Fermi 2 6400 North Dixie Hwy., Newport, MI 48166 Detroit Edison Ik April 28, 2003 NRC-03-0038 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington D C 20555-0001
Reference:
Fermi 2 NRC Docket No. 50-341 NRC License No. NPF-43
Subject:
Transmittal of Cycle 10 Core Operating Limits Report In accordance with Fermi 2 Technical Specification 5.6.5, Detroit Edison hereby submits a copy of the Core Operating Limits Report (COLR), Cycle 10, Revision 0.
This COLR will be used during the Fermi 2 tenth operating cycle.
Should you have any questions or require additional information, please contact me at (734) 586-4258.
Sincerely, Norman K. Peterson Manager - Nuclear Licensing Enclosure cc: M. A. Ring [w/o Enclosure]
J. F. Stang, Jr. [w/o Enclosure]
NRC Resident Office [w/Enclosure]
Regional Administrator - Region III [w/Enclosure]
Supervisor, Electric Operators, Michigan Public Service Commission [w/o Enclosure]
-Ami A DTE Energy Company
ENCLOSURE TO NRC-03-0038 CORE OPERATING LIMITS REPORT
[COLR]
CYCLE 10 REVISION 0
COLR - 10 Revision 0 Page I of 20 FERMI 2 CORE OPERATING LIMITS REPORT CYCLE 10 REVISION 0 Prepared by:
.R. Kiel ate Reload Core Design Team Leader Reviewed by:
J.b. Wines Date Station Nuclear Engineer B.L yers Date COLR Checlist Reviewer Approved by:
M.'C. Kikand Date Supervisor - Reactor Engineering April 2003
COLR - 10 Revision 0 Page 2 of 20 TABLE OF CONTENTS
1.0 INTRODUCTION
AND
SUMMARY
................................................ 4 2.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE ............................................ . 5 2.1 Definition ................................................ 5 2.2 Determination of MAPLHGR Limit .............................................. 5 2.2.1 Calculation of MAPFAC(P) ................................................ 7 2.2.2 Calculation of MAPFAC(F) ................................................ 8 3.0 MINIMUM CRITICAL POWER RATIO ................................................ 9 3.1 Definition .. 9 3.2 Determination of Operating Limit MCPR ............................. : . 9 3.3 Calculation of MCPR(P) .. 0 3.3.1 Calculation of Kp .1 3.3.2 Calculation of . 12 3.4 Calculation of MCPR(F) .. 13 4.0 LINEAR HEAT GENERATION RATE ...................................... 14 4.1 Definition ...................................... . 14 4.2 Determination of LHGR Limit .. .................................... 14 4.2.1 Calculation of LHGRFAC(P) ...................................... 15 4.2.2 Calculation of LHGRFAC(F) ...................................... 16 5.0 CONTROL ROD BLOCK INSTRUMENTATION ...................................... 17 5.1 Definition ...................................... 17
6.0 REFERENCES
...................................... 18
COLR - I0 Revision 0 Page 3 of 20 LIST OF TABLES TABLE 1 FUEL TYPE-DEPENDENT STANDARD MAPLHGR LIMITS .............................. 6 TABLE 2 FLOW-DEPENDENT MAPLHGR LIMIT COEFFICIENTS .................................... 8 TABLE 3 OLMCPRioo 1 105 AS A FUNCTION OF EXPOSURE AND .................................. 10 TABLE 4 FLOW-DEPENDENT MCPR LIMIT COEFFICIENTS .......................................... 13 TABLE 5 STANDARD LHGR LIMITS FOR VARIOUS FUEL TYPES ................................ 14 TABLE 6 FLOW-DEPENDENT LHGR LIMIT COEFFICIENTS ......................................... ;.16 TABLE 7 CONTROL ROD BLOCK INSTRUMENTATION SETPOINTS WITH FILTER ....................................... 17
COLR - 10 Revision 0 Page 4 of 20
1.0 INTRODUCTION
AND
SUMMARY
This report provides the cycle specific plant operating limits, which are listed below, for Fermi 2, Cycle 10, as required by Technical Specification 5.6.5. The analytical methods used to determine these core operating limits are those previously reviewed and approved by the Nuclear Regulatory Commission in GESTAR II.
