Exeikmn.
Exelon Nuclear www exeloncorp corn Nuclear Limerick Generating Station PO Box 2300 Pottstown, PA 19464 T.S. 6.9.1.8 April 30, 2003 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 Limerick Generating Station, Unit 1 and 2 Facility Operating License Nos. NPF-39 and NPF-85 NRC Docket Nos. 50-352 and 50-353
Subject:
2002 Annual Radioactive Effluent Release Report In accordance with Section 6.9.1.8 of Limerick Generating Station (LGS) Technical Specifications and 10CFR50.36(a), attached are following reports:
-The 2002 Annual Radioactive Effluent Release Report No. 28, for LGS
-The 2002 Annual Tower No. 1 Joint Frequency Distributions of Wind Direction and Speed by Atmospheric Stability Class Report No. 18 for LGS If you have any questions or require additional information, please do not hesitate to contact us.
Sincerely, 1 - c- ,
Robert C. Braun Vice President-LGS (acting)
Attachments:
cc: H. Miller, Administrator, Region I, USNRC A. Burritt, LGS USNRC Senior Resident Inspector J. Jang, Inspector Region I, USNRC
bcc: W. Levis - KSA 3N M. Gallagher - KSA 3P R. Braun - GML 5-1 D. Helker - KSA 3P R. Dickinson - SSB 2-3 W. Harris - GML 1-1 R. Newmaster - SSB 2-2 M. Kaminski - SSB 2-4 R. McCall - SSB 2-3 J. Toro - SMB 1-2 D. Wahl - KSA 3P D. Branham - SSB 2-2 D. Eisenhut - NSRB D. Dyckman - PADEP BRP L Weinstock - US EPA S. Focht - ANI
I cI Nuclear Annual Radioactive Effluent Release Report 2002 Limerick Generating Station
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT NO. 28 January 1, 2002 Through December 31, 2002 EXELON NUCLEAR LIMERICK GENERATING STATION UNITS NO. 1 AND 2 DOCKET NO. 50-352 (Unit 1)
DOCKET NO. 50-353 (Unit 2)
Submitted to The United States Nuclear Regulatory Commission Pursuant to Facility Operating License NPF-39 (Unit 1) and NPF-85 (Unit 2)
TABLE OF CONTENTS I. Introduction II. Tables
- Summary of Radioactive Gaseous Effluents
- Summary of Radioactive Liquid Effluents
- Solid Waste Disposition Report
- Offsite Radiation Dose Assessment
- Radiation Dose to Members of the Public Due to Their Activities Inside Site Boundary III. Attachments
- Supplemental Information - Assumptions Used in Report Generation
- Radiation Monitors Out-of-Service
- Revision to Previous Submittal
- Offsite Dose Calculation Manual Revisions
- Events 2
I. INTRODUCTION This submittal complies with the format described in Regulatory Guide 1.21, "Measuring, Evaluating and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water Cooled Nuclear Power Plants", Revision 1, June, 1974.
The following information is included as Tables to this report:
- A summary of the gaseous and liquid effluent releases for the report period. For 2002 data, where "0.00E+00" or a "Blank" is used, it denotes that no activity was found for samples analyzed per ODCM requirements. All LLD requirements listed in the ODCM were met. The estimated total errors stated in the gaseous and liquid summation of releases were the values quoted in past reports except for the volume of waste released and volume of dilution water for liquid releases. These errors are estimated from I&C calibration data. The Noble Gas Monitor data is analyzed to report noble gas effluent activities. When no activity is found in the Isotopic Analysis, the isotopic mixture is assumed to be that evaluated in the UFSAR (section 11.5, Table 11.5-4). If activity is found in the Isotopic Analysis, the isotopic mixture for the Noble Gas Monitor is determined from the Isotopic Analysis. The reported noble gas activities for gaseous releases are probably higher than actual noble gas releases due to a very high natural background of radon. The radon levels can vary by a wide margin from day to day and contribute to the majority of the noble gas monitor response.
- Composite particulate air samples and liquid radwaste composites, counted for beta emitters (e.g.
Fe-55, Sr-89, Sr-90) and gross alpha (air samples only), were submitted to an offsite vendor laboratory for analysis. Other required analyses were performed onsite. All vendor results were received and included in the report calculations.
Therefore the 2002 report is complete.
- A summary of solid waste dispositioned during the report period, to include: total activity shipped by waste type and the estimated composition of each type of waste by isotope; and the number of shipments, mode of transportation, destination, type of container, total container volume, and solidification agent.
3
- There was no contaminated oil burned in the Auxillary Boilers during 2002.
Additional Information:
- There were no changes to Radioactive Waste Treatment Systems during the report period.
- The Activities and Doses listed in this report are within the limits specified in 40CFR Part 190.
- Two of the tables from the 2001 ARERR contained typographical errors. The corrected tables are included in the "REVISION TO PREVIOUS SUBMITTAL" section.
4
II. TABLES A.
SUMMARY
OF RADIOACTIVE GASEOUS EFFLUENTS January 1, 2002 to December 31, 2002 (7 pages of Tables) 5
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:53:01 AM GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES Units Qtr 1 Qtr 2 Qtr 3 Qtr 4 A. FISSION AND ACTIVATION GASSES (estimated total error: 45.3 %)
- 1. Total Release Ci 3.23E+02 3.50E+02 5.48E+02 2.90E+02
- 2. Average Release uCi/sec 4.16E+01 4.46E+01 6.95E+01 3.31E+01 Rate for Period B. IODINES (estimated total error: 45.3 %)
- 1. Total 1-131 Ci 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00
- 2. Average Release uCi/sec 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Rate for Period C. PARTICULATES (estimated total error: 45.3 %)
- 1. Particulates with Ci 0.OOE+00 1.78E-06 6.45E-08 0.OOE+00 T 1/2 > 8 days
- 2. Average Release uCi/sec 0.OOE+00 2.27E-07 8.18E-09 0.OOE+00 Rate for Period
- 3. Gross Alpha Ci 3.22E-06 2.60E-06 3.29E-06 1.55E-06 D. TRITIUM (estimated total error: 45.3 %)
- 1. Total Release Ci 1.14E+01 1.35E+01 9.29E+00 1.34E+01
- 2. Average Release uCi/sec 1.46E+00 1.72E+00 1.18E+00 1.53E+00 6
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:53:01 AM GASEOUS EFFLUENTS FOR RELEASE POINT - NORTH STACK Continuous Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4
- 1. FISSION AND ACTIVATION GASSES KR-85 Ci 1.05E+01 8.46E+00 1.70E+01 7.76E+00 KR-85M Ci 2.78E+00 2.24E+00 4.50E+00 2.05E+00 KR-87 Ci 4.87E+00 3.93E+00 7.88E+00 3.60E+00 KR-88 Ci 8.62E+00 6.94E+00 1.39E+01 6.37E+00 XE-131M Ci 2.63E-01 2.12E-01 4.25E-01 1.94E-01 XE-133 Ci 9.80E-01 7.90E-01 1.59E+00 7.24E-01 XE-135 Ci 3.84E+01 3.09E+01 6.20E+01 2.83E+01 XE-135M Ci 2.45E+01 1.97E+01 3.96E+01 1.81E+01 XE-138 Ci 5.24E+01 4.22E+01 8.48E+01 3.87E+01 TOTAL FOR PERIOD Ci 1.43E+02 1.15E+02 2.32E+02 1.06E+02 (ABOVE)
- 2. IODINES None TOTAL FOR PERIOD Ci (ABOVE)
- 3. PARTICULATES (T 1/2 > 8 DAYS)
None TOTAL FOR PERIOD Ci (ABOVE) 7
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:53:01 AM GASEOUS EFFLUENTS FOR RELEASE POINT - UNIT 1 SOUTH STACK Continuous Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4
- 1. FISSION AND ACTIVATION GASSES AR-41 Ci 6.60E+00 9.17E+00 1.60E+01 7.30E+00 KR-85M Ci 1.58E+00 2.20E+00 3.84E+00 1.75E+00 KR-87 Ci 1.58E+00 2.20E+00 3.84E+00 1.75E+00 KR-88 Ci 1.58E+00 2.20E+00 3.84E+00 1.75E+00 XE-133 Ci 3.43E+01 4.76E+01 8.31E+01 3.79E+01 XE-135 Ci 1.79E+01 2.49E+01 4.35E+01 1.98E+01 XE-135M Ci 2.43E+01 3.37E+01 5.89E+01 2.69E+01 XE-138 Ci 3.69E+00 5.14E+00 8.96E+00 4.09E+00 TOTAL FOR PERIOD Ci 9.15E+01 1.27E+02 2.22E+02 1.01E+02 (ABOVE)
- 2. IODINES None TOTAL FOR PERIOD Ci (ABOVE)
- 3. PARTICULATES (T 1/2 > 8 DAYS)
None TOTAL FOR PERIOD Ci (ABOVE) 8
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:53:02 AM GASEOUS EFFLUENTS FOR RELEASE POINT - UNIT 2 SOUTH STACK Continuous Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4
- 1. FISSION AND ACTIVATION GASSES AR-41 Ci 6.39E+00 7.74E+00 6.78E+00 5.95E+00 KR-85M Ci 1.53E+00 1.85E+00 1.63E+00 1.43E+00 KR-87 Ci 1.53E+00 1.85E+00 1.63E+00 1.43E+00 KR-88 Ci 1.53E+00 1.85E+00 1.63E+00 1.43E+00 XE-133 Ci 3.32E+01 4.02E+01 3.52E+01 3.09E+01 XE-135 Ci 1.73E+01 2.10E+01 1.84E+01 1.62E+01 XE-135M Ci 2.35E+01 2.85E+01 2.49E+01 2.19E+01 XE-138 Ci 3.58E+00 4.33E+00 3.80E+00 3.33E+00 TOTAL FOR PERIOD Ci 8.86E+01 1.07E+02 9.41E+01 8.25E+01 (ABOVE)
- 2. IODINES None TOTAL FOR PERIOD Ci (ABOVE)
- 3. PARTICULATES (T 1/2 > 8 DAYS)
SR-89 Ci 1.78E-06 6.45E-08 TOTAL FOR PERIOD Ci 1.78E-06 6.45E-08 (ABOVE) 9
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:53:02 AM GASEOUS EFFLUENTS FOR RELEASE POINT - HOT MAINTENANCE SHOP Continuous Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4
- 1. FISSION AND ACTIVATION GASSES None TOTAL FOR PERIOD Ci (ABOVE)
- 2. IODINES None TOTAL FOR PERIOD Ci (ABOVE)
- 3. PARTICULATES (T 1/2 > 8 DAYS)
None TOTAL FOR PERIOD Ci (ABOVE) 10
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:53:02 AM GASEOUS EFFLUENTS FOR RELEASE POINT - OIL INCINERATION Batch Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4
- 1. FISSION AND ACTIVATION GASSES None TOTAL FOR PERIOD Ci (ABOVE)
- 2. IODINES None TOTAL FOR PERIOD Ci (ABOVE)
- 3. PARTICULATES (T 1/2 > 8 DAYS)
None TOTAL FOR PERIOD Ci (ABOVE) 11
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:53:02 AM GASEOUS EFFLUENTS FOR RELEASE POINT - OTHER BATCH RELEASES Batch Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4
- 1. FISSION AND ACTIVATION GASSES None TOTAL FOR PERIOD Ci (ABOVE)
- 2. IODINES None TOTAL FOR PERIOD Ci (ABOVE)
- 3. PARTICULATES (T 1/2 > 8 DAYS)
None TOTAL FOR PERIOD Ci (ABOVE) 12
II. TABLES B.
SUMMARY
OF RADIOACTIVE LIQUID EFFLUENTS January 1, 2002 to December 31, 2002 (2 pages of Tables) 13
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:52:45 AM LIQUID EFFLUENTS - SUMMATION OF ALL RELEASES Units Qtr 1 Qtr 2 Qtr 3 Qtr 4 A. FISSION AND ACTIVATION PRODUCTS (estimated total error: 62.8 %)
- 1. Total release Ci 1.36E-03 5.31E-04 7.54E-04 5.06E-04 (not including tritium, gasses, alpha)
- 2. Average diluted uCi/ml 2.12E-08 1.31E-08 1.89E-08 1.17E-08 concentration during Period B. TRITIUM (estimated total error:- 62.8 %)
- 1. Total Release Ci 8.13E+00 3.20E+00 4.84E+00 3.25E+00
- 2. Average diluted uCi/ml 1.26E-04 7.92E-05 1.21E-04 7.51E-05 concentration during Period C. DISSOLVED AND ENTRAINED GASSES (estimated total error: 62.8 %)
- 1. Total Release Ci 5.10E-05 0.OOE+00 0.OOE+00 0.00E+00
- 2. Average diluted uCi/ml 7.93E-10 0.OOE+00 0.OOE+00 0.00E+00 concentration during Period D. GROSS ALPHA RADIOACTIVITY (estimated total error: 62.8 %)
- 1. Total Release Ci 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 E. VOLUME OF WASTE RELEASED (PRIOR TO DILUTION) (est tot er: 0.7 %)
- 1. Volume Released Liters 2.30E+06 1.44E+06 1.41E+06 1.45E+06 F. VOLUME OF DILUTION WATER USED DURING PERIOD (est tot er: 3.0 %)
- 1. Dilution Volume Liters 6.20E+07 3.90E+07 3.85E+07 4.18E+07 14
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:52:46 AM LIQUID EFFLUENTS FOR RELEASE POINT - LIQUID RADWASTE DISCHARGE TO SCHULYKILL RIVER Batch Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4 CO-58 Ci 3.98E-05 1.85E-06 9-47E-07 2.30E-06 CO-60 C1 3.89E-04 2.38E-04 5.59E-04 2.47E-04 CR-51 C1 1.76E-05 3.90E-06 CS-134 Ci 2.73E-06 CS-137 Ci 1.42E-06 1.48E-05 1.22E-05 1.86E-04 FE-59 Ci 7.13E-05 7.44E-06 H-3 Ci 8.13E+00 3.20E+00 4.84E+00 3.25E+00 LA-140 Ci 1.07E-06 MN-54 C1 7.28E-04 2.03E-04 1.78E-04 3.82E-05 NA-24 Ci 2.65E-05 SR-89 Ci 5.19E-05 ZN-65 Ci 1.17E-04 8.27E-06 3.21E-06 4.97E-06 ZR-97 Ci 7.68E-07 Total For Above Ci 8.13E+00 3.20E+00 4.84E+00 3.25E+00 XE-133 C1 2.83E-05 XE-135 Ci 2.26E-05 Total For Above Ci 5.10E-05 15
II. TABLES C. SOLID WASTE DISPOSITION REPORT January 1, 2002 to December 31, 2002 (5 pages of Tables) 16
A. Solid waste shipped offsite for burial or disposal (not irradiated fuel) 1/1/02 - 12/31/02
- 1. Tvoe of waste Unit 12 Month Period Estimated Error %
- a. Spent resin, filters,m(3) 52.95 25%
sludges, evaporator Ci 4 .94E+02 bottoms, etc.
- b. Dry compressible m(3) 433.74 25%
waste, contaminated Ci 4.81E+00 equipment, etc.
- c. Irradiated None None components, control rods, etc.
- d. Other (Describe) None None B. Number of Shippments of Each Class Type 1/1/02 - 12/31/02 Category A - 26 shipments Type A LSA Category A - 3 shipments > Type A LSA Category A - 1 shipment Type B Category B - 44 shipments Type A LSA Category C - No Shipments Made Category D - No Shipments Made 17
Estimate of Major Nuclide Composition (By Waste Type)
Category A - Spent Resin, Filters, Sludges, Evaporator Bottoms, etc.
Isotope Waste Percent Waste Percent Waste Percent Class A Abundance Class B Abundance Class C Abundance Curies Curies Curies C-14 2.02E-01 0.18% 3.40E-02 0. 01%W 7. 74E-02 0.10%
Co-60 2. 74E+01 24.04% 1. 53E+02 50.12% 2. 03E+01 27.12%
Cs-137 4. 52E+00 3.96% 2.23E+00 0.73% 2. 13E+00 2.85%
H-3 2.70E-01 0.24% 7.22E-02 0. 02% 1. 60E-01 0.21%
I-129 1.99E-02 0 .02% 1.85E-03 0. 00% S. 23E-03 0.01%
Mn-54 1.32E+01 11.58% 6. 11E+01 20.01% 1. 55E+01 20.71%
Ni-63 4.38E+00 3.84% 9.02E-01 0.30% 3.46E+00 4 .62%
Pu-238 2.25E-03 0 . 00% 1.06E-03 0 . 00% 1. O1E-03 0 . 00%
Pu-239 3.53E-05 0. 00% 0. OOE+00 0 . 00% 2. 55E-07 0 . 00%
Pu-241 1.23E-03 0. 00% 1.44E-02 0 . 00% 0. OOE+00 0 . 00%
Sr-90 5.32E-02 0.05% 9.49E-02 0.03% 2. 05E-02 0.03%
Tc-99 3.20E-01 0.28% 1.OlE-O1 0.03% 1.79E-01 0.24%
Zn-65 6.22E+01 54 .56% 8.49E+01 27.81% 3.22E+01 43.03%
Cm-242 7. 92E-02 0 .07% 3.44E-04 0 . 00% 1.13E-04 0. 00%
Cm-243 9.20E-02 0.08% 6.65E-05 0. 00% 2.57E-04 0 . 00%
Co-58 7.38E-01 0.65% 2.OOE+00 0.66% 7. 97E-01 1.06%
Cr-51 4.O0E-Ol 0.35% O.OOE+00 0. 00% 1.48E-03 0. 00%
Ce-144 1.03E-01 0 . 09% 4. 13E-01 0.14% 0. OOE+00 0. 00%
Fe-55 1.16E-01 0.10% 1.29E-01 0.04% 4 .47E-03 0. 01%
Cs-134 7.03E-02 0.06% 2.97E-01 0.10% 0. OOE+00 0. 00%
Fe-59 1.57E-01 0.14% 0. OOE+00 0. 00% 2.35E-03 0. 00%
Co-57 2.69E-05 0 . 00% 0. OOE+00 0. 00% 0. OOE+00 0. 00%
Ni-59 1.07E-03 0 .00% 0. OOE+00 0. 00% 1.20E-03 0. 00%
Am-241 1.77E-07 0 . 00% 1. 18E-04 0. 00% 2.27E-07 0. 00%
Sb-125 1.49E-04 0 . 00% 0. OOE+00 0. 00% O.OOE-00 0. 00%
TOTALS 1.14E+02 100. 00% 3.05E+02 100.00% 7.48E+01 100.00%
Activity is estimated 18
Estimate of Major Nuclide Composition (By Waste Type)
Category B - Dry Compressible Waste, Contaminated Equipment, etc.
Isotope Waste Percent Class A Abundance Curies H-3 2. 17E-03 0. 05%
Cr-51 1. 03E+00 21.41%
Mn-54 3.44E-01 7.15%
Fe-55 3.25E-01 6.75%
Co-58 3. 13E-01 6.51%
Co-60 1. 64E+00 34.09%
Ni-63 3.75E-01 7.79%
Zn-65 6.54E-01 13.59%
Cs-137 1.11E-02 0.23%
Ce-144 3.77E-02 0.78%
Fe-59 6.51E-02 1.35%
Sr-89 6.82E-03 0.14%
Tc-99 4.87E-05 0.006 I-129 3.50E-06 0. 00%
Pu-238 7.39E-05 0. O00 Cm-242 2.32E-05 0. 00%
Cm-243/44 5.20E-06 0 . 00%
Nb-95 6.48E-03 0. 13%
Am-241 1.44E-05 0. 00%
Sb-124 4. 60E-06 0. 00%
Zr-95 5. 1OE-06 0 . 00%
Pu-239 5.20E-06 0. 00%
TOTALS 4.81E+00 100.00%
Activity is estimated 19
C. Solid Waste (Disposition)
Number of Mode of Destination Shipments Made Transportation 5 Truck Studsvik (THOR) to Barnwell 17 Truck Studsvik (THOR) to Envirocare 34 Truck Duratek to Envirocare 10 Truck US Ecology to Envirocare 1 Truck Limerick Generating Station to Barnwell 7 Truck Limerick Generating Station to Envirocare Comments:
33 Shipments were made from Limerick to Duratek for processing.
2 Shipments were made from Limerick to US Ecology for processing.
1 Shipment was made from Limerick to Alaron (DAW) for processing.
11 Shipments were made from Limerick to Studsvik (THOR) for processing No solidifications were performed.
D. Irradiated Fuel Shipments (Disposition)
Number of Mode of Destination Shipments Made Transportation 0 N/A N/A 20
E. Major Changes to Plant Radwaste Systems There were no major changes to plant Radwaste Systems.
F. Changes to procedure RW-C-100, "Solid Radwaste System Process Control Program (PCP)"
There were no changes to the Solid Radwaste System Process Control Program (PCP) in 2002.
21
II. TABLES D. OFFSITE RADIATION DOSE ASSESSMENT January 1, 2002 to December 31, 2002 (1 page Table) 22
LIMERICK GENERATING STATION - Units 1 & 2
SUMMARY
OF MAXIMUM INDIVIDUAL DOSES FOR PERIOD:
01/01/02 0:00 TO 12/31/02 23:59 APPLICABLE EST. AGE LOCATION % OF LIMIT EFFLUENT ORGAN DOSE GROUP DIST DIR APPLICABLE (MREM)
(MREM) (M) (TOWARD) LIMIT LIQUID TOTAL BODY 2.56E-03 ADULT RECEPTOR 1 4.27E-02 6.0 LIQUID LIVER 3.42E-03 TEEN RECEPTOR 1 1.71E-02 20.0 NOBLE GAS AIR DOSE 4.15E-01 ALL 762. ESE 2.08E+00 20.0 (GAMMA-MRAD)
NOBLE GAS AIR DOSE 2.48E-01 ALL 762. ESE 6.20E-01 40.0 (BETA-MRAD)
NOBLE GAS T.BODY 2.70E-01 ALL 762. ESE 1.35E+00 20.0 (GAMMA)
NOBLE GAS SKIN 5.06E-01 ALL 762. ESE 1.27E+00 40.0 (BETA)
IODINE, THYROID 2.26E-02 CHILD 805. ESE 7.53E-02 30.0 PARTICULATE, And TRITIUM DOSE 23
II. TABLES E. RADIATION DOSES TO MEMBERS OF THE PUBLIC DUE TO THEIR ACTIVITIES INSIDE SITE BOUNDARY January 1, 2002 to December 31, 2002 (2 pages of Tables) 24
TABLE II. E Page 1 of 2 RADIATION DOSES TO MEMBERS OF THE PUBLIC DUE TO THEIR ACTIVITIES INSIDE SITE BOUNDARY Per ODCM Control 3.6, the Annual Effluent Release Report shall include an assessment of the radiation doses from radioactive liquid and gaseous effluents to members of the public due to activities inside the Site Boundary during the report period. ODCM Controls state that Members of the Public shall include all persons not occupationally associated with the plant. This category does not include employees of the utility or contractors. Also excluded from this category are persons who enter the site to service equipment or to make deliveries. This category does include persons who use portions of the site for recreational, occupational education, or other purposes not associated with the plant. The Limerick Information Center on Longview Road near the rear exit of the plant, Frick's Lock on the west shore of the river and the railroad tracks which run above the east shore of the Schuylkill River are all areas within the site boundary where radiation dose of this type could occur. The dose to LGS Guards, State Police and National Guard personnel around the location of the Security Checkpoint at the entrance to the parking lot is also included in this report. The radiation doses to Members of the Public have been estimated using methodology stated in the ODCM. The maximum gaseous dose to members of the public at these locations is based on the following assumptions:
- 1. Yearly average meteorology and actual effluent releases.
- 2. Beta air dose attributed to noble gas releases.
- 3. Highest exposed sector of the railroad tracks (W), and the sectors enclosing Security Checkpoint, Frick's Lock and the Information Center available for occupancy.
- 4. The maximum expected occupancy factor is 251 of a working year in all locations.
- 5. Distance to the railroad tracks, which pass through the Site Boundary in the W sector, is approximately 225 meters.
- 6. Distance to the Limerick Information Center is approximately 884 meters in the ESE sector.
- 7. Distance to Frick's Lock is approximately 450 meters in the WSW sector.
- 8. Distance to Security Checkpoint is approximately 682 meters in NNE sector.
25
- i TABLE II.E Page 2 of 2 A summary of gaseous radiation doses to members of the public at these locations is included in this Attachment.
