPERABLE:

a.

Drywell floor drain sump monitoring system;

b.

One channel of either drywell atmospheric particulate monitoring system or drywell atmospheric gaseous monitoring system; and

c.

Drywell air cooler condensate flow rate monitoring system.

APPLICABILITY:

MODES 1, 2, and 3.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Drywell floor drain A.1 Restore drywell floor sump monitoring system drain sump monitoring 30 days inoperable.

system to OPERABLE status.

B. Required drywell B.1 Analyze grab samples Once per 24 atmospheric monitoring of drywell hours system inoperable.

atmosphere.

(continued)

I CLINTON 3.4 -17 Amendment No.16 3

RCS Leakage Detection Instrumentation 3.4.7 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C.

Drywell air cooler


NOTE-------------

condensate flow rate Not applicable when the monitoring system required drywell atmospheric inoperable.

monitoring system is inoperable.

C.1 Perform SR 3.4.7.1.

Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> D.

Required drywell D.1 Restore required atmospheric monitoring drywell atmospheric 30 days system inoperable.

monitoring system to OPERABLE status.

AND OR Drywell air cooler D.2 Restore drywell air 30 days condensate flow rate cooler condensate monitoring system flow rate monitoring inoperable.

system to OPERABLE status.

E.

Required Action and E.1 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time of Condition A, B, AND C, or D not met.

E.2 Be in MODE 4.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> F. All required leakage F.1 Enter LCO 3.0.3.

Immediately detection systems inoperable.

I CLINTON 3.4 -18 Amendment No. 163

RCS Specific Activity 3.4.8 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.8 RCS Specific Activity LCO

3.4.8 APPLICABILITY

The DOSE EQUIVALENT I-131 specific activity of the reactor coolant shall be S 0.2 pCi/gm.

MODE 1, MODES 2 and 3 with any main steam line not isolated.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

Reactor coolant


NOTE-------------

specific activity >

LCO 3.0.4.c is applicable.

0.2 pCi/gm and S 4.0 pCi/gm DOSE EQUIVALENT I-131.

A.1 Determine DOSE Once per EQUIVALENT I-131.

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> AND A.2 Restore DOSE 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> EQUIVALENT I-131 to within limits.

B.

Required Action and B.1 Determine DOSE Once per associated Completion EQUIVALENT I-131.

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> Time of Condition A not met.

AND OR B.2.1 Isolate all main 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> steam lines.

Reactor coolant specific activity >

OR 4.0 pCi/gm DOSE EQUIVALENT I-131.

B.2.2.1 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND B.2.2.2 Be in MODE 4.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> I

CLINTON 3.4 -20 Amendment No.163

RHR Shutdown Cooling System-Hot Shutdown 3.4.9 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.9 Residual Heat Removal (RHR) Shutdown Cooling System-Hot Shutdown LCO 3.4.9 Two RHR shutdown cooling subsystems shall be OPERABLE, and, with no recirculation pump in operation, at least one RHR shutdown cooling subsystem shall be in operation.


NOTES--------------------------

1.

Both RHR shutdown cooling subsystems and recirculation pumps may be removed from operation for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> per 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period.

2.

One RHR shutdown cooling subsystem may be inoperable for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for performance of Surveillances.

APPLICABILITY:

MODE 3 with reactor steam dome pressure less than the RHR cut in permissive pressure.

ACTIONS


NOTE----------------------------------

Separate Condition entry is allowed for each RHR shutdown cooling subsystem.

___-__________-______-_______________________________________-_____contned (continued)

I CLINTON 3.4 -22 Amendment No. 163

ECCS -Operating 3.5.1 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) AND REACTOR CORE ISOLATION COOLING (RCIC) SYSTEM 3.5.1 ECCS-Operating LCO

3.5.1 APPLICABILITY

Each ECCS injection/spray subsystem and the Automatic Depressurization System (ADS) function of seven safety/

relief valves shall be OPERABLE.

MODE 1, MODES 2 and 3, except ADS valves are not required to be OPERABLE with reactor steam dome pressure

  • 150 psig.

ACTIONS


NOTE---------------------------------------

LCO 3.0.4.b is not applicable to HPCS.

I CONDITION REQUIRED ACTION COMPLETION TIME A.

One low pressure ECCS A.1 Restore low pressure 7 days injection/spray ECCS injection/spray subsystem inoperable.

subsystem to OPERABLE status.

B.

High Pressure Core B.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Spray (HPCS) System administrative means inoperable.

RCIC System is OPERABLE when RCIC is required to be OPERABLE.

AND B.2 Restore HPCS System 14 days to OPERABLE status.

(continued)

CLINTON 3.5 -1 Amendment No. 163

RCIC System 3.5.3 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) AND REACTOR CORE ISOLATION COOLING (RCIC) SYSTEM 3.5.3 RCIC System LCO

3.5.3 APPLICABILITY

The RCIC System shall be OPERABLE.

MODE 1, MODES 2 and 3 with reactor steam dome pressure > 150 psig.