The cycle specific limits contained within this report are valid for the full range of the licensed operating domain.
OPERATING LIMIT TECHNICAL SPECIFICATION APLHGR 3.2.1 MCPR 3.2.2 LHGR 3.2.3 RBM 3.3.2.1 APLHGR = AVERAGE PLANAR LINEAR HEAT GENERATION RATE MCPR = MINIMUM CRITICAL POWER RATIO LHGR = LINEAR HEAT GENERATION RATE RBM = ROD BLOCK MONITOR SETPOINTS
COLR - 10 Revision 0 Page 5 of 20 2.0 AVERAGE PLANAR LINEAR HEAT GENERATION RATE TECH SPEC IDENT OPERATING LIMIT 3.2.1 APLHGR 2.1 Definition The AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR) shall be applicable to a specific planar height and is equal to the sum of the LINEAR HEAT GENERATION RATEs (LHGRs) for all the fuel rods in the specified bundle at the specified height divided by the number of fuel rods in the fuel bundle at the height.
2.2 Determination of MAPLHGR Limit The maximum APLHGR (MAPLHGR) limit is a function of reactor power, core flow, fuel type, and average planar exposure. The limit is developed, using NRC approved methodology described in References 1 and 2, to ensure gross cladding failure will not occur following a loss of coolant accident (LOCA). The MAPLHGR limit ensures that the peak clad temperature during a LOCA will not exceed the limits as specified in 10CFR50.46(b)(1) and that the fuel design analysis criteria defined in References 1 and 2 will be met.
The MAPLHGR limit during dual loop operation is calculated by the following equation:
MAPLHGR,,,M = MIN (MAPLHGR (P), MAPLHGR (F))
where:
MAPLHGR (P) = MAPFAC (P) x MAPLHGRSI MAPLHGR (F) = MAPFA C (F) x MAPLHGRszrh Within four hours after entering single loop operation, the MAPLHGR limit is calculated by the following equation:
MAPLHGR,,, = MIN (MAPLHGR (P), MAPLHGR (F), MAPLHGR (SLO))
where:
MAPLHGR (SLO) = 0.73 x MAPLHGRsM-
COLR - 10 Revision 0 Page 6 of 20 MAPLHGRsTD, the standard MAPLHGR limit, is defined at a power of 3430 MWt and flow of 105 Mlbs/hr for each fuel type as a function of average planar exposure and is presented in Table
- 1. When hand calculations are required, MAPLHGRsTD shall be determined by interpolation from Table 1. MAPFAC(P), the core power-dependent MAPLHGR limit adjustment factor, shall be calculated by using Section 2.2.1. MAPFAC(F), the core flow-dependent MAPLHGR limit adjustment factor, shall be calculated by using Section 2.2.2.
TABLE 1 FUEL TYPE-DEPENDENT STANDARD MAPLHGR LIMITS Exposure MAPLHGR GWD/ST KW/FT 0.0 13.42 19.72 13.42 27.22 12.29 63.50 8.90 This MAPLHGR Limit Array applies to all Cycle 10 fuel Fuel Types 14 = GEl I-P9CUB380-12GZ-IOOT-146-T6 17 = GEl l-P9CUB380-1 IGZ-lOOT-146-T6-2542 15 = GE I l-P9CUB378-4G6/8G5-I OOT- 146-T6-3955 18 = GEl I-P9CUB404-12GZ-1 OOT-146-T6-2543 16 = GEl I-P9CUB396-13GZ-1OOT-146-T6-3954 19 = GEI 1-P9CUB408-12GZ-IOOT-146-T6-2604 20 = GEI I-P9CUB380-12GZ-IOOT-146-T62605
COLR - 10 Revision 0 Page 7 of 20 2.2.1 Calculation of MAPFAC(P)
The core power-dependent MAPLHGR limit adjustment factor, MAPFAC(P), shall be calculated by one of the following equations:
For 0 <P <25:
No thermal limits monitoring is required.