RADIATION DOSE TO MEMBERS OF THE PUBLIC WITHIN LIMERICK GENERATING STATION SITE BOUNDARY FOR AFFECTED SECTORS AND DISTANCES APPROX. GAMMA BETA AIR IODINE/PART/H3 IODINE/PART/H3 LOCATION SECTO DISTANE AIR DOSE, ORGAN DOSE, INGEST DOSE, R (METERS) DOSE, MRAD(1) MRAD (2) MREM (3) MREM(4)
FRICK'S WSW 450 2.61E-02 1.56E-02 1.42E-03 1.18E-03 LOCK INFO. ESE 884 8.32E-02 4.96E-02 4.53E-03 3.78E-03 CENTER R.R. W 225 1.01E-01 6.OOE-02 5.47E-03 4.56E-03 TRACKS NATIONAL NNE 682 5.81E-02 3.47E-02 3.16E-03 2.64E-03 GUARD/
SECURITY CHECK POINT Notes:
(1) The limit for Gamma Air Dose = 20 mrad/y (ref. ODCM I3.3.3b)
(2) The limit for Beta Air Dose = 40 mrad/y (ref. ODCM I3.3.3b)
(3) The limit for Iodine/Particulate/H3 Organ Dose = 30 mrem/y (ref. ODCM I3.3.4b)
(4) The limit for Iodine/Particulate/H3 Ingestion Dose = 30 mrem/y (ref. ODCM I3.3.4b) 26
III. ATTACHMENTS A. SUPPLEMENTAL INFORMATION Facility: Limerick Generating Station - Units 1 and 2 License : NPF-39 (Unit 1) and NPF-85 (Unit 2)
- 1. Requlatory Limits (Technical Specification Limits)
A. Noble Gases:
- 1. < 500 mRem/y - total body - "instantaneous" limits
< 3000 mRem/y - skin per ODCM Control 3.3.2
- 2. < 10 mRad - air gamma - quarterly air dose limits
< 20 mRad - air beta per ODCM Control 3.3.3
- 3. < 20 mRad - air gamma - yearly air dose limits
< 40 mRad - air beta per ODCM Control 3.3.3 B. Iodines. tritium, particulates with half life > 8 days:
- 1. < 1500 mRem/y - any organ - "instantaneous" limits (inhalation per ODCM Control 3.3.2 path)
- 2. < 15 mRem - any organ - quarterly dose limits per ODCM Control 3.3.4
- 3. < 30 mRem - any organ - yearly dose limits per ODCM Control 3.3.4 C. Liquid Effluents:
Concentration - < 10CFR20 -f"instantaneous" limits Appendix B, Table II, Col.2
- per ODCM Control 3.2.2
< 3 MRem - total body - quarterly dose limits
< 10 mRem - any organ per ODCM Control 3.2.3
< 6 mRem - total body - yearly dose limits
< 20 mRem - any organ per ODCM Control 3.2.3 27
III. ATTACHMENTS (continued)
- 2. Maximum Permissible Concentrations Per LGS ODCM Control 3.2.2, MPCs are not used to calculate permissible release rates and concentrations for gaseous releases. The MPCs specified in 10CFR20, Appendix B, Table II, Column 2 for identified nuclides are used to calculate permissible release rates and concentrations for liquid releases.
28
III. ATTACHMENTS (continued)
- 3. Measurements and Approximations of Total Radioactivity A. Fission and Activation Gases in Gaseous Effluents:
The method used for Gamma Isotopic Analysis is the Canberra Genie System with a gas Marinelli beaker. Noble gas releases are continuously monitored by a radiation monitoring system with the data stored on a computer system (RMDS). The monitor data is analyzed to report noble gas effluent activities. When no activity is found in the Isotopic Analysis, the isotopic mixture is assumed to be that evaluated in the UFSAR (section 11.5, Table 11.5-4). If activity is found in the Isotopic Analysis, the isotopic mixture for the noble gas monitor is determined from the Isotopic Analysis.
B. Iodine in Gaseous Effluents:
The method used is the Canberra Genie System with a charcoal cartridge.
C. Particulate in Gaseous Effluents:
The method used is the Canberra Genie System with an air particulate sample, 47 mm filter.
D. Gamma Isotopic Analysis in Liquid Effluents:
The method used is the Canberra Genie System using a 1.0 liter Marinelli beaker. A Radwaste Liquid Discharge Pre-Release report is generated to ensure that the dose and activity to be released is within limits.
E. Tritium in Liquid and Gaseous Effluents:
Tritium in Liquid Effluents is analyzed using a Liquid Scintillation Counter.
Air from stack effluents is passed through two bubblers in series and an aliquot of the water from each bubbler analyzed using a Liquid Scintillation Counter.
29
III. ATTACHMENTS (continued)
- 4. Batch Liquid Releases Summary January 1, 2002 to December 31, 2002 (1 page Table) 30
III. ATTACHMENTS (continued)
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2002 DATE: 02/05/2003 9:52:46 AM LIQUID EFFLUENTS FOR RELEASE POINT - LIQUID RADWASTE DISCHARGE TO SCHULYKILL RIVER Batch Mode Qtr 1 Qtr 2 Qtr 3 Qtr 4 Number of Batch Releases 3.80E+01 2.70E+01 2.60E+01 2.60E+01 Total time period for 2.76E+03 1.76E+03 1.71E+03 1.74E+03 batch releases (min)
Maximum time period for 9.58E+01 8.39E+01 8.79E+01 7.54E+01 batch release (min)
Average time period for 7.27E+01 6.51E+01 6.58E+01 6.69E+01 batch release (min)
Minimum time period for 3.08E+01 3.45E+01 3.44E+01 3.03E+01 batch release (min)
Average stream flow 5.49E+05 8.98E+05 1.98E+05 1.26E+06 (Schuylkill River) during periods of release of effluents into a flowing stream (gpm) 31
III. ATTACHMENTS (continued)
- 5. Batch Gaseous Release (January 1, 2002 to December 31, 2002)
(1 page Table)
- Oil Incineration
- Other Batch Releases
- Average Energy of Release 32
III. ATTACHMENTS (continued)
GASEOUS EFFLUENTS FOR RELEASE POINT - OTHER BATCH RELEASES Batch Mode Qtr 1 Qtr 2 Qtr 3 Qtr 4 Number of Batch Releases O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Total time period for O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 batch releases (min)
Maximum time period for O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 batch release (min)
Average time period for O.OOE+00 O.OOE+00 O.OQE+00 O.OOE+00 batch release (min)
Minimum time period for O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 batch release (min)
AVERAGE ENERGY OF DECAY FOR ACTIVATION AND FISSION GASES FOR 2002 Average Beta Energy of decay: 3.01E-01 MeV Average Gamma Energy of decay: 5.08E-01 MeV 33
III. ATTACHMENTS (continued)
- 6. Abnormal Releases A. Liquld There were no significant abnormal liquid releases for year 2002. There was one unplanned release which is described on page 39.
B. Gaseous There were no significant abnormal gaseous releases for year 2002.
- 7. Description of LGS Effluent Release Points Gaseous Release Point = North Stack, Common Gaseous Release Point = Unit 1 South Stack Gaseous Release Point = Unit 2 South Stack Gaseous Release Point = Hot Maintenance Shop Gaseous Release Point = Oil Incineration - Aux Boiler A Gaseous Release Point = Other Batch Releases Liquid Release Point = Liquid Radwaste Discharge
- 8. Description of LGS Liquid Dose Receptors Receptor 1 = LGS Liquid Radwaste Discharge Point Receptor 2 = Citizens Home Water Company Receptor 3 = Phoenixville Water Company Receptor 4 = Philadelphia Suburban Water Company Receptor 5 = City of Philadelphia Crew Course B. RADIATION MONITORS OUT-OF-SERVICE CONDITION There are no radiation monitor out-of-service conditions to report.
34
III. ATTACHMENTS (continued)
C. REVISION TO PREVIOUS SUBMITTAL Two of the tables from the 2001 Annual Radioactive Effluent Release Report contained several typographical errors. The first table with errors is on page 22 of the 2001 report. The "Total For Above" activities listed were actually from the 2000 report. The second table with errors is on page 28 of the 2001 report. The headings on two columns were listed as "Class A".
They should have been "Class B" and "Class C". The corrected pages for the 2001 report are listed on the next three pages.
35
III. ATTACHMENTS (continued)
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2001 DATE: 02/13/2002 2:59:24 PM LIQUID EFFLUENTS FOR RELEASE POINT - LIQUID RADWASTE DISCHARGE TO SCHULYKILL RIVER Batch Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4 AG-llOM ci O . OOE+00 O.OOE+00 9.48E-07 0. OOE+00 BA-139 ci O. OOE+00 O. OOE+00 0. OOE+00 0. OOE+00 BA- 140 ci O . OOE+00 O . OOE+00 0.OOE+00 0. OOE+00 BA- 14 1 O.OOE+00 O.OOE+O0 0. OOE+00 0. OOE+00 BA-142 Ci 0. OOE+00 0. OOE+00 0. OOE+00 0. OOE+00 BR-83 Ci O. OOE+00 O. OOE+00 0. OOE+00 0. OOE+00 BR-84 ci O . OOE+00 O . OOE+00 0. OOE+0O 0. OOE+00 BR-85 O.OOE+00 O.OOE+00 O . OOE+00 0. OOE+0O C-14 O. OOE+00 0. OOE+00 0. OOE+0O O.OOE+00 CE-141 ci O . OOE+00 O . OOE+00 O.OOE+00 0. OOE+00 CE-143 ci O.OOE+0O O. OOE+00 0. OOE+00 0. OOE+00 CE-144 ci O.OOE+00 O . OOE+00 0. OOE+00 O . OOE+00 CO-58 ci
- 5. 06E-04 9. 92E-04 4.84E-04 2.08E-04 ci CR-51 4.45E-04 4. 76E-04 2.44E-05 0. OOE+00 ci CS-134 O. OOE+00 O. OOE+00 0. OOE+00 O. OOE+00 CS-136 ci
- 0. OOE+00 O.OOE+0O 0. OOE+00 0. OOE+00 ci CS-137 5. 07E-06 2.23E-05 0. OOE+00 2.17E-05 ci CS-138 O. OOE+00 O. OOE+00 0. OOE+00 O.OOE+00 ci CU-64 O . OOE+00 O. OOE+00 O.OOE+00 0. OOE+00 FE-55 Ci O OOE+00 O . OOE+00 0. OOE+O0 0. OOE+00 FE-59 ci O. OOE+00 1.80E-05 0. OOE+00 O. OOE+OO H-3 1. 37E+01 1 60E+01 8. 74E+00 3.43E+00 ci I-130 O.OOE+00 0. OOE+00 0. OOE+00 O.OOE+00 ci I-131 0. OOE+00 O . OOE+00 O.OOE+00 0. OOE+00 I-132 O.OOE+00 0. OOE+00 0. OOE+00 0. OOE+00 1-133 Ci O. OOE+00 O.OOE+00 0. OOE+00 0. OOE+0O ci I-134 O.OOE+O0 0. OOE+00 0. OOE+00 O. OOE+00 ci I-135 O.OOE+00 0. OOE+00 0. OOE+00 O.OOE+00 LA-140 ci
- 0. OOE+00 6.50E-06 O.OOE+00 0. OOE+00 LA-142 O. OOE+00 0. OOE+00 0. OOE+00 0. OOE+00 MN-54 ci
- 2. 70E-05 6.49E-04 5. 69E-05 O.OOE+0O MN-56 ci O . OOE+00 0. OOE+00 0. OOE+00 O.OOE+O0 MO-99 O . OOE+00 5. 19E-06 3.21E-07 O.OOE+00 NA-24 ci O . OOE+00 0. OOE+00 O.OOE+00 O.OOE+00 NB-95 Ci O. OOE+00 O. OOE+00 O.OOE+00 0. OOE+0O ND-147 O.OOE+00 O.OOE+00 0. OOE+00 O. OOE+0O NI-63 0. OOE+00 0. OOE+OO O. OOE+00 O. OOE+O0 36
III. ATTACHMENTS (continued)
SITE: LIMERICK GENERATING STATION - UNITS 1 & 2 EFFLUENT REPORT - 2001 DATE: 02/13/2002 2:59:24 PM LIQUID EFFLUENTS FOR RELEASE POINT - LIQUID RADWASTE DISCHARGE TO SCHULYKILL RIVER Batch Mode Nuclide Released Units Qtr 1 Qtr 2 Qtr 3 Qtr 4 NI-65 ci O.OOE+00 O.OOE+00 O.OOE+00 0. OOE+00 NP-239 ci O.OOE+00 O.OOE+00 O.OOE+00 0. OOE+00 P-32 ci O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 PR-143 ci O.OOE+00 O.OOE+00 0. OOE+00 0. OOE+00 PR-144 ci 0. OOE+00 0. OOE+00 O.OOE+00 0 . OOE+00 RB -86 ci 0. OOE+00 0. OOE+00 O.OOE+00 0. OOE+00 RB-88 0. OOE+00 0. OOE+00 0. OOE+00 O.OOE+00 Ci RB-89 0. OOE+00 0. OOE+00 0. OOE+00 O.OOE+00 ci RU-103 0. OOE+00 O.OOE+00 0. OOE+00 O.OOE+00 ci RU-105 0. OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 ci RU-106 0. OOE+00 O.OOE+00 0. OOE+00 O.OOE+00 ci SR-89 0. OOE+00 O.OOE+00 0. OOE+00 O.OOE+00 ci SR-90 0. OOE+00 O.OOE+00 0. OOE+00 O.OOE+00 ci SR-91 0. OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 ci SR-92 0. OOE+00 O.OOE+00 0. OOE+00 0. OOE+00 ci TC-101 0. OOE+00 0. OOE+00 0. OOE+00 0.00E+00 ci TC-99M 0. OOE+00 O.OOE+00 0. OOE+00 0. OOE+00 ci TE-125M 0. OOE+00 O.OOE+00 0. OOE+00 0. OOE+00 ci TE-127M 0. OOE+00 O.OOE+00 0 . OOE+00 O.OOE+00 ci TE-127 0. OOE+00 O.OOE+00 O.OOE+00 0.OOE+00 ci TE-129M O.OOE+00 0. OOE+00 0. OOE+00 O.OOE+00 ci TE-129 0. OOE+00 O.OOE+00 O.OOE+00 0. OOE+00 ci TE-131M O.OOE+00 O.OOE+00 0. OOE+00 0. OOE+00 ci TE-131 O.OOE+00 O.OOE+00 0. OOE+00 O.OOE+00 ci TE-132 0. OOE+00 O.OOE+00 O.OOE+00 0. OOE+00 Ci W-187 0. OOE+00 0. OOE+00 O.OOE+00 0. OOE+00 ci Y-90 0. OOE+00 O.OOE+00 0. OOE+00 O.OOE+00 Ci Y-91M 0. OOE+00 0. OOE+00 O. OOE+00 0. OOE+00 ci Y-91 0. OOE+00 0. OOE+00 0. OOE+00 0. OOE+00 ci Y-92 0. OOE+00 O.OOE+00 0. OOE+00 0. OOE+00 ci Y-93 0. OOE+00 0. OOE+00 0. OOE+00 O.OOE+00 ci ZN-65 7.84E-04 2.17E-03 2.40E-05 4.64E-05 ci ZN-69 0. OOE+00 O.OOE+00 0 . OOE+00 0. OOE+00 ci ZR-95 0. OOE+00 O.OOE+00 0. OOE+00 O.OOE+00 ci ZR-97 0. OOE+00 0. OOE+00 0 . OOE+00 0. OOE+00 Total For Above Ci 1.37E+01 1.60E+01 8.74E+00 3.43E+00 37
III Attachments (continued)
Estimate of Major Nuclide Composition (By Waste Type)
Category C - Irradiated Components, Control Rods, etc.
Isotope Waste Percent Waste Percent Class B Abundance Class C Abundance Curies Curies H-3 4.50E-05 0.00% 2.33E-01 o.oo%
C-14 3.60E-05 0.00% 3.18E+00 0.00%
Cr-51 4.90E+00 32.92% 4.77E+02 0.64%
Mn-54 3.46E-01 2.32% 1.15E+03 1.55%
Fe-55 2.84E+00 19.08% 3.46E+04 46.69%
Ni-59 0.00E+00 0.00% 1.16E+01 0.02%
Co-60 4.78E+00 32.11% 3.48E+04 46.96%
Ni-63 0.OOE+00 0.00% 2.09E+03 2.82%
Zn-65 2.02E+00 13.57% 0.OOE+00 0.00%
Zr-95 0.OOE+00 0.00% 4.96E+00 0.01%
Tc-99 1.94E-04 0.00% 1.14E-02 0.00%
Sb-125 0.OOE+00 0.00% 9.68E+02 1.31%
I-129 2.91E-06 0.00% 0.OOE+00 0.00%
Pu-238 0.OOE+00 0.00% 1.08E-02 0.00%
PU-239/40 0.OOE+00 0.00% 1.83E-05 0.00%
Pu-241 0.OOE+00 0.00% 3.36E-03 0.00%
Am-241 0.OOE+00 0.00% 6.28E-06 0.00%
Cm-242 0.OOE+00 0.00% 1.14E-03 0.00%
Cm-243/44 0.OOE+00 0.00% 5.05E-04 0.00%
Nb-94 0.OOE+00 0.00% 6.94E-02 0.00%
U-235 0.OOE+00 0.00% 7.63E-08 0.00%
Np-237 0.OOE+00 0.00% 7.89E-07 0.00%
Pu-242 0.OOE+00 0.00% 1.27E-06 0.00%
Am-243 0.OOE+00 0.00% 6.24E-07 0.00%
TOTALS 1.49E+01 100.00% 7.41E+04 100.00%
Activity is estimated 38
III. ATTACHMENTS (continued)
D. OFFSITE DOSE CALCULATION MANUAL REVISIONS The ODCM was not revised during the year 2002.
E. UNPLANNED RELEASES
- 1. Traces of Tritium found in Holding Pond On two occasions during 2002, Tritium was found at very low concentration levels in the Waste Water Holding Pond. On February 15, 2002, Tritium was detected at a concentration of 8.49E-6 uCi/cc and on November 15, 2002, Tritium was again detected at a concentration of 1.14E-6 uCi/ml. The Tritium activity was discovered as part of a routine test (RT-5-104-800-0) to look for tritium in normally clean systems. Both of these events were traced to a break in the Unit 2 CST steam heating return line to the auxiliary boilers. With the break in the Unit 2 CST steam heating return line, boiler blowdowns and various vents in the steam heating system, an unplanned release of small amounts of tritium to the environment resulted. The amount of tritium released was reduced as much as possible through various station preventative and corrective actions.
Based on Holding Pond and Auxiliary Boiler analyses, the total amount of Tritium released to the environment from the two unplanned releases was 0.139 Curies. This value represents less than 0.2% of the annual amount of tritium released from other planned releases at LGS and is well below allowable limits.
The Unit 2 CST steam heating line was repaired during the 2003 Unit 2 refuel outage.