ACTIONS I


NOTE-------------------------------------- -

LCO 3.0.4.b is not applicable to RCIC.

I CONDITION REQUIRED ACTION COMPLETION TIME A.

RCIC System A.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable'.

administrative means High Pressure Core Spray System is OPERABLE.

AND A.2 Restore RCIC System 14 days to OPERABLE status.

B.

Required Action and B.1 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.

AND B.2 Reduce reactor steam 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> dome pressure to 5 150 psig.

CLINTON 3.5 -10 Amendment No. 163

Primary Containment Hydrogen Recombiners 3.6.3.1 3.6 CONTAINMENT SYSTEMS 3.6.3.1 Primary Containment Hydrogen Recombiners LCO 3.6.3.1 APPLICABILITY:

Two primary containment hydrogen recombiners shall be OPERABLE.

MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One primary A.1 Restore primary 30 days containment hydrogen containment hydrogen recombiner inoperable.

recombiner to OPERABLE status.

B. Two primary B.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> containment hydrogen administrative means recombiners that the hydrogen inoperable.

control function is maintained.

AND B.2 Restore one primary 7 days containment hydrogen recombiner to OPERABLE status.

C.

Required Action and C.1 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.

I Amendment No. 163 CLINTON 3.6 -36

Primary Containment and Drywell Hydrogen Igniters 3.6.3.2 3.6 CONTAINMENT SYSTEMS 3.6.3.2 Primary Containment and Drywell Hydrogen Igniters LCO 3.6.3.2 Two divisions of primary containment and drywell hydrogen igniters shall be OPERABLE, each with > 90% of the associated igniter assemblies OPERABLE.

APPLICABILITY:

MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

One primary A.2 Restore primary 30 days containment and containment and drywell hydrogen drywell hydrogen igniter division igniter division to inoperable.

OPERABLE status.

B.

Two primary B.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> containment and administrative means drywell hydrogen that the hydrogen igniter divisions control function is inoperable.

maintained.

AND B.2 Restore one primary 7 days containment and drywell hydrogen igniter division to OPERABLE status.

(continued)

I CLINTON 3.6-38 Amendment No. 163

Containment/Drywell Hydrogen Mixing Systems 3.6.3.3 3.6 CONTAINMENT SYSTEMS 3.6.3.3 Containment/Drywell Hydrogen Mixing Systems LCO 3.6.3.3 APPLICABILITY:

Two Containment/Drywell Hydrogen Mixing Systems shall be OPERABLE.

MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

One Containment/

A.1 Restore Containment/

30 days Drywell Hydrogen Drywell Hydrogen Mixing System Mixing System to inoperable.

OPERABLE status.

B.

Two Containment/

B.1 Verify by 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Drywell Hydrogen administrative means Mixing Systems that the hydrogen inoperable.

control function is maintained.

AND B.2 Restore one 7 days Containment/Drywell Hydrogen Mixing System to OPERABLE status.

C.

Required Action and C.1 Be in MODE 3.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Completion Time not met.

I CLINTON

3. 6-4 1 Amendment No. 1 6 3

AC Sources-Operating 3.8.1 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 AC Sources-Operating LCO 3.8.1 The following AC electrical power sources shall be OPERABLE:

a.

Two qualified circuits between the offsite transmission network and the onsite Class 1E AC Electric Power Distribution System; and

b.

Three diesel generators (DGs).

APPLICABILITY:

MODES 1, 2, and 3.


NOTE----------------------------

Division 3 AC electrical power sources are not required to be OPERABLE when High Pressure Core Spray System is inoperable.

ACTIONS


NOTE-------------------------------------

LCO 3.0.4.b is not applicable to DGs.

CONDITION REQUIRED ACTION COMPLETION TIME A.

One offsite circuit A.1 Perform SR 3.8.1.1 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable.

for OPERABLE offsite circuit.

AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter AND A.2 Restore offsite 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> circuit to OPERABLE status.

AND 17 days from discovery of failure to meet LCO (continued)

CLINTON 3.8-1 Amendment No.1 6 3

SVC Protection Systems 3.8.11 3.8 ELECTRICAL POWER SYSTEMS 3.8.11 Static VAR Compensator (SVC) Protection Systems LCO 3.8.11 An SVC Protection System consisting of two redundant protection subsystems shall be OPERABLE for each inservice SVC.

APPLICABILITY:

During SVC operation ACTIONS


NOTE-------------------------------------

Separate Condition entry is allowed for each SVC Protection System.

CONDITION REQUIRED ACTION COMPLETION TIME A.

One subsystem of an A.1 Restore SVC 30 days SVC Protection System protection subsystem inoperable.

to OPERABLE status.

B.

Both subsystems of an B.1 Restore one SVC 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> SVC Protection System protection subsystem inoperable.

to OPERABLE status.

C. Required Action and C.1 Open SVC output 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> associated Completion breaker(s) to remove Time not met.

SVC from service.

I CLINTON 3.8-44 Amendment No163