For 25 <P < 30:
With turbine bypass OPERABLE, For core flow < 50 Mlbs/hr, MAPFA C (P) = 0.606 + 0.0038 (P - 30)
For core flow > 50 Mlbs/hr, MAPFAC (P) = 0.586 + 0.0038 (P - 30)
With turbine bypass INOPERABLE For core flow < 50 Mlbs/hr, MAPFAC(P) = 0.490 + 0.005(P - 30)
For core flow > 50 Mlbs/hr, MAPFAC(P) = 0.438+0.0050(P-30)
For 30 <P< 100:
MAPFAC(P) = 1.0+0.005224(P-100) where: P =Core power (fraction of rated power times 100).
COLR-10 Revision 0 Page 8 of 20 2.2.2 Calculation of MAPFAC(F)
The core flow-dependent MAPLHGR limit adjustment factor, MAPFAC(F), shall be calculated by the following equation:
WT MAPFAC(F) = MIN(L.O, 4FX 10 +-BF) 100 where:
WT = Core flow (Mlbs/hr).
AF = Given in Table 2.
BF = Given in Table 2.
TABLE 2 FLOW-DEPENDENT MAPLHGR LIMIT COEFFICIENTS Maximum Core Flow*
(Mlbs/hr) AF BF 110 0.67874 0.4358 As limited by the Recirculation System MG Set mechanical scoop tube stop setting.
0
- 10 Revision COLR COLR -10 Revision 0 Page 9 of 20 3.0 MINKIUM CRITICAL POWER RATIO TECH SPEC IDENT OPERATING LIMIT 3.2.2 MCPR 3.1 Definition The MINIMUM CRITICAL POWER RATIO (MCPR) shall be the smallest Critical Power Ratio (CPR) that exists in the core for each type of fuel. The CPR is that power in the assembly that is calculated by application of the appropriate correlation(s) to cause some point in the assembly to experience boiling transition, divided by the actual assembly operating power.
3.2 Determination of Operating Limit MCPR The required Operating Limit MCPR (OLMCPR) at steady-state rated power and flow operating conditions is derived from the established fuel cladding integrity Safety Limit MCPR of 1.07 and an analysis of abnormal operational transients. To ensure that the Safety Limit MCPR is not exceeded during any anticipated abnormal operational transient, the most limiting transients have been analyzed to determine which event will cause the largest reduction in CPR. Three different core average exposure conditions are evaluated. The result is an Operating Limit MCPR which is a function of exposure and t. t is a measure of scram speed, and is defined in Section 3.3.2.
The OLMCPR shall be calculated by the following equation:
OLMCPR = MAX(MCPR(P), MCPR(F))
MCPR(P), the core power-dependent MCPR operating limit, shall be calculated using Section 3.3.
MCPR(F), the core flow-dependent MCPR operating limit, shall be calculated using Section 3.4.
In case of Single Loop Operation, the Safety Limit MCPR is increased by 0.02 to 1.09, but OLMCPR does not change.
COLR- 10 Revision 0 Page 10 of 20 3.3 Calculation of MCPR(P)
MCPR(P), the core power-dependent MCPR operating limit, shall be calculated by the following equation:
MCPR(P) = Kpx0LMCPR)01 oo 05 Kp, the core power-dependent MCPR Operating Limit adjustment factor, shall be calculated by using Section 3.3.1.
OLMCPR 10 0 1/ 0 5 shall be determined by interpolation from Table 3, and I shall be calculated by using Section 3.3.2.
TABLE 3 OLMCPR 10 011 05 AS A FUNCTION OF EXPOSURE AND T EXPOSURE CONDITION (MVM/ST) OLMCPR 1001105 Both Turbine Bypass and Moisture Separator Reheater OPERABLE BOC to 8800 T=0 1.29 T =I 1.36 8800 to 10300 1.31 T= 1 1.38 10300 to EOC T=0 1.34 T= I 1.45 Either Turbine Bypass or Moisture Separator Reheater INOPERABLE BOC to EOC T=1 1.39 T =I 1.50 Both Turbine Bypass and Moisture Separator Reheater INOPERABLE BOC to EOC T=0 1.42 T= I 1.53
COLR-10 RevisionO Page 11 of 20 3.3.1 Calculation of Kp The core power-dependent MCPR operating limit adjustment factor, Kp, shall be calculated by using one of the following equations:
For O<P<25:
No thermal limits monitoring is required.