39
NUGlear Joint Frequency Distribution of Wind Speed and Direction by Atmospheric Stability Class 2002 Limerick Generating Station
Exelon Nuclear LIMERICK GENERATING STATION DOCKET NO. 50-352 (Unit 1)
DOCKET NO. 50-353 (Unit 2)
Tower No. 1 Joint Frequency Distributions of Wind Speed and Direction by Atmospheric Stability Class 2002 Report No. 18 Submitted to The United States Nuclear Regulatory Commission Pursuant to Facility Operating License NPF-39 (Unit 1) and NPF-85 (Unit 2)
2002 ANNUAL DISPERSION CALCULATIONS AT SPECIFIC POINTS OF INTEREST
Table I Limerick Generating Station 2002 Annual Dispersion Calculations at Specific Points of Interest North Vent, Flow = 363,000 cfm X/Q X/Q Type of No Decay 8.05 Day Decay Location Direction Distance Undepleted Depleted D/Q (miles) (meters) (sec/m 3 ) (sec/r 3 ) (m-2)
Site Boundary S 047 762 3.169E-7 2.909E-7 2.426E-9 Site Boundary SSW 0.47 762 2.11OE-7 1.936E-7 1.209E-9 Site Boundary SW 0.55 884 1.509E-7 1.371E-7 1.086E-9 Site Boundary WSW 0 53 854 2.013E-7 1.834E-7 1.249E-9 Site Boundary W 0.53 854 2 288E-7 2.083E-7 1.792E-9 Site Boundary WNW 0.49 793 1.414E-7 1.294E-7 1.149E-9 Site Boundary NW 0.47 762 1.368E-7 1.255E-7 1.013E-9 Site Boundary NNW 0.55 884 2.220E-7 2.021 E-7 1.800E-9 Site Boundary N 0 55 884 4.908E-7 4.468E-7 3.521E-9 Site Boundary NNE 0.49 793 8.924E-7 8.1 82E-7 5.275E-9 Site Boundary NE 0.49 793 7.182E-7 6.596E-7 4.145E-9 Site Boundary ENE 0.49 793 6.845E-7 6.284E-7 3.864E-9 Site Boundary E 0.47 762 1.057E-6 9.722E-7 8.508E-9 Site Boundary ESE 0.47 762 2.023E-6 1.855E-6 1.439E-8 Site Boundary SE 0.47 762 9.713E-7 8.91 OE-7 9.037E-9 Site Boundary SSE 0.63 1006 3.551 E-7 3.199E-7 2.868E-9 Railroad Tracks S 0.19 300 1.425E-6 1.366E-6 8.664E-9 Railroad Tracks SSW 0.14 225 1.544E-6 1.493E-6 6.498E-9 Railroad Tracks SW 0.14 225 1.307E-6 1.264E-6 7.347E-9 Railroad Tracks WSW 0.14 225 1.662E-6 1.607E-6 7.615E-9 Railroad Tracks W 0.14 225 1.914E-6 1.851 E-6 1.21 OE-8 Railroad Tracks WNW 0.21 345 5.247E-7 5.033E-7 3.894E-9 Railroad Tracks NW 0.28 450 2.973E-7 2.799E-7 2.039E-9 Information Ctr. ESE 0.55 884 1.619E-6 1.471 E-6 1.1 64E-8 Fricks Lock WSW 0 28 450 5.071 E-7 4.775E-7 2.900E-9 Nat'l Guard Sta. NNE 0 42 682 1.116E-6 1.031E-6 6.507E-9 METEOROLOGICAL EVALUATION SERVICES
Table I Limerick Generating Station 2002 Annual Dispersion Calculations at Specific Points of Interest North Vent, Flow = 363,000 cfm XIQ XIQ Type of No Decay 8 05 Day Decay Location Direction Distance Undepleted Depleted D/Q
. (miles) (meters) (sec/m 3) (sec/m 3 ) (m2)
Site Boundary S 0 47 762 3.169E-7 2.909E-7 2.426E-9 Site Boundary SSW 047 762 2.11OE-7 1.936E-7 1 209E-9 Site Boundary SW 0 55 884 1 509E-7 1 371E-7 1.086E-9 Site Boundary WSW 0 53 854 2.013E-7 1.834E-7 1 249E-9 Site Boundary W 0.53 854 2 288E-7 2 083E-7 1.792E-9 Site Boundary WNW 0.49 793 1.414E-7 1.294E-7 1.149E-9 Site Boundary NW 0.47 762 1.368E-7 1.255E-7 1.013E-9 Site Boundary NNW 0.55 884 2.220E-7 2.021 E-7 1.800E-9 Site Boundary N 0.55 884 4 908E-7 4 468E-7 3.521 E-9 Site Boundary NNE 0.49 793 8 924E-7 8.182E-7 5 275E-9 Site Boundary NE 0 49 793 7.182E-7 6 596E-7 4.145E-9 Site Boundary ENE 0 49 793 6 845E-7 6.284E-7 3.864E-9 Site Boundary E 0 47 762 1.057E-6 9.722E-7 8.508E-9 Site Boundary ESE 0.47 762' 2.023E-6 1.855E-6 1.439E-8 Site Boundary SE 0.47 762 9.713E-7 8.910E-7 9.037E-9 Site Boundary SSE 0.63 1006 3.551E-7 3.199E-7 2.868E-9 Railroad Tracks S 0.19 300 1.425E-6 1 366E-6 8 664E-9 Railroad Tracks SSW 0.14 225 1.544E-6 1.493E-6 6.498E-9 Railroad Tracks SW 0.14 225 1.307E-6 1 264E-6 7.347E-9 Railroad Tracks WSW 0.14 225 1 662E-6 1 607E-6 7.615E-9 Railroad Tracks W 0.14 225 1.914E-6 1.851E-6 1.21OE-8 Railroad Tracks WNW 0.21 345 5.247E-7 5.033E-7 3.894E-9 Railroad Tracks NW 0.28 450 2.973E-7 2.799E-7 2.039E-9 Information Ctr. ESE 0.55 884 1.619E-6 1.471E-6 1.164E-8 Fricks Lock WSW 0 28 450 5.071E-7 4.775E-7 2.900E-9 Nat'l Guard Sta. NNE 0 42 682 1.116E-6 1.031E-6 6.507E-9 METEOROLOGICAL EVALUATION SERVICES
Table 2 Limerick Generating Station 2002 Annual Dispersion Calculations at Specific Points of Interest South Vent, Flow = 144,000 cfm XIQ XIQ Type of No Decay 8.05 Day Decay Location Direction Distance Undepleted Depleted DIQ (miles) (meters) (secIM3) (sec/mr) (m )
Site Boundary S 0.47 762 3 524E-7 3.235E-7 2.627E-9 Site Boundary SSW 0 47 762 2 317E-7 2.127E-7 1 319E-9 Site Boundary SW 0.55 884 1.673E-7 1.520E-7 1.208E-9 Site Boundary WSW 0.53 854 2.212E-7 2.016E-7 1.524E-9 Site Boundary W 0.53 854 2.571 E-7 2.343E-7 2.169E-9 Site Boundary WNW 0.49 793 1.616E-7 1 479E-7 1.285E-9 Site Boundary NW 0.47 762 1.544E-7 1.418E-7 1.119E-9 Site Boundary NNW 0.55 884 2 544E-7 2.322E-7 1.918E-9 Site Boundary N 0.55 884 5 541 E-7 5.056E-7 3.738E-9 Site Boundary NNE 0 49 793 9.948E-7 9.134E-7 6 096E-9 Site Boundary NE 0 49 793 8.069E-7 7.424E-7 5.032E-9
-Site Boundary ENE 0.49 793 7.766E-7 7.142E-7 5.219E-9 Site Boundary E 0 47 762 1.184E-6 1.090E-6 1.040E-8 Site Boundary ESE 0.47 762 2.205E-6 2.022E-6 1.517E-8 Site Boundary SE 0 47 762 1.058E-6 9.705E-7 9 945E-9 Site Boundary SSE 0 63 1006 3 913E-7 3.526E-7 3.260E-9 Railroad Tracks S 0.19 300 1.581 E-6 1.515E-6 9.623E-9 Railroad Tracks SSW 0 14 225 1.687E-6 1 631 E-6 7.148E-9 Railroad Tracks SW 0.14 225 1.441E-6 1.394E-6 8.088E-9 Railroad Tracks WSW 0.14 225 1.814E-6 1.754E-6 8 346E-9 Railroad Tracks W 0.14 225 2.137E-6 2.067E-6 1.357E-8 Railroad Tracks WNW 0.21 345 5.997E-7 5.719E-7 4.403E-9 Railroad Tracks NW 0.28 450 3.339E-7 3.144E-7 2.285E-9 Information Ctr. ESE 0.55 884 1.768E-6 1.607E-6 1.223E-8 Fricks Lock WSW 0.28 450 5.543E-7 5.219E-7 3.254E-9 Nat'l Guard Sta. NNE 0 42 682 1.236E-6 1.1432-6 7.521E-9 METEOROLOGICAL EVALUATION SERVICES
Table 3 Limerick Generating Station 2002 Annual Dispersion Calculations for Inhalation Pathway Receptors North Vent, Flow = 363,000 cfm XIQ XIQ No Decay 8.05 Day Decay Direction Distance Undepleted Depleted DIQ (miles) (meters) (secIM3 ) (sec/m 3 ) (m-2)
N 0.60 965 4 355E-7 3.944E-7 3.138E-9 NNE 0.50 805 8.736E-7 8 003E-7 5.167E-9 NE 0 80 1287 3.845E-7 3 469E-7 2 205E-9 ENE 0.60 965 5.208E-7 4.731 E-7 2.986E-9 E 0.60 965 7.614E-7 6.912E-7 6.106E-9 ESE 0.50 805 1.864E-6 1.703E-6 1.330E-8 SE 1.00 1609 3 214E-7 2.828E-7 3.041 E-9 SSE 1.00 1609 1.842E-7 1 626E-7 1 559E-9 S 0.80 1287 1.491 E-7 1.329E-7 1.249E-9 SSW 1.00 1609 7.724E-8 6 854E-8 5.983E-10 SW 0.60 965 1.330E-7 1.201 E-7 9.850E-10 WSW 0.80 1287 1.161E-7 1 038E-7 9.041E-10 W 0 60 965 1.915E-7 1.729E-7 1.555E-9 WNW 0.70 1126 8 565E-8 7.671E-8 7.150E-10 NW 1.30 2092 4.322E-8 3 870E-8 3.134E-10 L NNW 0.90 1448 1.243E-7 1.116E-7 9.475E-10 METEOROLOGICAL EVALUATION SERVICES
Table 4 Limerick Generating Station 2002 Annual Dispersion Calculations for Inhalation Pathway Receptors South Vent, Flow = 144,000 cfm XIQ XIQ No Decay 8 05 Day Decay Direction Distance Undepleted Depleted DIQ (miles) (meters) (sec/rn3) (secIM3 ) (m-2)
N 0 60 965 4 956E-7 4 503E-7 3.318E-9 NNE 0.50 805 9 747E-7 8 943E-7 5.969E-9 NE 0 80 1287 4.583E-7 4.167E-7 2.677E-9 ENE 0 60 965 5.980E-7 5.449E-7 4 060E-9 E 0.60 965 8.656E-7 7.882E-7 7.424E-9 ESE 0.50 805 2.032E-6 1 858E-6 1.401E-8 SE 1.00 1609 3.553E-7 3 132E-7 3 247E-9 SSE 1.00 1609 2.080E-7 1.842E-7 1.697E-9 S 0.80 1287 1.670E-7 1.491E-7 1.330E-9 SSW 1.00 1609 9.1OE-8 8 150E-8 6.599E-10 SW 0.60 965 1.481E-7 1.338E-7 1.168E-9 WSW 0.80 1287 1.346E-7 1.212E-7 1.188E-9 W 0.60 965 2.161E-7 1.953E-7 1.902E-9 WNW 0.70 1126 9 846E-8 8.825E-8 8 535E-10 NW 1.30 2092 5.583E-8 5.061E-8 3.334E-10 NNW 0.90 1448 1.524E-7 1.381E-7 9.880E-10 METEOROLOGICAL EVALUATION SERVICES
Table 5 Limerick Generating Station 2002 Annual Dispersion Calculations for Ingestion Pathway Receptors North Vent, Flow = 363,000 cfm Vegetation Pathway Meat Pathway Cow Pathway Goat Pathway Distance DIQ Distance DIQ Distance D/Q Distance D/Q Direction (miles) (meters) 2 2 2 (m-) (miles) (meters) (m ) (miles) (meters) (m. ) (miles) (meters) (m 2)
N 1.60 2574 7.983E-10 2.12 3414 5 911 E-10 4.70 7562 2.767E-10 NNE 0.50 805 5.167E-9 0.98 1585 2.001E-9 -
NE 1.50 2414 9.511E-10 0.68 1097 2.713E-9 - -
ENE 1.80 2896 6 670E-10 2.41 3871 4.232E-10 - -
E 1.10 1770 2.442E-9 1.17 1890 2.205E-9 - -
ESE 1.20 1931 3.563E-9 2 80 4511 9 351E-10 1.10 1770 4.096E-9 1.10 1770 4 096E-9 SE 1.10 1770 2 637E-9 4.50 7241 2.756E-10 - - - -
SSE 1 20 1931 1.214E-9 4.49 7224 2 064E-10 4 70 7562 2 067E-10 - - -
S 1.20 1931 7.622E-10 1 88 3018 4.885E-10 2 30 3701 3 521E-10 - - -
SSW 1.40 2253 4.084E-10 0.89 1433 6 431 E-10 1.80 2896 2 909E-10 - - -
SW 0.60 965 9.850E-10 1.76 2835 3 801 E-10 3.00 4827 2.051E-10 - - -
WSW 0.80 1287 9.041 E-10 1.33 2134 6 691 E-10 2.80 4505 2.659E-10 - - -
W 2 20 3540 3 230E-10 2.54 4084 2 697E-10 -
WNW 0.70 1126 7.150E-10 - -
NW 1.60 2574 2.402E-10 4.14 6660 9.153E-11 NNW 1.20 1931 6 407E-10 3.93 6325 2 057E-10 METEOROLOGICAL EVALUATION SERVICES
Table 6 Limerick Generating Station 2002 Annual Dispersion Calculations for Ingestion Pathway Receptors South Vent, Flow = 144,000 cfm Vegetation Pathway Meat Pathway Cow Pathway Goat Pathway Distance D/Q Distance D/Q Distance D/Q Distance D/Q Direction (miles) 2 (meters) (m-) (miles) (meters) (m-2) (miles) (meters) (m2) (miles) (meters) (m 2)
N 1.60 2574. 9.345E-10 2.12 3414. 8.129E-10 4.70 7562. 2 784E-10 NNE 0.50 805. 5.969E-9 0.98 1585. 2.405E-9 - -
NE 1.50 2414. 1.046E-9 0.68 1097. 3.345E-9 -
ENE 1.80 2896. 7.078E-10 2.41 3871. 4.363E-10 -
E 1.10 1770. 2.830E-9 1.17 1890. 2.540E-9 - - - -
ESE 1.20 1931. 3.609E-9 2 80 4511. 9.699E-10 1.10 1770 4.154E-9 1.10 1770 4.154E-9 SE 1.10 1770. 2.794E-9 4 50 7241. 2.791E-10 - - - - -
SSE 1.20 1931. 1.274E-9 4.49 7224. 2.388E-10 4.70 7562. 2.161 E-10 -
S 1.20 1931. 8 818E-10 1.88 3018. 4.925E-10 2.30 3701. 3.727E-10 -
SSW 1.40 2253. 4.135E-10 0.89 1433. 7.521 E-10 1.80 2896. 3.082E-10 -
SW 0 60 965. 1.168E-9 1 76 2835. 3.737E-10 3 00 4827. 2.142E-10 -
WSW 0 80 1287. 1.188E-9 1.33 2134. 6 543E-10 2 80 4505. 2.861E-10 -
W 2.20 3540. 3.474E-10 2 54 4084. 2.986E-10 - -
WNW 0.70 1126. 8.535E-10 - -
NW 1.60 2574. 2.563E-10 4 14 6660. 1.160E-10 NNW 1.20 1931. 7.11OE-10 3.93 6325. 2.100E-10 METEOROLOGICAL EVALUATION SERVICES
N w E S
3.5 7.5 12.5 18.5 7245 FIGURE 1 Limerick Gen. Sta.
WIND SPEED CLASS BOUNDARIES Wind Level 1, 30-ft (MILES/HOJR) 2002 Annual NOTES: Wind Rose DIAGRAM OF THE FREQUENCY OF OCCURRENCE OF EACH WIND DIRECTION.
WIND DIRECTION IS THE DIRECTION FROM WHICH THE WIND IS BLOWING.
EXAMPLE - WIND IS BLOWING FROM THE NORTH 4.7 PERCENT OF THE TIME.
METEOROLOGICAL EVALUATION SERVICES
sI N
- w. E S
24.5 3.5 7.5 12.5 18.5 2 FIGURE 2
_ _ n Limerick Gen. Sta.
WIND SPEED CLASS BOUNDARIES Wind Level 2, 175-ft (MILES/HOUR) 2002 Annual NOTES: Wind Rose DIAGRAM OF THE FREQUENCY OF OCCURRENCE OF EACH WIND DIRECTION.
WIND DIRECTION IS THE DIRECTION FROM WHICH THE WIND IS BLOWING.
EXAMPLE - WIND IS BLOWING FROM THE NORTH 4.9 PERCENT OF THE TIME.
METEOROLOGICAL EVALUATION SERVICES
Attachment I Limerick Generating Station 2002 Annual Dispersion Calculations Run 1 - Combined North Vent Annual X/Q Values Run 2 - Combined North Vent Annual X/Q Values, Depleted and Decayed with an 8.05 Day Half Life Run 3 - Combined North Vent Annual D/Q Values Run 4 - Unit 1 and Unit 2 South Vent Annual X/Q Values Run 5 - Unit 1 and Unit 2 South Vent Annual X/Q Values, Depleted and Decayed with an 8.05 Day Half Life Run 6 - Unit 1 and Unit 2 South Vent Annual D/Q Values
CHI/Q (SEC/M3) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS NORTH VENT; 363,000 cfm Vs - 7.69 m/sec, VENT DIA - 5.33 m SECTOR BEARING (DEGREES)
DISTANCE METERS NNE NE ENE E ESE SE SSE S
- 22. 5 45.0 67. 5 90. 0 112. 5 135. 0 157. 5 180. 0 225.00 7 .041E-06 5. 528E-06 5. 316E-06 7. 589E-06 1.506E-05 6.996E-06 3.995E-06 2. 329E-06 300.00 4. 318E-06 3. 407E-06 3. 270OE-06 4. 673E-06 9.23 9E-06 4.311E-06 2.4447E-06 1. 425E-06 345.00 3. 387E-06 2. 681E-06 2. 570OE-06 3. 67 3E-06 7.247E-06 3.38 8E-06 1. 919E-06 1. 117E-06 450.00 2. 131E-06 1. 698E-06 1.624E-06 2. 326E-06 4. 558E-06 2.14 4E-06 1.207E-06 7. 038E-07 682.00 1.116E-06 8. 953E-07 8.543E-07 1.244E-06 2. 399E-06 1.14 9E-06 6.370E-07 3. 745E-07 762.00 9. 440E-07 7. 592E-07 7.240E-07 1.057E-06 2 .023E-06 9.7 13E-07 5. 377E-01 3.169E-07 793.00 8. 924E-07 7. 182E-07 6. 845E-07 1 .OOOE-06 1.906E-06 9.154E-07 5. 070E-07 2. 99 1E-07 805.00 8.73 6E-07 7. 033E-07 6. 702E-07 9.7 93E-07 1.864E-06 8. 951E-07 4. 958E-07 2.926E-07 854.00 8.04 1E-07 6.484E-07 6. 170E-07 9.019E-07 1.705 E-06 8. 191E-07 4. 542E-07 2. 684 E-07 884.00 7.662E-07 6. 184E-07 5.880E-07 8. 596E-07 1. 619E-06 7. 774 E-07 4 .3 14E-07 2.55 1E-07 965.00 6. 782E-07 5.492E-07 5.208E-07 7. 614E-07 1.417E-06 6. 8OOE-07 3. 780E-07 2.24 1E-07 975.00 6.687E-07 5.417E-07 5. 135E-07 7. 507E-07 1.395E-06 6. 694E-07 3. 722E-07 2. 207E-07 1006.00 6. 407E-07 5.198 E-07 4. 921E-07 7. 194E-07 1.331E-06 6.38 2E-07 3. 551E-07 2. 107E-07 1097.00 5. 725E-07 4. 658E-07 4.397E-07 6. 425E-07 1. 177E-06 5. 627E-07 3. 140E-07 1.867E-07 1126.00 5. 53 6E-07 4. 509E-07 4. 251E-07 6.2 10E-07 1. 134E-06 5.417E-07 3.025E-07 1.800E-07 1287.00 4. 678E-07 3. 845E-07 3. 58 8E-07 5.23 1E-07 9. 377E-07 4.450E-07 2.500E-07 1.4 91E-07 1433.00 4. llOE-07 3.4 15E-07 3. 145E-07 4 .569E-07 8. 065E-07 3.7 98E-07 2.14 9E-07 1.282E-07 1448.00 4 .060E-07 3.378E-07 3. 106E-07 4.5S1OE-07 7 .94 9E-07 3.74 1E-07 2. 118E-07 1.263E-07 1585.00 3. 666E-07 3.08 6E-07 2. 795E-07 4.040E-07 7. 038E-07 3.28 2E-07 1. 877E-07 1.118E-07 1609.00 3.608SE-07 3.043E-07 2. 750OE-07 3. 969E-07 6.906E-07 3.214E-07 1.84 2E-07 1.097E-07 1770.00 3.270E-07 2.7 98E-07 2. 483E-07 3. 556E-07 6.142E-07 2. 820E-07 1. 644E-07 9.754E-08 1890.00 3.065E-07 2.650E-07 2. 319E-07 3.300E-07 5. 682E-07 2. 58 3E-07 1.529E-07 9.04 1E-08 1931.00 3.00O1E-07 2. 605E-07 2.2 68E-07 3.221E-07 5.542E-07 2.510E-07 1. 495E-07 8.828E-08 2092.00 2. 784 E-07 2. 446E-07 2.093E-07 2. 947E-07 5.077E-07 2.27 1E-07 1.383E-07 8. 125E-08 2134.00 2.734E-07 2. 408E-07 2.052E-07 2. 88 3E-07 4.973E-07 2. 218E-07 1.359E-07 7.969E-08 2253.00 2.603E-07 2. 311E-07 1.94 6E-07 2 .718E-07 4.704E-07 2.08 1E-07 1 .297E-07 7.576E-08 2414.00 2.4 47E-07 2. 19 6E-07 1.820E-07 2. 521E-07 4. 392E-07 1.923E-07 1.2 30E-07 7. 14OE-08 2574.00 2.4 68E-07 2. 132E-07 1.73 5E-07 2. 368E-07 4. 082E-07 1.789E-07 1. 185E-07 6. 910E-08 2835.00 2. 575E-07 2 .048E-07 1.622E-07 2. 158E-07 3. 657E-07 1.612E-07 1. 134E-07 6.701E-08 2896.00 2. 615E-07 2.032E-07 1.599E-07 2. 115E-07 3. 570E-07 1.576E-07 1.126E-07 6. 674E-08 3018.00 2,714E-07 2. 002E-07 1.557E-07 2.034E-07 3. 407E-07 1 .510E-07 1.112E-07 6. 639E-08 3414.00 3. 184E-07 1.933E-07 1.450E-07 1. 817E-07 2. 975E-07 1.344E-07 1.091E-07 6. 657E-08 3540.00 3.333E-07 1.921E-07 1.424E-07 1. 759E-07 2 .861E-07 1.301E-07 1.090E-07 6 696E-08 3701.00 3.457E-07 1. 909E-07 1.395E-07 1.691E-07 2.727E-07 1.251E-07 1.094E-07 6. 766E-08 3871.00 3.464E-07 1.902E-07 1.368E-07 1.625E-07 2.597E-07 1.204E-07 1.101E-07 6.865E-08 4084 .00 3.28 8E-07 1.908E-07 1.33 7E-07 1. 544E-07 2. 447E-07 1. 145E-07 1.093E-07 6. 947E-08 4505.00 2.847E-07 1.966E-07 1.264E-07 1. 379E-07 2. 183E-07 1.027E-07 9.781lE-08 6. 763E-OB 4511.00 2.84 1E-07 1.96 6E-07 1.263E-07 1.377E-07 2. 17 9E-07 1.026E-07 9.767E-08 6. 761E-08 4827.00 2. 561E-07 1.979E-07 1.220E-07 1.273E-07 2. 012E-07 9.504 E-08 9.034 E-08 6. 662E-08 Run I 6325.00 1.688E-07 1.5 11E-07 1.215E-07 9. 887E-08 6660.00 1.573E-07 1.40 9E-07 1.228E-07 9. 645E-08 1 . 584E-07 7. 116E-08 7. 174 E-08 5.7 12E-08 North Vent X/Q
