ML033030060
| ML033030060 | |
| Person / Time | |
|---|---|
| Site: | Harris (NPF-063) |
| Issue date: | 10/10/2003 |
| From: | Ogle C NRC/RGN-II/DRS/EB |
| To: | Scarola J Carolina Power & Light Co |
| References | |
| EA-00-022, EA-01-310, FOIA/PA-2003-0358 IR-02-011 | |
| Download: ML033030060 (42) | |
See also: IR 05000400/2002011
Text
UNITED STATES
NUCLEAR REGULATORY COMMISSION
REGION II
SAM NUNN ATLANTA FEDERAL CENTER
61 FORSYTH STREET SW SUITE 23T85
4-
ATLANTA, GEORGIA 30303-8931
,g-00-022
- EA-01 -310
Carolina Power & Light Company
ATTN: Mr. James Scarola
Vice President - Harris Plant
Shearon Harris Nuclear Power Plant
P. 0. Box 165, Mail Code: Zone 1
New Hill, North Carolina 27562-0165
SUBJECT:
SHEARON HARRIS NUCLEAR POWER PLANT - NRC INSPECTION REPORT
50-400/02-11
Dear Mr. Scarola:
On December 20, 2002, the U.S. Nuclear Regulatory Commission (NRC) completed a triennial
fire protection inspection at your Shearon Harris Nuclear Power Plant. The enclosed inspection
report documents the inspection findings, which were discussed on that date with you and other
members of your staff.
The inspection examined the effectiveness of activities conducted under your license relating to
implementation of your NRC-approved fire protection program. The Inspectors reviewed
selected procedures and records, observed activities, and interviewed personnel.
rl
e-
results of this inspection, the inspectors identified nine findings and related
rent Vlations that collectively have a potential safety significance of greater than very low
sign icnce; however, a safety significance determination has not yet been completed. These
issues could have presented a potential immediate safety concern. However, the issues are
entered into your corrective action program and compensatory measures are in place while
long-term corrective measures are being implemented. Please be advised that the
characterization and number of these findings could potentially change with further NRC review.
In addition, since some of these findings are related to your corrective action for the previous
violation associated with the Thermo-Lag fire barrier assembly between the 'B' train switch
room/auxiliary control panel room and the 'A' train cable spreading room, aad the afety.
A _gnifican~' h%~ nnt YahApn iterrind, that violation will remain open.
-1-i7
2
In accordance with 10 CFR 2.790 of the NRC's Rules of Practice," a copy of this letter and its
enclosure will be publicly available in the NRC Public Document Room or from the Publicly
Available Records (PARS) component of NRC's document system (ADAMS). ADAMS is
accessible from the NRC Web site at http://www.nrc.aov/readina-rm/adams.html (the Public
Electronic Reading Room).
Sincerely,
Charles R. Ogle, Chief
Engineering Branch 1
Division of Reactor Safety
Docket No.: 50-400
License No.: NPF-63
Enclosure: NRC Inspection Report 50-400/02-11
w/Attachments
cc w/encl:
James W. Holt, Manager
Performance Evaluation and
Regulatory Affairs
CPB 9
Carolina Power & Light Company
Electronic Mail Distribution
Robert J. Duncan'll
Director of Site Operations
Carolina Power & Light Company
Shearon Harris Nuclear Power Plant
Electronic Mail Distribution
Benjamin C. Waldrep
Plant General Manager-Harris Plant
Carolina Power & Light Company
Shearon Harris Nuclear Power Plant
Electronic Mail Distribution
Terry C. Morton, Manager
Support Services
Carolina Power & Light Company
Shearon Harris Nuclear Power Plant
Electronic Mail Distribution
(cc w/encl cont'd - See page 3)
3
(cc w/encl cont'd)
John R. Caves, Supervisor
Licensing/Regulatory Programs
Carolina Power & Light Company
Shearon Harris Nuclear Power Plant
Electronic Mail Distribution
William D. Johnson
Vice President & Corporate Secretary
Carolina Power & Light Company
Electronic Mail Distribution
John H. O'Neill, Jr.
Shaw, Pittman, Potts & Trowbridge
2300 N. Street, NW
Washington, DC 20037-1128
Beverly Hall, Acting Director
Division of Radiation Protection
N. C. Department of Environmental
Commerce & Natural Resources
Electronic Mail Distribution
Peggy Force
Assistant Attorney General
State of North Carolina
Electronic Mail Distribution
Public Service Commission
State of South Carolina
P.O. Box 11649
Columbia, SC 29211
Chairman of the North Carolina
Utilities Commission
P. O. Box 29510
Raleigh, NC 27626-0510
Robert P. Gruber
Executive Director
Public Staff NCUC
4326 Mail Service Center
Raleigh, NC 27699-4326
(cc w/encl cont'd - See page 4)
4
(cc w/encl cont'd)
Linda Coleman, Chairman
Board of County Commissioners
of Wake County
P. 0. Box 550
Raleigh, NC 27602
Gary Phillips, Chairman
Board of County Commissioners
of Chatham County
Electronic Mail Distribution
Distribution w/encl:
L Slack, EICS
C. Patel, NRR
OEMAIL
RIDSNRRDIPMLIPB
PUBLIC
OFFICE
RI:DRS
RII:DRS
RlI:DRS
RI:DRP
RII:DRS
RII:DRS
RI:DRP
SlIGNATURE
NAME
RSchn
GWiseman
PFilion
RHagar
SWalker
DCPaye
PFredflckson
DATE
111J2003
1/J21-20
1I./J2003
1
-i_2I003
11Z?03
E-MAILCOPY?-
YES
NO.
YES
NO
YES
NO
YES
NO
V
N
YES
NO
PUBUC DOCUMENT
YES
NO
I
L
OFFICIAL RECORD COPY
DOCUMENT NAME: S:\\DRS\\Eng Branch 1\\HARRISFP02.11R3.wpd
IOFFICE
RI:EICS
Rll:
Rll:
Rll:
Rl:
RI:
Rll:
SIGNATURE
NAME
CEvans
DATE
1/_/2003
1/_.f003
1/J2003
1Lf2003
1/J2003
1LJ2003
1J2003
E-MAIL COPY?
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
-YES
NO
YES
N
PUBUC DOCUMENT
YES NO
UrTltsA KrWKU UUVT
UUi.UMtNI NAMA: b:Wtiibrlg ranCn I
F1AMKibW-1 I M.WPU
U.S. NUCLEAR REGULATORY COMMISSION
REGION II
Docket No.:
License No.:
50-400
Report No.:
Licensee:
Facility:
Location:
Dates:
Inspectors:
50-400/02-11
Carolina Power & Light (CP&L)
Shearon Harris'Nuclear Power Plant
5413 Shearon Harris Road
New Hill, NC 27562
October 21 - 25, 2002 (Week 1)
November 4 - 8,2002 (Week 2)
December 16 - 20, 2002 (Week 3)
P. Fillion, Reactor Inspector, Region II
R. Hagar, Resident Inspector, Shearon Harris (Week 3 only)
C. Payne, Fire Protection Team Leader, Region II (Week 3 only)
R. Schin, Senior Reactor Inspector, Region II (Lead Inspector)
S. Walker, Reactor Inspector (Week 3 only)
G. Wiseman, Senior Fire Protection Inspector, Region II
(Weeks 1 & 2)
Accompanying
Personnel:
Approved by:
N. Staples, Inspector Trainee, Region II (Weeks 1 & 2)
Charles R. Ogle, Chief
Engineering Branch 1
Division of Reactor Safety
Enclosure
SUMMARY OF FINDINGS
IR 05000400/2002-011; Carolina Power & Light; 10/21/2002 - 12/20/2002; Shearon Harris
Nuclear Power Plant, Triennial Baseline Inspection of the Fire Protection Program.
The inspection was conducted by a team of regional inspectors and the Shearon Harris resident
inspector. Nine findings were identified that collectively have a potential safety significance of
greater than very low significance; however, a safety significance determination has not yet
been completed. The significance of issues is indicated by their color (Green, White, Yellow,
Red) using IMC 0609 "Significance Determination Process' (SDP). Findings for which the SDP
does not apply may be "Green" or be assigned a severity level after NRC management review.
The NRC's program for overseeing the safe operation of commercial nuclear power reactors is
described in NUREG-1 649, "Reactor Oversight Process," Revision 3, dated July 2000.
A.
Inspector Identified and Self-Revealing Findings
Comerstones: Mitigating Systems and Initiating Events
TBD. Physical and procedural protection for equipment that was relied on for safe
shutdown (SSD) during a fire in safe shutdown analysis (SSA) areas 1-A-BAL-B1, 1-A-
BAL-B2, and 1-A-EPA of the reactor auxiliary building were inadequate. Motor-operated
valve 1 CS-1 65, volume control tank outlet to charging/safety injection pumps was not
protected physically or procedurally from maloperation due to a fire. Consequently, a
fire in one of the three SSA areas could result in a reactor coolant pump seal loss of
coolant accident (LOCA) with no high pressure safety injection available.
An apparent violation of Operating License Condition 2.F, the Fire Protection Program,
and TS 6.8.1 was identified. This finding is unresolved pending completion of a
significance determination. The finding is greater than minor because it could result In a
loss of equipment that was relied upon for SSD from a fire and could initiate a LOCA
event. Also, when assessed in combination with other findings identified in this report,
the significance could be greater than very low significance. (Section 1 R05.03.b.1)
TBD. Physical and procedural protection for equipment that was relied on for safe
shutdown (SSD) during a fire In safe shutdown analysis (SSA) area 1-A-BAL-B-B5 of
the reactor auxiliary building were inadequate. Motor-operated valves 1 CS-1 69,
charging/safety injection pump (CSIP) suction cross-connect; 1CS-214, CSIP mini-flow
isolation; 1CS-218, CSIP discharge cross-connect; and 1CS-219, CSIP discharge
cross-connect; were not protected physically or procedurally from maloperation due to a
fire. Consequently, a fire in SSA area 1 -A-BAL-B-B5 could result in a loss of all
charging and high pressure safety injection.
An apparent violation of Operating License Condition 2.F, the Fire Protection Program,
and TS 6.8.1 was identified. This finding is unresolved pending completion of a
significance determination. The finding is greater than minor because it could result in a
loss of equipment that was relied upon for SSD from a fire. Also, when assessed in
combination with other findings identified in this report, the significance could be greater
than very low significance. (Section 1 R05.03.b.2)
2
TBD. Physical and procedural protection for equipment that was relied on for safe
shutdown (SSD) during a fire in safe shutdown analysis (SSA) area 1-A-BAL-B-B4 of
the reactor auxiliary building were inadequate. Motor operated valves 1CS-166, volume
control tank outlet to charging/safety injection pumps (CSIPs); and 1CS-1 68, CSIP
suction cross-connect; were not protected physically or procedurally from maloperation
due to a fire. Consequently, a fire in SSA area 1-A-BAL-B-B4 could result in a loss of all
charging and high pressure safety injection.
An apparent violation of Operating License Condition 2.F, the Fire Protection Program,
and TS 6.8.1 was identified. This finding is unresolved pending completion of a
significance determination. The finding is greater than minor because it could result in a
loss of equipment that was relied upon for SSD from a fire. Also, when assessed in
combination with other findings identified in this report, the significance could be greater
than very low significance. (Section 1 R05.03.b.3)
TBD. Physical and procedural protection for equipment that was relied on for safe
shutdown (SSD) during a fire in safe shutdown analysis (SSA) area 1 -A-BAL-C of the
reactor auxiliary building were inadequate. Motor operated valves 1CC-208, component
cooling water (CC) supply to reactor coolant pump (RCP) seals; and 1 CC-251, CC
return from RCP seals; were not protected physically or procedurally from maloperation
due to a fire. Consequently, a fire in SSA area 1 -A-BAL-C could potentially result in an
RCP seal loss of coolant accident (LOCA).
An apparent violation of Operating License Condition 2.F, the Fire Protection Program,
and TS 6.8.1 was identified. This finding is unresolved pending completion of a
significance determination. The finding is greater than minor because it could result in a
loss of equipment that was relied upon for SSD from a fire and could initiate a LOCA
event. Also, when assessed in combination with other findings identified in this report,
the significance could be greater than very low significance. (Section 1 R05.03.b.4)
TBD. Many local manual operator actions were used in place of the required physical
protection of cables for equipment relied on for safe shutdown (SSD) during a fire,
without obtaining NRC approval for these deviations from the approved fire protection
program. This condition applied to all areas that were inspected, including the new
auxiliary control panel fire area that had been recently created as corrective action for
previous Violation 50-400/02-08-01. This reliance on large numbers of local manual
actions, in place of the required physical protection of cables, could potentially result in
an increased risk of loss of equipment that was relied upon for SSD from a fire.