For 25<P<30:
When turbine bypass is OPERABLE, Kp= (KBYP +(0. 026 x (30 - P)))
OLMCPR100 ,105 where: KByp = 1.90 for core flow < 50 Mibs/hr
= 2.23 for core flow > 50 Mlbs/hr When turbine bypass is INOPERABLE, KP = (KBYP + (0.054x (30 -P)))
OLMCPRioo 1 los where: KBYP = 2.26 for core flow < 50 Mlbs/hr
= 3.03 for core flow > 50 Mlbs/hr For 30 < P < 45 Kp = 1.28 + (0.0134 x (45-P))
For 45<P<60 Kp= 1.15 + (0.00867 x (60 - P))
For 60 <P < 100:
Kp= 1.0 + (0.003 75 x (100-P))
where: P = Core power (fraction of rated power times 100).
COLR- 10 Revision 0 Page 12 of 20 3.3.2 Calculation of T The value of t, which is a measure of the conformance of the actual control rod scram times to the assumed average control rod scram time in the reload licensing analysis, shall be calculated by using the following equation:
TrA - TB where: A= 1.096 seconds rB = 0.830 + 0.019 x 1.65 n seconds
- N.
Tave END 1=1 n = number of surveillance tests performed to date in cycle, Ni = number of active control rods measured in the ith surveillance test, r = average scram time to notch 36 of all rods measured in the i'b surveillance test, and N, = total number of active rods measured in the initial control rod scram time test for the cycle (Technical Specification Surveillance Requirement 3.1.4.4).
The value of t shall be calculated and used to determine the applicable OLMCPRloo/105 value from Table 3 within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of the conclusion of each control rod scram time surveillance test required by Technical Specification Surveillance Requirements 3.1.4.1, 3.1.4.2, and 3.1.4.4.
Prior to performance of the initial scram time measurements for the cycle, a t value of 1.0 shall be used to determine the applicable OLMCPR1 OO/ 105 value from Table 3.
0
- 10 Revision COLR COLR - Il0 Revision 0 Page 13 of 20 3.4 Calculation of MCPR(F)
MCPR(F), the core flow-dependent MCPR operating limit, shall be calculated by using the following equation:
MCPR(F)= MAX(1.20, (AFX -0 + BF))
10w0 where:
WT = Core flow (Mlbs/hr).
AF = Given in Table 4.
BF = Given in Table 4.
TABLE 4 FLOW-DEPENDENT MCPR LIMIT COEFFICIENTS Maximum Core Flow*
(Mlbs/hr) AF BF 110 -0.5956 1.727 As limited by the Recirculation System MG Set mechanical scoop tube stop setting.
COLR-10 RevisionO Page 14 of20 4.0 LINEAR HEAT GENERATION RATE TECH SPEC IDENT OPERATING LIMIHTl 3.2.3 LHGR 4.1 Definition The LINEAR HEAT GENERATION RATE (LHGR) shall be the heat generation rate per unit length of fuel rod. It is the integral of the heat flux over the heat transfer area associated with the unit length. By maintaining the operating LHGR below the applicable LHGR limit, it is assured that all thermal-mechanical design bases and licensing limits for the fuel will be satisfied.
4.2 Determination of LHGR Limit The maximum LHGR limit is a function of reactor power, core flow, fuel and rod type, and fuel rod nodal exposure. The limit is developed, using NRC approved methodology described in References 1 and 2, to ensure the cladding will not exceed its yield stress and that fuel thermal-mechanical design criteria will not be violated during any postulated transient events. The LHGR limit ensures the fuel mechanical design requirements as defined in References 1 and 2 will be met.