- 1. 565E-07 6.78 8E-08 7.04 3E-08 5. 400E-08 7224 .00 1.405E-07 1.2 60E-07 1. 183E-07 9.314E-08 1. 555E-07 6.312E-08 6.828E-08 4.937E-08 7241.00 1.400E-07 1.256E-07 1. 180E-07 9.305SE-08 1. 555E-07 6.299E-08 6.821E-08 4. 924E-08 7562.00 1.318E-07 1.183E-07 1.114E-07 8.85 3E-08 1. 522E-07 6. 130E-08 6.697E-08 4. 928E-08 8047.00 1.207E-07 1.084 E-07 1.02 4E-07 8.238E-08 1.478E-07 5. 916E-08 6.4 91E-08 4. 922E-08 16093.00 4.749E-08 4.291E-08 4.091E-08 4. 083E-08 8. 338E-08 4.276E-08 2. 921E-08 2. 631E-08 32187.00 1.790E-08 1.622E-08 1.54 9E-08 1. 850E-08 3. 218E-08 1.865E-08 1.092E-08 9.797E-09 48280.00 1.030OE-08 9.350OE-09 8.905E-09 1.071E-08 1. 870E-08 1. 071E-08 6.302E-09 5. 657E-09 64374.00 7. 116E-09 6.4 63E-09 6. 173E-09 7. 406E-09 1.296E-08 7. 391E-09 4.331E-09 3.87 6E-09 80467.00 5. 312E-09 4.829E-09 4. 624E-09 5.534E-09 9.701E-09 5.5 15E-09 3.2 16E-09 2 870E-09
CHI/Q (SEC/M3) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS NORTH VENT; 363,000 cfm Vs = 7.69 m/sec, VENT DIA = 5.33 m SECTOR BEARING (DEGREES)
DISTANCE METERS SSW SW WSW W WNW NW NNW 11 202.5 225.0 247.5 270.0 292.5 315.0 337.5 360.0 225.00 1.544E-06 1.307E-06 1.662E-06 1.914E-06 1.096E-06 9.899E-07 2.005E-06 4.501E-06 300.00 9.437E-07 7.992E-07 1.020E-06 1.173E-06 6.699E-07 6.036E-07 1.224E-06 2.749E-06 345.00 7.389E-07 6.256E-07 8.006E-07 9.197E-07 5.247E-07 4.722E-07 9.577E-07 2.152E-06 450.00 4.646E-07 3.955E-07 5.071E-07 5.813E-07 3.303E-07 2.973E-07 6.012E-07 1.350E-06 682.00 2.488E-07 2.187E-07 2.786E-07 3.172E-07 1.768E-07 1.610E-07 3.201E-07 7.104E-07 762.00 2.110E-07 1.863E-07 2.371E-07 2.695E-07 1.497E-07 1.368E-07 2.717E-07 6.021E-07 793.00 1.993E-07 1.761E-07 2.239E-07 2.545E-07 1.414E-07 1.294E-07 2.573E-07 5.698E-07 805.00 1.951E-07 1.724E-07 2.192E-07 2.491E-07 1.384E-07 1.267E-07 2.521E-07 5.581E-07 854.00 1.792E-07 1.585E-07 2.013E-07 2.288E-07 1.271E-07 1.167E-07 2.326E-07 5.146E-07 884.00 1.705E-07 1.509E-07 1.915E-07 2.176E-07 1.209E-07 1.111E-07 2.220E-07 4.908E-07 965.00 1.500E-07 1.330E-07 1.687E-07 1.915E-07 1.063E-07 9.832E-08 1.975E-07 4.355E-07 975.00 1.478E-07 1.311E-07 1.663E-07 1.886E-07 1.047E-07 9.692E-08 1.949E-07 4.295E-07 1006.00 1.412E-07 1.254E-07 1.590E-07 1.803E-07 1.001E-07 9.285E-08 1.872E-07 4.119E-07 1097.00 1.254E-07 1.118E-07 1.418E-07 1.603E-07 8.880E-08 8.298E-08 1.685E-07 3.690E-07 1126.00 1.210E-07 1.080E-07 1.371E-07 1.547E-07 8.565E-08 8.025E-08 1.634E-07 3.571E-07 1287.00 1.009E-07 9.128E-08 1.161E-07 1.295E-07 7.124E-08 6.789E-08 1.404E-07 3.030E-07 1433.00 8.793E-08 8.086E-08 1.033E-07 1.131E-07 6.165E-08 5.987E-08 1.256E-07 2.671E-07 1448.00 8.682E-08 7.999E-08 1.023E-07 1.117E-07 6.081E-08 5.917E-08 1.243E-07 2.640E-07 1585.00 7.840E-08 7.364E-08 9.473E-08 1.007E-07 5.425E-08 5.380E-08 1.143E-07 2.390E-07 1609.00 7.724E-08 7.279E-08 9.376E-08 9.912E-08 5.329E-08 5.303E-'8 1.129E-07 2.353E-07 1770.00 7.112E-08 6.862E-08 8.906E-08 9.031E-08 4.795E-08 4.873E-08 1.047E-07 2.139E-07 1890.00 6.813E-08 6.691E-08 8.721E-08 8.547E-08 4.497E-08 4.632E-08 9.984E-08 2.010E-07 1931.00 6.737E-08 6.655E-08 8.683E-08 8.408E-08 4.412E-08 4.562E-08 9.838E-08 1.970E-07 2092.00 6.527E-08 6.575E-08 8.591E-08 7.966E-08 4.146E-08 4.322E-08 9.325E-08 1.832E-07 2134.00 6.491E-08 6.567E-08 8.579E-08 7.871E-08 4.090E-08 4.267E-08 9.204E-08 1.800E-07 2253.00 6.426E-08 6.572E-08 8.572E-08 7.642E-08 3.957E-08 4.128E-08 8.888E-08 1.716E-07 2414.00 6.406E-08 6.629E-08 8.607E-08 7.404E-08 3.825E-08 3.972E-08 8.514E-08 1.616E-07 2574.00 6.190E-08 6.493E-08 8.378E-08 7.165E-08 3.645E-08 3.809E-08 8.673E-08 1.617E-07 2835.00 5.893E-08 6.302E-08 8.039E-08 6.859E-08 3.405E-08 3.584E-08 9.056E-08 1.642E-07 2896.00 5.831E-08 6.262E-08 7.964E-08 6.798E-08 3.356E-08 3.537E-08 9.165E-08 1.652E-07 3018.00 5.712E-08 6.182E-08 7.816E-08 6.684E-08 3.265E-08 3.447E-08 9.404E-08 1.673E-07 3414.00 5.361E-08 5.920E-08 7.348E-08 6.361E-08 3.004E-08 3.179E-08 1.037E-07 1.775E-07 3540.00 5.261E-08 5.842E-08 7.209E-08 6.272E-08 2.933E-08 3.103E-08 1.075E-07 1.821E-07 3701.00 5.138E-08 5.743E-08 7.035E-08 6.164E-08 2.846E-08 3.011E-08 1.127E-07 1.887E-07 3871.00 5.013E-08 5.641E-08 6.858E-08 6.054E-08 2.761E-08 2.918E-08 1.181E-07 1.955E-07 4084.00 4.977E-08 5.600E-08 6.729E-08 5.924E-08 2.667E-08 2.893E-08 1.223E-07 1.998E-07 4505.00 5.508E-08 5.933E-08 6.915E-08 5.690E-08 2.524E-08 3.305E-08 1.189E-07 1 907E-07 4511.00 5.516E-08 5.938E-08 6.918E-08 5.687E-08 2.522E-08 3.311E-08 1.189E-07 1.905E-07 4827.00 5.942E-08 6.176E-08 7.116E-08 5.536E-08 2.421E-08 3.710E-08 1 130E-07 1.765E-07 6325.00 5.272E-08 5.833E-08 7.861E-08 6.539E-08 1.935E-08 5.569E-08 7.705E-08 1.168E-07 6660.00 4.912E-08 5.551E-08 7.743E-08 7.150E-08 1.833E-08 5.454E-08 7.172E-08 1.087E-07 7224.00 4.388E-08 5.062E-08 7.349E-08 7.322E-08 1.681E-08 4.972E-08 6.398E-08 9.707E-08 7241.00 4.373E-08 5.047E-08 7.333E-08 7.307E-08 1.677E-08 4.956E-08 6.377E-08 9.675E-08 7562.00 4.165E-08 4.787E-08 7.048E-08 6.933E-08 1.729E-08 4.669E-08 6.006E-08 9.107E-08 8047.00 3.844E-08 4.394E-08 6.478E-08 6.358E-08 1.821E-08 4.277E-08 5.502E-08 8.342E-08 16093.00 1.491E-08 1.671E-08 2.487E-08 2.463E-08 1.159E-08 1.660E-08 2.144E-08 3.250E-08 32187.00 5.444E-09 6.030E-09 9.105E-09 9.109E-09 4.252E-09 6.182E-09 7.976E-09 1.208E-08 48280.00 3.120E-09 3.462E-09 5.163E-09 5.186E-09 2.434E-09 3.535E-09 4.576E-09 6.920E-09 64374.00 2.120E-09 2.340E-09 3.523E-09 3.556E-09 1.658E-09 2.431E-09 3.142E-09 4.751E-09 80467.00 1.560E-09 1.713E-09 2.605E-09 2.640E-09 1.223E-09 1.808E-09 2.333E-09 3.528E-09
DEPLETED CHI/ (SEC/M3) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS NORTH VENT; 363,000 cfm, 8.05 DAY DECAY Vs = 7.69 mn/sec, VENT DIA = 5.33 m SECTOR BEARING (DEGREES)
DISTANCE METERS NNE NE ENE E ESE SE SSE S 22.5 45.0 67. 5 90. 0 112. 5 135. 0 157. 5 180. 0 225. 00 6.80 9E-06 5.34 6E-06 5. 141E-06 7. 33 9E-66 1.456E-05 6. 765E-06 3.864E-06 2. 252E-06 300. 00 4.140E-06 3.267E-06 3. 135E-06 4.481E-06 8. 85 5E-06 4.132E-06 2.346E-06 1.366E-06 345. 00 3.231E-06 2 .558E-06 2.451E-06 3. 504 E-06 6.90 9E-06 3.230E-06 1.829E-06 1.065E-06 450. 00 2.008E-06 1.601E-06 1.530E-06 2. 191E-06 4.291E-06 2. 018E-06 1. 137E-06 6. 627E-07 682.00 1.031E-06 8.284E-07 7. 902E-07 1.150E-06 2.213E-06 1.060E-06 5.881E-07 3.458E-07 762.00 8. 675E-07 6. 987E-07 6. 661E-07 9.722E-07 1. 85 5E-06 8. 910E-07 4.934E-07 2. 909E-07 793.00 8. 182 E-07 6. 596E-07 6.284E-07 9. 176E-07 1.74 4E-06 B.377E-07 4.641E-07 2 .739E-07 805.00 8. 003E-07 6. 454E-07 6. 148E-07 8.978E-07 1.70 3E-06 8. 184E-07 4.535E-07 2. 677E-07 85 4.00 7. 342E-07 5. 931E-07 5.642E-07 8.2 42E-07 1. 553E-06 7. 461E-07 4. 139E-07 2. 447E-07 884. 00 6.982E-07 5. 64 6E-07 5.367E-07 7.84 1E-07 1. 471E-06 7. 065E-07 3. 922E-07 2. 321E-07 965. 00 6.14 9E-07 4.991E-07 4.731E-07 6.912E-07 1.280E-06 6. 142E-07 3. 415E-07 2.02 6E-07 975.00 6.05 8E-07 4.920E-07 4. 662E-07 6.810E-07 1. 25 9E-06 6.04 1E-07 3. 360E-07 1.994E-07 1006.00 5.79 6E-07 4 .714E-07 4.461E-07 6.516E-07 1. 199E-06 5.747E-07 3. 199E-07 1.900E-07 1097.00 5. 165E-07 4 .215E-07 3. 976E-07 5. 804E-07 1. 056E-06 5.04 8E-07 2.8 18E-07 1.678E-07 112 6.00 4.991E-07 4. 079E-07 3. 84 1E-07 5. 607E-07 1.016E-06 4. 854E-07 2.7 12E-07 1.615E-07 1287. 00 4.203E-07 3.469E-07 3.231E-07 4.704E-07 B.355E-07 3. 962E-07 2. 228 E-07 1.329E-07 14 33.00 3.683E-07 3.07B8E-07 2.825E-07 4.097E-07 7. 152E-07 3. 363E-07 1.906E-07 1. 137E-07 1448. 00 3.638E-07 3.04 4E-07 2 .789E-07 4.043E-07 7.04 6E-07 3. 310E-07 1.878E-07 1. 120E-07 1585. 00 3.27 9E-07 2. 780E-07 2. 505E-07 3.612E-07 6.215E-07 2. 890E-07 1.657E-07 9.87 4E-08 1609.00 3.227E-07 2.742E-07 2.4 64E-07 3.548E-07 6.095E-07 2. 828 E-07 1.626E-07 9. 681E-08 1770.00 2.92 1E-07 2. 522E-07 2 .221E-07 3.170E-07 5. 400E-07 2.4 69E-07 1.446E-07 8.577E-08 1890.00 2.73 6E-07 2.389E-07 2. 072E-07 2.937E-07 4.984E-07 2.253E-07 1.343E-07 7. 933E-08 1931.00 2.67 9E-07 2.34 9E-07 2. 026E-07 2.865E-07 4.858E-07 2. 188E-07 1.312E-07 7.742E-08 2092. 00 2.484 E-07 2. 208E-07 1. 867E-07 2.617E-07 4.442E-07 1. 973E-07 1.214E-07 7. 117E-08 2134.00 2.440E-07 2. 175E-07 1. 831E-07 2.560E-07 4.350E-07 1. 926E-07 1. 192E-07 6. 981E-08 2253. 00 2.323E-07 2 .089E-07 1. 73 5E-07 2.411E-07 4. 112E-07 1.805E-07 1. 139E-07 6. 639E-08 24 14.00 2. 185E-07 1.987E-07 1. 622E-07 2.235E-07 3. 837E-07 1.665E-07 1.082E-07 6.2 62E-08 257 4.00 2.2 17E-07 1 .934E-07 1.548E-07 2.098E-07 3. 561E-07 1.547E-07 1.044E-07 6. 081E-08 2835. 00 2. 33 8E-07 1.865E-07 1. 450E-07 1.911E-07 3. 182E-07 1.392E-07 1.005E-07 5. 935E-08 28 96.00 2. 380E-07 1. 85 1E-07 1.431E-07 1. 873E-07 3. 104 E-07 1. 360E-07 9.981E-08 5. 920E-08 3018.00 2. 484E-07 1.827E-07 1.395E-07 1.80 1E-07 2. 958E-07 1.303E-07 9.88 3E-08 5. 908E-08 34 14. 00 2. 902E-07 1. 77 3E-07 1.303E-07 1.610E-07 2. 578E-07 1. 160E-07 9. 777E-08 5. 979E-08 35 40. 00 2. 991E-07 1.765E-07 1.281E-07 1.55 9E-07 2. 477E-07 1. 123E-07 9.7 98E-08 6.030E-08 3701.00 3.026E-07 1.75 8E-07 1.257E-07 1.4 98E-07 2. 35 8E-07 1 .081E-07 9.858E-08 6. 112E-08 3871. 00 2. 937E-07 1.754 E-07 1. 235E-07 1.440OE-07 2.24 3E-07 1 .040E-07 9.960E-08 6.224E-08 408 4.00 2.708E-07 1.759E-07 1. 209E-07 1.368E-07 2. 111E-07 9. 891E-08 9.91 1E-08 6. 318E-08 4505. 00 2.299E-07 1.779E-07 1.147E-07 1.219E-07 1.876E-07 8.84 6E-08 8.85 2E-08 6.167E-08 4511. 00 2.294E-07 1.77 9E-07 1.14 6E-07 1.217E-07 1.873E-07 8. 833E-08 8.838 E-08 6. 165E-08 4827. 00 2.04 6E-07 1.74 4E-07 1. 108E-07 1. 123E-07 1.724E-07 8. 167E-08 8. 162E-08 6.085 E-08 Run 2 6325.00 1.29 6E-07 1. 196E-07 1.058E-07 8.702E-08 1.356E-07 6. 067E-08 6.467E-08 5.2 19E-08 North Vent XIQ 6660. 00 1.200E-07 1.109E-07 1. 029E-07 B.501E-08 1.345E-07 5. 784 E-08 6.352E-08 7224. 00 1.060E-07 9.823E-08 9. 20 6E-08 8.226E-08 1.34 6E-07 5. 375E-08 6. 136E-08 4.925E-08 4 .488E-08 Depleted and 724 1.00 1.05 6E-07 9.78 8E-08 9. 169E-08 8.2 18E-08 1.347E-07 5. 363E-08 6. 128E-08 4.476E-08 Decayed 75 62. 00 9.879E-08 9.16 6E-08 8. 574E-OB 7. 803E-08 1.319E-07 5. 226E-08 5.968E-08 4.479E-08 8047. 00 8.961E-08 8 .333E-08 7. 774E-08 7.238E-08 1.283 E-07 5.055E-08 5. 660E-08 4.467E-08 16093.00 3.193E-08 3.005E-08 2 .736E-08 3.399E-08 6.308E-08 3. 494E-08 1. 986E-08 1. 808E-08 32187.00 1.023E-08 9. 689E-09 8. 816E-09 1. 179E-08 2.073E-08 1.112E-08 6. 351E-09 5.753E-09 48280.00 5.23 9E-09 4.755E-09 4.506E-09 6.015E-09 1.060E-08 5. 660E-09 3 .271E-09 2.962E-09 64374.00 3.288 E-09 2.97 1E-09 2. 834E-09 3 .761E-09 6. 635 E-09 3.54 1E-09 2.04 6E-09 1.84 4E-09 80467.00 2. 22 2E-09 2. 007E-09 1.918E-09 2.53 1E-09 4. 465E-09 2. 385E-09 1. 378E-09 1. 237E-09
DEPLETED CHI/Q (SECIM3)
LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATION~S NORTH VENT; 363,000 cfmn, 8.05 DAY DECAY Vs = 7.69 In/sec, VENT DIA- 5.33 m DISTANCE SECTOR BEARING (DEGREES)
METERS SSW SW WSWW W WNW 202. 5 225. 0 247. 5 NW NNW N 270. 0 292. 5 315. 0 337. 5 360. 0 225.00 1.493E-06 1.264E-06 1. 607E-06 1.-851E-06 1. 060E-06 300.00 9. 045E-07 7 . 660E-0 7 9.573E-07 1. 939E-06 4. 353E-06
- 9. 78 1E-07 1.-125E-06 6. 421E-07 345.00 7. 044E-07 5.965E-07 5. 78 6E-07 1. 173E-06 2. 635E-06 7.633E-07 8.7 69E-07 5.003E-07 450.00 4. 374E-07 3.723 E-07 4. 502E-07 9. 134E-07 2.052E-06 4.775E-07 5. 47 3E-07 3. 11OE-07 682.00 2.297E-07 2. 018 E-07 2 .799E-07 5. 663E-07 1. 271E-06 2.571E-07 2. 927E-07 1. 632E-07 762.00 1. 936E-07 1.708E-07 1.4 86E-07 2. 956E-07 2.174E-07 2. 471E-07 1.37 3E-07 6. 561E-07 793.00 1.825E-07 1.611E-07 1.255E-07 2.4 94E-07 2.04 9E-07 2 .329E-07 1. 294 E-07 5. 528E-07 805.00 1. 784 E-07 1.576E-07 1. 185E-07 2. 357E-07 2.004E-07 2. 277E-07 1.265E-07 5. 220E-07 854.00 1. 633E-07 1.444E-07 1. 159E-07 2. 307E-07 1.834 E-07 2.083E-07 1. 157E-07 5. 109E-07 884.00 1. 550E-07 1. 371E-07 1.063E-07 2. 121E-07 1.741E-07 1. 977E-07 1.098E-07 4. 694E-07 965.00 1.356E-07 1. 201E-07 1.011E-07 2.021E-07 1.525E-07 1 .729E-07 9.59 9E-08 4 .468E-07 975.00 1. 335E-07 1. 183E-07 8. 89 1E-08 1.789E-07 1.50 1E-07 1. 702E-07 9.446E-08 3 . 944E-07 1006.00 1.273E-07 1. 129E-07 8. 75 9E-08 1.764E-07 1.433E-07 1.624E-07 9. 006E-08 3. 887E-07 1097.00 1. 126E-07 1.003E-07 8. 375E-08 1.692E-07 1.274 E-07 1. 438E-07 7. 962E-08 3.722E-07 1126.00 1. 086E-07 9.688E-08 7.463E-08 1.520E-07 1.230E-07 1.387E-07 7. 671E-08 3. 326E-07 1287.00 9.007E-08 8.149E-08 7.21liE-08 1.473E-07 1.038E-07 1. 155E-07 6. 34 2E-08 3.2 16E-07 1433.00 7. 819E-08 7.205E-08 6. 077E-08 1. 262E-07 9.230OE-08 1.00 6E-07 5. 463E-08 2 .719E-07 1448.00 7. 718E-08 7. 127E-08 S.34 6E-08 1. 128E-07
- 8. 473E-08 8. 935E-08 4.790E-08 2. 363E-07 1609.00 6. 854 E-08 6.490E-08 4 .799E-08 1.027E-07 2. 136E-07 8.389E-08 8 .792E-08 4.703E-08 1770.00 6. 313E-08 6.136E-08 4. 729E-08 1.014E-07 2. 103E-07 7.998E-08 8. 008E-08 4.223E-08 1890.00 6.059E-08 6. 004E-08 4. 347E-08 9.4 lOE-08 1. 910E-07 7.860E-08 7. 583E-08 3.959E-08 1931.00 5. 99 6E-08 5. 979E-08 4 .136E-08 8.985E-08 1.793E-07
- 7. 835E-08 7. 462E-08 3.885E-08 2092.00 5. 834E-08 5. 940E-08 7. 793E-08 4. 075E-08 8.857E-08 1.758E-07 2134.00 7. 086E-08 3. 656E-08 3.870E-08
- 5. 773E-08 5. 970E-08 7.8 14E-08 8.304E-08 1. 606E-07 2414.00 6. 819E-08 3. 500E-08 3.70 6E-08 5.78 5E-08 6.053E-08 7. 879E-08 8.030E-08 1. 532E-07 2574.00 6. 628E-08 3. 396E-08 3.57 5E-08
- 4. 885E-08 5.458E-08 6.764E-08 8. 674E-08 1. 523E-07 3540.00 5. 769E-08 2. 692E-08 2. 887E-08 4.796E-08 5. 389E-08 6. 63 6E-08 9. 655E-08 1. 633E-07
- 6. 192E-08 5. 396E-08 2. 399E-08 4505.00 5. 068E-08 5. 495E-08 2. 639E-08 1. 107E-07 1. 770E-07 6.3 69E-08 5. 190E-08 2.275E-08 4511.00 5. 076E-08 5. 500E-08 3. 052E-08 1.034E-07 1. 609E-07 6.371E-08 5. 187E-08 2.274E-08 4827.00 5. 480E-08 5. 723E-08 3 059E-08 1.032E-07 1.606E-07 6.55 4E-08 5. 053E-08 2. 185E-08 6325.00 4. 332E-08 5.018E-08 3. 452E-08 9. 466E-08 1.433E-07 6.892E-08 5. 992E-08 1.743E-08 6660.00 4. 016E-08 4. 646E-08 4. 712E-08 5 932E-08 8. 991E-08 6.58 6E-08 6. 276E-08 1.648E-08 7224.00 3.557E-08 4.037E-08 4. 381E-08 5. 487E-08 8. 322E-08
- 5. 879E-08 5. 692E-08 1. 504E-08 7562.00 3.279E-08 3.688E-08 3. 760E-08 4. 827E-08 7.326E-08 5.42 1E-08 5.223E-08 1.557E-08 8047.00 2. 932E-08 3.306E-08 3. 502E-08 4.496E-08 6. 847E-08
- 2. 601E-09 2. 614E-09 1.237E-09 64374.00 9. 822E-10 1.071E-09 1.785E-09 2. 317E-09 3. 534E-09 1.607E-09 1.624E~-09 7. 660E-10 80467.00 6.533E-10 7.073E-10 1.112E-09 1. 444E-09 2. 207E-09 1 .071E-09 1.OBBE-09 5. 113E-10 7.469E-10 9.68 9E-10 1.485E-09
D/Q (/M2) D/Q /M2)LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS NORTH VENT; 363,000 cfmn, 8.05 DAY DECAY Vs = 7.69 mn/sec, VENT DIA= 5.33 mn SECTOR BEARING (DEGREES)
DISTANCE METERS NNE NE ENE S ESE SE SSE S