An apparent violation of Operating License Condition 2.F and the Fire Protection
Program was identified. This finding is unresolved pending completion of a significance
determination. The finding is greater than minor because it could potentially result in an
increased risk of loss of equipment that was relied upon for SSD from a fire. Also, when
assessed In combination with other findings identified in this report, the significance
could be greater than very low significance. (Section 1 R05.04.b.1)
TBD. Procedure steps for safe shutdown (SSD) from a fire and related corrective action
for previous Violation 50-400/02-08-01 were inadequate. For a fire in the new auxiliary
control panel fire area, certain cables were not physically protected from the fire and
3
certain SSD procedure steps, that were used in place of physical protection of cables,
involved excessive challenges to operators. Consequently, a fire in the ACP fire area
could result in a loss of all auxiliary feedwater.
An apparent violation of Operating License Condition 2.F, the Fire Protection Program,
and TS 6.8.1 was identified. This finding is unresolved pending completion of a
significance determination. The finding is greater than minor because it could result in a
loss of equipment that was relied upon for SSD from a fire. Also, when assessed in
combination with other findings identified in this report, the significance could be greater
than very low significance. (Section 1 R05.04.b.2)
TBD. A procedure for safe shutdown (SSD) from a fire and related corrective action for
previous Violation 50-400/02-08-01 were inadequate. For a fire in certain safe shutdown
analysis areas of the reactor auxiliary building, including the new auxiliary control panel
fire area, there were too many SSD procedure contingency actions to respond to
potential spurious actuations for the one designated SSD non-licensed operator to
perform all of them. Consequently, equipment that was relied on for SSD may not be
available.
An apparent violation of Operating License Condition 2.F, the Fire Protection Program,
and TS 6.8.1 was identified. This finding Is unresolved pending completion of a
significance determination. The finding is greater than minor because it could result in a
loss of equipment that was relied upon for SSD from a fire. Also, when assessed in
combination with other findings identified in this report, the significance could be greater
than very low significance. (Section 1 R05.04.b.3)
TBD. A procedure for safe shutdown (SSD) from a fire was inadequate. For a fire in
safe-shutdown analysis areas near the boric acid tank (BAT) in the reactor auxiliary
building, the SSD procedure directed operators to take charging/safety injection pump
(CSIP) suction from the BAT even if BAT level indication were lost. However, the
charging volume needed for reactor coolant system cooldown would have emptied the
BAT and damaged the CSIP.
An apparent violation of Operating License Condition 2.F, the Fire Protection Program,
and TS 6.8.1 was identified. This finding Is unresolved pending completion of a
significance determination. The finding is greater than minor because it could result in a
loss of equipment that was relied upon for SSD from a fire. Also, when assessed in
combination with other findings identified in this report, the significance could be greater
than very low significance. (Section 1 R05.04.b.4)
TBD. Required battery-backed emergency lights were not provided in locations where
operators were required to perform actions for safe shutdown (SSD) from a fire. This
condition affected SSD during fires in all of the areas inspected in the reactor auxiliary
building, including the new auxiliary control panel fire area that was created as
corrective action for previous Violation 50-400/02-08-01. The lack of required lighting
could result in an increased risk of operators failing to perform the SSD actions in a
timely and accurate manner.
An apparent violation of Operating License Condition 2.F
the Fire Prote
n
Prograas identified. This finding is unresolved pendg completion of a significance
determfination. The finding is greater than minor because it could result in an increased
risk of operators failing to perform the SSD actions in a timely and accurate manner.
Also, when assessed in combination with other findings identified in this report, the
significance could be greater than very low significance. (Section 1 R05.06.b)
B.
Licensee-ldentified Violations
None
ORT DETAILS
1. REACTOR SAFET
Cornerstones: Initiating Events and Mitigating Systems
1R05 FIRE PROTECTION
.01
Systems Required To Achieve and Maintain Post-Fire SSD Circuit Analysis
a.
Inspection Scope
The team evaluated the licensee's approved fire protection program (FPP) against
applicable requirements, including Operating License NFP-63, Operating License
Condition (OLC) 2.F, FPP; Branch Technical Position (BTP) Chemical Engineering
Branch (CMEB) 9.5-1 (NUREG-0800), July 1981; related NRC Safety Evaluation Reports
(SERs) in NUREG 1038, and plant Technical Specifications (TS). The team evaluated all
areas of this inspection, as documented below, against these requirements. The team
used the licensee's Individual Plant Examination for External Events (IPEEE) and in-plant
tours to select four risk significant fire areas/zones for inspection. The four fire
areas/zones selected were:
Fire Zone 1-A-4-CHLR; part of Fire Area 1-A-BAL-B:
This fire zone was located on the 261 foot level (ground level) of the reactor
auxiliary building (RAB). It was further subdivided in the licensee's SSA into SSA
areas 1-A-BAL-B-B1 [including the 'A' chiller and motor-driven auxiliary feedwater
(AFW) pump flow control valves (FCVs)] and 1-A-BAL-B-B2 [including the 'B'
chiller and turbine-driven AFW pump FCVs]. A significant fire in either of these
areas would require shutdown of the unit from the main control room (MCR) and
additional manual operator actions in various areas of the plant.
Fire Zone 1-A-4-COM-E; part of Fire Area 1-A-BAL-B:
This fire zone was located on the 261 foot level (ground level) of the RAB. It was
further subdivided in the licensee's SSA into SSA areas 1-A-BAL-B-B4 [including
480V motor control center (MCC) 1 B35-SB] and 1 -A-BAL-B-B5 [including 480V
MCC 1A35-SA]. A significant fire in either of these areas would require shutdown
of the unit from the MCR and additional manual operator actions in various areas
of the plant.
Fire Area 1-A-EPA:
This fire zone was located on the 261 foot level (ground level) of the RAB. It
included electrical penetration room 'A'. A significant fire in this area would
require shutdown of the unit from the MCR and additional manual operator
actions in various areas of the plant.
2
Fire Area 1-A-BATB:
This fire zone was located on the 286 foot level (above ground level) of the RAB.
It included the 'B' electrical battery room. A significant fire in this area would
require shutdown of the unit from the MCR and additional manual operator
actions in various areas of the plant.
The team reviewed the post-fire SSD capability and the fire protection features to verify
that at least one post-fire safe shutdown success path would be maintained free of fire
damage during a fire in any of the selected fire areas/zones. The team reviewed the
licensee's fire protection program, including the SSA and supporting calculations, to
determine the systems required to achieve post-fire SSD. The team also reviewed the
Safe Shutdown Equipment List, system flow diagrams, and the Fire Hazards Analysis
(FHA) in the Updated Final Safety Analysis Report (UFSAR) for each of the selected fire
areas to evaluate the completeness and adequacy of the SSD analysis and the systems
relied upon to mitigate fires in the selected fire areas. Specific licensee documents and
drawings reviewed during the inspection are listed in Attachment 1.
b.
Findings
The team found that the licensee's SSA method had identified cables that were required
for control room operation of SSD equipment during fires in certain areas but were not
physically protected from those fires. For these cables, the SSA method relied generally
on operator manual actions to either prevent or mitigate damage resulting from a fire
(e.g., locally open the breaker to an MOV and locally operate the MOV using the
handwheel), rather than on features which physically protect the cables. Using this
method, the licensee generally chose to physically protect these cables only if no
reasonable operator action could be Identified to prevent or mitigate the fire damage.
Consequently, the licensee had identified and relied on more than 100 local manual
operator actions to achieve and maintain hot shutdown conditions during fires. The
licensee had not requested deviation approvals from the NRC for these operator actions,
and had not verified or validated the operator actions to the extent that would have been
involved in NRC reviews of deviation requests. This SSD methodology contributed to the
findings and unresolved items (URIs) that are described in the following sections.
.02
Fire Protection of SSD Caoabilitv
a.
Inspection Scope
The team reviewed UFSAR Section 9.5.1, Appendix 9.5A, FHA; the FPP manual; and
the plant administrative procedures used to prevent fires and control combustible
hazards and ignition sources. This review was to verify that the objectives established by
the NRC-approved FPP were satisfied. The team also toured the selected plant fire
areas observing the licensee's implementation of these procedures. The team also
reviewed the FPP transient combustible permit logs, and fire emergency/incident
investigation reports, for the years 2000-2002. Corrective action program action
requests (ARs) resulting from fire, smoke, sparks, arcing, and equipment overheating
incidents for the same period were also reviewed to assess the effectiveness of the fire
3
prevention program and to identify any maintenance or material condition problems
related to fire incidents.
The team reviewed flow diagrams and engineering calculations associated with the 'B'
train battery room heating, ventilation, and air conditioning (HVAC) systems. This review
was done to verify that systems used to accomplish safe shutdown would not be inhibited
by a potential hydrogen gas fire in the 'B' battery room due to Inoperable ventilation
supply and exhaust fans. The team also reviewed the TS Limiting Condition for
Operation (LCO) requirements for loss of ventilation in the 'B' train battery room to verify
that appropriate timely actions were specified to ensure that hydrogen gas
concentrations generated by the station batteries remained below explosive limits.
The team toured the plant's primary fire brigade staging and dress-out areas to ass -
the condition of fire fighting a
ge
control equipment. Fire brigade personal
protective equipment
in brig
staging area lockers was reviewed to. evaluat
equipment accessibility tridfunctionalit. Additionally, the team examined whether
backup emergency lightihg w'as provi ed for access pathways to and within the fir
brigade staging and dre
u are
in support of fire brigade operations should
power
failure occur during the fire
ency. The team also observed whether emergency
exit lighting was provided for personnel evacuation pathways to the outside exits as
identified In the National Fire Protection Association (NFPA) 101, Ufe Safety Code and
Occupational Safety and Health Administration (OSHA) Part 1910, Occupational Safety
and Health Standards. The adequacy of the fire brigade's self-contained breathing
apparatus (SCBAs) was reviewed as was the availability of supplemental breathing air
tanks.
Team members also toured the selected fire areas and compared the associated fire
pre-plans with as-built plant conditions. This was done to verify that they were consistent
with the fire protection features and potential fire conditions described in the UFSAR.
Additionally, the team reviewed drawings and engineering flood analysis associated with
the 261-foot elevation reactor auxiliary building floor and equipment drain system to verify
that those actions required for SSD would not be inhibited by fire suppression activities or
leakage from fire suppression systems.
The team reviewed the fire brigade response procedure, fire brigade organization, and
training and drill program administration procedures. Fire drill critiques of operating shifts
for the period of March 2001 through October 2002 were reviewed to verify that fire
brigade drills had been conducted in high fire risk plant areas. Fire brigade training/drill
records for 2002 were also reviewed to verify that the fire brigade personnel
qualifications, brigade drill response time, and brigade performance met the
requirements of the licensee's approved FPP. Additionally, the team observed a fire drill
to verify the licensee's Implementation of the fire brigade organization, training, and drill
program administration procedures. The team observed the actions of the site fire
brigade, offsite fire department, and fire drill monitors; and attended the drill critique.
b.
Findings
No findings of significance were identified.
4
.03
Post-Fire SSD Circuit Analysis
a.
Inspection ScoDe
The team reviewed the adequacy of separation and fire barriers provided for the power
and control cabling of equipment relied on for SSD during a fire in the selected fire
areas/zones. On a sample basis, the team reviewed the SSA and the electrical
schematics for power and control circuits of SSD components, and looked for the
potential effects of open circuits, shorts to ground, and hot shorts. This review focused
on the cabling of selected components for the charging/safety injection system, AFW
system, and CC system. The team traced the routing of cables by using the cable
schedule and conduit and tray drawings. Walkdowns were performed to compare 1-hour
and 3-hour barriers (conduit and tray fire barrier wraps) to barriers indicated on the
drawings. Circuit and cable routings were reviewed for the following equipment:
1 CS-1 65, volume control tank (VCT) outlet MOV;
iCS-168, CSIP suction cross connect MOV;
ICS-1 69, CSIP suction cross connect MOV;
1CS-214, CSIP minimum flow MOV;
1CS-217, CSIP discharge cross connect MOV;
1CS-21 8, CSIP discharge cross connect MOV;
1CS-219, CSIP discharge cross connect MOV;
1 CS-278, boric acid tank (BAT) to CSIP MOV;
BAT level instrumentation;.