TABLE 5 STANDARD LHGR LIMITS FOR VARIOUS FUEL TYPES Most Limiting Uranium Only Fuel Rods Gadolinia Bearing Fuel Rods Exposure LHGR Exposure LHGR GWD/ST KW/FT GWD/ST KW/FT 0.0 14.40 0.0 12.30 13.24 14.40 10.32 12.30 27.22 12.29 23.44 10.50 63.50 8.90 57.51 7.60 The LHGR Limit Arrays apply to all Cycle 10 fuel iel Types 14 = GEII-P9CUB380-l2GZ-IOOT-146-T6 17 = GEI I-P9CUB380-l IGZ-IOOT-146-T6-2542 15 = GE I -P9CUB378-4G6/8G5-IOOT-146-T6-3955 18= GE1 I-P9CUB404-12GZ-1OOT-146-T6-2543 16 = GE Il-P9CUB396-13GZ-IOOT-146-T6-3954 19= GEI 1-P9CUB408-12GZ-IOOT-146-T6-2604 20= GEII-P9CUB380-12GZ-IOOT-146-T6-2605
COLR - 10 Revision 0 Page 15 of 20 The LHGR limit during dual loop operation is calculated by the following equation:
LHGRLJMZ = MIN (LHGR (P), LHGR (F))
where:
LHGR (P) = LHGRFA C (P) x LHGRS LHGR (F) =LHGRFAC (F) x LHGRm>TD LHGRSTD, the standard LHGR limit, is defined at a power of 3430 MWt and flow of 105 Mlbs/hr for each fuel and rod type as a function of fuel rod nodal exposure and is presented in Table 5.
Table 5 contains only the most limiting Gadolinia LHGR limit for the maximum allowed Gadolinia concentration of the applicable fuel product line. When hand calculations are required, LHGRSTD shall be determined by interpolation from Table 5. LHGRFAC(P), the core power-dependent LHGR limit adjustment factor, shall be calculated by using Section 4.2.1.
LHGRFAC(F), the core flow-dependent LHGR limit adjustment factor, shall be calculated by using Section 4.2.2.
4.2.1 Calculation of LHGRFAC(P)
The core power-dependent LHGR limit adjustment factor, LHGRFAC(P), shall be calculated by one of the following equations:
For 0 < P < 25:
No thermal limits monitoring is required.
COLR -10 Revision 0 Page 16 of 20 For 25 <P <30:
With turbine bypass OPERABLE, For core flow < 50 Mlbs/hr, LHGRFAC(P) = 0.606 + 0.0038 (P - 30)
For core flow > 50 Mlbs/hr, LHGRFAC (2) = 0.586 + 0.0038 (P - 30)
With turbine bypass INOPERABLE, For core flow < 50 Mlbs/hr, LHGRFAC(P,)=0.490 + 0.0050(P-30)
For core flow > 50 Mlbs/hr, LHGRFAC(Pr= 0.438 + 0.0050(P- 30)
For 30<P<100:
LHGRFA CO = 1.0 + 0. 005224(P -100) where: P = Core power (fraction of rated power times 100).
COLR - 10 Revision 0 Page 17 of 20 4.2.2 Calculation of LHGRFAC(F)
The core flow-dependent LHGR limit adjustment factor, LHGRFAC(F), shall be calculated by the following equation:
WT LHGRFAC(F)=MIN(l.O, AFX- +BF) 100 where:
WT = Core flow (Mlbs/hr).
AF = Given in Table 6.
BF = Given in Table 6.
TABLE 6 FLOW-DEPENDENT LHGR LIMIT COEFFICIENTS Maximum Core Flow*
(Mlbs/hr) AF - BF 110 0.67874 0.4358 As limited by the Recirculation System MG Set mechanical scoop tube stop setting.
COLR- 10 Revision 0 Page 18 of 20 5.0 CONTROL ROD BLOCK INSTRUMENTATION TECH SPEC IDENT SETPOINT 3.3.2.1 RBM 5.1 Definition The nominal trip setpoints and allowable values of the control rod withdrawal block instrumentation are shown in Table 6. These values are consistent with the bases of the APRM Rod Block Technical Specification Improvement Program (ARTS) and the MCPR operating limits.