- 22. 5 45.0 67.5 90. 0 112.5 135. 0 157. 5 180. 0 225.00 2. 983E-08 2. 114 E-08 2.0815-08 4. 693E-08 8.399E-08 5. 365E-08 2.382E-08 1.261E-08 300.00 2. 055E-08 1.480E-08 1. 4425-08 3.2 185-08 5.703E-08 3.636E-08 1. 621E-08 8. 664E-09 345.00 1.68 3E-08 1.227E-08 1. 188E-08 2. 627E-08 4.617E-08 2. 942E-08 1. 317E-08 7. 103E-09 450.00 1. 161E-08 8.701E-09 8.308E-09 1.8005-08 3. 10 6E-08 1. 976E-08 8.938E-09 4. 928E-09 682.00 6.507E-09 5 .061E-09 4.745E-09 9.96 6E-09 1.689E-08 1.065E-08 4. 906E-09 2.812E-09 762.00 5.574E-09 4.368E-09 4.0785-09 8.508E-09 1.439E-08 9.037E5-09 4.185E-09 2. 42 6E-09 793.00 5.27 5E-09 4.145E-09 3.864E-09 8.04 1E-09 1.359E-08 8.522E-09 3. 955E-09 2. 304E-09 805.00 5. 167E-09 4.064E-09 3.787E-09 7.872E-09 1. 330E-08 8.337E-09 3. 872E-09 2.259E-09 854.00 4 .762E-09 3. 75 9E-09 3.507E-09 7.23 8E-09 1.2225-08 7. 660E-09 3.5 62E-09 2. 09 3E-09 884.00 4. 542E-09 3. 60 1E-09 3. 349E-09 6.904E-09 1. 164E-08 7.287E-09 3.397E-09 2.003E-09 965.00 4 .031E-09 3.216E-09 2.9865-09 6. 10 6E-09 1. 032E-08 6.452E-09 3.024E-09 1. 800E-09 975.00 3. 976E-09 3. 173E-09 2.952E-09 6.035E-09 1. 017 E-08 6.363E-09 2.986E-09 1.778E-09 1006.00 3.810OE-09 3. 045E-09 2.830E-09 5.772E-09 9. 724E5-09 6.0885-09 2.8 68E-09 1.712E-09 1097.00 3.350E-09 2.7 13E-09 2. 495E-09 5.04 9E-09 8.482E-09 5. 320E-09 2.5S37 5-09 1.522E-09 1126.00 3.22 3E-09 2. 616E-09 2.4015-09 4.8475-09 8. 145E-09 5. 113E-09 2.450E-09 1.471E-09 1287.00 2. 667E-09 2. 205E-09 2. 013E-09 3.958E-09 6.653E-09 4.205E-09 2.063E-09 1.24 9E-09 1433.00 2.304 E-09 1.928E-09 1.737E-09 3.375E-09 5. 663E-09 3.591E-09 1.817E-09 1. 106E-09 1448.00 2.27 1E-09 1.904E-09 1. 712E-09 3.329E-09 5.57 6E-09 3.54 0E-09 1.791E-09 1.094E-09 1585.00 2.00OIE-09 1.700E-09 1.517E-09 2.905E-09 4.881E-09 3. 107E-09 1.5S91E-09 9.816E-10 1609.00 1.954E-09 1. 664E-09 1.481E-09 2.83 6E-09 4.763E-09 3. 041E-09 1.559E-09 9. 620E-10 1770.00 1.711E-09 1.466E-09 1.288E-09 2.442E-09 4.096E-09 2. 637E-09 1.364E-09 8. 492E-10 1890.00 1.55 6E-09 1.330E-09 1. 185E-09 2.205E-09 3. 68 9E-09 2. 397E-09 1.243E-09 7.816E-10 1931.00 1.517E-09 1. 292E-09 1. 153E-09 2.133E-09 3. 563E-09 2. 321E-09 1.214E-09 7. 622E-10 2092.00 1.35 2E-09 1. 151E-09 1.033E-09 1.8945-09 3. 150OE-09 2. 065E-09 1.09 3E-09 6. 968E-10 2134.00 1. 317E-09 1. 125E-09 1.004E-09 1. 836E-09 3. 05 3E-09 2.005E-09 1.063E-09 6.7 99E-10 2253.00 1. 22 3E-09 1.042E-09 9.271lE-10 1. 692E-09 2. 803E-09 1.849E-09 9.824E-10 6. 472E-10 2414.00 1.115E-09 9. 511E-10 8. 417E-10 1.526E-09 2.516E-09 1. 665E-09 8. 926E-10 6. 087E-10 2574.00 1.0 61E-09 8.7 32E-10 7. 792E-10 1.392E-09 2. 27OE-09 1.503E-09 8.023E-10 5.728E-10 2835.00 9. 50 6E-10 7. 616E-10 6.835E-10 1.2085-09 1. 946E-09 1.287E-09 6.787E-10 S.251ES-10 2896.00 9.229E-10 7. 371E-10 6. 670E-10 1.168 E-09 1.881E-09 1.244E-09 6.558E-10 5.114E-10 3018.00 8.665E-10 6. 937E-10 6.2 96E-10 1.094E-09 1.7 62E-09 1. 165E-09 6. 127E-10 4.885E-10 3414.00 9.131E-10 5.72 6E-10 S.205ES-10 9.112E-10 1.450E-09 9.53 6E-10 5. 342E-10 4 .016E-10 3540.00 8.019E-10 5. 44OE-10 4.914E-10 8. 635E-10 1.371E-09 8. 994 E-10 5. 098E-10 3.783E-10 3701.00 6.985E-10 5. 188E-10 4.571E-10 8.059E-10 1.278E-09 8. 379E-10 4. 819E-10 3.521E-10 3871.00 6.404E-10 5. 278E-10 4.2325-10 7. 524E-10 1. 192E-09 7. 801E-10 4. 557E-10 3. 322E-10 4084.00 8.301lE-10 5. 695SE-10 3.885E-10 6. 933E-10 1.099E-09 7. 185E-10 4.234E-10 3. 172E-10 4505.00 7. 977 E-10 5.02 6E-10 3.305E-10 5. 888E-10 9. 371E-10 6.122E-10 3.596E-10 2.78 9E-10 4511.00 7. 969E-10 5.003E-10 3.298E-10 5. 875E-10 9. 351E-10 6.108E-10 3.S588E-10 2 .784E-10 4827.00 7. 32 3E-10 4.156E-10 2. 967E-10 5. 251lE-10 8. 376E-10 5.470E-10 3.206E-10 2.55S6E-10 Run 3 6325.00 4. 64 3E-10 3. 191E-10 2.649E-10 3.347E-10 5. 531E-10 3.4 8E-10 2. 047 E-10 1.668E-10 North Vent DIQ 6660.00 4.24 6E-10 2.94 4E-10 2.283E-10 3.063E-10 5. 089E-10 3. 184E-10 1.890E-10 1.528E-10 7224.00 3. 688E-10 2. 600E-10 2. 3765-10 2. 672E-10 4. 429E-10 2.767E-10 2.064E-10 1. 330E-10 7241.00 3. 67 3E-10 2. 591E-10 2. 403E-10 2. 661E-10 4. 412E-10 2. 756E-10 2.07 7E-10 1.325E-10 7562.00 3.408E-10 2. 429E-10 2. 313E-10 2.470E-10 4.091E-10 2.55S3E-10 2.067E-10 1.2 30E-10 8047.00 3.0 68E-10 2. 220E-10 2. ISOE-10 2.221lE-10 3. 682E-10 2.2975-10 1.961E-10 1.151E-10 16093.00 9.255SE-l1 8.063E-11 7. 071E-11 7.942E-11 1.880E-10 1.003E-10 6. 619S-11 5.2185-11 32187.00 2.793E-11 2.728E-11 2. 126E-11 3.797E-11 6.21lOS-l1 3.520E-11 1. 995E-11 1.5S99E-11 48280.00 1.383E-11 1.169E-11 1.053E-11 1.845SE-li 3.012E-11 1. 72 0E-11 9. 871E-12 7.884E-12 64374.00 8.OlOE-12 6.797E-12 6. 099E-12 1.0 61E-11 1.725SE-11 9. 915E-12 5.737E-12 4.587E-12 80467.00 5.2 19E-12 4.4285-12 3. 973E-12 6.867E-12 1. 112E-11 6. 434E-12 3.749E-12 3.002E-12
D/Q (UM2)
LGS 2002 EFFLUENT REPORT A1NNUAL DISPERSION CALCULATIONS NORTH VENT; 363,000 cfm, 8.05 DAY DECAY Vs = 7.69 m/sec, VENT DIA = 5.33 m SECTOR BEARING (DEGREES)
DISTANCE METERS SSW SW WSW W WNW NW NNW 202. 5 225.0 247. 5 270. 0 N 292. 5 315.0 337. 5 360. 0 225.00 6.498E-09 7. 347 E-09 7.615E-09 1 .210E-08 7. 106E-09 5. 390E-09 1 .224E-08 300.00 4.439E-09 4. 985E-09 5.197 E-09 2. 395E-08
- 8. 199E-09 4.812E-09 3. 676E-09 345.00 3. 621E-09 4.04 1E-09 4.235E-09 8. 336E-09 1. 635E-08 6.637E-09 3.-894E-09 2. 988E-09 6.7 63E-09 450.00 2. 483E-09 2. 730E-09 2.900E-09 1.330E-08 4.464E-09 2. 616E-09 2.03 9E-09 4. 580E-09 682.00 1.401E-09 1. 515E-09 1.648E-09 9.044E-09 2.437E-09 1. 422E-09 1.166E-09 762.00 1.20 9E-09 1. 306E-09 1.4 31E-09 2. 545E-09 5. 017E-09 2.084E-09 1.214E-09 1.013E-09 793.00 1. 148E-09 1.24 1E-09 1.363E-09 2. 188E-09 4.300E-09
- 1. 933E-09 1. 125E-09 9.473E-10 2. 034E-09 854.00 1.04 6E-09 1. 132E-09 1.24 9E-09 3.990E-09 1 .792E-09 1.037E-09 8.8 17E-10 884.00 1. 002E-09 1. 086E-09 1.205E-09 1. 880E-09 3.688E-09 1.7 19E-09 9. 902E-10 8. 491E-10 965.00 9. 050E-10 9. 850E-10 1.104 E-09 1. 800E-09 3.521E-09
- 1. 555E-09 8.834E-10 7. 716E-10 975.00 8. 947E-10 9.744E-10 1. 610E-09 3.138E-09 1.0 93E-09 1 .540E-09 8. 720OE-10 1006.00 8. 635E-10 9. 425E-10 7. 630E-10 1. 589E-09 3.097E-09 1.070E-09 1 .482E-09 8. 376E-10 1097.00 7.798E-10 8. 554E-10 7.367E-10 1.530E-09 2. 971E-09 9.952E-10 1.34 6E-09 7. 408E-10 1126.00 7. 627E-10 8.357E-10 6. 58 3E-10 1.351E-09 2. 619E-09 9.676E-10 1.309E-09 7. 150E-10 6.399E-10 1287.00 6.797E-10 7.556E-10 9.04 1E-10 1.303E-09 2. 522E-09
- 1. 153E-09 6.089E-10 5.51iBE-10 1.090E-09 1433.00 6. 431E-10 7. 471E-10 8. 881E-10 2. 092E-09 1.059E-09 5. 460E-10 4.972E-10 9.5 94E-10 1448.00 6. 445 E-10 7. 466E-10 8.909E-10 1.816E-09 1.04 6E-09 5. 413E-10 4.921lE-10 1565.00 6. 09 9E-10 7.229E-10 8.739E-10 9.475SE-10 1. 792E-09 9.495E-10 5. 027E-10 4. 451E-10 8.462E-10 1609.00 5. 983E-10 7. 132E-10 8. 617E-10 1. 584E-09 9.342E-10 5.009E-10 4.362E-10 1770.00 5. 454E-10 6.73 6E-10 8.02 6E-10 8.278 E-10 1. 549E-09 8.395E-10 4.476E-10 3.863E-10 7.241lE-10 1890.00 5. 036E-10 6.330E-10 7.553E-10 1. 346E-09 7 .772E-10 4. 221E-10 3.54 9E-10 6.606E-10 1931.00 4. 919E-10 6. 171E-10 7.34 7E-10 1. 230E-09
- 7. 530E-10 4. 094E-10 3.468E-10 6.407E-10 2092.00 4. 506E-10 5.E11E-10 6.854E-10 1. 193E-09 6.8 16E-10 3. 730E-10 3.134E-10 2134.00 4. 411E-10 5. 508E-10 5.724E-10 1 .064E-09
- 6. 691E-10 6.696E-10 3. 627E-10 3.057E-10 2253.00 4.084E-10 5. 191E-10 5.568E-10 1.035E-09 6.310E-10 6.223JE-10 3.427E-10 2.8 61E-10 2414.00 3.758 E-10 4.791E-10 5.207E-10 9.59 3E-10 5.7 68E-10 5. 689E-10 3. 196E-10 2. 627E-10 2574.00 3.434E-10 4. 366E-10 4.765E-10 8.705E-10 5.27 8E-10 5. 159E-10 2. 906E-10 2. 402E-10 2835.00 3. 002E-10 3. 801E-10 4.559E-10 7.983E-10 4.602E-10 4.488E-10 2. 535E-10 2. 107E-10 2896.00 2. 909E-10 3. 680E-10 4.159E-10 7. 498E-10 4 .459E-10 4. 352E-10 2. 457E-10 2.04 6E-10 3018.00 2. 739E-10 3. 458E-10 4. 122E-10 7. 378E-10
- 4. 197E-10 4. 089E-10 2. 319E-10 1.933E-10 3414.00 2. 334E-10 2. 901E-10 3. 950E-10 6.998E-10 3.54 8E-10 3. 413E-10 1. 939E-10 1.657E-10 3540.00 2. 238E-10 2. 772E-10 3. 362E-10 5.911E-10 3.384E-10 3. 230E-10 1.841lE-10 1.577E-10 3701.00 2. 114E-10 2. 629E-10 3. 681E-10 6. 148E-10 3.188E-10 3. 029E-10 1.727E-10 1.484E-10 3871.00 2. 002E-10 2.489E-10 3. 656E-10 7. 091E-10 3.020E-10 2. 859E-10 1. 621E-10 1.396E-10 4084 .00 1.918E-10 2. 407E-10 3.511E-10 6.287E-10 2.863E-10 2. 697E-10 1. 507E-10 1.301E-10 4505.00 1.746E-10 3. 06 6E-10 5.228 E-10 2.24 4E-10 2.659E-10 2.4 lQE-10 1.290E-10 1.142E-10 4511.00 1. 744E-10 2.24 3E-10 2.429E-10 4.171E-10 2.664E-10 2. 404E-10 1.287E-10 1.142E-10 4827.00 1. 773E-10 2.051lE-10 2. 421E-10 4.162E-10 2.4 65E-10 2. 196E-10 1. 156E-10 1.093E-10 6325.00 1. 234E-10 1.54 3E-10 2. 453E-10 5. 113E-10 1.955E-10 1 .78BE-10 7. 492E-11 9 028E- .1 6660.00 1. 141E-10 2.057E-10 3 765E-10
- 1. 405E-10 1.755E-10 1.693E-10 6.870E-11 7224.00 9. 153E-11 1.881E-10 3. 443E-10 1.011E-10 1.323E-10 1.565E-10 1. 567E-10 S.994 E-11 7241.00 1 .006E-10 1.635E-10 2 990E-10
- 1. 007E-10 1. 323E-10 1.5 65E-10 1. 581E-10 5.971bE-11 1 .002E-10 1. 629E-10 2.97 8E-10 7562.00 1.038E-10 1.316E-10 1.5 69E-10 1. 604E-10 5. 512E-11 9. 500E-11 1.534E-10 2. 767E-10 8047.00 1.003E-10 1 .234E-10 1.517E-10 1. 471E-10 5.289E-11 8.54 6E-11 1.382E-10 2.486E-10 16093.00 3. 172E-11 3.80 9E-11 4.658E-11 4.459E-11 2. 572E-11 2.590E-11 4.170E-11 7. 525E-11 32187.00 9.52 9E-12 1. 145E-11 1.400E-11 1.340E-11 7. 782E-12 7.787E-12 1.254 E-11 2. 262E-11 48280.00 4.715E-12 5. 667E-12 6.932E-12 6. 635E-12 3.855E-12 3.855E-12 6.209E-12 1. 121E-11 64374.00 2.735E-12 3.283E-12 4.016E-12 3.844E-12 2. 233E-12 2.233E-12 3. 597E-12 6. 496E-12 80467.00 1.78 3E-12 2. 139E-12 2. 616E-12 2.504E-12 1.45 5E-12 1. 455E-12 2. 343E-12 4.232E-12
CHI/Q (SEC/M3) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS SOUTH VENT; 144,000 cfm Vs = 7.32 rn/sec, VENT DIA = 3.44 mn SECTOR BEARING (DEGREES)
DISTANCE METERS NNE NE ENS E ESE SE SSE S
- 22. 5 45.0 67 . 5 90. 0 112. 5 13 5.0 157. 5 180. 0 225. 00 7. 720OE-06 6.053E-06 5. 891E-06 8.338 E-06 1.6385-05 7. 62 1E-06 4 .390E-06 2. 582E-06 300. 00 4.736E-06 3.7385-06 3.630E-06 5. 137E-06 1.005E-05 4. 696E-06 2. 690E-06 1.581E-06 34 5.00 3.7 17E-06 2. 94 6E-06 2.85 6E-06 4.041E-06 7. 88 5E-06 3. 691E-06 2. 109E-06 1.239E-06 450. 00 2. 342E-06 1.873E-06 1.811E-06 2.5 64E-06 4. 961E-06 2.3355-06 1.328E-06 7.8 10E-07 682. 00 1.236E-06 9. 978E-07 9.630E-07 1. 386E-06 2. 613E-06 1.25 1E-06 7.0085-07 4.163E-07 762 .00 1.050OE-06 8.509E-07 8.200E-07 1. 184E-06 2. 20 5E-06 1.058 E-06 5.915E-07 3.524E-07 793. 00 9. 948E-07 8.069E-07 7. 766E-07 1. 122E-06 2. 078 E-06 9.971E-07 5. 578E-07 3.32 6E-07 805.00 9.747E-07 7. 909E-07 7. 609E-07 1.100E-06 2.032E-06 9.750E-07 5.455SE-07 3.254E-07 854 .00 9.006E-07 7. 329E-07 7. 029E-07 1.017E-06 1.861E-06 8. 924E5-07 4.997E-07 2. 986E-07 88 4.00 8.602E-07 7.015E-07 6. 712E-07 9. 712E-07 1.7685-06 8. 471E-07 4.747E-07 2.838E-07 965 .00 7. 671E-07 6.2 97E-07 5.980E-07 8. 656E-07 1.551E-06 7. 415E-07 4. 162E-07 2.494E-07 975. 00 7. 570E-07 6.2 19E-07 5. 901E-07 8. 54 0E-07 1.528E-06 7. 300E-07 4.099E-07 2. 456E-07 1006.00 7.275E-07 5.99 3E-07 5.6685-07 8. 202E-07 1.459E-06 6.962E-07 3.913E-07 2.34 6E-07 1097. 00 6.547E-07 5.429E-07 5.091E-07 7. 363E-07 1.293E-06 6.14 6E-07 3. 465E-07 2.0815-07 1126.00 6.34 6E-07 5.275E-07 4. 930E-07 7. 129E-07 1.2475-06 5.918E-07 3. 34 0E-07 2. 007E-07 1287. 00 5.432E-07 4.583E-07 4.199E-07 6.0535-07 1.037E-06 4.877E-07 2.775E-07 1. 670E-07 1433. 00 4.820E-07 4.130E-07 3. 706E-07 5.319E-07 8.972E-07 4.177E-07 2. 402E-07 1.446E-07 144 8.00 4.766E-07 4.090E-07 3. 662E-07 5.2535-07 8.8495-07 4.115E-07 2. 369E-07 1. 426E-07 1585 .00 4. 334E-07 3.773E-07 3.311E-07 4.725E-07 7. 877E-07 3.625E-07 2. 116E-07 1.273E-07 1609. 00 4.270E-07 3.72 6E-07 3 .259E-07 4.645E-07 7.73 6E-07 3.553E-07 2.0805-07 1. 251E-07 1770. 00 3.891E-07 3.4 46E-07 2. 953E-07 4.172E-07 6.916E-07 3.134E-07 1.87 6E-07 1. 127E-07 18 90.00 3. 654E-07 3.2 69E-07 2. 762E-07 3.876E-07 6.419E-07 2.88 2E-07 1.757E-07 1. 055E-07 1931. 00 3. 581E-07 3.2 14E-07 2.702E-07 3.784 5-07 6.267E-07 2.8055E-07 1.72 2E-07 1. 033E-07 2092. 00 3.324E-07 3.016E-07 2. 494E-07 3.463E-07 5.757E-07 2.550E-07 1.607E-07 9. 620OE-08 2134 .00 3.264E-07 2. 969E-07 2. 445E-07 3.38 9E-07 5. 643E-07 2.493E-07 1. 581E-07 9.461E-08 2253. 00 3.106E-07 2.845E-07 2. 318E-07 3. 193E-07 5.34 6E-07 2.34 6E-07 1.517E-07 9. 05 9E-08 2414 .00 2. 917E-07 2. 6955-07 2. 166E-07 2.960E-07 4. 998E-07 2. 177E-07 1.44 6E-07 8. 608E-08 2574 .00 2. 954E-07 2. 610E-07 2.066E-07 2.7795-07 4. 64 4E-07 2. 03 2E-07 1.399E-07 8.416E-08 2835 .00 3. 108E-07 2. 499E-07 1.933E-07 2.530E-07 4. 156E-07 1.8 38S-07 1.34 7E-07 8.24 6E-08 289 6.00 3. 163E-07 2. 477E-07 1.906E-07 2. 478E-07 4.05 6E-07 1.799E-07 1.33 8E-07 8. 22 5ES-O 3018 .00 3.294E-07 2. 438E-07 1.857E-07 2. 382E-07 3.868E-07 1 .726E-07 1.3235-07 8. 199E-08 34 14 .00 3. 772E-07 2. 35 1E-07 1.732E-07 2. 122E-07 3. 369E-07 1.539E-07 1.30IE-07 8.230E-08 3540. 00 3.847E-07 2. 335E-07 1.702E-07 2.053E-07 3. 237E-07 1.4 90E-07 1.300E-07 8.2755-08 3701. 00 3. 82 1E-07 2. 319E-07 1. 670E-07 1. 972E-07 3. 082E-07 1.4 33E-07 1.304E-07 8.359E-08 3871 .00 3. 651E-07 2. 305E-07 1.642E-07 1.894E-07 2. 932E-07 1.378E-07 1.313E-07 8.480E-08 4084 .00 3. 377E-07 2. 297E-07 1. 607E-07 1.7985-07 2. 75 9E-07 1.311E-07 1.300E-07 8.573E-08 4505. 00 2. 903E-07 2. 300E-07 1.5205-07 1.599E-07 2. 454E-07 1.172E-07 1. 155E-07 8. 302E-08 4511. 00 2. 897E-07 2.2 99E-07 1.519E-07 1.597E-07 2. 450E-07 1.170E-07 1.15 3E-07 8.298E-08 4827 .00 2. 606E-07 2 .235E-07 1.463E-07 1. 472E-07 2. 2585-07 1. 081E-07 1.0615-07 8. 139E-08 Run 4 6325. 00 1.713E-07 6660. 00 1. 595E-07 1.557E-07 1.451E-07
- 1. 336E-07 1.ll0E-07 1.766E-07 7. 663E-08 8.017E-08 6.380E-08 722 4 .00 1.425E-07 1.2 96E-07 1. 221E-07 1.070E-07 1.761E-07 7. 124E-08 7. 665E-08 5.7925-08 724 1.00 1.420E-07 1.2 92E-07 1.217E-07 1.06 9E-07 1.762E-07 7. 109E-08 7.654E-08 5.775E-08 7562.00 1.3365-07 1.2 16E-07 1. 146E-07 1. 015E-07 1.7235-07 6. 924E-08 7.44 6E-08 5.73 6E-08 804 7. 00 1.224E-07 1.114E-07 1.04 9E-07 9. 409E-08 1.669E-07 6. 692E-08 7. 109E-08 5. 652E-08 16093. 00 4.808E-08 4.3785-08 4.143E-08 4.4 85E-08 8.770OE-08 4.655E-08 2.965E-08 2. 673E-08 32187 .00 1.813E-08 1.648E-08 1.570E-08 1.911E-08 3.339E-08 1.894ES-08 1. 106E-08 9.904E-09 48280.00 1.043E-08 9.454E-09 9. 027E-09 1.100E-08 1.929E-08 1.08 6E-08 6.377E-09 5.7 11E-09 64374 .00 7.208E-09 6.534E-09 6.2585-09 7.5 96E-09 1.335E-08 7.4 93E-09 4.3 80E-09 3.910E-09 80467 .00 5.381E-09 4.883E-09 4.687E-09 5. 670ES-09 9.975E-09 5.5895-09 3.252E-09 2.894E-09
CHI/Q (SEC/M3) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS SOUTH VENT; 144,000 cfm Vs = 7.32 m/sec, VENT DIA = 3.44 m SECTOR BEARING (DEGREES)