1 CC-207, CC supply to RCP seals MOV;
1 CC-208, CC supply to RCP seals MOV;
ICC-249, CC return from RCP seals MOV;
1 CC-251, CC return from RCP seals MOV;
1 RC-1 17, pressurizer power-operated relief valve (PORV) block valve;
ISI-310, containment sump to 'A' RHR pump MOV;
1SI-311, containment sump to 'B' RHR pump MOV;
mot
n
pump 1
,,n~tr-driven AFW pump 1B;
and e turbine-driven AFW pump.
The team also reviewed studies of overcurrent protection on both alternating current (AC)
and direct current (DC) systems to identify whether fire induced faults could result in
defeating the safe shutdown functions.
b.
Findings
(1) SSA Areas 1 -A-BAL-B-B1. 1 -A-BAL-B-B2. and 1-A-EPA of the RAB
Introduction
The team identified an unresolved item (URI) involving failure to follow the FPP and TS
6.8.1. The URI involved failure to protect equipment that was relied on for SSD during a
5
fire in SSA areas 1 -A-BAL-B1, 1 -A-BAL-B2, and 1-A-EPA of the RAB from fire damage.
MOV 1 CS-1 65, volume control tank outlet to CSIPs, was not protected physically or
procedurally from maloperation due to a fire. Consequently, a fire in one of the three
SSA areas could result in a reactor coolant pump seal loss of coolant accident (LOCA)
with no high pressure safety injection available.
DescriDtion
The team found that the control power cable for charging system MOV 1 CS-1 65; which
was relied upon to remain open for SSD during a fire in SSA areas 1-A-BAL-B-B1 and 1-
A-BAL-B-B2, and In fire area 1-A-EPA; was routed through those areas with no fire
barrier. As a result, the control power cable for the MOV was vulnerable to fire-induced
hot shorts which could result in spurious valve operation. The lack of a required fire
barrier was not recognized in the SSA and no procedural guidance was included in
Abnormal Operating Procedure (AOP)-36, Safe Shutdown Following a Fire, Rev. 21, for
operators to prevent maloperation of 1 CS-1 65 prior to damage occurring to SSD
equipment. Consequently, a fire in one of the three SSA areas could cause 1CS-165 to
spuriously close, isolate all CSIP suction flowpaths, and immediately damage the
operating SSD CSIP.
For fires in SSA areas 1 -A-BAL-B-B1, 1 -A-BAL-B-B2, or 1-A-EPA the SSD analysis relied
on SSD Division 2 equipment to achieve and maintain hot shutdown. This included
reliance on CSIP 'B' for RCS makeup water, RCP seal cooling, reactivity control by
boration, and high pressure safety injection. The SSA assumed that CSIP 'A' was not
assured to be unaffected by the fire and CSIP 'C' was not assured to be available.
Consequently, a failure of CSIP 'B' could result in a loss of all charging and high pressure
safety injection. Also, for a fire in any of these three SSA areas, CC flow to the RCP
seals was not protected. The team found that the control power cable to MOV 1 CC-207,
CC flow to RCP seals, was routed through the same three SSA areas in the same cable
tray with the control power cable to 1 CS-1 65. AOP-36 included no operator action to
prevent spurious operation of MOV 1 CC-207. Spurious closure of MOV I CC-207 would
stop all CC flow to the seals of all three RCPs. Thus, the potential consequences of a
fire In any of the three SSA areas could be an RCP seal LOCA with no charging or high
pressure injection.
Also, the team found that the control power cables for MOVs 1 CC-252, CC return from
RCP seals, and 1CC-249, CC return from RCP seals, were routed through SSA area 1-
A-BAL-B-B2 and could be affected by a fire in that area. AOP-36 included an operator
action to prevent spurious actuation of 1 CC-252 for a fire in SSA area 1 -A-BAL-B-B2.
That action included opening the breaker to MOV 1 CC-252 on MCC 1 El 2. However, the
SSD NLO would likely not be able to safely do that action during a fire in SSA area 1-A-
BAL-B-B2 because MCC 1 El 2 was located in that SSA area. AOP-36 Included no
operator action for 1 CC-249. Spurious closure of 1 CC-252 or 1 CC-249 would stop all
CC flow to the RCP seals. The team noted that, while the operator action for I CC-252
may not be needed for a fire in SSA area 1-A-BAL-B-B2 because the charging system
was supposed to provide RCP seal cooling, this inappropriate procedural action (sending
an operator into an area where there was a fire) could delay the SSD NLO from
performing other procedure actions that were required to achieve SSD.
6
In addition, the team found that modification ESR 01-00087, which was installed in
January 2002, had affected this condition and missed an opportunity to correct it. ESR
01-00087 changed the CSIP mini-flow path so that it would go to the VCT instead of
going directly to the CSIP suction. Prior to the ESR, if 1CS-165 spuriously closed, the
running CSIP would still have some suctiori although probably not enough to prevent
pump damage. After the ESR, If I CS-1 65 spuriously closed, the running CSIP would
have no suction and CSIP failure would be more certain and more immediate. ESR 01-
00087 failed to recognize this effect and missed an opportunity to identify and correct the.
condition.
Analysis
This finding had more than minor safety significance because it affected the objectives of
the Mitigating Systems and Initiating Events Cornerstones of Reactor Safety. The finding
affected the availability and reliability of systems that mitigate initiating events to prevent
undesirable consequences. It also affected the likelihood of occurrence of initiating
events that challenge critical safety functions. Also, when assessed in combination with
other findings identified in this report, the significance could be greater than very low
significance. However, the finding remains unresolved pending completion of a
significance determination.
Enforcement
OLC 2.F required that the licensee implement and maintain in effect all provisions of the
approved FPP as described in the Final Safety Analysis Report. The UFSAR, Section
9.5.1, FPP, stated that outside containment, where cables or equipment (including
associated non-essential circuits that could prevent operation or cause maloperation due
to hot shorts, open circuits, or shorts to ground) of redundant safe shutdown divisions of
systems necessary to achieve and maintain cold shutdown conditions are located within
the same fire area outside of primary containment, one of the redundant divisions must
be ensured to be free of fire damage. Section 9.5.1 further stated that If both divisions
are located in the same fire area, then one division is to be physically protected from fire
damage by one of three methods: 1) a three-hour fire barrier, 2) a one-hour fire barrier
plus automatic detection and suppression, or 3) a 20-foot separation with no intervening
combustibles and with automatic detection and suppression. The licensee had received
no NRC approvals for deviating from these requirements.
TS 6.8.1 required procedures as recommended by Regulatory Guide (RG) 1.33 and
procedures for fire protection program implementation. RG 1.33 recommended
procedures for combating emergencies, including fires. The licensee's interpretation of
their fire protection program was that they could and would rely on proceduralized
operator actions in place of physically protecting SSD equipment from fire damage (see
Section 1 R05.04.b.1). However, the licensee had failed to provide procedural guidance
in AOP-36 for operators to prevent maloperation of MOV 1 CS-165.
Contrary to the above requirements, the licensee failed to ensure that one of the
redundant divisions (i.e., SSD Division 2, including MOV 1CS-1 65) would be free of fire
damage. MOV 1 CS-1 65 was not protected from fire damage, either by one of the
7
physical methods described above or by procedures. The licensee entered the find g
into the corrective action program as AR 76260.
This finding and apparent violation (AV) are unresolved pending completion of a
significance determination, in combination with the other fire protection issues i ntified
in this report. This item is identified as URI 50-400/02-11-01, Failure to Protect
1 CS-1 65, VCT Outlet to CSIPs, From Maloperation Due To a Fire.
(2)
SSA Area 1 -A-BAL-B-B5 of the RAB
Introduction
The team identified a URI involving failure to follow the FPP and TS 6.8.1. The URI
involved failure to protect equipment that was relied on for SSD during a fire in SSA area
1-A-BAL-B-B5 from fire damage. MOVs lCS-169, CSIP suction cross-connect; 1CS-
214, CSIP mini-flow isolation; 1CS-218, CSIP discharge cross-connect; and 1CS-219,
CSIP discharge cross-connect; were not protected physically or procedurally from
maloperation due to a fire. Consequently, a fire in SSA area 1 -A-BAL-B-B5 could result
in a loss of all charging and high pressure safety injection.
Description
The team found that the control power cables for charging system MOVs O
CS-1 69, 1 CS-
214, 1 CS-218, and 1 CS-219, which were relied upon to remain open for SSD di. -
fire in SSA area 1 -A-BAL-B-B5, were routed through that area with incomplete f
barriers. The control cables were unprotected for about one foot above MCC 1-
and inside the MCC. The team noted that spurious actuations due to hot shorts
control cables were unlikely to occur during a fire in or near the MCC because t
supply breaker to the MCC could trip first or electrical components within the br(
/
could be affected by the heat from the fire such that the spurious actuations cou
precluded. However, the team found no testing or analysis proving that spuriou:
actuations could not occur.
This lack of required fire barriers was recognized In the SSA for 1 CS-1 69, 1 CS-,
1 CS-218, and procedural guidance was included in AOP-36 for operators to pre....
maloperation of these valves. However, the procedural guidance was not adequate.
AOP-36 directed operators to go to MCC 1A35-SA and open the breakers for 1CS-169
and 1CS-214 to prevent spurious operation. However, operators would not be able to
safely do that in all scenarios because the required actions were in the area of the fire
that could cause the spurious operation. AOP-36 directed operators to go to MCC 1 35-
SB, in another room, to open the breaker for 1CS-218. However, operators would not be
able to do that because the breaker for CS-218 was actually located on MCC 1A35-SA.
The SSA had not identified a need for operator action to prevent maloperation of 1 CS-
219 and AOP-36 Included no action steps for that valve.
AOP-36 did include the following guideline for operators:
Monitor for spurious valve and
pump operation which may result in equipment damage (for example, CSIP suction
valves.)" The team noted that closure of a CSIP suction valve could result in pump
damage within seconds; before operators could respond to an annunciator, analyze the
8
condition, and take action to prevent pump damage. Another AOP-36 guideline was:
"When directed by the Unit Shift Supervisor, then shut down equipment and de-energize
electrical busses located within the fire area."
Operators stated that they would de-
energize MCC 1A35-SA if the fire brigade team leader or another operator told them that
the MCC was on fire or if they observed spurious actuations that could be initiating from
the MCC. However, the team noted that normally the fire brigade would not arrive and
attack the fire until about 20 minutes after the control room sounded the fire alarm, and
spurious actuations could occur well before that. By procedure, control room operators
would respond to a single fire detector annunciator by sending an NLO to verify that
there was a fire and that the fire was large enough to warrant sounding the fire alarm and
calling out the fire brigade. However, if the control room operators received annunciation
from two or more fire detectors, which would be very likely in the event of fire large
enough to present an operational safety concem, then they would not send an NLO but
Instead would immediately sound the fire alarm and call out the fire brigade. So it was
likely that the first visual report on a large fire would not be received in the control room
until about 20 minutes after the fire alarm. By that time, the fire would have likely filled
the room with smoke so that the fire brigade would not be able to immediately identify if
the MCC was on fire.
The team concluded that it was unlikely that the control room would de-energize MCC
1A35-SA before spurious actuations could occur. Consequently, a fire in this area, near
or in MCC 1A35-SA, could cause any of the four MOVs to spuriously close. Closure of
1 CS-214 would stop all mini-flow from all CSIPs. Closure of 1 CS-218 or 1 CS-219 would
stop charging flow from SSD CSIP 'B'. If such a loss of charging flow or CSIP mini-flow
occurred, operators would receive an alarm in the control room and would probably have
time to diagnose the condition and initiate recovery actions before CSIP damage
occurred. However, closure of 1CS-169 would stop all suction to SSD CSIP 'B' and
Immediately damage the pump.
For a fire in SSA area 1-A-BAL-B-B5, the SSD analysis was to rely on SSD Division 2
equipment. This included reliance on CSIP 'B' for RCS makeup water, RCP seal cooling,
reactivity control by boration, and high pressure safety injection. CSIP 'A' was not
assured to be unaffected by the fire and CSIP 'C' was not assured to be available. The
team noted that MOVs powered from MCC 1A35-SA could affect CSIP 'A' and CSIP 'C'.