TABLE 7 CONTROL ROD BLOCK INSTRUMENTATION SETPOINTS WITH FILTER Setpoint Trip Setpoint Allowable Value LPSP 27.0 28.4 IPSP 62.0 63.4 HPSP 82.0 83.4 LTSP 117.0 118.9 ITSP 112.2 114.1 HTSP 107.2 109.1 DTSP 94.0 92.3 where:
LPSP Low power setpoint; Rod Block Monitor (RBM) System trip automatically bypassed below this level IPSP Intermediate power setpoint HPSP High power setpoint LTSP Low trip setpoint ITSP Intermediate trip setpoint HTSP High trip setpoint DTSP Downscale trip setpoint
COLR - 10 Revision 0 Page 19 of 20
6.0 REFERENCES
- 1. "General Electric Standard Application for Reactor Fuel (GESTAR II)," NEDE-24011-P-A, Revision 14 as amended by Amendment 25
- 2. "The GESTR-LOCA and SAFER Models for the Evaluation of the Loss-of-Coolant Accident
- SAFER/GESTR Application Methodology," NEDE 23785-1-PA, Revision 1, October 1984
- 3. "Fermi-2 SAFER/GESTR-LOCA, Loss-of-Coolant Accident Analysis," NEDC-31982P, July 1991, and Errata and Addenda No. 1, April 1992
- 4. "Fuel Bundle Information Report for Fermi 2 Reload 9 Cycle 10," Global Nuclear Fuel, 0000-0007-4899-FIBR, Revision 0, January 2003
- 5. "Supplemental Reload Licensing Report for Fermi 2 Reload 9, Cycle 10," Global Nuclear Fuel, 0000-0007-4899-SRLR, Revision 0, January 2003
- 6. Letter from T. G. Colburn to W. S. Orser, "Fermi Amendment No. 87 to Facility Operating License No. NPF-43 (TAC NO. M82102)," September 9, 1992
- 7. Letter from J. F. Stang to W. S. Orser, "Amendment No. 53 to Facility Operating License No.
NPF-43: (TAC No. 69074)," July 27, 1990
- 8. "Maximum Extended Operating Domain Analysis for Detroit Edison Company Enrico Fermi Energy Center Unit 2," GE Nuclear Energy, NEDC-31843P, July 1990
- 9. "Cycle 10 Offrated ARTS Limits" letter TMFR 03-0061 from P. R. Kiel to File dated April 11, 2003
- 10. "Power Range Neutron Monitoring System," DC-4608, Vol. XI DCD, Rev. B and DC-4608 Vol. I Rev. D.
- 11. Letter from Andrew J. Kugler (USNRC) to Douglas R. Gipson (Detroit Edison), "Fermi Issuance of Amendment RE: Safety Limit Minimum Critical Power Ratio Limits for Cycle 8 (TAC NO. MA7372)," dated March 30, 2000
- 12. Letter from Greg Porter to B. L. Myers, "Scram Times for Improved Tech Specs." GP-99014, October 22, 1999 containing DRF A12-00038-3, Vol. 4 information from G. A. Watford, GE, to Distribution,
Subject:
Scram Times versus Notch Position
COLR - 10 Revision 0 Page 20 of 20
6.0 REFERENCES
- 13. Methodology and Uncertainties for Safety Limit MCPR Evaluations, NEDC-32601P-A, August 1999
- 14. Power Distribution Uncertainties for Safety Limit MCPR Evaluation, NEDC-32694P-A, August 1999
- 15. R-Factor Calculation Method for GE11, GE12, and GE13 Fuel, NEDC-32505P-A, Revision 1, July 1999
- 16. "Improved LHGR Limits (designated as "GEl 1/13-UPGRADE") for GE1 I Fuel in Fermi,"
Global Nuclear Fuel, GNF-J1 103057-265, August 2001
- 17. "Turbine Control Valve Out-Of-Service for Enrico Fermi Unit-2," GE - Nuclear Energy, GE-NE-J1 1-03920-07-01, October 2001
- 18. Licensing Topical Report, "Qualification of the One-Dimensional Core Transient Model for Boiling Water Reactors," Volume 1, NEDO-24154-A 78NED290R1, August 1986