DISTANCE METERS SSW SW WSW W WNW NW NNW N 202.5 225.0 247.5 270.0 292.5 315.0 337.5 360.0 225.00 1.687E-06 1.441E-06 1.814E-06 2.137E-06 1.254E-06 1.110E-06 2.243E-06 4.961E-06 300.00 1.031E-06 8.811E-07 1.114E-06 1.311E-06 7.659E-07 6.769E-07 1.369E-06 3.031E-06 345.00 8 073E-07 6.898E-07 8.746E-07 1.028E-06 5.997E-07 5.298E-07 1.071E-06 2.373E-06 450.00 5.083E-07 4.361E-07 5.543E-07 6.499E-07 3.774E-07 3.339E-07 6.722E-07 1.490E-06 682.00 2.732E-07 2.414E-07 3.050E-07 3.554E-07 2.020E-07 1.813E-07 3.599E-07 7.903E-07 762.00 2.317E-07 2.059E-07 2.598E-07 3.022E-07 1.711E-07 1.544E-07 3.073E-07 6.731E-07 793.00 2.189E-07 1.947E-07 2.456E-07 2.856E-07 1.616E-07 1.463E-07 2.918E-07 6.385E-07 805.00 2.143E-07 1.907E-07 2.404E-07 2.796E-07 1.582E-07 1.433E-07 2.862E-07 6.259E-07 854.00 1.970E-07 1.755E-07 2.212E-07 2.571E-07 1.453E-07 1.324E-07 2.656E-07 5.794E-07 884.00 1.874E-07 1.673E-07 2.108E-07 2.447E-07 1.383E-07 1.264E-07 2.544E-07 5.541E-07 965.00 1.653E-07 1.481E-07 1.867E-07 2.161E-07 1.217E-07 1.127E-07 2.290E-07 4.956E-07 975.00 1.628E-07 1.460E-07 1.842E-07 2.130E-07 1.199E-07 1.112E-07 2.262E-07 4.893E-07 1006.00 1.558E-07 1.399E-07 1.767E-07 2.039E-07 1.146E-07 1.069E-07 2.183E-07 4.707E-07 1097.00 1.388E-07 1.257E-07 1.592E-07 1.821E-07 1.020E-07 9.643E-08 1.987E-07 4.249E-07 1126.00 1.342E-07 1.218E-07 1.545E-07 1.761E-07 9.846E-08 9.356E-08 1.934E-07 4.122E-07 1287.00 1.135E-07' 1.051E-07 1.346E-07 1.493E-07 8.254E-08 8.084E-08 1.694E-07 3.546E-07 1433.00 1.007E-07 9.544E-08 1.237E-07 1.322E-07 7.219E-08 7.276E-08 1.538E-07 3.162E-07 1448.00 9.970E-08 9.468E-08 1.228E-07 1.307E-07 7.130E-08 7.207E-08 1.524E-07 3.128E-07 1585.00 9.208E-08 8.943E-08 1.172E-07 1.196E-07 6.444E-08 6.676E-08 1.417E-07 2.856E-07 1609.00 9.110E-08 8.879E-08 1.166E-07 1.180E-07 6.347E-08 6.599E-08 1.401E-07 2.815E-07 1770.00 8.625E-08 8.604E-08 1.139E-07 1.092E-07 5.812E-08 6.172E-08 1.307E-07 2.575E-07 1890.00 8.423E-08 8.531E-08 1.131E-07 1.045E-07 5.524E-08 5.926E-08 1.250E-07 2.425E-07 1931.00 8.377E-08 8.524E-08 1.130E-07 1.031E-07 5.443E-08 5.852E-08 1.232E-07 2.379E-07 2092.00 8.264E-08 8.533E-08 1.128E-07 9.866E-08 5.186E-08 5.583E-08 1.167E-07 2.213E-07 2134.00 8.248E-08 8.542E-08 1.127E-07 9.769E-08 5.132E-08 5.517E-08 1.151E-07 2.174E-07 2253.00 8.230E-08 8.585E-08 1.127E-07 9.526E-08 5.001E-08 5.347E-08 1.109E-07 2.071E-07 2414.00 8.251E-08 8.671E-08 1.128E-07 9.261E-08 4.868E-08 5.144E-08 1.059E-07 1.947E-07 2574.00 7.959E-08 8.459E-08 1.090E-07 8.964E-08 4.643E-08 4.919E-08 1.077E-07 1.947E-07 2835.00 7.530E-08 8.137E-08 1.031E-07 8.551E-08 4.327E-08 4.595E-08 1.119E-07 1.968E-07 2896.00 7.437E-08 8.065E-08 1.018E-07 8.464E-08 4.261E-08 4.525E-08 1.131E-07 1.976E-07 3018.00 7.256E-08 7.922E-08 9.929E-08 8.296E-08 4.134E-08 4.391E-08 1.159E-07 1.996E-07 3414.00 6.716E-08 7.466E-08 9.153E-08 7.807E-08 3.766E-08 3.991E-08 1.273E-07 2.108E-07 3540.00 6 560E-08 7.329E-08 8.926E-08 7.669E-08 3.662E-08 3.878E-08 1.315E-07 2.156E-07 3701.00 6.369E-08 7.160E-08 8.649E-08 7.499E-08 3.537E-08 3.740E-08 1.366E-07 2.214E-07 3871.00 6.176E-08 6.987E-08 8.372E-08 7.330E-08 3.412E-08 3 604E-08 1 408E-07 2 254E-07 4084.00 6.083E-08 6.880E-08 8.148E-08 7.133E-08 3.273E-08 3.545E-08 1.415E-07 2.235E-07 4505.00 6.600E-08 7.156E-08 8.296E-08 6.797E-08 3.053E-08 4.003E-08 1.303E-07 2.011E-07 4511.00 6.607E-08 7.160E-08 8.300E-08 6.793E-08 3.050E-08 4.011E-08 1.301E-07 2 007E-07 4827.00 6.958E-08 7.316E-08 8.542E-08 6.593E-08 2.899E-08 4.505E-08 1.190E-07 1.810E-07 6325.00 5.527E-08 6.220E-08 8.780E-08 7.629E-08 2.241E-08 5.976E-08 7.801E-08 1.184E-07 6660.00 5.141E-08 5.829E-08 8.409E-08 7.975E-08 2.115E-08 5.618E-08 7.260E-08 1.102E-07 7224.00 4.580E-08 5.212E-08 7.626E-08 7.478E-08 1.929E-08 5.015E-08 6.474E-08 9.838E-08 7241.00 4.565E-08 5.195E-08 7.601E-08 7.454E-08 1.924E-08 4.998E-08 6.453E-08 9.805E-08 7562.00 4.301E-08 4.883E-08 7.150E-08 7.013E-08 1.974E-08 4.700E-08 6.070E-08 9.224E-08 8047.00 3.938E-08 4.462E-08 6.537E-08 6.416E-08 2.065E-08 4.298E-08 5.555E-08 8.443E-08 16093.00 1.505E-08 1.679E-08 2.497E-08 2.477E-08 1.171E-08 1.667E-08 2.157E-08 3.280E-08 32187.00 5.489E-09 6.060E-09 9.142E-09 9.163E-09 4.289E-09 6.206E-09 8.025E-09 1.219E-08 48280.00 3.146E-09 3.479E-09 5.185E-09 5.217E-09 2.454E-09 3.549E-39 4.604E-09 6.987E-09 64374.00 2.137E-09 2.352E-09 3.538E-09 3.578E-09 1.672E-09 2.440E-09 3.162E-09 4.797E-09 80467.00 1.572E-09 1.721E-09 2.616E-09 2.656E-09 1.233E-09 1.815E-09 2.347E-09 3.562E-09
DEPLETED CHI/ (SEC/M3) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS SOUTH VENT; 144,000 cfm, 8.05 DAY DECAY Vs = 7.32 m/sec, VENT DIA - 3.44 m SECTOR BEARING (DEGREES)
DISTANCE METERS NNE NE ENE 2 ESE SE SSE S
- 22. 5 45.0 67. 5 90.0 112. 5 135. 0 157. 5 180. 0 225.00 7.4 66E-06 5.855E-06 5.697E-06 8.064E-06 1.5842-05 7.370E-06 4.2452-06 2. 497E-06 300.00 4.5402-06 3.5852-06 3.480E-06 4.9262-06 9. 634E-06 4.501E-06 2.578 2-06 1.515E-06 345.00 3.54 5E-06 2.811E-06 2.725E-06 3. 8542-06 7.517E-06 3.519E-06 2.0 112-06 1.1822-06 450.00 2.2072-06 1.7662-06 1.707E-06 2. 4162-06 4. 670E-06 2.199E-06 1.2502-06 7. 355E-07 682.00 1.143E-06 9.24 3E-07 8. 917E-07 1.2832-06 2. 411E-06 1. 155E-06 6.470E-07 3.84 4E-07 762.00 9. 663E-07 7. 843E-07 7. S555E-07 1.0902-06 2. 022E-06 9. 705E-07 5.428E-07 3.2352-07 793.00 9.134E-07 7. 424E-07 7.1422-07 1.0322-06 1.902E-06 9. 1252-07 5.1062-07 3.04 6E-07 805.00 8.94 3E-07 7. 273E-07 6.992E-07 1.0102-06 1.85 82-06 8.9152-07 4.9892-07 2.978E-07 854.00 8.239E-07 6.722E-07 6.44 1E-07 9.312E2-07 1.6952-06 8. 129E-07 4.5542-07 2.722E-07 884.00 7.85 6E-07 6. 424E-07 6.1412-07 8.8812-07 1.607E-06 7. 6992-07 4.3162-07 2.582E-07 965.00 6.97 6E-07 5.74 6E-07 5.449E-07 7. 882E-07 1.402E-06 6.6992-07 3.762E-07 2.25 62-07 975.00 6.88 12-07 5. 673E-07 5.374E-07 7. 7732-07 1.37 92-06 6.5892-07 3.7012-07 2.220E-07 1006.00 6.604E-07 5.460E-07 5. 1552-07 7. 4552-07 1.315E-06 6.2722-07 3.52 6E-07 2.116E-07 1091.00 5.933E-07 4. 941E-07 4.621E-07 6.6792-07 1.161E-06 5.515E-07 3.1122-07 1.8'712-07 1126.00 5.747E-07 4.800E-07 4.473E-07 6.4632-07 1.119E-06 5. 3052-07 2.9972-07 1.802E-07 1287.00 4.908E-07 4.167E-07 3.800E-07 5.4712-07 9.259E-07 4.3452-07 2.476E-07 1.4912-07 1433.00 4.3492-07 3.755E-07 3. 346E-07 4.7962-07 7.977E-07 3.703E-07 2.1352-07 1.285E-07 1448.00 4.2992-07 3.719E-07 3.3062-07 4.7352-07 7.865E-07 3.64 62-07 2.1052-07 1.2682-07 1585.00 3.906E-07 3. 431E-07 2.985E-07 4.2502-07 6.978E-07 3.1982-07 1.875E2-07 1.128E-07 1609.00 3.8472-07 3.3882-07 2. 938E-07 4.1772-07 6. 85 0E-07 3.132E-07 1.84 22-07 1. 108E2-07 1770.00 3.502E-07 3.134E-07 2. 657E-07 3.74 3E-07 6.105E-07 2.75 12-07 1.6572-07 9.9592-08 1890.00 3.2872-07 2.9742-07 2. 482E-07 3.4722-07 5.655E-07 2. 522E-07 1.5512-07 9.3142-08 1931.00 3.2202-07 2. 924E-07 2. 427E-07 3.387E-07 5.517E-07 2. 453E-07 1.5202-07 9.1232-08 2092.00 2.9872-07 2. 7452-07 2.238E-07 3.0952-07 5.061E-07 2.224E-07 1.4182-07 8.4 972-08 2134.00 2.934E-07 2.703E-07 2. 195E-07 3.0272-07 4.959E-07 2.174E-07 1.396E-07 8. 358E2-08 2253.00 2.7 92E-07 2.591E-07 2. 079E-07 2.85 0E-07 4.696E-07 2.044 2-07 1. 34 12-07 8.0112-08 2414.00 2.6222-07 2.455E-07 1.9422-07 2.6392-07 4.388E-07 1.8942-07 1.2802-07 7.6232-08 2574.00 2.669E-07 2. 382 E-07 1.8542-07 2.4772-07 4.070E-07 1.767E-07 1.2422-07 7.480E-08 2835.00 2.835E-07 2.2852-07 1.737E-07 2.25 32-07 3. 632E-07 1.596E-07 1.201E-07 7.373E-08 2896.00 2.893E-07 2.2 672-07 1.713E-07 2.2072-07 3.542E-07 1.5622-07 1.194E-07 7.3632-08 3018.00 3.024E-07 2.234E-07 1.67IE-07 2. 120E-07 3. 374E2-07 1.4982-07 1.1832-07 7. 358E2-08 3414.00 3.34 92-07 2.164E-07 1.5 642-07 1.8882-07 2. 9312-07 1.3362-07 1.171E-07 7.439E-08 3540.00 3. 3472-07 2.150E-07 1.539E-07 1. 827E2-07 2. 814E2-07 1.2942-07 1.174E-07 7.4 962-08 3701.00 3.2272-07 2. 132E-07 1.5132-07 1.75 52-07 2. 6752-07 1.24 52-07 1.180E-07 7.590E-08 3871.00 2.9992-07 2. 109E-07 1.4 902-07 1.6852-07 2.5422-07 1. 1972-07 1.191E-07 7. 718E2-08 4084.00 2.740E-07 2. 0822-07 1.4 61E-07 1.5992-07 2.3882-07 1. 1382-07 1.183E-07 7.8192-08 4505.00 2.3272-07 2.014E-07 1.384E-07 1.419E-07 2. 1162-07 1.014E-07 1.04 8E-07 7. 58 1E-08 4511.00 2.3222-07 2. 012E-07 1.3832-07 1.4162-07 2. 112E-07 1.012E-07 1.0462-07 7.5782-08 4827.00 2.070E-07 1.8892-07 1.331E-07 1.3032-07 1.94 12-07 9. 33 5E-08 9.607E-08 7. 439E-08 Run 5 6325.00 1.309E-07 1. 197E-07 6660.00 1.2112-07 1. 109E-07
- 1. 137E-07 1.005E-07 1.530E-07 6. 876E-08 7.4072-08 6.182E-08 South Vent XIQ 1.0 622-07 9. 811E-08 1.523E-07 6. 55 5E-08 7. 1872-08 5. 805E-08 7224.00 1.07 0E-07 9.801E-08 9.218E-08 9. 464E-08 1.529E-07 6.0912-08 6.72 02-08 5. 248E2-08 Depleted and 7241.00 1.0662-07 9.766E-08 9.182E-08 9.454E-08 1.5292-07 6. 078E-08 6.704E-08 5.233E-08 Decayed 7562.00 9.9702-08 9. 135E-08 8.58 02-08 8.9512-08 1.4962-07 5. 92 8E-08 6.4 07E-08 5. 189E-08 8047.00 9.04 2E-08 8.290E-08 7.7772-08 8.269E-08 1.4 492-07 5.74 1E-08 5.931E-08 5.063E-08 16093.00 3.22 12-08 2. 960E-08 2.7702-08 3. 621E-08 6.284E2-08 3.630E-08 2.004E-08 1.8112-08 32187.00 1.035E-08 9. 499E-09 8.931E-09 1.146E-08 2.0362-08 1. 090E-08 6.380E-09 5. 7192-09 48280.00 5.304E-09 4 .788E-09 4.566E-09 5.845E-09 1.03 92-08 5.559E-09 3.2812-09 2.9372-09 64374.00 3.329E-09 3. 003E-09 2.871E-09 3.658E-09 6.5072-09 3.480E-09 2.05 02-09 1.825E-09 80467.00 2.250E-09 2.028E-09 1.943E-09 2. 465E-09 4.383E-09 2.347E-09 1.379E-09 1.222E2-09
DEPLETED CHI/Q (SEC/M3) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS SOUTH VENT; 144,000 cfm, 8.05 DAY DECAY Vs = 7.32 m/sec, VENT DIA - 3.44 m SECTOR BEARING (DEGREES)
DISTAIICE METERS SSW SW WSW W WNW NW NNW 1N 202.5 225.0 247.5 270.0 292.5 315.0 337.5 360.0 225.00 1.631E-06 1.394E-06 1.754E-06 2.067E-06 1.212E-06 1.073E-06 2.170E-06 4.798E-06 300.00 9.880E-07 8.445E-07 1.068E-06 1.256E-06 7.342E-07 6.489E-07 1.313E-06 2.905E-06 345.00 7.696E-07 6.576E-07 8.338E-07 9.797E-07 5.719E-07 5.051E-07 1.022E-06 2.263E-06 450.00 4.786E-07 4.106E-07 5.219E-07 6.118E-07 3.554E-07 3.144E-07 6.332E-07 1.403E-06 682.00 2.522E-07 2.228E-07 2.816E-07 3.280E-07 1.864E-07 1.674E-07 3.325E-07 7.303E-07 762.00 2.127E-07 1.888E-07 2.384E-07 2.772E-07 1.569E-07 1.418E-07 2.824E-07 6.188E-07 793.00 2.005E-07 1.782E-07 2.248E-07 2.614E-07 1.479E-07 1.340E-07 2.676E-07 5.857E-07 805.00 1.961E-07 1.743E-07 2.199E-07 2.556E-07 1.446E-07 1.312E-07 2.623E-07 5.738E-07 854.00 1.796E-07 1.599E-07 2.016E-07 2.342E-07 1.323E-07 1.207E-07 2.427E-07 5.296E-07 884.00 1.705E-07 1.520E-07 1.917E-07 2.225E-07 1.256E-07 1.151E-07 2.322E-07 5.056E-07 965.00 1.495E-07 1.338E-07 1.690E-07 1.953E-07 1.099E-07 1.021E-07 2.081E-07 4.503E-07 975.00 1.472E-07 1.318E-07 1.665E-07 1.923E-07 1.082E-07 1.007E-07 2.056E-07 4.443E-07 1006.00 1.405E-07 1.262E-07 1.595E-07 1.838E-07 1.032E-07 9.665E-08 1.981E-07 4.269E-07 1097.00 1.249E-07 1.130E-07 1.434E-07 1.637E-07 9.150E-08 8.704E-08 1.802E-07 3.847E-07 1126.00 1.206E-07 1.095E-07 1.391E-07 1.582E-07 8.825E-08 8.442E-08 1.753E-07 3.730E-07 1287.00 1.016E-07 9.426E-08 1.212E-07 1.336E-07 7.360E-08 7.281E-08 1.534E-07 3.202E-07 1433.00 9.005E-08 8.567E-08 1.116E-07 1.181E-07 6.416E-08 6.552E-08 1.393E-07 2.851E-07 1448.00 8.911E-08 8.501E-08 1.108E-07 1.168E-07 6.336E-08 6.490E-08 1.381E-07 2.820E-07 1585.00 8.236E-08 8.051E-08 1.062E-07 1.068E-07 5.717E-08 6.015E-08 1.285E-07 2.573E-07 1609.00 8.150E-08 7.999E-08 1.056E-07 1.053E-07 5.629E-08 5.948E-08 1.270E-07 2.536E-07 1770.00 7.739E-08 7.787E-08 1.037E-07 9.765E-08 5.155E-08 5.572E-08 1.187E-07 2.318E-07 1890.00 7.580E-08 7.750E-08 1.034E-07 9.353E-08 4.904E-08 5.357E-08 1.135E-07 2.183E-07 1931.00 7.548E-08 7.755E-08 1.034E-07 9.236E-08 4.834E-08 5.293E-08 1.119E-07 2.140E-07 2092.00 7.481E-08 7.801E-08 1.036E-07 8.861E-08 4.620E-08 5.061E-08 1.061E-07 1.991E-07 2134.00 7.475E-08 7.818E-08 1.036E-07 8.780E-08 4.575E-08 5.004E-08 1.047E-07 1.956E-07 2253.00 7.484E-08 7.883E-08 1.038E-07 8.581E-08 4.470E-08 4.857E-08 1.010E-07 1.864E-07 2414.00 7.535E-08 7.991E-08 1.041E-07 8.365E-08 4.367E-08 4.682E-08 9.647E-08 1.752E-07 2574.00 7.275E-08 7.805E-08 1.006E-07 8.112E-08 4.170E-08 4.482E-08 9.851E-08 1.760E-07 2835.00 6.891E-08 7.516E-08 9.523E-08 7.757E-08 3.893E-08 4.192E-08 1.030E-07 1.789E-07 2896.00 6.806E-08 7.451E-08 9.401E-08 7.681E-08 3.834E-08 4.129E-08 1.043E-07 1.798E-07 3018.00 6.642E-08 7.321E-08 9.162E-08 7.536E-08 3.723E-08 4.008E-08 1.071E-07 1.821E-07 3414.00 6.151E-08 6.903E-08 8.437E-08 7.109E-08 3.397E-08 3.648E-08 1.183E-07 1.936E-07 3540.00 6.008E-08 6.776E-08 8.224E-08 6.986E-08 3.305E-08 3.544E-08 1.218E-07 1.969E-07 3701.00 5.832E-08 6.618E-08 7.962E-08 6.835E-08 3.193E-08 3.419E-08 1.249E-07 1.992E-07 3871.00 5.653E-08 6.456E-08 7.699E-08 6.684E-08 3.081E-08 3.294E-08 1.261E-07 1.986E-07 4084.00 5.569E-08 6.354E-08 7.484E-08 6.506E-08 2.956E-08 3.245E-08 1.231E-07 1.911E-07 4505.00 6.057E-08 6.606E-08 7.608E-08 6.201E-08 2.759E-08 3.697E-08 1.080E-07 1.634E-07 4511.00 6.064E-08 6.609E-08 7.611E-08 6.197E-08 2 756E-08 3.705E-08 1.078E-07 1.630E-07 4827.00 6.330E-08 6.745E-08 7.833E-08 6.016E-08 2.620E-08 4.188E-08 9.545E-08 1.444E-07 6325.00 4.333E-08 5.041E-08 7.260E-08 6.745E-08 2.014E-08 4.734E-08 5.964E-08 9.060E-08 6660.00 4.006E-08 4.593E-08 6.711E-08 6.598E-08 1.898E-08 4.290E-08 5.515E-08 8.382E-08 7224.00 3.534E-08 3.972E-08 5.795E-08 5.640E-08 1.727E-08 3.767E-08 4.866E-08 7.402E-08 7241.00 3.521E-08 3.956E-08 5.770E-08 5.618E-08 1.722E-08 3.753E-08 4.849E-08 7.375E-08 7562.00 3.262E-08 3.674E-08 5.354E-08 5.239E-08 1 771E-08 3.500E-08 4.529E-08 6.892E-08 8047.00 2.941E-08 3.313E-08 4.834E-08 4.738E-08 1.856E-08 3.169E-08 4.103E-08 6.246E-08 16093.00 1.007E-08 1.122E-08 1.668E-08 1.654E-08 7.861E-09 1.114E-08 1.443E-08 2.200E-08 32187.00 3.127E-09 3.441E-09 5.187E-09 5.201E-09 2.449E-09 3.526E-09 4.570E-09 6.981E-09 48280.00 1.593E-09 1.754E-09 2.611E-09 2.629E-09 1.247E-09 1.791E-09 2.331E-09 3.566E-09 64374.00 9.816E-10 1.074E-09 1.613E-09 1.633E-09 7.723E-10 1.117E-09 1.453E-09 2.228E-09 80467.00 6.523E-10 7.088E-10 1.076E-09 1.094E-09 5.155E-10 7.497E-10 9.748E-10 1.499E-09
D/0 (/M2) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS SOUTH VENT; 144,000 cfmn, 8.05 DAY DECAY Vs - 7.32 rn/sec, VENT DIA= 3.44 m SECTOR BEARING (DEGREES)
DISTANCE METERS NNE NE ENE ESE SE SSE S
- 22. 5 45. 0 67.5 90.0 112.5 135. 0 157. 5 18010 225.00 3. 422E-08 2. 604 E-08 2. 639E-08 5.4 35E-08 8. 974E-08 5 .777E-08 2. 643E-08 1. 405E-08 300.00 2.365E-08 1.8 37E-08 1.869E-08 3.784E-08 6. 08 5E-08 3.934E-08 1. BIOE-08 9. 623 E-09 345.00 1.94 1E-08 1.525E-08 1.557E-08 3. 115E-08 4. 922E-08 3.190E-08 1.472E-08 7.866E-09 450.00 1.343E-08 1.077E-08 1. 109E-08 2. 168E-08 3.30 1E-08 2.152E-08 1.00O1E-08 5.417E-09 682.00 7.52 1E-09 6. 167E-09 6.394E-09 1.215E-08 1.78 4E-OB 1. 169E-08 5. 492E-09 3.055E-09 762.00 6.44 1E-09 5. 30 8E-09 5. 505E-09 1. 040E-08 1.517E-08 9.94 5E-09 4.68IE-09 2. 627E-09 793.00 6.09 6E-09 5.032E-09 5.219E-09 9. 838 E-09 1.431E-08 9.38 6E-09 4.422E-09 2.4 92E-09 805.00 5.969E-09 4. 931E-09 5. 113E-09 9. 632E-09 1.401E-08 9. 183E-09 4.328E-09 2. 44 3E-09 854.00 5.524 E-09 4. 620E-09 4.722E-09 8. 844E-09 1.28 6E-08 8. 458E-09 4.025E-09 2. 25 8E-09 884.00 5.308E-09 4. 425E-09 4.499E-09 8.4 16E-09 1.22 3E-08 8. 05 2E-09 3. 845E-09 2.15 9E-09 965.00 4.704E-09 4.012E-09 4. 060E-09 7. 424E-09 1.078E-08 7. 120E-09 3. 437E-09 1.934E-09 975.00 4. 670E-09 3. 954 E-09 4. 004E-09 7.316E-09 1.063E-08 7.015E-09 3.392E-09 1.909E-09 1006.00 4. 485E-09 3.797E-09 3. 826E-09 7. 021E-09 1.015E-08 6.70 6E-09 3.26OE-09 1.836E-09 1097.00 4.004E-09 3.34 5E-09 3. 344 E-09 6.087E-09 8.827E-09 5. 852 E-09 2.870E-09 1. 627E-09 1126.00 3.886E-09 3.224E-09 3. 20 5E-09 5.832E-09 8.4 65E-09 5. 617E-09 2 .761E-09 1. 571E-09 1287.00 3. 199E-09 2. 677E-09 2. 605E-09 4.692E-09 6. 861E-09 4.573E-09 2. 316E-09 1. 330E-09 1433.00 2.752E-09 2.280E-09 2 .204E-09 3.956E-09 5. 818E-09 3.87 9E-09 2.003E-09 1. 185E-09 1448.00 2.728E-09 2 .254E-09 2. 167E-09 3. 89 1E-09 5.726E-09 3.8 17E-09 1. 979E-09 1. 174E-09 1585.00 2. 405E-09 1.979E-09 1 .884E-09 3.384E-09 4 .971E-09 3.328E-09 1. 73 9E-09 1.084 E-09 1609.00 2. 350OE-09 1.930OE-09 1.84 1E-09 3.301E-09 4.850E-09 3.24 7E-09 1. 697E-09 1.063E-09 1770.00 2.038E-09 1.668E-09 1.574E-09 2.830OE-09 4. 154E-09 2. 794 E-09 1.4 58E-09 9. 635E-10 1890.00 1.85 1E-09 1.508E-09 1. 415E-09 2.54 OE-09 3. 737E-09 2. 520OE-09 1. 318E-09 9.04 2E-10 1931.00 1.797E-09 1.45 6E-09 1. 371E-09 2.452E-09 3. 609E-09 2. 438E-09 1. 274E-09 8.818E-10 2092.00 1.600E-09 1.305E-09 1.20 9E-09 2. 159E-09 3. 17 3E-09 2.147E-09 1. 126E-09 8 .219E-10 2134.00 1. 548E-09 1.265E-09 1. 170E-09 2.089E-09 3. 074E-09 2.079E-09 1. 090E-09 8. 040E-10 2253.00 1. 438E-09 1.15 7E-09 1.069E-09 1. 911E-09 2. 822E-09 1.908E-09 9. 991E-10 7. 571E-10 2414.00 1.285E-09 1.04 6E-09 9.54 3E-10 1. 710E-09 2. 571E-09 1.712E-09 8. 955E-10 7. 039E-10 2574.00 1.162E-09 9.504E-10 8. 583E-10 1.537E-09 2. 321E-09 1.538 E-09 8. 031E-10 6. 396E-10 2835.00 9.860E-10 8.05 6E-10 7. 313E-10 1. 313E-09 2.002E-09 1. 312E-09 6.934E-10 5. 456E-10 2896.00 9.698E-10 7.807E-10 7.078E-10 1. 269E-09 1.937E-09 1.26 6E-09 6.830E-10 5.2 69E-10 3018.00 1.138 E-09 7.3332E-10 6. 59 6E-10 1. 189E-09 1.815E-09 1. 182E-09 6.621E-10 4. 925E-10 3414.00 8.433E-10 6. 68 OE-10 5.362E-10 9.725E-10 1.502E-09 9. 666E-10 5.851E-10 4. 019E-10 3540.00 7. 620E-10 7. 139E-10 5. 058E-10 9. 159E-10 1.421E-09 9. 106E-10 5.542E-10 3.806E-10 3701.00 6.985E-10 7. 53 8E-10 4. 699E-10 8.505SE-10 1.32 8E-09 8.4 67E-10 5. 139E-10 3 .727E-10 3871.00 9. 604E-10 7.038E-10 4 .363E-10 7. 888E-10 1.23 9E-09 7. 869E-10 4 .781E-10 3.708E-10 4084.00 9.B88 E-10 6.13 4E-10 4. 066E-10 7.236E-10 1.14 3E-09 7.237E-10 4.389E-10 3.513E-10 4505.00 8.399E-10 4.621E-10 4. 012E-10 6.129E-10 9.721lE-10 6.162E-10 3.7 30E-10 3.007E-10 4511.00 8. 383E-10 4.603E-10 4.013E-10 6. 116E-10 9.699E-10 6.148E-10 3 .722E-10 3.OOOE-10 4827.00 7. 474E-10 3. 87SE-10 4 .319E-10 5.454E-10 8. 675E-10 5. 503E-10 3. 327E-10 2. 686E-10 Run 6 6325.00 4. 683E-10 3.872E-10 2. 438E-10 3. 436E-10 5.70 8E-10 3.505E-10 2. 306E-10 1.7 17E-10 South Vent DIQ 6660.00 4.282E-10 3.54 3E-10 2.222E-10 3. 144E-10 5.221E-10 3.205E-10 2. 543E-10 1.571E-10 7224.00 3.7 18E-10 3.080OE-10 2.7 60E-10 2.74 9E-10 4.537E-10 2. 802E-10 2. 388E-10 1.3 67E-10 7241.00 3.703E-10 3.0 68E-10 2.75 6E-10 2.74 2E-10 4 .51GE-10 2. 791E-10 2.374E-10 1.361E-10 7562.00 3. 435E-10 2.84 8E-10 2.573E-10 2.545E-10 4.193E-10 2. 627E-10 2. 161E-10 1. 373E-10 8047.00 3 .084E-10 2.5 60E-10 2. 321E-10 2.287 E-10 3.7 90E-10 2.468E-10 1. 898E-10 1 .497E-10 16093.00 9.28 6E-11 7.816E-11 7.074E-11 1. 054 E-10 1.921lE-10 1.084E-10 6. 665E-11 5.2 57E-11 32187.00 2.793E-11 2.37 9E-11 2. 126E-11 4 .O011E-11 6.647E-11 3.2 63E-11 2.003E-11 1.578E-11 48280.00 1. 383E-11 1. 173E-11 1.05 3E-11 1. 928E-11 3. 188E-11 1.610E-11 9. 917E-12 7.804E-12 64374 .00 8. O1OE-12 6.797E-12 6.099E-12 1. 098E-11 1.8 10E-11 9.32OE-12 5. 754E-12 4.533E-12 80467.00 5.2 19E-12 4. 42GE-12 3. 973E-12 7. 04 1E-12 1.151E-11 6.068E-12 3.754E-12 2.960E-12