While the SSA did not assure that CC would be available, the team did not identify any
vulnerabilities of CC to a fire in this area. Consequently, the team concluded that the,
potential consequences of a fire in SSA area 1-A-BAL-B5 GQ4M be a loss of all charging
and high pressure safety injection.
C/Uzel
Analysis
This finding had more than minor safety significance because it affected the objectives of
the Mitigating Systems Comerstone. The finding affected the availability and reliability of
systems that mitigate initiating events to prevent undesirable consequences. Also, when
assessed in combination with other findings identified in this report, the significance could
be greater than very low significance. However, the finding remains unresolved pending
completion of a significance determination.
Enforcement
9
U
As described in Section 1 R05.03.b.1 above, OLC 2.F re
ired that one of the redundant
divisions (i.e., SSD DMsion 2, including MOVs 1CS-169,1CS-214,1CS-218, and 1CS-
219) would be free of fire damage. Also, TS 6.8.1 required procedVes for imp menting
the fire protection program and for combating fires.
, 4
x
Contrary to the above requirements, the licensee failed to
ts'ur
hat one of the
redundant divisions (SSD Division 2, including MOVs 1 C 69,6
CS-214,1 CS-218, and
CS-219) would be free of fire damage. MOVs 1CS-169,1CS-214, 1CS-218, and 1CS-
219 were not protected from fire damage, either by one of the physical methods
described above or by procedures. The licensee entered the finding into the corrective
action program as ARs 76260 and 80212.
This finding and AV are unresolved pending completion of a significance determination,
in combination with the other fire protection issues dentified in this report. This Item is
identified as URI 50-400/02-11-02, Failure to Protect Charging System MOVs 1 CS-1 69,
1CS-214, ICS-218, and 1CS-219 From Maloperation Due To a Fire.
(3)
SSA Area 1-A-BAL-B-B4 of the RAB
Introduction
The team Identified a URI involving failure to follow the FPP and TS 6.8.1. The URI
involved failure to protect equipment that was relied on for SSD during a fire In SSA area
1-A-BAL-B-4 from fire damage. MOVs 1CS-166, VCT Outlet to CSIPs; CS-168, CSIP
Suction Cross-connect; and 1CS-217, CSIP Discharge Cross-connect; were not
protected physically or procedurally from maloperation due to a fire. Consequently, a fire
in SSA area 1-A-BAL-B-4 could result in a loss of all charging and high pressure safety
injection.
Description
The team found that the control power cables for charging system MOVs 1 CS-1 66, 1 CS-
168, and 1CS-217, which were relied upon to remain open for SSD during a fire in SSA
area 1-A-BAL-B-B4, were routed through that area with incomplete fire barriers. The
control cable for MOV 1 CS-1 66 was unprotected for about one foot above MCC 1 B35-SB
and inside the MCC. The control power cables for MOVs 1CS-168 and 1CS-217 were
unprotected inside MCC 1 B35-SB. This lack of required fire barriers was not recognized
in the SSA and no procedural guidance was included in AOP-36 for operators to prevent
or mitigate maloperation of these valves. Consequently, a fire in this area, near or in
MCC 1 B35-SB, could cause 1 CS-1 66 or 1 CS-1 68 to spuriously close, which would stop
all suction to SSD CSIP 'A', and immediately damage the pump. If CSIP 'C' were aligned
to be used in place of CSIP 'A', then the fire could cause spurious closure of 1CS-217
and stop charging flow from CSIP 'C'.
For a fire in SSD area 1 -A-BAL-B-B4, the SSD analysis was to rely on SSD Division 1
equipment. This included reliance on CSIP 'A' for RCS makeup water, reactivity control
by boration, and high pressure safety injection. CSIP 'B' was not assured to be
10
unaffected by the fire and CSIP 'C' was not assured to be available. Also, when all three
CSIPs were available, the 'C' CSIP would be aligned to the 'B' train; and it would take
licensee personnel several hours to align the 'C' CSIP to the 'A' train. Consequently, a
failure of CSIP 'A' could result in a loss of all charging and high pressure safety injection.
If CSIP 'C' were aligned to be operating in place of CSIP 'A', and a maloperation of lCS-
217 caused a loss of charging flow, operators would receive a loss of charging flow alarm
and would probably have time to diagnose and respond to the condition before the CSIP
was damaged.
In addition, the team found that modification ESR 01-00087, which was Installed in
January 2002, had affected the significance of the lack of protection for 1 CS-1 66. As
described above for 1 CS-168, ESR 01-00087 was a missed opportunity to identify and
correct the lack of protection for 1 CS-1 66.
Analysis
This finding had more than minor safety significance because it affected the objectives of
the Mitigating Systems Cornerstone of Reactor Safety. The finding affected the
availability and reliability of systems that mitigate initiating events to prevent undesirable
consequences. Also, when assessed in combination with other findings identified in this
report, the significance could be greater than very low significance. However, the finding
remains unresolved pending completion of a significance determination.
Enforcement
As described in Section 1 R05.03.b.1 above, OLC 2.F required that one of the redundant
divisions (i.e., SSD Division 1, including MOVs CS-1 66, CS-1 68, and 1CS-217) would
be free of fire damage. Also, TS 6.8.1 required procedures for implementing the fire
protection program and for combating fires.
Contrary to the above requirements, the licensee failed to assure that one of the
redundant divisions (SSD Division 1, including MOVs lCS-1 66, 1CS-1 68, and 1CS-217)
would be free of fire damage. MOVs 1CS-166, 1CS-168, and CS-217 were no
protected from fire damage, either by one of the physical methods described ab
procedures. The licensee entered the finding into the corrective action program
76260.
This finding and
are unresolved pending completion of a significance detem
in combinatio
'th the other fire protection issues Identified in this report. This
X C'
identified as URI 50-400/02-11-03, Failure to Protect Charging System MOVs 1
V'
1CS-1 68, and 1CS-217 From Maloperation Due To a Fire.
(4)
Introduction
The team identified a URI involving failure to follow the FPP and TS 6.8.1. The URI
Involved failure to protect equipment that was relied on for SSD during a fire in SSA area
1-A-BAL-C from fire damage. MOV 1 CC-251, CC Return From RCP Seals; and MOV
11
1 CC-208, CC Supply To RCP Seals, were not protected either physically or procedurally
from maloperation due to a fire in SSA area 1 -A-BAL-C. Consequently, a fire in that SSA
area could potentially result in an RCP seal LOCA.
Description
The team found that the control power cables for CC system MOVs 1 CC-251 and 1 CC-
208, which were relied upon to remain open for SSD during a fire in SSA area 1 -A-BAL-
C, were routed through that area and into MCC 1 B31 in that area with no fire barrier.
Fire area 1-A-BAL-C was located on the 286 foot level of the auxiliary building, above
electrical penetration room 'B'. This lack of required fire barriers and need for operator
actions was recognized in the SSA but no procedural guidance was included in AOP-36
for operators to prevent or mitigate maloperation of these valves. Consequently, a fire in
this area could cause 1 CC-251 or 1 CC-208 to spuriously close, which would stop all CC
flow to the RCP seals.
For a fire in area 1-A-BAL-C, the SSD analysis relied on SSD Division 1 equipment. This
included reliance on CC to cool the RCP seals. CSIP supply to the RCP seals was not
assured to be unaffected by the fire. Consequently, a loss of CC to the RCP seals could
potentially result in a loss of all RCP seal cooling which could in turn result in an RCP
seal failure and a LOCA.
Analysis
This finding had more than minor safety significance because it affected the objectives of
the Initiating Events Cornerstone of Reactor Safety. The finding affected the likelihood of
occurrence of initiating events that challenge critical safety functions. Also, when
assessed in combination with other findings identified in this report, the significance could
be greater than very low significance. However, the finding remains unresolved pending
completion of a significance determination.
Enforcement
As described In Section 1 R05.03.b.1 above, OLC 2.F required that one of the redundant
divisions (i.e., SSD Division 1, Including MOVs 1 CC-251 and 1 CC-208) would be free of
fire damage. Also, TS 6.8.1 required procedures for implementing the fire protection
program and for combating fires.
Contrary to the above requirements, the licensee failed to assure that one of the
redundant divisions (SSD Division 1, including MOVs 1 CC-251 and I CC-208) would be
free of fire damage. MOVs 1 CC-251 and 1 CC-208 were not protected from fire damage,
either by one of the physical methods described above or by procedures. The licensee
entered the finding into the corrective action program as AR 80089.
This finding and AV are unresolved pending completion of a significance determination,
in combination with the other fire protection issues identified in this report. This item is
identified as URI 50-400/02-11-04, Failure to Protect.MOVs 1 CC-251 and 1 CC-208, CC
for RCP Seals, From Maloperation Due To a Fire.
f0U'
12
.04
Operational Implementation of SSD Caoabilitv
a.
Inspection Scope
The team reviewed and walked down the local manual actions needed to achieve and
maintain hot shutdown for fires in all of the selected areas/zones as described in Section
1 R05.01.a. These manual actions were described in procedure AOP-036, Safe
Shutdown Following a Fire, Rev. 21.
The team also followed up on open VIO 50-400/02-08-01, Failure to Implement and
Maintain NRC Approved Fire Protection Program Safe Shutdown System Separation
Requirements. That VIO and related White finding had been left open in IR 50-400/02-
08. In a supplement to that IR dated October 4, 2002, the NRC had stated that licensee
modifications had reduced the risk significance of the degraded Thermo-Lag barrier to
that of a Green finding. However, VIO 50-400/02-08-01 was left open pending further
NRC review of licensee corrective actions and the development of internal NRC
inspection guidance, related to use of local manual actions as opposed to one of the
protection methods identified in NRC Position C.5.b.(2) of Branch Technical Position
(BTP) CMEB 9.5-1. During this inspection, the team reviewed and walked down the local
manual actions, needed to achieve and maintain hot shutdown, that were proceduralized
by the licensee during this inspection In AOP-36, Rev. 24, for the new ACP room fire
area.
The team reviewed and walked down the manual actions described above to verify that:
The procedures used for SSD were available to the appropriate staff.
The procedures used for SSD were consistent with the SSA methodology and
assumptions and also were consistent with fire pre-plan procedures.
The actions were described in the fire-protection-related licensing-basis
documents.
The procedures were written so that operator actions could be correctly
performed within the times assumed in the SSA.
Personnel required to achieve and maintain the plant in hot shutdown condition
from the MCR could be provided from normal onsite staff, exclusive of the fire
brigade.
Operator and fire brigade staffing would be adequate to complete the required
manual actions:
Operators had sufficient access to the equipment to perform the required actions.
Access to remote shutdown equipment and operator manual actions would not be
inhibited by smoke migration from one area to adjacent plant areas used to
accomplish SSD.
13
The training program for operators included appropriate lesson plans and job
performance measures (JPMs) for SSD activities.
b.
Findings
(1)
Reliance on Manual Actions In Place of Required Physical SeDaration or Protection
Introduction
The team identified a URI involving failure to follow the FPP. The URI was related to the
licensee's reliance on many manual actions in place of the required physical separation
or protection.
Descridption
The team found that the licensee used many local manual operator actions to achieve
and maintain hot shutdown in place of the required physical separation or protection of
cables and equipment. Further, the licensee had not obtained NRC approval for these
deviations from the approved FPP. This condition applied to all areas inspected,
including the new ACP fire area that had been recently created as corrective action for
previous Violation 50-400102-08-01. The local manual operator actions that were
reviewed are listed in Attachment 2. The team assessed that during a fire, an SSD NLO
would reasonably be able to perform each of the individual reviewed operator actions,
except those that are identified below as other findings. However, reliance on all of these
manual actions in place of physical separation or protection could increase the risk of
failure of SSD equipment to operate during a fire. There could be a risk that the NLO
would fail to perform every manual action in a timely and accurate manner, without
encountering unforseen difficulties or making a mistake.
Analysis
This issue could have more than minor safety significance because it could affect the
objectives of the Mitigating Systems Comerstone of Reactor Safety. The issue could
potentially affect the availability and reliability of sytems that mitigate initiating events to
prevent undesirable consequences. Also, when assessed in combination with other
findings identified in this report, the significance could be greater than very low
significance. However, the finding remains unresolved pending completion of a
significance determination.
Enforcement
As described in Section 1 R05.03.b.1 above, OLC 2.F required that one of the redundant
divisions would be free of fire damage. Further, if both divisions were located in the
same area, then one of the divisions was to be physically protected from fire damage by
one of three specified methods. The licensee's approved FPP did not provide for
reliance on operator actions in place of physical separation or protection of SSD
equipment. In addition, OLC 2.F and the UFSAR, Section 9.5.1, FPP, included quality
assurance requirements for fire protection. The FPP stated that a QA program was
14
being used to identify and rectify any possible deficiencies in design, construction, and
operation of the fire protection systems.
Contrary to the above requirements, the licensee failed to assure that one of the
redundant divisions would be free of fire damage by using one of the specified methods.
of physical protection. The licensee had not obtained NRC approval for reliance on the
operator actions listed in Attachment 2 in place of the required physical separation or
protection. In addition, those operator actions in Attachment 2 that are in place of
physical protection of cables in the new ACP fire area represent inadequate corrective
action for previous Violation 50-400/02-08-01. The licensee had entered this issue into
their corrective action program as AR 69721.
This finding and AV are unresolved pending completion of a significance determination,
in combination with the other fire protection issues identified in this report. This item is
identified as URI 50-400/02-11-05, Reliance on Manual Actions in Place of Required
Physical Separation or Protection.
(2)
Fire SSD ODerator Actions With Excessive Challenaes
Introduction
The team identified a URI involving failure to follow the FPP and TS 6.8.1. The URI was
related to certain procedure steps for SSD from a fire and for related corrective action for
previous VIO 50-400/02-08-01, associated with an inadequate Thermo-Lag fire barrier
assembly between the 'B' train switchgear room/ACP room and the 'A' train cable
spreading room. For the new ACP room fire area, certain cables were not physically
protected from the fire and certain SSD procedure steps, that were used in place of
physical protection of cables, involved excessive challenges to operators. Consequently,
a fire in the ACP fire area could result in a loss of all auxiliary feedwater.
Description
For a fire in Fire Area 1-A-ACP, AOP-36 steps 2.c and 14.a required the NLO to remove
fuses from transfer panel 1 B. Completing these steps would include the following
challenges:
The subject transfer panel was physically located approximately 20 feet from the
ACP room door. With a fire in the ACP room, the area around the transfer panel
could become uninhabitable before the NLO could complete these steps,
because some smoke from the fire could enter the transfer panel area from
around the door while the door was closed, and because smoke would certainly
enter the transfer panel area when the door was opened by the fire brigade to
attack the fire.
To physically reach the subject fuses, the NLO would need to place his or her
entire body inside a cabinet with an opening that was approximately 15 inches
wide. Also, the inside of the cabinet included energized electrical components on
each side of the cabinet, with about 15 inches of width between them. The
15
licensee had not ensured that all NLOs were physically capable of safely entering
that cabinet - the team noted that some NLOs were more than 15 inches wide.
Because the subject fuses were located on a panel inside the cabinet and
approximately seven feet above floor level, all but the tallest NLOs would need to
use a narrow, custom-made wooden step-stool inside the cabinet to be able to
reach the fuses. The team noted that the location of the step-stool was not
controlled.
Because the subject fuses were also located behind a plexiglass fuse cover that
was held in place by small metal screws, the NLO would need to raise his or her
hands above the level of his or her head and use a metal screwdriver to remove
the fuse cover. The licensee had not ensured that all NLOs were physically
capable of completing this activity. Furthermore, because this activity involved
manipulating a metal screwdriver inside an energized electrical cabinet, the team
considered the activity to involve a personnel safety hazard.
To identify the correct fuses to be pulled, the NLO must first identify the cabinet in
which the fuses are located, and then identify the fuses themselves, within that
cabinet. The team observed that the subject cabinet was physically adjacent to
four identical cabinets, that these cabinets were not labeled on the side from
which the NLO would enter, and that the instructions in AOP-036 did not identify
the subject cabinet. Furthermore, the team observed that the labels which
uniquely identified the subject fuses within the cabinet were difficult to see - they
were partially obscured by cables which had been landed on adjacent terminal
blocks.
The team considered that these challenges were excessive and that there was not
reasonable assurance that all NLOs would be able to perform the actions during a fire.
Consequently, operators would not able to start the turbine-driven AFW pump and the
AFW system could become unavailable. The team concluded that these procedure
steps were inadequate and that consequently they represented inadequate corrective
action for VIO 50-400/02-08-01.
Analysis
This finding had more than minor significance because it affected the objectives of the
Mitigating Systems Comerstone of Reactor Safety. The finding affected the availability
and reliability of systems that mitigate initiating events to prevent undesirable
consequences. Also, when assessed in combination with other findings identified in this
report, the significance could be greater than very low significance. However, the finding
remains unresolved pending completion of a significance determination.
Enforcement
As described in Section 1 R05.03.b.1 above, OLC 2.F required that one of the redundant
divisions would be free of fire damage. Further, if both divisions were located in the
same area, then one of the divisions was to be physically protected from fire damage by
one of three specified methods. The licensee's approved FPP did not provide for
16
reliance on operator actions in place of physical separation or protection of SSD
equipment. Also, TS 6.8.1 required procedures for implementing the fire protection
program and for combating fires. In addition, OLC 2.F and the UFSAR, Section 9.5.1,
FPP, included quality assurance requirements for fire protection. The FPP stated that a
QA program was being used to identify and rectify any possible deficiencies in design,
construction, and operation of the fire protection systems.
Contrary to the above requirements, the licensee failed to protect the turbine-driven AFW
pump from effects of a fire where it was relied on for SSD. In addition, the licensee's
corrective actions for a previous VIO 50-400/02-08-01 were inadequate because they
failed to rectify deficiencies in design, construction, and operation related to SSD from a
fire in the area of the ACP room. The licensee entered the finding into the corrective
action program as AR 80214.
This finding and AV are unresolved pending completion of a significance determination,
in combination with the other fire protection issues identified in this report. This item is
identified as URI 50-400/02-11-06, Fire SSD Operator Actions With Excessive
Challenges.
(3)
Too Many SSD Actions for Operators to Perform
Introduction
The team identified a URI involving failure to follow the FPP and TS 6.8.1. The URI was
related to an inadequate procedure for SSD from a fire and for Inadequate corrective
action for VIO 50-400/02-08-01. For a fire in certain SSA areas of the RAB (including the
new ACP fire area), AOP-36 included too many SSD contingency actions to respond to
potential spurious actuations for the one designated SSD NLO to perform all of the
actions. Consequently, equipment that was relied on for SSD may not be available.
DescriDtion
The team found that for each fire SSA area inspected, AOP-036 required operators to
complete a relatively large number of manual actions outside the main control room. The
team determined that the normal shift operating crew included four NLOs; three were
assigned to the fire brigade and one was assigned to be the SSD NLO. The local
manual operator actions required to achieve and maintain hot shutdown for each of the
fire areas inspected are listed in Attachment 2 to this report. The most demanding fire
areas were fire area 1-A-ACP, which included about 55 such actions, and fire area 1-A-
BAL-B, which included about 39 such actions.
Also, since the SSA did not ensure that offsite power would not be lost due to a fire in
any of the SSA areas inspected, operators were expected to be able to respond to a loss
of offsite power (LOOP) and reactor trip while performing the fire SSD actions. The team
noted that a LOOP or reactor trip could place even more demands on the one NLO who
was not fighting the fire.
The team found that while most of the manual actions in these SSA areas involved one-
time actions (like opening a breaker), others could require the NLO to monitor plant
17
conditions and make system adjustments over an extended period of time. The manual
actions which could require dedicated NLO attention, and thus possibly detract from the
successful and timely performance of subsequent required local manual operator
actions, included the following:
In Section 3.0 of AOP-036, which was to be performed for a fire in any-of the SSA
areas inspected, Step 13.b(3) required the NLO to establish continuous
communications with the MCR, locally shut 1 CS-228 to isolate the normal
charging flow control valve (FCV) and then to locally control charging flow by
throttling the bypass valve, 1CS-227. Both valves were in close proximity and
located in the scalloped area of the 248-ft level in the RAB. This area was
located in the radiation-controlled area (RCA) and radiation levels at these valves
were elevated but within 10 CFR 20 limits. A sound powered phone with a long
extension cord was located in the area to allow the NLO to wait In low dose areas
between valve manipulations f the NLO's radio was not functional. However,
local manual operator actions subsequent to this step could be adversely
Impacted [e.g., Section 3.0, Step 14.b for locally responding to a failed open
steam generator power operated relief valve (PORV)].
In Attachment 1 of AOP-036, Step 13.c for fire area 1-A-ACP required the NLO to
locally operate a PORV on the C steam generator, to obtain and maintain the
desired RCS temperature. AOP-36 requires operators to trip the reactor If the fire
is not contained in the ACP panel or involves any electrical cable tray.
Consequently, during a large fire in the ACP room the unit would not be at steady
state when this action was undertaken, and because a fire in this area may
complicate operator efforts to stabilize the plant, the NLO who undertakes this
action may be required to monitor RCS temperature and make appropriate
adjustments to the PORV position almost continuously and for some time, until
the plant Is reasonably stable.
In Attachment 1 of AOP-036, Step 1 4.b for fire area 1 -A-ACP required the NLO to
throttle 1 AF-1 49 to maintain level in the C steam generator. For the same
reasons as described above, the NLO who undertakes this action may be
required to continue to monitor steam-generator level and make appropriate
adjustments to the position of 1AF-149 almost continuously and for some time,
until the plant is reasonably stable.
The team found that some of the required manual actions would be completed inside the
radiologically controlled area (RCA), while others would be completed outside the RCA.
The team also observed that completing the manual actions in AOP-036, in the order in
which they are described in that procedure, would require the SSD NLO to enter and exit
the RCA several times. The team noted that:
some manual actions involved valves identified as potentially contaminated or
located in contamination areas,
radioactive radon gas can become associated with anyone who passes through
the RCA,
18
hand or foot contamination as well as radon gas can cause a portal monitor to
alarm, and
anyone who is in a portal monitor when it alarms must wait at the exit point for
health physics (HP) technicians to complete a detailed survey to determine the
true cause of the alarm, before proceeding.
The team noted that the licensee had no emergency dosimeters or rapid ingress/egress
procedures in place for use during plant emergency situations. The team therefore
considered that every time the SSD NLO exited the RCA, that NLO may experience a
portal-monitor alarm, and may therefore be forced to wait for HP technicians to arrive at
the exit and complete a detailed survey before proceeding. The team received a portal
monitor alarm on many occasions during this inspection. Operators stated that, if they
received such an alarm during a fire, they would wait for an HP technician before
proceeding to perform SSD actions.
The team considered that the manual actions in AOP-036 could not reasonably be
completed by the available staff, because:
the SSD NLO may be required to complete as many as 55 manual actions,
several manual actions required dedicated operator attention,
some of the manual actions could require a considerable amount of time to
complete,
some manual actions could be delayed by RCA portal-monitor alarms, and
only one NLO would have been available to complete all SSD manual actions.
The team concluded that the SSD NLO may not be able to accomplish some required
manual actions in a timely manner. Consequently, some equipment relied on for SSD
may not be available. For example, the SSD NLO may not be able to respond to a failed
open steam generator PORV, locally throttle a steam generator PORV, or throttle AFW.
The team therefore considered AOP-36 to be inadequate.
Analysis
This finding had more than minor significance because It affected the objectives of the
Mitigating Systems Cornerstone of Reactor Safety. The finding affected the availability
and reliability of systems that mitigate initiating events to prevent undesirable
consequences. Also, when assessed in combination with other findings identified in this
report, the significance could be greater than very low significance. However, the finding
remains unresolved pending completion of a significance determination.
Enforcement
As described in Section 1 R05.03.b.1 above, OLC 2.F required that one of the redundant
divisions would be free of fire damage. Further, if both divisions were located in the
19
same area, then one of the divisions was to be physically protected from fire damage by
one of three specified methods. Also, TS 6.8.1 required procedures for implementing the
fire protection program and for combating fires. In addition, OLC 2.F and the UFSAR,
Section 9.5.1, FPP, included quality assurance requirements for fire protection. The FPP
stated that a QA program was being used to identify and rectify any possible deficiencies
in design, construction, and operation of the fire protection systems.
Contrary to the above requirements, the licensee failed to protect various equipment
either physically or procedurally from the effects of a fire where that equipment was relied
on for SSD. In addition, the licensee's corrective actions for previous VIO 50-400/02-08-
01 were inadequate because they failed to rectify deficiencies in design, construction,
and operation related to SSD from a fire In the area of the ACP room. The licensee
entered the findin
to the corrective action program as AR 80215.
a
This finding
d AV are unresolved pending completion of a significance determination,
in combin ion with the other fire protection issues identified in this report. This item is
identified as URI 50-400/02-11-07, Too Many SSD Actions for Operators to Perform.