D/Q (/M2) LGS 2002 EFFLUENT REPORT ANNUAL DISPERSION CALCULATIONS SOUTH VENT; 144,000 cfm, 8.05 DAY DECAY Vs = 7.32 m/sec, VENT DIA = 3.44 m SECTOR BEARING (DEGREES)
DISTANCE METERS SSW SW WSW W WNW NW NNW N 202.5 225.0 247.5 270.0 292.5 315.0 337.5 360.0 225.00 7.148E-09 8.088E-09 8.346E-09 1.357E-08 8.044E-09 6.082E-09 1.357E-08 2.635E-08 300.00 4.880E-09 5.486E-09 5.737E-09 9.249E-09 5.446E-09 4.143E-09 9.203E-09 1.792E-08 345.00 3.977E-09 4.445E-09 4.693E-09 7.513E-09 4.403E-09 3.363E-09 7.449E-09 1.454E-08 450.00 2.721E-09 3.001E-09 3.254E-09 5.112E-09 2.952E-09 2.285E-09 5.012E-09 9.832E-09 682.00 1.530E-09 1.662E-09 1.911E-09 2.882E-09 1.596E-09 1.292E-09 2.746E-09 5.387E-09 762.00 1.319E-09 1.432E-09 1.673E-09 2.489E-09 1.360E-09 1.119E-09 2.350E-09 4.601E-09 793.00 1.252E-09 1.360E-09 1.598E-09 2.363E-09 1.285E-09 1.065E-09 2.225E-09 4.350E-09 805.00 1.228E-09 1.334E-09 1.571E-09 2.318E-09 1.258E-09 1.045E-09 2.180E-09 4.260E-09 854.00 1.145E-09 1.253E-09 1.524E-09 2.169E-09 1.164E-09 9.709E-10 2.010E-09 3.921E-09 884.00 1.105E-09 1.208E-09 1.493E-09 2.086E-09 1.114E-09 9.312E-10 1.918E-09 3.738E-09 965.00 1.043E-09 1.168E-09 1.451E-09 1.902E-09 1.009E-09 8.440E-10 1.708E-09 3.318E-09 975.00 1.030E-09 1.154E-09 1.450E-09 1.878E-09 9.978E-10 8.343E-10 1.685E-09 3.273E-09 1006.00 1.021E-09 1.155E-09 1.434E-09 1.824E-09 9.766E-10 8.046E-10 1.617E-09 3.148E-09 1097.00 9.516E-10 1.089E-09 1.340E-09 1.628E-09 8.753E-10 7.234E-10 1.422E-09 2.766E-09 1126.00 9.286E-10 1.092E-09 1.306E-09 1.573E-09 8.535E-10 6.995E-10 1.369E-09 2.661E-09 1287.00 8.223E-10 9.963E-10 1.188E-09 1.336E-09 7.330E-10 5.968E-10 1.138E-09 2.201E-09 1433.00 7.521E-10 9.124E-10 1.089E-09 1.181E-09 6.553E-10 5.296E-10 9.977E-10 1.907E-09 1448.00 7.468E-10 9.056E-10 1.076E-09 1.174E-09 6.530E-10 5.239E-10 9.880E-10 1.882E-09 1585.00 6.762E-10 8.438E-10 9.783E-10 1.051E-09 5.929E-10 4.714E-10 8.892E-10 1.670E-09 1609.00 6.599E-10 8.254E-10 9.594E-10 1.029E-09 5.793E-10 4.617E-10 8.736E-10 1.632E-09 1770.00 5.816E-10 7.168E-10 8.417E-10 9.015E-10 5.021E-10 4.073E-10 7.787E-10 1.428E-09 1890.00 5.295E-10 6.517E-10 7.628E-10 8.164E-10 4.623E-10 3.781E-10 7.266E-10 1.312E-09 1931.00 5.149E-10 6.314E-10 7.426E-10 7.916E-10 4.475E-10 3.674E-10 7.110E-10 1.272E-09 2092.00 4.595E-10 5.650E-10 6.718E-10 7.036E-10 4.022E-10 3.334E-10 6.612E-10 1.153E-09 2134.00 4.465E-10 5.477E-10 6.543E-10 6.829E-10 3.904E-10 3.249E-10 6.410E-10 1.128E-09 2253.00 4.135E-10 5.060E-10 6.033E-10 6.349E-10 3.648E-10 3.028E-10 5.945E-10 1.048E-09 2414.00 3.772E-10 4.602E-10 5.478E-10 5.758E-10 3.300E-10 2.813E-10 5.485E-10 9.546E-10 2574.00 3.498E-10 4.216E-10 5.027E-10 5.218E-10 2.997E-10 2.563E-10 5.338E-10 9.345E-10 2835.00 3.142E-10 3.737E-10 4.491E-10 4.498E-10 2.596E-10 2.237E-10 4.661E-10 8.307E-10 2896.00 3.082E-10 3.639E-10 4.403E-10 4.355E-10 2.515E-10 2.170E-10 4.546E-10 7.998E-10 3018.00 2.972E-10 3.490E-10 4.248E-10 4.077E-10 2.380E-10 2.045E-10 4.260E-10 7.505E-10 3414.00 2.629E-10 3.237E-10 3.868E-10 3.567E-10 2.001E-10 1.716E-10 4.357E-10 8.129E-10 3540.00 2.491E-10 3.199E-10 3.726E-10 3.474E-10 1.897E-10 1.631E-10 4.283E-10 8.028E-10 3701.00 2.375E-10 3.056E-10 3.594E-10 3.347E-10 1.782E-10 1.536E-10 3.861E-10 6.725E-10 3871.00 2.239E-10 2.894E-10 3.435E-10 3.182E-10 1.670E-10 1.443E-10 3.332E-10 5.762E-10 4084.00 2.108E-10 2.693E-10 3.246E-10 2.986E-10 1.555E-10 1.338E-10 2.902E-10 5.045E-10 4505.00 1.841E-10 2.349E-10 2.861E-10 2.588E-10 1.327E-10 1.240E-10 2.799E-10 5.797E-10 4511.00 1.840E-10 2.344E-10 2.854E-10 2.582E-10 1.324E-10 1.239E-10 2.791E-10 5.830E-10 4827.00 2.093E-10 2.142E-10 2.579E-10 2.332E-10 1.190E-10 1.125E-10 3.020E-10 5.992E-10 6325.00 1.465E-10 1.514E-10 1.862E-10 1.905E-10 7.657E-11 1 003E-10 2.100E-10 3.794E-10 6660.00 1.343E-10 1.534E-10 1.735E-10 1.599E-10 7.020E-11 1.160E-10 1.921E-10 3.469E-10 7224.00 1.173E-10 1.480E-10 1.749E-10 1.751E-10 6.123E-11 1.030E-10 1.668E-10 3.013E-10 7241.00 1.168E-10 1.474E-10 1.754E-10 1.752E-10 6.099E-11 1.026E-10 1.661E-10 3.001E-10 7562.00 1.143E-10 1.394E-10 1.705E-10 1.640E-10 5.954E-11 9.578E-11 1.543E-10 2.784E-10 8047.00 1.047E-10 1.260E-10 1.541E-10 1.481E-10 5.412E-11 8.610E-11 1.386E-10 2.500E-10 16093.00 3.187E-11 3.811E-11 4.658E-11 4.459E-11 2.589E-11 2.590E-11 4.172E-11 7.535E-11 32187.00 9.578E-12 1.146E-11 1.400E-11 1.340E-11 7.787E-12 7.787E-12 1.254E-11 2.265E-11 48280.00 4.742E-12 5.671E-12 6.932E-12 6.635E-12 3.855E-12 3.855E-12 6.209E-12 1.121E-11 64374.00 2.747E-12 3.286E-12 4.016E-12 3.844E-12 2.233E-12 2.233E-12 3.597E-12 6.496E-12 80467.00 1.790E-12 2.141E-12 2.616E-12 2.504E-12 1.455E-12 1.455E-12 2.343E-12 4.232E-12
Attachment 2 Limerick Generating Station 2002 Annual Joint Frequency Distributions of Wind Speed, Wind Direction and Atmospheric Stability Class Level 1 - Meteorological Tower No. 1, 30-ft Level Level 2 - Meteorological Tower No. 1, 175-ft Level
LIMERICK GENERATING STATION DIGLAPSE VERSION 1.0 LAPSE RATE WIND ROSE PROGRAM TO COMPUTE JOINT FREQUENCY DISTRIBUTIONS OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS DIGLAPSE ALSO COMPUTES THE JOINT DATA RECOVERY RATE AS REQUIRED BY REGULATORY GUIDE 1.23. FOR BOTH THE JOINT FREQUENCY DISTRIBUTION AND DATA RECOVERY CALCULATIONS BOTH THE PRIMARY AND BACKUP SENSORS SPECIFIED IN TABLE I3.1-1 OF THE LGS OFFSITE DOSE CALCULATION MANUAL ARE USED.
THE PRIMARY AND BACK UP SENSORS USED IN THE ATTACHED DISTRIBUTIONS ARE AS FOLLOWS:
PARAMETER TOWER 1 TOWER 2 (PRIMARY) (BACKUP)
WIND SPEED LEVEL 1 30 FT. OR 159 FT.
LEVEL 2 175 FT. OR 304 FT.
WIND DIRECTION LEVEL 1 30 FT. OR 159 FT.
LEVEL 2 175 FT. OR 304 FT.
DELTA TEMPERATURE LEVELS 1 & 2 266-26 FT. OR 300-26 FT.
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 LAPSE RATE: LE -1.9 DEG C/1OOM DELTA T: (266-26FT)
CLASS A WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7. 6-12. 5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENiT N 0 0.0 0 0.0 3 0.0 5 0.1 1 0.0 0 0.0 0 NNE 0 0.0 0 0.0 0.0 9 0.1 0 0.0 0 0.0 0 0.0 0 NE 0 0.0 0 0.0 0 0.0 0 0.0 0.0 0 0.0 0 0.0 0 0.0 ENE 0 0 0.0 0 0.0 0 0.0 0.0 0 0.0 1 0.0 0 0.0 0 E 0 0.0 0 0.0 0 0.0 1 0.0 0.0 0 0.0 0 0.0 2 0.0 0 0.0 0 0.0 0 0.0 ESE 0 0.0 0 0.0 0 0.0 2 0.0 2 0.0 0 0.0 0 0.0 0 SE 0 0.0 0 0.0 0.0 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 SSE 0 0 0.0 0 0.0 0.0 0 0.0 6 0.1 0 0.0 0 0.0 S 0 0 0.0 0 0.0 6 0.1 0.0 0 0.0 9 0.1 3 0.0 0 0.0 SSW 0 0 0.0 0 0.0 12 0.1 0.0 0 0.0 13 0.1 15 0.2 0 SW 0 0.0 0 0.0 0 0.0 28 0.3 0.0 0 0.0 15 0.2 7 0.1 0 0.0 WSW 0 0 0.0 0 0.0 22 0.3 0.0 0 0.0 6 0.1 2 0.0 5 0.1 W 0 0 0.0 0 0.0 13 0.1 0.0 0 0.0 21 0.2 7 0.1 0 WNW 0.0 0 0.0 0 0.0 28 0.3 0 0.0 0 0.0 3 0.0 3 0.0 0 0.0 6 0.1 0 0.0 NW 0 0.0 0 0.0 2 0.0 12 0.1 1 0.0 1 0.0 1 0.0 NNW 0 0.0 0 0.0 5 0.1 0 0.0 0 0.0 1 0.0 3 0.0 0 0.0 0 0.0 4 0.0 0 0.0 0 0.0 79 0.9 48 0.5 10 0.1 7 0.1 0 0.0 144 1.6 MEAN WIND SPEED: 8.2 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 LAPSE RATE: -1.8 TO -1.7 DEG C/1OOM DELTA T: (266-26FT) CLASS B WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12. 6-18 .5 18. 6-24 .5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 1 0.0 5 0.1 5 0.1 0 0.0 0 0.0 0 0.0 11 0.1 NUE 0 0.0 0 0.0 5 0.1 0 0.0 0 0.0 0 0.0 0 0.0 5 0.1 NE 0 0.0 1 0.0 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 3 0.0 ENE 0 0.0 0 0.0 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 2 0.0 E 0 0.0 0 0.0 0 0.0 3 0.0 1 0.0 0 0.0 0 0.0 4 0.0 ESE 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 SE 0 0.0 0 0.0 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 2 0.0 SSE 0 0.0 0 0.0 1 0.0 0 0.0 0 0.0 0 0.0 1 0 0.0 0.0 S 0 0.0 0 0.0 3 0.0 2 0.0 0 0.0 0 0.0 0 0.0 5 0.1 SSW 0 0.0 0 0.0 11 0.1 3 0.0 1 0.0 0 0.0 0 0.0 15 0.2 SW 0 0.0 0 0.0 20 0.2 4 0.0 0 0.0 0 0.0 0 0.0 24 0.3 WSW 0 0.0 1 0.0 18 0.2 7 0.1 2 0.0 0 0.0 0 0.0 28 0.3 W 0 0.0 2 0.0 19 0.2 5 0.1 2 0.0 0 0.0 0 0.0 28 0.3 WNW 0 0.0 0 0.0 9 0.1 7 0.1 17 0.2 3 0.0 0 0.0 36 0.4 NW 0 0.0 0 0.0 13 0.1 14 0.2 10 0.1 7 0.1 0 0.0 44 0.5 NNW 0 0.0 0 0.0 3 0.0 18 0.2 2 0.0 0 0.0 0 0.0 23 0.3 0 0.0 5 0.1 113 1.3 68 0.8 35 0.4 10 0.1 0 0.0 231 2.6 MEAN WIND SPEED: 8.8 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 LAPSE RATE: -1.6 TO -1.5 DELTA T: (266-26FT) DEG C/1OOM CLASS C WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12. 6-18. 5 18.6-24.5 GE 24. 6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 0 0.0 10 0.1 9 0.1 0 0.0 0 0.0 NNE 0 0.0 0 0.0 5 0 0.0 19 0.2 0.1 3 0.0 0 0.0 0 NE 0 0.0 2 0.0 0.0 0 0.0 8 0.1 5 0.1 0 0.0 0 0.0 ENE 0 0.0 0 0.0 0 0.0 7 0.1 0 0.0 8 0.1 4 0.0 E 0 0 0.0 0 0.0 0 0.0 12 0.0 3 0.0 3 0.0 3 0.0 0.1 ESE 0 0.0 0 0.0 0 0.0 0 0.0 1 0.0 3 0.0 4 9 0.1 0.0 3 0.0 0 0.0 0 SE 0 0.0 1 0.0 1 0.0 0.0 11 0.1 1 0.0 0 0.0 0 SSE 0 0.0 4 0.0 0.0 0 0.0 3 0.0 1 0.0 2 0.0 0 0.0 0 S 0 0.0 1 0.0 0 0.0 7 0.1 0.0 5 0.1 10 0.1 1 0.0 SSW 0 0.0 0 0 0.0 0 0.0 17 0.2 0.0 29 0.3 12 0.1 0 0.0 SW 0 0.0 0 0.0 0 0.0 41 0.5 5 0.1 41 0.5 9 0.1 0 WSW 0 0.0 0 0.0 0 0.0 55 0.0 4 0.0 32 0.4 14 0.2 0.6 2 0.0 0 0.0 0 0.0 W 0 0.0 6 0.1 25 0.3 20 52 0.6 0.2 3 0.0 0 0.0 0 0.0 WNW 0 0.0 0 0.0 22 0.3 54 0.6 23 0.3 18 0.2 5 0.1 0 NW 0 0.0 0 0.0 23 0.3 0.0 68 0.8 43 0.5 19 0.2 4 0.0 0 NNW 0 0.0 0 0.0 10 0.0 89 1.0 0.1 28 0.3 4 0.0 1 0.0 0 0.0 43 0.5 0 0.0 27 0.3 223 2.5 185 2.1 50 0.6 10 0.1 0.0 495 5.7 MEAN WIND SPEED: 8.2 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 LAPSE RATE: -1.4 TO -0.5 DEG C/1OOM DELTA T: (266-26FT) CLASS D WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 44 0.5 122 1.4 49 0.6 2 0.0 0 0.0 0 0.0 217 2.5 NNE 0 0.0 48 0.5 76 0.9 15 0.2 0 0.0 0 0.0 0 0.0 139 1.6 NE 0 0.0 49 0.6 119 1.4 30 0.3 1 0.0 0 0.0 0 0.0 199 2.3 ENE 0 0.0 58 0.7 201 2.3 31 0.4 0 0.0 0 0.0 0 0.0 290 3.3 E 0 0.0 37 0.4 100 1.1 87 1.0 7 0.1 0 0.0 0 0.0 231 2.6 ESE 0 0.0 27 0.3 53 0.6 41 0.5 0 0.0 0 0.0 0 0.0 121 1.4 SE 0 0.0 26 0.3 46 0.5 23 0.3 0 0.0 0 0.0 0 0.0 95 1.1 SSE 0 0.0 19 0.2 95 1.1 46 0.5 4 0.0 2 0.0 0 0.0 166 1.9 S 0 0.0 45 0.5 97 1.1 75 0.9 14 0.2 1 0.0 0 0.0 232 2.6 SSW 0 0.0 49 0.6 122 1.4 61 0.7 10 0.1 0 0.0 0 0.0 242 2.8 SW 0 0.0 70 0.8 105 1.2 32 0.4 1 0.0 0 0.0 0 0.0 208 2.4 WSW 0 0.0 40 0.5 135 1.5 28 0.3 3 0.0 0 0.0 0 0.0 206 2.4 W 0 0.0 62 0.7 127 1.5 123 1.4 36 0.4 1 0.0 0 0.0 349 4.0 WNW 0 0.0 66 0.8 233 2.7 235 2.7 110 1.3 16 0.2 1 0.0 661 7.5 NW 0 0.0 51 0.6 184 2.1 259 3.0 146 1.7 26 0.3 0 0.0 666 7.6 NNW 0 0.0 44 0.5 103 1.2 94 1.1 26 0.3 1 0.0 0 0.0 268 3.1 0 0.0 735 8.4 1918 21.9 1229 14.0 360 4.1 47 0.5 1 0.0 4290 49.0 MEAN WIND SPEED: 7.1 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 LAPSE RATE: -0.4 TO 1.5 DEG C/1OOM DELTA T: (266-26FT)
CLASS E WIND SPEED GROUPS (MPH) 0 0-0.5 0 6-3.5 3.6-7.5 7. 6-12.5 12. 6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 1 0.0 49 0.6 29 0.3 2 0.0 0 0.0 0 0.0 0 0.0 81 0.9 NNE 0 0.0 45 0.5 20 0.2 2 0.0 0 0.0 0 0.0 0 0.0 67 NE 0 0.0 34 0.4 16 0.8 0.2 2 0.0 0 0.0 0 0.0 ENE 0 0 0.0 52 0.6 0.0 43 0.5 19 0.2 1 0.0 0 0.0 0 0.0 0 0.0 63 0.7 E 1 0.0 42 0.5 27 0.3 8 0.1 0 0.0 0 0.0 0 0.0 78 0.9 ESE 0 0.0 32 0.4 18 0.2 0 0.0 1 0.0 0 0.0 0 0.0 51 0.6 SE 0 0.0 28 0.3 25 0.3 3 0.0 0 0.0 0 0.0 0 0.0 56 0.6 SSE 1 0.0 41 0.5 54 0.6 23 0.3 0 0.0 0 0.0 0 0.0 119 1.4 S 0 0.0 39 0.4 94 1.1 25 0.3 2 0.0 0 0.0 0 0.0 160 SSW 0 0.0 82 0.9 68 1.8 0.8 11 0.1 0 0.0 0 0.0 SW 0 0.0 161 1.8 1 0.0 103 1.2 69 0.8 3 0.0 0 0.0 0 0.0 0 0.0 176 2.0 WSW 0 0.0 101 1.2 57 0.7 0 0.0 0 0.0 0 0.0 0 0.0 158 W 0 0.0 130 1.5 1.8 78 0.9 5 0.1 1 0.0 0 0.0 WNW 0 0.0 214 2.4 0 0.0 128 1.5 131 1.5 21 0.2 2 0.0 0 0.0 0 0.0 282 3.2 NW 0 0.0 63 0.7 80 0.9 19 0.2 1 0.0 0 0.0 0 0.0 163 1.9 NNW 1 0.0 48 0.5 40 0.5 5 0.1 0 0.0 0 0.0 0 0.0 94 1.1 5 0.1 1008 11.5 825 9.4 130 1.5 7 0.1 0 0.0 0 0.0 1975 22.6 MEAN WIND SPEED: 3.9 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 LAPSE RATE: 1.6 TO 4.0 DEG C/1OOM DELTA T: (266-26FT) CLASS F WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7. 6-12 .5 12. 6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 4 0.0 30 0.3 6 0.1 0 0.0 0 - 0.0 0 0.0 0 0.0 40 0.5 NNE 0 0.0 33 0.4 5 0.1 0 0.0 0 0.0 0 0.0 0 0.0 38 0.4 NE 1 0.0 32 0.4 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 33 0.4 ENE 1 0.0 45 0.5 4 0.0 0 0.0 0 0.0 0 0.0 0 0.0 50 0.6 E 0 0.0 29 0.3 6 0.1 0 0.0 0 0.0 0 0.0 0 0.0 35 0.4 ESE 0 0.0 16 0.2 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 18 0.2 SE 0 0.0 15 0.2 10 0.1 0 0.0 0 0.0 0 0.0 0 0.0 25 0.3 SSE 0 0.0 15 0.2 13 0.1 1 0.0 0 0.0 0 0.0 0 0.0 29 0.3 S 0 0.0 21 0.2 23 0.3 0 0.0 0 0.0 0 0.0 0 0.0 44 0.5 SSW 1 0.0 31 0.4 15 0.2 0 0.0 0 0.0 0 0.0 0 0.0 47 0.5 SW 1 0.0 42 0.5 14 0.2 1 0.0 0 0.0 0 0.0 0 0.0 58 0.7 WSW 1 0.0 67 0.8 14 0.2 0 0.0 0 0.0 0 0.0 0 0.0 82 0.9 W 3 0.0 118 1.3 17 0.2 0 0.0 0 0.0 0 0.0 0 0.0 138 1.6 WNW 3 0.0 148 1.7 22 0.3 1 0.0 0 0.0 0 0.0 0 0.0 174 2.0 NW 1 0.0 93 1.1 9 0.1 3 0.0 0 0.0 0 0.0 0 0.0 106 1.2 NNW 2 0.0 53 0.6 6 0.1 0 0.0 0 0.0 0 0.0 0 0.0 61 0.7 18 0.2 788 9.0 166 1.9 6 0.1 0 0.0 0 0.0 0 0.0 978 11.2 MEAN WIND SPEED: 2.4 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 LAPSE RATE: GT 4.0 DEG C/1OOM DELTA T: (266-26FT)