(4)
Using the BAT Without Level Indication
Introduction
The team Identified a URI involving failure to follow the FPP and TS 6.8.1. The URI was
related to an inadequate procedure for SSD from a fire. For a fire in SSA area 1-A-BAL-
B, the SSD procedure directed operators to take CSIP suction from the BAT even if BAT
level indication were lost. However, the charging volume needed for RCS cooldown
would have emptied the BAT and damaged the SSD CSIP.
Description
The team found that, for a fire in SSA area 1-A-BAL-B-B2 or -B3, near the BAT, AOP-36
directed operators to use the BAT as a suction source for the CSIPs even if the BAT
level indication was lost due to the fire. This alignment was to be used in preparation for
and during a cooldown of the RCS. However, the team analyzed that the charging
volume needed for RCS cooldown would have emptied the BAT and damaged the SSD
CSIP.
The SSA stated that, if BAT level indication was lost due to a fire, then the RWST was to
be used as a suction source for the CSIPs. However, this analysis was not implemented
in AOP-36. AOP-36 was inadequate because it failed to recognize that the charging
volume needed for RCS cooldown would have emptied the BAT and damaged the SSD
CSIP.
Analysis
This finding had more than minor significance because it affected the objectives of the
Mitigating Systems Cornerstone of Reactor Safety. The finding affected the availability
and reliability of systems that mitigate initiating events to prevent undesirable
consequences. Also, when assessed in combination with other findings identified in this
Ve
20
report, the significance could be greater than very low significance. However, the finding
remains unresolved pending completion of a significance determination.
Enforcement
As described in Section 1 R05.03.b.1 above, OLC 2.F required that one of the redundant
divisions would be free of fire damage. Further, if both divisions were located in the
same area, then one of the divisions was to be physically protected from fire damage by
one of three specified methods. Also, TS 6.8.1 required procedures for implementing the
fire protection program and for combating fires.
Contrary to the above requirements, the licensee failed to protect the BAT level indication
from effects of a fire where it was relied on for SSD, and the AOP-36 reliance on using
the BAT without levedication was inadequate. The licensee entered the finding into
the corrective a
program as AR 75065.
This finding nd AV are unresolved pending completion of a significance determination,
in combin ion with the other fire protection issues identified in this report. This item is
identfied as URI 50-400/02-11-08, Using the Boric Acid Tank Without Level Indication.
.05
Emeraency Communications
a.
Inspection Scope
The team reviewed the adequacy of the communication systems relied upon to
coordinate the shutdown of the unit and fire brigade duties, including the site paging
(PA), portable radio, and sound-powered phone systems. The team reviewed the
licensee's portable radio channel features to assess whether the system and its
repeaters were protected from exposure fire damage. During walkdowns of sections of
the post-fire SSD procedure, the team checked if adequate communications equipment
would be available for the personnel performing the procedure. The team also reviewed
the periodic testing of the site fire alarm and PA systems; maintenance checklists for the
sound-powered phone circuits and amplifiers; and inventory surveillance of post-fire SSD
operator equipment to assess whether the maintenance/surveillance test program for the
communications systems was sufficient to verify proper operation of the systems.
b.
Firidings
No findings of significance were identified.
.06
Emeraency Lighting
a.
Inspection Scope
The team reviewed the design and operation of DC emergency lighting system self-
contained, battery powered emergency lighting units (ELUs) as described in UFSAR
Sections 9.5.1 .2.2.e and 9.5.3. During plant walk downs of selected areas where
operators performed local manual actions defined in the post-fire SSD procedure, the
team inspected area ELUs for operability and checked the aiming of lamp heads to
21
determine if adequate Illumination was available to correctly and safely perform the
actions required by the procedures. The team inspected emergency lighting features
along access and egress pathways used during SSD activities for adequacy and
personnel safety. The locations and identification numbers on the ELUs were compared
to design drawings to confirm the as-built configuration. The team also checked if these
battery power supplies were rated with at least an 8-hour capacity. In addition, the team
reviewed the manufacturer's Information and the licensee's licensee periodic
maintenance tests to verify that the ELUs were properly designed and were being
maintained in an operable manner.
b.
Findings
Introduction
U
The team identified a URI involving failure to provide fixed, self-contained lighting with
individual eight-hour-minimum battery power supplies in areas that must be manned for
safe shutdown and for inadequate corrective action for previous VIO 50-400/02-08-01.
Descridtion
In the SSA areas in which the team walked down safe shutdown manual actions, the
team identified that the locations for local manual operator actions listed in Attachment 3
to this report would not be illuminated by fixed, self-contained lighting with individual
eight-hour-minimum battery power supplies. Some of these local manual operator
actions that were lacking required illumination had been added as corrective action for
previous VIO 50-400/02-08-01.
The team observed that about 17 of the locations for local manual operator actions had
no emergency lighting, as identified in Attachment 3. [The team also observed that many
more locations for local manual operator actions had fluorescent lights, that would be
powered by the safety-related emergency diesel generators, that could provide
emergency illumination. However, these lights did not meet the requirements for lights
with eight-hour batteries. These locations are separately identified in Attachment 3.
Also, the team noted that the licensee had not requested NRC exemptions from the
requirement to provide lights with eight-hour batteries.]
The team also observed that all NLOs routinely carried flashlights and had access to
more flashlights that were stored in the auxiliary building. The team assessed that, by
using a flashlight, the SSD NLO would be able to perform the required actions but that
those actions would take more time to perform when relying on illumination by a flashlight
and could be less reliable.
Analysis
This finding had more than minor significance because it affected the objectives of the
Mitigating Systems Cornerstone of Reactor Safety. The finding affected the availability
and reliability of systems that mitigate initiating events to prevent undesirable
consequences. Also, when assessed in combination with other findings identified in this
22
report, the significance could be greater than very low significance. However, the finding
remains unresolved pending completion of a significance determination.
Enforcement
OLC 2. F. and UFSAR Section 9.5.1 stated that BTP 9.5-1 was used in the design of the
fire protection program for safety-related systems and equipment and for other plant
areas containing fire hazards that could adversely affect safety-related systems. BTP
9.5-1, Section C.5.g, "Lighting and Communication," paragraph (1), required that fixed
self-contained lighting consisting of fluorescent or sealed-beam units with individual
eight-hour-minimum battery power supplies should be provided in areas that must be
manned for safe shutdown and for access and egress routes to and from all fire areas.
In addition, OLC 2.F and the UFSAR, Section 9.5.1, FPP, included quality assurance
requirements for fire protection. The FPP stated that a QA program was being used to
identify and rectify any possible deficiencies in design, construction, and operation of the
fire protection systems.
Contrary to the above requirements, the licensee failed to provide fixed self-contained
lighting consisting of fluorescent or sealed-beam units with individual eight-hour-minimum
battery power supplies in the location of the manual actions identified above and listed in
Attachment 3. In addition, the licensee's corrective actions for previous VIO 50-400/02-
08-01 were inadequate because they failed to rectify deficiencies in design, construction,
and operation related to SSD from a fire in the area of the ACP room. The licensee
entered this finding into the corrective action program as AR 79047.
This finding and AV are unresolved pending completion of a significance determination,
in combination with the other fire protection issues identified in this report. This item is
identified as URI 50-400/02-11-09, Failure to Provide Required Emergency Ughting for
SSD Operator Actions.
.07
Cold Shutdown Reoairs
a.
Inspection ScoDe
The team reviewed existing procedures and examined plant equipment to establish that
the licensee had dedicated repair procedures, equipment, and materials to accomplish
repairs .of damaged components required for cold shutdown, that these components
could be made operable, and that cold shutdown could be achieved within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The
team examined cold shutdown repair equipment and replacement electrical power and
control cables for systems needed to take the plant to cold shutdown following a large
fire. The team evaluated the estimated manpower and the time required to perform post-
fire repairs for reasonableness.
b.
Findings
No findings of significance were identified.
23
.08
Fire Barriers and Fire Area/Zone/Room Penetration Seals
a.
Inspection Scope
The team walked down the selected fire zones/areas to evaluate the adequacy of the fire
resistance of barrier enclosure walls, ceilings, floors, and cable protection. This
evaluation also included fire barrier penetration seals, fire doors, fire dampers, cable tray
fire stops, and fire barrier partitions to ensure that at least one train of SSD equipment
would be maintained free of fire damage from a single fire. The team observed the
material condition and configuration of the installed fire barrier features and also
reviewed construction details and supporting fire endurance tests for the installed fire
barrier features. The team compared the observed fire barrier penetration seal
configurations to the design drawings and tested configurations. The team also
compared the penetration seal ratings with the ratings of the barriers in which they were
installed. In addition, the team reviewed licensing documentation, engineering
evaluations of Generic Letter 86-10 fire barrier features, and NFPA code deviations to
verify that the fire barrier installations met design requirements and license commitments.
b.
Findings
No findings of significance were identified.
.09
Fire Protection Systems. Features, and EguiDment
a.
Inspection Scope
The team reviewed flow diagrams, electrical schematic diagrams, periodic test
procedures, engineering technical evaluations for NFPA code deviations, operational
valve lineup procedures, and cable routing data for the power and control circuits of the
motor-driven fire pump, the diesel-driven fire pump, and the fire protection water supply
system yard mains. The review evaluated whether the common fire protection water
delivery and supply components could be damaged or inhibited by fire-induced failures of
electrical power supplies or control circuits and subsequent possible loss of fire water
supply to the plant. Additionally, team members walked down the fire protection water
supply system in selected fire areas to assess the adequacy of the system material
condition, consistency of the as-built configuration with engineering drawings, and
operability of the system in accordance with applicable administrative procedures and
NFPA standards.
The team examined the adequacy of installed fire protection features in accordance with
the fire area and system spatial separation and design requirements in BTP CMEB 9.5
4-The team walked down accessible portions of the fire detection and alarm systems in
the selected fire areas to evaluate the engineering design and operation of the installec~
configurations. The team also reviewed engineering drawings for fire detector spacing
and locations in the four selected fire areas for consistency with the licensee's fire
protection plan and the requirements in NFPA 72E.
The team also walked down the selected fire zones/areas with automatic sprinkler
suppression systems installed to assure proper type, placement and spacing of the
24
heads/nozzles and the lack of obstructions. The team examined vendor information,
engineering evaluations for NFPA code deviations, and design calculations to verify that
the required suppression system density for each protected area was available.
The team reviewed the adequacy of the design, installation and operation of the manual
suppression standpipe and fire hose system for the selected fire areas. The team
examined design calculations and evaluations to verify that the required fire hose water
flow and sprinkler system density for each protected area were available. The team
checked a sample of manual fire hose lengths to determine whether they would reach
the SSD equipment. Additionally, the team observed placement of the fire hoses and
extinguishers to assess consistency with the fire fighting pre-plan drawings.
b.
Findings
No findings of significance were identified.
.10
Compensatory Measures
a.
Inspection Scope
The team reviewed the licensee's Fire Protection System Engineering Status Reviews
which identified each fire protection system's performance problems and regulatory
issues. The team also reviewed the Fire Protection Out of Service Log generated for the
last 18 months and associated compensatory measures. The review was performed to
verify that the risk associated with removing fire protection and/or post-fire systems or
components was properly assessed and adequate compensatory measures were
implemented In accordance with the approved fire protection program.
b.
Findings
No findings of significance were identified.
4.
OTHER ACTIVITIES (OA)
40A2 Identification and Resolution of Problems
a.
Inspection ScoDe
The team reviewed the corrective action program procedures and a selected sample of
condition reports associated with the Harris FPP to verify that the licensee had an
appropriate threshold for identifying issues. The team also reviewed licensee audits and
assessments of fire protection and safe shutdown. The team evaluated the effectiveness
of the corrective actions for the identified issues.
b.
Findings
The team found that licensee corrective actions for VIO 50-400/02-08-01 regarding an
Inadequate fire barrier wall were inadequate, in that the licensee's corrective actions for
1'
7
~
that violation contributed to four of the findings described above. Since the findings are
JA
25
unresolved pending completion of the significance determination, VIO 50-400102-08-01
will remain open.
The team also found that licensee audits and self-assessments in the area of SSD were
weak. The audits and self-assessments had not identified the types of findings that this
inspection found. Contributing factors included a lack of attention to detail; for example,
not tracing cable routings or walking down operator actions as was done in this
inspection. In addition, the CP&L corporate Nuclear Assessment Section (NAS) audits of
fire protection at Shearon Harris did not look at SSD. A Peer Report included in the
November 2000 NAS audit of Shearon Harris fire protection stated: Harris NAS Fire
Protection Program Audits of recent past have not included fire events safe shutdown
within the scope of the audits due to a reliance on engineering self-assessments. It is
the opinion of the auditor that the scope of future Harris NAS Fire Protection
assessments should include fire events safe shutdown related documentation and
activities." However, the team noted that subsequent NAS audits of Harris fire
protection did not audit SSD.
The team noted that the licensee's initial corrective actions to the findings described in
this report were timely and responsive. The licensee revised SSD procedures three
times during the inspection, made a 10 CFR 50.72 report to the NRC, and stationed an
additional SSD NLO.
40A6 Meetings
Exit Meeting Summary
The team presented the inspection results to Mr. J. Scarola and members of his staff at
the conclusion of the inspection on December 20, 2002. The licensee acknowledged the
findings presented. Proprietary information is not included in this inspection report.
SUPPLEMENTAL INFORMATION
Partial List of Persons Contacted
Licensee
D. Baksa, Supervisor, Equipment Perfromance
J. Caves, Licensing Supervisor
R. Duncan, Director of Site Operations
M. Fletcher, Manager, Fire Protection Program
P. Fulford, Superintendent, Design Engineering
C. Georgeson, Supervisor, El&C Design
W. Gregory, Operations Fire Protection Specialist
W. Gurganion, Manager, NAS
T. Hobbs, Manager, Operations
A. Khanpour, Manager, Engineering
F. Lane, Jr., Senior Nuclear Work Management Specialist
J. Laque, Manager, Maintenance
T. Morton, Site Services Manager
J. Scarola, Site Vice President
B. Waldrep, Plant General Manager
NRC
J. Brady, Senior Resident Inspector, Shearon Harris
H. Christensen, Deputy Director, Division of Reactor Safety (DRS), Region II (RI)
C. Ogle, Chief, Engineering Branch 1, DRS, RII
Items Opened. Closed, and Discussed
Opened
50-400/02-11-01
50-400/02-11-02
50-400102-1 1-03
50-400/02-11-04
URI
URI
Failure to Protect Charging System MOV I CS-1 65, VCT
Outlet to CSIPs, From Maloperation Due To a Fire (Section
1 R05.03.b.1)
Failure to Protect Charging System MOVs 1CS-169, 1CS-
214, 1 CS-218, and 1CS-219 From Maloperation Due To a
Fire (Section 1 R05.03.b.2)
Failure to Protect Charging System MOVs 1 CS-1 66, 1 CS-
168, and ICS-217 From Maloperation Due To a Fire
(Section 1 R05.03.b.3)
Failure to Protect Component Cooling MOVs 1CC-251 and
1CC-208, CC for RCP Seals, From Maloperation Due To a
Fire (Section 1 R05.03.b.4)
Attachment 1
2
50-400/02-11-05
50-400/02-11-06
50-400/02-11-07
50-400/02-11-08
50-400/02-11-09
URI
URI
Reliance on Manual Actions in Place of Required Physical
Separation or Protection From a Fire (Section 1 R05.04.b.1)
Fire SSD Operator Actions With Excessive Challenges
(Section 1 R05.04.b.2)
Too Many Fire SSD Actions for Operators to Perform
(Section 1 R05.04.b.3)
Using the Boric Acid Tank Without Level Indication (Section
1 R05.04.b.4)
Failure to Provide Required Emergency Lighting for SSD
Operator Actions (Section 1 R05.06.b)
Closed
None
Discussed
50-400/02-08-01
V10
Failure to Implement and Maintain NRC Approved Fire
Protection Program Safe Shutdown System Separation
Requirements (Section 40A2b
I-,
-i
List of Inspection Documents Reviewed
PROCEDURES
AOP-036, Safe Shutdown Following a Fire, Rev. 21 and Rev. 24
AOP-038, Rapid Downpower, Rev. 2
AP-301, Seasonal Weather Preparations and Monitoring, Rev. 34
EOP-EPP-004, Reactor Trip Response, Rev. 10
EOP-Guide-1, Path 1 Guide, Rev. 14
FIR-NGGC-0003, Hot Work Permit, Rev. 0
FPP-001, Fire Protection Program Manual, Rev. 22
FPP-002, Fire Emergency, Rev. 22
FPP-003, Fire Investigation Report, Rev. 7
FPP-004, Transient Combustible Control, Rev. 12
FPP-005, Duties of a Fire Watch, Rev. 15
FPP-007, Control of Flammable and CombustibleFPP-013, Fire Protection - Minimum
Requirements and Mitigating Actions, Rev. 30
FPP-014, Fire Protection Surveillance Requirements, Rev. 12
FPT-3002, Fire Main Valve Position Verification, Rev. 15
FPT-3006, Fire Main Flow Test, Rev. 6
Attachment 1
3
FPT-31 01, Fire Hose Rack Inspection: Auxiliary Building, Rev. 11
FPT-3120, Fire Hose Valve Operability Test: Auxiliary Building, Rev. 4
FPT-3151, Fire Extinguisher Inspection: Auxiliary Building, Rev. 0
FPT-3425, Fire Damper Inspection: Reactor Auxiliary Building, 286 Elevation, Rev. 9
FPT-3550, Fire Penetration Seal Visual Inspection, Rev. 10
MPT-E0030, Self Contained DC Emergency Lighting System Test/Inspection, Rev. 16
MPT-E0032, Self Contained DC Emergency Lighting System Eight Hour Life Test, Rev. 14
MST-10277, Electrical Power Feed Switchover for RHR Inlet Isolation Valve 1 RH-i
(1 RH-V502SB-1)
OP-110, Section 8.3, Venting the Si Accumulators, Rev. 18
OP-1 72, Reactor Auxiliary Building HVAC System, Rev. 25
RTP-006, Maintaing Floor Drain Loop Seals, Rev. 7
TPP-219, Emergency Services Training Program, Rev. 9
DESIGN CRITERIA AND DESIGN BASIS DOCUMENTS
DBD-315, Fire Detection System, Rev. 1
DBD-316, Fire Barrier System, Rev. 1
DBD-317, Water-Based Fire Suppression System, Rev. 0
SD-149, System Description Fire Protection/Detection Systems, Rev. 16
ENGINEERING CALCULATIONS AND EVALUATIONS
4-RMB, High Resistance Grounding Calculation - 6.9 kV System, Rev. 5, dated 2/19/93
E-5506, Appendix R Coordination Study, Rev. 7, dated 5/17/02
HNP-M'BMRK-002, Code Compliance Evaluation NFPA 72 D
-Fire Detection Systems, Rev. 0
HNP-M/BMRK-003, Code Compliance Evaluation NFPA 80
-Standard for Fire Doors and Windows, Rev. 0
HNP-M/BMRK-005, Code Compliance Evaluation NFPA 10
-Portable Fire Extinguishers, Rev. 0
HNP-MIBMRK-006, Code Compliance Evaluation NFPA 14
-Standpipe and Hose Systems, Rev. 0
HNP-M/BMRK-008, Code Compliance Evaluation NFPA 20
-Standard for Outside Protection, Rev. 0
HNP-M/BMRK-009, Code Compliance Evaluation NFPA 13
-Sprinkler Systems, Rev. 0
HNP-9-RAB-6B, SWGR RM. UB" Ventilation System Served by AH-13, Rev. 2
COMPLETED MAINTENANCE AND SURVEILLANCE TEST PROCEDURESIRECORDS
Periodic Maintenance Checklist Tables CL-E-001 3, -0038, -0053, Safe Shutdown Testing for
PA Amplifiers and Sound Powered Phone Circuits, dated November 4, 2002
Work Order Package 00192587, Perform MPT-E0030, dated March 1, 2002
Work Order Package 00125222, Perform MPT-E0032, dated December 11, 2001
Work Order Package 00132600, Perform MPT-E0032, dated January 21, 2002
FPT-3120, Fire Hose Valve Operability Test: Auxiliary Building, dated March 8, 2002
Attachment 1
4
FPT-3205, Fire Detector Functional Test: Local Fire Detector Control Panel 5, dated October 2,
2002
FPT-3206, Fire Detector Functional Test: Local Fire Detector Control Panel 6, dated July 30,
2002
FPT-3302, Main Drain Test Auxiliary Building, dated May 18, 2001
FPT-3550, Fire Penetration Seal Visual Inspection, E385A, dated February 28, 1998
FPT-3550, Fire Penetration Seal Visual Inspection, E374, dated April 20,1991
FPT-3550, Fire Penetration Seal Visual Inspection, P839, dated February 2, 1998
DRAWINGS
84-60823A-01, Sheets 1 and 2, I-T-E/Gould Motor Control Center Layout for MCC 1A35-SA,
Rev 6
84-60823A-01, Sheet 1, MCC 1A35-SA, Rev. 7
84-60823A-01, Sheet 2, MCC 1A35-SA, Rev. 7
84-60823A-05, Sheet 1, MCC 1 B35-SB, Rev. 2
84-60823A-06, Sheet 2, MCC 1 B35-SB, Rev. 4
1364-93040, EC-1 through EC-6 Internal Conduit Fire Seals, Rev 3
1364-93049, EL-1 and EL-2 WalVFloor Electrical Fire Seals, Rev 3
CAR-2165-G-1 97S01, Fire Protection Piping Reactor Auxiliary Building, Sht. 1, Rev. 15
CAR-2166-341, Reactor Auxiliary Building Lighting, Sht. 1, Rev. 5
CAR-2166-342, Reactor Auxiliary Building Lighting, Sht. 2, Rev. 6
CAR-2166-345, Reactor Auxiliary Building Lighting, Sht. 1, Rev. 9
CAR-2166-401/2581, Control Wiring Diagram, Motor Driven Fire Pump, Rev. 9
CAR-2166-401/2583, Control Wiring Diagram, Diesel Driven Fire Pump, Rev. 6
CAR-2166 B-401, Sheet 160, Pressurizer Power Relief Isolation Valve 1-8000A, Rev. 20
CAR-2166 B-401, Sheet 161, Pressurizer Power Relief Isolation Valve 1-8000B, Rev. 19
CAR-2166 B-401, Sheet 1922, Auxiliary Feedwater Pump 1 B-SB (MD), Rev. 11
CAR-2166 B-401, Sheet 1921, Auxiliary Feedwater Pump 1A-SA (MD), Rev. 10
CAR-2166 B-401, Sheet 1978, Auxiliary Feedwater Turbine Governor System 1 X-SB, Rev. 7
CAR-2166 B-401, Sheet 419, Containment Sump to RHR 1-8812B (1 SI-311), Rev. 22
CAR-2166 B-401, Sheet 418, Containment Sump to RHR 1-8812A (1SI-310), Rev. 20
CAR-2166 SK-E-542S08, Sheet 1, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.2
CAR-2166 SK-E-542S09, Sheet 2, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.3
CAR-2166 SK-E-542S10, Sheet 3, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], El 236.0', REV.2
CAR-2166 SK-E-S1 1, Sheet 4, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.2
CAR-2166 SK-E-542S12, Sheet 1, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.4
CAR-2166 SK-E-542S13, Sheet 2, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.3
CAR-2166 SK-E-542S1 4, Sheet 3, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.3
CAR-2166 SK-E-542S15, Sheet 4, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Attachment 1
5
Plan], Unit 1, REV.3
CAR-2166 SK-E-542S1 6, Sheet 1, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.4
CAR-2166 SK-E-542S1 8A, Sheet 1, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.4
CAR-2166 SK-E-542S1 8B, Sheet 1, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.4
CAR-2166 SK-E-542S23, Sheet 1, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.3
CAR-2166 SK-E-542S1 6, Sheet 1, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.2
CAR-2166 SK-E-542S17, Sheet 2, Reactor Auxiliary Building SSD Analysis [Tray and Conduit
Plan], Unit 1, REV.5
CAR-2166 SK-E-542S1 8A, Sheet 3A, Reactor Auxiliary Building SSD Analysis [Tray and
Conduit Plan], Unit 1, REV.5
CAR-2166 SK-E-542S18B, Sheet 3B, Reactor Auxiliary Building SSD Analysis [Tray and
Conduit Plan], Unit 1, REV.3
CAR-2166 SK-E-542S20, Sheet 1, Reactor Auxiliary Building SSD Analysis Tray and Conduit
Plan], Unit 1, REV.3
CAR-2166 B-401, Sheet 959, RCP Thermal Barrier Containment Isolation Valve 1 -9483
(1CC-249), Rev. 18
CAR-2166 B-401, Sheet 962, RCP Thermal Barrier Containment Isolation Valve 1 -9484
(1CC-251), Rev. 16
CAR-2166 B-401, Sheet 947, RCP Thermal Barrier Isolation Valve 1 FCV-685 (1CC-252), Rev.
14
CAR-2166 B-401, Sheet 956, RCP Component Cooling Water Supply Isolation Valve 1 -9480B
(ICC-208), Rev. 15
CAR-2166 B-401, Sheet 955, RCP Component Cooling Water Supply Isolation Valve 1 -9480A
(1 CC-169), Rev. 14
CAR-2166 B-401, Sheet 245, Volume Control Tank Outlet Isolation Valve 1-LCV-1 15E
(1 CS-1 66), Rev. 21
CAR-2166 B-401, Sheet 243, Volume Control Tank Outlet Isolation Valve 1 -LCV-1 15C
(1 CS-1 65), Rev. 20
CAR-2166 B-401, Sheet 297, Charging/Safety Injection Pump Discharge Header Isolation
Valve 1-8132A (1 CS-219), Rev. 19
CAR-2166 B-401, Sheet 294, Charging/Safety Injection Pump Suction Header Isolation Valve
1-8130B (1 CS-168), Rev. 18
CAR-2166 B-401, Sheet 299, Charging/Safety Injection Pump Discharge Header Isolation
Valve 1-8133A (1 CS-218), Rev. 19
CAR-2166 B-401, Sheet 295, Charging/Safety Injection Pump Suction Header Isolation Valve
1-8131A (1CS-169), Rev. 19
CAR-2166 B-401, Sheet 270, Charging/Safety Injection Pumps Miniflow Isolation Valve 1-8106
(1CS-214), Rev. 17
CAR-2166-G-037S01, One Line Wiring Diagram Bus 1-4A, Rev. 11
CAR-2168-G-506S01, HVAC - Reactor Auxiliary Building, Plan El. 261, Rev. 12
CAR-2168-G-506S01, HVAC - Reactor Auxiliary Building, Plan El. 286, Rev. 12
CAR-2168-G-517SO5, Air Flow Diagram, Rev. 17
Attachment 1
e
l:
6
CAR-2168-G-61 1, Plumbing and Drainage, Rev. 13
CAR-2168-G-614S01, Riser Diagram, Plumbing and Drainage, Rev. 4
CAR-SH-E-1 OB, Ebasco Specification 210-73, Motor Control Centers for Use in Central Power
Station- Class 1 E, Rev. 13
CAR-SH-IN-24, Fire Protection Multi-cycle Deluge Valve System Logic, Rev. 10
CPL-2165-G1OOOS12, Sheet 2, SSD Flow Diagram Safety Injection System, Rev. 0
CPL-2165-G1000S13, Sheet 3, SSD Flow Diagram Safety Injection System, Rev. 0
CPL-2165-GlOOOS21, Sheet 3, SSD Component Cooling Water System, Rev. 0
CPL-2165-S - 1365, Simplified Flow Diagram for CVCS System, Rev. 17
CPL-2165-G1 00S23, SSD HVAC Essential Services Chilled Water Condenser Flow Diagram
Unit, 1-SA, Div 1, Rev. 1
CPL-2165-GI 000S26, SSD HVAC Essential Services Chilled Water Condenser Flow Diagram
Unit, 1-SB, Div 2, Rev.
CPL-2165-G1000516, Sheet 3, SSD HVAC Essential Services Chilled Water Condenser Flow
Diagram Unit, 1-SA, Div 1, Rev. 1
FD-CAR-1.10(L) 3, Detector Locations - Reactor Auxiliary Building, Plan El. 261, Rev. 5
FD-CAR-1.10(L) 4, Detector Locations - Reactor Auxiliary Building, Plan El. 286, Rev. 6
APPLICABLE CODES AND STANDARDS
NFPA 10, Standard for the Installation of Portable Extinguishers, 1978 Edition
NFPA 13, Standard for the Installation of Sprinkler Systems, 1978 Edition
NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 1976 Edition
NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 1978 Edition.
NFPA 20, Standard for the Installation of Centrifugal Fire Pumps, 1972 Edition
NFPA 24, Outside Protection, 1977 Edition
NFPA 72D, Standard for the Installation, Maintenance and Use of Proprietary Signaling
Systems for Guard, Fire Alarm, and Supervisory Service, 1975 Edition.
NFPA 72E, Automatic Fire Detectors, 1978 Edition.
NFPA 80A, Standard on Fire Doors and Windows, 1970 Edition.
NFPA 90A, Standard on Air Conditioning and Ventilating Systems, 1979 Edition.
NFPA 101, Lfe Safety Code, 1976 Edition
NUREG-1552, Supplement 1, Fire Barrier Penetration Seals in Nuclear Power Plants, dated
January 1999
OSHA 29 CFR Part 1910.36
Underwriters Laboratory, Fire Resistance Directory, dated January 1998
OTHER DOCUMENTS
EC-50147, Fire Protection System Pressure Changes, Rev.0
Ebasco Services Inc., Cable and Raceway System Reports
Ebasco Specification 210-73, Motor Control Centers for use in Central Power Station - Class
1E, Rev.13
Fire Brigade Lesson Plan HO-LP-12.6-22, Placing a Hose Rack in Operation, Rev 3
Fire Pre-Plan A19-5-261-0602, RAB Fire Zone 1-A-4-CHLR, Rev.3
Fire Pre-Plan A22-5-261-0606, RAB Fire Zone 1-A-4-COME, Rev.3
Fire Pre-Plan A27-5-261-0614, RAB Fire Zone 1-A-EPA, Rev.3
Attachment 1
.
a -
7
Fire Pre-Plan A38-6-286-0647, RAB Fire Zone 1-A-BATB, Rev.3
Fire Pre-Plan T05-10-821-06682, Turbine Building Fire Zone 1-G-286, Rev.1
FP-941, Field Change, Location of Cable Tray Fire Breaks, Rev. 1
Transient Combustible Permit Logs (FPP-004) for the period 2001-2002
Fire Brigade Drill Logs (FNP-0-AP-27) for operating shifts for the period 2001-2002
Fire Brigade Shift Schedule and Training Matrix for November 9, 2002
UFSAR Figures 9.5A-8 and 9.5A-9, Fire Protection-Reactor Auxiliary Bldg.
PA System Engineering Status Review, dated April 11, 2002
Fire Protection System Engineering Status Review, dated September 11, 2002
Fire Detection System Engineering Status Review, dated September 11, 2002
Fire Protection Out of Service Log, for the period 2000-2002, dated October 7, 2002
Gould Shawmut Publication T-3889, Fuse Selectivity Ratios for 250 V Applications Up To
200,000 RMS SYM Amperes
Letter from P Gaffney, Ebasco, to W. Helms, CP&L, on the subject of 6.9 kV Grounding, dated
January 16, 1991
TECHNICAL MANUALSNENDOR INFORMATION
Akron Brass Company, Turbojet Fire Hose Nozzle Model 1720, dated October 16, 2002
Angus Industrial Fire Hose Products, Red Chief-Lightweight Attack Hose, dated October 16,
2002
C&D Technologies, Battery Model LCR-19, dated November 1, 2002
Data Sheet J 2.5, Model F Sprinklers, Automatic Sprinkler Corporation
Data Sheet NC48-194, Rate Compensated Thermal Detector, Johnson Controls Inc.
ID-PQL, Gould Technologies Vendor Manual, 8/27/85
AR REPORTS, AUDITS. AND SELF ASSESSMENTS REVIEWED
AR 02956, Evaluate NRC IN 99-07
AR 25032, NFPA 14 Code Deviations
AR 71908, OSHA Emergency Lights for Personnel Evacuation Failed to Function
AR 73540, Safe Shutdown Program Self-Assessment
AR 73607, Safe Shutdown Program Self-Assessment
AR 73719, Safe Shutdown Program Self-Assessment
Assessment 023155, Fire Protection Program, performed during 9/11/00 - 9/21/00
Assessment 056309, Safe Shutdown in Case of Fire Program, performed during 9/23/02 -
.9/25/02
Assessment 056314, Fire Protection Program,-performed during 03/02-08/02
Assessment 067063, Fire Brigade Training Program, performed during 07/29/02 - 08/02102
Assessment ENG 99-022, Fire Protection Safe Shutdown Program, performed during 10/04/99
- 10/08/99
Assessment H-FP-99-01, Harris Fire Protection, performed during 12/06/99 - 12/17/99
Assessment H-FP-00-01, Fire Protection, performed during 10/16/00 - 10/27/00
Assessment H-FP-01 -01, Fire Protection, performed during 08/06/01 - 08/16/01
Assessment H-FP-02-01, Fire Protection, performed during 08/12102 - 08/16/02
Attachment 1
-
CORRECTIVE ACTION PROGRAM ACTION REQUEST REPORTS GENERATED AS A
RESULT OF THIS INSPECTION
AR 75065, Discrepancy Between SSA and AOP-36 Regarding Actions to Take in the Event
That Boric Acid Tank Level Indication is Lost due to a Fire
AR 75258, AOP-36 Incorrectly Directs Operators to Use the B Chiller During a Fire at the B
Chiller.
AR 75337, AOP-36 Incorrectly Lists the Location of the Starter for MOV 1 CS-218 as MCC
1 B35-SB. The Starter for 1 CS-21 8 is In MCC 1 B35-SA.
AR 75339, Fire In The Turbine Building Can Cause Loss Of Both Fire Pumps
AR 76260, Fire In MCC 1 B35-SB Could Cause Spurious Closure of 1 CS-166 or 1 CS-1 68 Which
Would Isolate the A CSIP From its Suction Source. Also, Fire in MCC1A35-SA Could
Cause Spurious Closure of 1CS-219 and Stop the Preferred Normal Charging Flow
Path. The SSA Does Not Include Analysis or Immediate Operator Actions to Prevent
These Conditions
AR 76405, Plant Modification ESR 01-00087, CSIP Recirc Flowpath Change, did not Recognize
that the SSA and AOP-36 Should have been Revised to Account for Potential Spurious
Closure of the VCT Outlet Valves, 1 CS-1 65 and 1 CS-1 66
AR 76584, P&ID Drawing for MCC 1 B35-SB has Incorrect Descriptions for Two Breakers
AR 76621, Fire Hose Nozzles Used In The Plant Are Not Approved For Energized Electrical
Equipment And Do Not Match The FSAR Description
AR 76623, Evaluate Transient Combustible Load Allowance For Fire Zones Not Surrounded By
AR 76626, Evaluate Loss Of PA, Radio Communications, and Fire Detection Systems In The
Communications Room
AR 76632, NRC FP Walkdown Observations - No Battery-Backed Lighting for 1 CS-214 Manual
Actions and Three of Four Normal Lights Out; also the SSD AO is Not Assigned a
Portable Radio for Communications Use in the Event of a Fire
AR 76993, Review NLO Training on AOP-36
AR 77527, A Review of the ARs Initiated as a Result of the 2002 SSD Self-Assessment and the
NRC Triennial FP Inspection Indicates a Trend Concerning Inconsistencies Between the
Safe Shutdown Analysis and Implementing Procedure AOP-30
AR 79047, Additional Ughting Required for Performance of SSD Tasks
AR 79567, AOP-36 Walkthrough Validation Concern for MCC 1 E12 Operator Actions that are
In the Fire Area
AR 79582, AOP-36 Walkthrough Validation Comments
AR 80045, Component Cooling Valves that Provide Seal Protection for Reactor Coolant Pumps
have Incorrect SSD Division Designator in the SSA (Calculation E-5524)
AR 80089, Valve 1 CC-251, CCW to RCP Thermal Barriers, is powered from MCC 1 B31 -SB,
Which Is Located in Fire Area 1-A-EPB and Unprotected From a Fire in That Area.
Consequently, the SSD Credited RCP Thermal Barrier Cooling Could Be Lost During a Fire in
1-A-EPB.
AR 80144, Need to Reword Steps in AOP-36
AR 80161, Review NRC IE Circular 77-03, 'Fire Inside a Motor Control Center'
Attachment 1