CLASS G WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7. 6-12. 5 12. 6-18. 5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 34 0.4 1 0.0 0 0.0 0 0.0 0 0.0 0 0.0 35 0.4 NNE 1 0.0 23 0.3 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 26 0.3 NE 0 0.0 20 0.2 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 20 0.2 ENE 0 0.0 22 0.3 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 24 0.3 E 0 0.0 15 0.2 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 15 0.2 ESE 0 0.0 15 0.2 5 0.1 0 0.0 0 0.0 0 0.0 0 0.0 20 0.2 SE 0 0.0 19 0.2 5 0.1 0 0.0 0 0.0 0 0.0 0 0.0 24 0.3 SSE 0 0.0 13 0.1 15 0.2 0 0.0 0 0.0 0 0.0 0 0.0 28 0.3 S 0 0.0 14 0.2 15 0.2 0 0.0 0 0.0 0 0.0 0 0.0 29 0.3 SSW 0 0.0 16 0.2 18 0.2 0 0.0 0 0.0 0 0.0 0 0.0 34 0.4 SW 0 0.0 26 0.3 5 0.1 0 0.0 0 0.0 0 0.0 0 0.0 31 0.4 WSW 0 0.0 37 0.4 3 0.0 0 0.0 0 0.0 0 0.0 0 0.0 40 0.5 W 1 0.0 56 0.6 4 0.0 0 0.0 0 0.0 0 0.0 0 0.0 61 0.7 WNW 2 0.0 88 1.0 18 0.2 1 0.0 0 0.0 0 0.0 0 0.0 109 1.2 NW 4 0.0 70 0.8 14 0.2 0 0.0 0 0.0 0 0.0 0 0.0 88 1.0 NNW 2 0.0 54 0.6 3 0.0 0 0.0 0 0.0 0 0.0 0 0.0 59 0.7 10 0.1 522 6.0 110 1.3 1 0.0 0 0.0 0 0.0 0 0.0 643 7.3 MEAN WIND SPEED: 2.3 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 DELTA T: (266-26FT) ALL STABILITY CLASSES WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PEPCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 5 0.1 158 1.8 176 2.0 70 0.8 3 0.0 0 0.0 0 0.0 412 4.7 NNE 1 0.0 149 1.7 113 1.3 20 0.2 0 0.0 0 0.0 0 0.0 283 3.2 NE 1 0.0 138 1.6 142 1.6 32 0.4 1 0.0 0 0.0 0 0.0 314 3.6 ENE 1 0.0 168 1.9 237 2.7 36 0.4 0 0.0 0 0.0 0 0.0 442 5.0 E 1 0.0 126 1.4 136 1.6 103 1.2 8 0.1 0 0.0 0 0.0 374 4.3 ESE 0 0.0 91 1.0 81 0.9 47 0.5 4 0.0 0 0.0 0 0.0 223 2.5 SE 0 0.0 89 1.0 89 1.0 27 0.3 0 0.0 0 0.0 0 0.0 205 2.3 SSE 1 0.0 92 1.1 185 2.1 72 0.8 4 0.0 2 0.0 0 0.0 356 4.1 S 0 0.0 120 1.4 246 2.8 115 1.3 17 0.2 1 0.0 0 0.0 499 5.7 SSW 1 0.0 178 2.0 276 3.2 102 1.2 11 0.1 0 0.0 0 0.0 568 6.5 SW 2 0.0 246 2.8 269 3.1 56 0.6 1 0.0 0 0.0 0 0.0 574 6.6 WSW 1 0.0 250 2.9 265 3.0 51 0.6 12 0.1 0 0.0 0 0.0 579 6.6 W 4 0.0 374 4.3 291 3.3 160 1.8 42 0.5 1 0.0 0 0.0 872 10.0 WNW 5 0.1 430 4.9 438 5.0 291 3.3 147 1.7 30 0.3 1 0.0 1342 15.3 NW 5 0.1 277 3.2 325 3.7 339 3.9 177 2.0 38 0.4 0 0.0 1161 13.3 NNW 5 0.1 199 2.3 165 1.9 146 1.7 35 0.4 2 0.0 0 0.0 552 6.3 33 0.4 3085 35.2 3434 39.2 1667 19.0 462 5.3 74 0.8 1 0.0 8756 100.0 MISSING HOURS: 4 MEAN WIND SPEED: 5.6
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 1 DELTA T: (266-26FT)
DIRECTION VS SPEED ONLY WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 5 0.1 158 1.8 176 2.0 70 0.8 3 0.0 0 0.0 0 NNE 1 0.0 150 1.7 0.0 412 4.7 113 1.3 20 0.2 0 0.0 NE 0 0.0 0 0.0 284 3.2 1 0.0 138 1.6 142 1.6 32 0.4 1 0.0 0 0.0 0 0.0 ENE 1 0.0 168 1.9 237 2.7 314 3.6 36 0.4 0 0.0 0 0.0 E 1 0.0 0 0.0 442 5.0 126 1.4 136 1.6 103 1.2 8 0.1 ESE 0 0 0.0 0 0.0 374 4.3 0.0 91 1.0 81 0.9 47 0.5 4 0.0 0 0.0 0 0.0 223 SE 0 0.0 89 1.0 89 1.0 27 2.5 0.3 0 0.0 0 0.0 0 SSE 1 0.0 92 0.0 205 2.3 1.1 185 2.1 72 0.8 4 0.0 S 0 2 0.0 0 0.0 356 4.1 0.0 120 1.4 246 2.8 115 1.3 17 0.2 1 0.0 0 0.0 499 SSW 1 0.0 178 2.0 276 3.2 102 5.7 1.2 11 0.1 0 0.0 0 SW 2 0.0 246 0.0 568 6.5 2.8 269 3.1 56 0.6 1 0.0 WSW 1 0 0.0 0 0.0 574 6.6 0.0 250 2.9 265 3.0 51 0.6 12 0.1 0 0.0 0 0.0 579 W 4 0.0 374 4.3 291 3.3 6.6 160 1.8 42 0.5 1 0.0 WNW 5 0.1 0 0.0 872 10.0 430 4.9 438 5.0 291 3.3 147 1.7 NW 5 30 0.3 1 0.0 1342 15.3 0.1 277 3.2 325 3.7 339 3.9 177 2.0 38 0.4 0 0.0 1161 NNW 5 0.1 199 2.3 165 1.9 13.3 146 1.7 35 0.4 2 0.0 0 0.0 552 6.3 33 0.4 3086 35.2 3434 39.2 1667 19.0 462 5.3 74 0.8 0.0 8757 100.0 MISSING HOURS: 3 MEAN WIND SPEED: 5.6
LIMERICK MET DATA 1/02-12/02 LIMERICK GENERATING STATION DATA RECOVERY
SUMMARY
LEVEL 1 - TOWER 1 30' OR TOWER 2 159' PARAMETER COUNT PERCENT PRIMARY SPEED GOOD HOURS 8283 94.55%
BACKUP SPEED GOOD HOURS 8147 93.00%
BACKUP SPEED HOURS USED 474 5.41%
TOTAL AVAILABLE SPEED HOURS 8757 99.97%
PRIMARY DIRECTION GOOD HOURS 8312 94.89%
BACKUP DIRECTION GOOD HOURS 8147 93.00%
BACKUP DIRECTION HOURS USED 445 5.08%
TOTAL AVAILABLE DIRECTION HOURS 8757 99.97%
PRIMARY (266-26') DELTA TEMP HOURS 5274 60.21%
BACKUP (300-26') DELTA TEMP HOURS 8142 92.95%
BACKUP DELTA TEMP HOURS USED 3482 39.75%
TOTAL AVAILABLE DELTA TEMP HOURS 8756 99.95%
LEVEL 1 JOINT DATA RECOVERY: 8756 99.95%
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 LAPSE RATE: LE -1.9 DEG C/1OOM DELTA T: (266-26FT)
CLASS A WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7. 6-12.5 12. 6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 0 0.0 0 0.0 6 0.1 2 0.0 1 0.0 0 0.0 9 0.1 NNE 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 NE 0 0.0 0 0.0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 ENE 0 0.0 0.0 0 0.0 0 0.0 0 0.0 1 0.0 0 0.0 0 0.0 0 0.0 1 0.0 E 0 0.0 0 0.0 0 0.0 1 0.0 0 0.0 0 0.0 0 0.0 1 ESE 0 0.0 0 0.0 0.0 0 0.0 3 0.0 0 0.0 0 0.0 SE 0 0.0 0 0.0 3 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 SSE 0 0.0 0 0.0 2 0.0 4 0.0 0 0.0 0 0.0 0 0.0 6 0.1 S 0 0.0 0 0.0 2 0.0 6 0.1 2 0.0 0 0.0 0 0.0 10 0.1 SSW 0 0.0 0 0.0 4 0.0 14 0.2 12 0.1 1 0.0 0 0.0 31 0.4 SW 0 0.0 0 0.0 5 0.1 11 0.1 6 0.1 1 0.0 1 0.0 24 0.3 WSW 0 0.0 0 0.0 2 0.0 9 0.1 3 0.0 3 0.0 0 W 0 0.0 0 0.0 17 0.2 0.0 1 0.0 17 0.2 8 0.1 0 0.0 1 WNW 0 0.0 0 0.0 27 0.3 0.0 0 0.0 0 0.0 1 0.0 1 0.0 5 NW 0 0.0 0.1 7 0.1 0 0.0 0 0.0 2 0.0 1 0.0 0 0.0 0 0.0 3 0.0 NNW 0 0.0 0 0.0 0 0.0 1 0.0 2 0.0 2 0.0 0 0.0 5 0.1 0 0.0 0 0.0 16 0.2 75 0.9 37 0.4 9 0.1 0.1 144 1.6 MEAN WIND SPEED: 12.4 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 LAPSE RATE: -1.8 TO -1.7 DEG C/1OOM DELTA T: (266-26FT) CLASS B WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 1 0.0 2 0.0 9 0.1 3 0.0 0 0.0 0 0.0 15 0.2 NNE 0 0.0 0 0.0 6 0.1 1 0.0 0 0.0 0 0.0 0 0.0 7 0.1 NE 0 0.0 0 0.0 1 0.0 0 0.0 0 0.0 0 0.0 0 0.0 1 0.0 ENE 0 0.0 0 0.0 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 2 0.0 E 0 0.0 0 0.0 0 0.0 2 0.0 1 0.0 1 0.0 0 0.0 4 0.0 ESE 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 0 0.0 SE 0 0.0 0 0.0 1 0.0 1 0.0 0 0.0 0 0.0 0 0.0 2 0.0 SSE 0 0.0 0 0.0 0 0.0 1 0.0 0 0.0 0 0.0 0 0.0 1 0.0 S 0 0.0 0 0.0 0 0.0 4 0.0 2 0.0 0 0.0 0 0.0 6 0.1 SSW 0 0.0 0 0.0 4 0.0 8 0.1 3 0.0 1 0.0 0 0.0 16 0.2 SW 0 0.0 0 0.0 9 0.1 12 0.1 7 0.1 1 0.0 0 0.0 29 0.3 WSW 0 0.0 0 0.0 4 0.0 14 0.2 4 0.0 2 0.0 1 0.0 25 0.3 W 0 0.0 0 0.0 6 0.1 13 0.1 6 0.1 5 0.1 5 0.1 35 0.4 WNW 0 0.0 0 0.0 2 0.0 8 0.1 8 0.1 9 0.1 3 0.0 30 0.3 NW 0 0.0 0 0.0 2 0.0 13 0.1 10 0.1 6 0.1 5 0.1 36 0.4 NNW 0 0.0 0 0.0 2 0.0 12 0.1 6 0.1 2 0.0 0 0.0 22 0.3 0 0.0 1 0.0 41 0.5 98 1.1 50 0.6 27 0.3 14 0.2 231 2.6 MEAN WIND SPEED: 12.7 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 LAPSE RATE: -1.6 TO -1.5 DEG C/IOOM DELTA T: (266-26FT)
CLASS C WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3. 6-7.5 7. 6-12.5 12. 6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 0 0.0 6 0.1 16 0.2 3 0.0 0 0.0 0 0.0 25 NNE 0 0.0 0 0.0 4 0.0 0.3 3 0.0 1 0.0 0 0.0 0 0.0 NE 0 0.0 1 0.0 5 0.1 8 0.1 1 0.0 0 0.0 0 0.0 0 0.0 ENE 0 0.0 1 0.0 5 0.1 7 0.1 6 0.1 1 0.0 0 0.0 0 0.0 E 0 0.0 0 0.0 5 0.1 13 0.1 3 0.0 1 0 0 0 0.0 0 0.0 ESE 0 0.0 0 0.0 1 0.0 9 0.1 1 0.0 7 0.1 0 0.0 0 0.0 SE 0 0.0 0 0.0 1 0.0 9 0.1 1 0.0 1 0.0 0 0.0 SSE 0 0.0 0 0.0 3 0.0 0 0.0 0 0.0 3 0.0 0 0.0 S 0 0.0 0 0.0 0 0.0 3 0.0 1 0.0 7 0.1 6 0.1 12 0.1 SSW 0 0 0.0 0 0.0 26 0.3 0.0 1 0.0 10 0.1 21 0.2 9 0.1 1 0.0 0 0.0 42 0.5 SW 0 0.0 0 0.0 15 0.2 28 0.3 11 0.1 1 0.0 2 0.0 57 0.7 WSW 0 0.0 3 0.0 9 0.1 24 0.3 9 0.1 4 0.0 0 0.0 W 0 0.0 3 0.0 14 0.2 49 0.6 14 0.2 24 0.3 8 0.1 3 0.0 WNW 0 0.0 0 0.0 9 66 0.8 0.1 25 0.3 24 0.3 15 0.2 5 NW 0 0.0 0 0.1 78 0.9 0.0 1 0.0 25 0.3 24 0 3 6 NNW 0 0.1 4 0.0 60 0.7 0.0 0 0.0 3 0.0 15 0.2 18 0.2 3 0.0 1 0.0 40 0.5 0 0.0 10 0.1 95 1.1 192 2.2 145 1.7 38 0.4 15 0.2 495 5.7 MEAN WIND SPEED: 11.9 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 LAPSE RATE: -1.4 TO -0.5 DEG C/1OOM DELTA T: (266-26FT) CLASS D WIND SPEED GROUPS (MPH) 0.0-0 .5 0.6-3.5 3.6-7.5 7.6-12.5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 29 0.3 70 0.8 106 1.2 29 0.3 1 0.0 0 0.0 235 2.7 NNE 0 0.0 20 0.2 57 0.7 64 0.7 14 0.2 2 0.0 0 0.0 157 1.8 NE 0 0.0 22 0.3 68 0.8 109 1.2 20 0.2 0 0.0 1 0.0 220 2.5 ENE 0 0.0 15 0.2 122 1.4 121 1.4 6 0.1 0 0.0 0 0.0 264 3.0 E 0 0.0 13 0.1 63 0.7 102 1.2 49 0.6 3 0.0 0 0.0 230 2.6 ESE 0 0.0 11 0.1 32 0.4 51 0.6 24 0.3 1 0.0 0 0.0 119 1.4 SE 0 0.0 6 0.1 43 0.5 42 0.5 21 0.2 0 0.0 0 0.0 112 1.3 SSE 0 0.0 6 0.1 50 0.6 72 0.8 34 0.4 6 0.1 0 0.0 168 1.9 s 0 0.0 19 0.2 66 0.8 114 1.3 56 0.6 10 0.1 2 0.0 267 3.0 SSW 0 0.0 20 0.2 63 0.7 110 1.3 72 0.8 12 0.1 1 0.0 278 3.2 SW 0 0.0 20 0.2 83 0.9 75 0.9 30 0.3 7 0.1 1 0.0 216 2.5 WSW 0 0.0 10 0.1 37 0.4 94 1.1 46 0.5 4 0.0 0 0.0 191 2.2 W 0 0.0 19 0.2 66 0.8 120 1.4 120 1.4 59 0.7 13 0.1 397 4.5 WNW 0 0.0 14 0.2 96 1.1 235 2.7 228 2.6 108 1.2 30 0.3 711 8.1 NW 0 0.0 24 0.3 49 0.6 131 1.5 172 - 2.0 67 0.8 25 0.3 468 5.3 NNW 0 0.0 19 0.2 60 0.7 92 1.1 77 0.9 9 0.1 0 0.0 257 2.9 0 0.0 267 3.0 1025 11.7 1638 18.7 998 11.4 289 3.3 73 0.8 4290 49.0 MEAN WIND SPEED: 10.7 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 LAPSE RATE: -0.4 TO 1.5 DEG C/1OOM DELTA T: (266-26FT)
CLASS E WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7. 6-12.5 12. 6-18. 5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 9 0.1 24 0.3 36 0.4 1 0.0 0 0.0 0 NNE 0 0.0 11 0.1 25 0.3 0.0 70 0.8 14 0.2 3 0.0 0 0.0 NE 0 0.0 14 0.2 23 0 0.0 53 0.6 0.3 16 0.2 1 0.0 ENE 0 0.0 17 0 0.0 0 0.0 54 0.6 0.2 21 0.2 12 0.1 0 0.0 E 0 0.0 0 0.0 0 0.0 50 0.6 19 0.2 27 0.3 14 0.2 5 0.1 ESE 0 0.0 8 0 0.0 0 0.0 65 0.7 0.1 24 0.3 16 0.2 4 0.0 SE 0 0.0 12 1 0.0 0 0.0 53 0.6 0.1 25 0.3 14 0.2 2 0.0 SSE 0 0.0 11 0 0.0 0 0.0 53 0.6 0.1 30 0.3 40 0.5 21 0.2 S 0 0.0 6 0 0.0 0 0.0 102 1.2 0.1 67 0.8 96 1.1 29 0.3 SSW 0 0.0 11 0 0.0 0 0.0 198 2.3 0.1 87 1.0 89 1.0 25 0.3 SW 0 0.0 13 2 0.0 0 0.0 214 2.4 0.1 87 1.0 70 0.8 11 0.1 WSW 0 0.0 8 0 0.0 0 0.0 181 2.1 0.1 50 0.6 74 0.8 12 0.1 W 0 0.0 8 0 0.0 0 0.0 144 1.6 0.1 65 0.7 93 1.1 18 0.2 WNW 0 0.0 14 0 0.0 0 0.0 184 2.1 0.2 93 1.1 151 1.7 38 0.4 NW 0 0.0 23 2 0.0 0 0.0 298 3.4 0.3 41 0.5 64 0.7 12 0.1 NNW 0 0.0 8 0 0.0 0 0.0 140 1.6 0.1 44 0.5 57 0.7 7 0.1 0 0.0 0 0.0 116 1.3 0 0.0 192 2.2 733 8.4 856 9.8 189 2.2 5 0.1 0 0.0 1975 22.6 MEAN WIND SPEED: 8.0 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 LAPSE RATE: 1.6 TO 4.0 DEG C/1OOM DELTA T: (266-26FT)
CLASS F WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12. 6-18.5 18. 6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 22 0.3 22 0.3 14 0.2 0 0.0 0 0.0 0 0.0 0.7 NNE 0 0.0 8 0.1 8 0.1 4 0.0 1 0.0 58 0 0.0 0 0.0 21 0.2 NE 0 0.0 13 0.1 9 0.1 0 0.0 0 0.0 0 0.0 0 0.0 0.3 ENE 0 0.0 9 0.1 13 0.1 1 0.0 0 22 0.0 0 0.0 0 0.0 0.3 E 0 0.0 13 0.1 5 0.1 6 0.1 0 0.0 23 0 0.0 0 0.0 0.3 ESE 0 0.0 3 0.0 11 0.1 3 0.0 0 0.0 0 24 0.0 0 0.0 0.2 SE 0 0.0 10 0.1 12 0.1 1 0.0 0 0.0 0 17 0.0 0 0.0 0.3 SSE 0 0.0 14 0.2 11 0.1 8 0.1 1 0.0 23 0 0.0 0 0.0 34 0.4 S 0 0.0 6 0.1 27 0.3 20 0.2 3 0.0 0 0.0 0 0.0 56 0.6 SSW 0 0.0 20 0.2 34 0.4 30 0.3 4 0.0 0 0.0 0 0.0 88 1.0 SW 0 0.0 9 0.1 33 0.4 14 0.2 1 1 0.0 0.0 0 0.0 58 0.7 WSW 0 0.0 11 0.1 37 0.4 30 0.3 5 0.1 0 0.0 0 0.0 83 0.9 W 0 0.0 17 0.2 52 0.6 27 0.3 0 1 0.0 0.0 0 0.0 97 1.1 WNW 0 0.0 22 0.3 102 1.2 80 0.9 8 0.1 0 0.0 0 0.0 212 2.4 NW 0 0.0 13 0.1 57 0.7 19 0.2 2 0.0 0 0.0 0 0.0 91 1.0 NNW 0 0.0 8 0.1 52 0.6 11 0.1 0 0.0 0 0.0 0 0.0 71 0.8 0 0.0 198 2.3 485 5.5 268 3.1 26 0.3 1 0.0 0 0.0 978 11.2 MEAN WIND SPEED: 6.2 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 LAPSE RATE: GT 4.0 DEG C/1OOM DELTA T: (266-26FT)
CLASS G WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7. 6-12. 5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 5 0.1 7 0.1 3 0.0 0 0.0 0 0.0 0 0.0 15 0.2 NNE 0 0.0 1 0.0 5 0.1 2 0.0 1 0.0 0 0.0 0 0.0 9 0.1 NE 0 0.0 0 0.0 2 0.0 0 0.0 0 0.0 0 0.0 0 0.0 2 0.0 ENE 0 0.0 12 0.1 9 0.1 0 0.0 0 0.0 0 0.0 0 0.0 21 0.2 E 0 0.0 11 0.1 14 0.2 0 0.0 0 0.0 0 0.0 0 0.0 25 0.3 ESE 0 0.0 3 0.0 4 0.0 0 0.0 0 0.0 0 0.0 0 0.0 7 0.1 SE 0 0.0 10 0.1 4 0.0 1 0.0 0 0.0 0 0.0 0 0.0 15 0.2 SSE 0 0.0 7 0.1 8 0.1 6 0.1 0 0.0 0 0.0 0 0.0 21 0.2 S 0 0.0 5 0.1 25 0.3 12 0.1 0 0.0 0 0.0 0 0.0 42 0.5 SSW 0 0.0 7 0.1 33 0.4 36 0.4 1 0.0 0 0.0 0 0.0 77 0.9 SW 0 0.0 13 0.1 34 0.4 20 0.2 1 0.0 0 0.0 0 0.0 68 0.8 WSW 0 0.0 16 0.2 25 0.3 18 0.2 0 0.0 0 0.0 0 0.0 59 0.7 W 0 0.0 15 0.2 38 0.4 10 0.1 1 0.0 0 0.0 0 0.0 64 0.7 WNW 0 0.0 20 0.2 67 0.8 33 0.4 6 0.1 0 0.0 0 0.0 126 1.4 NW 0 0.0 18 0.2 34 0.4 12 0.1 1 0.0 0 0.0 0 0.0 65 0.7 NNW 0 0.0 5 0.1 17 0.2 4 0.0 1 0.0 0 0.0 0 0.0 27 0.3 0 0.0 148 1.7 326 3.7 157 1.8 12 0.1 0 0.0 0 0.0 643 7.3 MEAN WIND SPEED: 5.9 MISSING: 0
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 DELTA T: (266-26FT) ALL STABILITY CLASSES WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12.6-18.5 18. 6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 66 0.8 131 1.5 190 2.2 38 0.4 NNE 2 0.0 0 0.0 427 4.9 0 0.0 40 0.5 105 1.2 88 1.0 20 0.2 2 0.0 0 0.0 255 2.9 NE 0 0.0 50 0.6 108 1.2 126 1.4 21 0.2 0 0.0 1 0.0 306 3.5 ENE 0 0.0 54 0.6 172 2.0 141 1.6 7 0.1 0 0.0 0 0.0 374 4.3 E 0 0.0 56 0.6 114 1.3 128 1.5 56 0.6 4 0.0 0 0.0 358 4.1 ESE 0 0.0 25 0.3 72 0.8 74 0.8 35 0.4 2 0.0 0 0.0 208 2.4 SE 0 0.0 38 0.4 86 1.0 60 0.7 24 0.3 0 0.0 0 0.0 208 2.4 SSE 0 0.0 38 0.4 101 1.2 134 1.5 56 0.6 6 0.1 0 0.0 335 3.8 S 0 0.0 37 0.4 194 2.2 258 2.9 104 1.2 10 0.1 2 0.0 605 6.9 SSW 0 0.0 59 0.7 235 2.7 308 3.5 126 1.4 17 0.2 1 0.0 746 8.5 SW 0 0.0 55 0.6 266 3.0 230 2.6 67 0.8 11 0.1 4 0.0 633 7.2 WSW 0 0.0 48 0.5 164 1.9 263 3.0 79 0.9 13 0.1 1 0.0 568 6.5 W 0 0.0 62 0.7 242 2.8 294 3.4 178 2.0 72 0.8 22 0.3 870 9.9 WNW 0 0.0 70 0.8 369 4.2 532 6.1 313 3.6 135 1.5 43 0.5 1462 16.7 NW 0 0.0 78 0.9 184 2.1 266 3.0 222 2.5 79 0.9 34 0.4 863 9.9 NNW 0 0.0 40 0.5 178 2.0 192 2.2 111 1.3 16 0.2 1 0.0 538 6.1 0 0.0 816 9.3 2721 31.1 3284 37.5 1457 16.6 369 4.2 109 1.2 8756 100.0 MISSING HOURS:
MEAN WIND SPEED: 9.4
LIMERICK MET DATA 1/02-12/02 JOINT DISTRIBUTION OF WIND DIRECTION AND SPEED BY ATMOSPHERIC STABILITY CLASS WIND: LEVEL 2 DELTA T: (266-26FT) DIRECTION VS SPEED ONLY WIND SPEED GROUPS (MPH) 0.0-0.5 0.6-3.5 3.6-7.5 7.6-12.5 12.6-18.5 18.6-24.5 GE 24.6 SUM PERCENT DIRECTION SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT SUM PERCENT N 0 0.0 66 0.8 131 1.5 190 2.2 38 0.4 2 0.0 0 0.0 NNE 0 0.0 40 0.5 106 1.2 88 427 4.9 1.0 20 0.2 2 0.0 0 0.0 NE 0 0.0 50 0.6 108 1.2 256 2.9 126 1.4 21 0.2 0 0.0 1 ENE 0 0.0 54 0.6 0.0 306 3.5 172 2.0 141 1.6 7 0.1 0 E 0 0.0 0.0 0 0.0 374 4.3 56 0.6 114 1.3 128 1.5 56 0.6 ESE 0 4 0.0 0 0.0 358 4.1 0.0 25 0.3 72 0.8 74 0.8 35 0.4 2 0.0 0 0.0 208 SE 0 0.0 38 0.4 86 1.0 60 0.7 2.4 24 0.3 0 0.0 0 0.0 208 SSE 0 0.0 38 0.4 101 1.2 134 2.4 1.5 56 0.6 6 0.1 0 0.0 S 0 0.0 37 0.4 194 2.2 258 335 3.8 2.9 104 1.2 10 0.1 2 0.0 SSW 0 0.0 59 0.7 235 2.7 605 6.9 308 3.5 126 1.4 17 0.2 1 SW 0 0.0 55 0.0 746 8.5 0.6 266 3.0 230 2.6 67 0.8 11 WSW 0 0.0 0.1 4 0.0 633 7.2 48 0.5 164 1.9 263 3.0 79 0.9 W 0 13 0.1 1 0.0 568 6.5 0.0 62 0.7 242 2.8 294 3.4 178 2.0 72 0.8 22 0.3 870 9.9 WNW 0 0.0 70 0.8 369 4.2 532 6.1 313 3.6 135 1.5 43 0.5 1462 NW 0 0.0 78 0.9 184 2.1 16.7 266 3.0 222 2.5 79 0.9 34 0.4 NNW 0 0.0 40 0.5 863 9.9 178 2.0 192 2.2 111 1.3 16 0.2 1 0.0 538 6.1 0 0.0 816 9.3 2722 31.1 3284 37.5 1457 16.6 369 4.2 109 1.2 8757 100.0 MISSING HOURS: 3 MEAN WIND SPEED: 9.4
LIMERICK MET DATA 1/02-12/02 LIMERICK GENERATING STATION DATA RECOVERY
SUMMARY
LEVEL 2 - TOWER 1 175' OR TOWER 2 304' PARAMETER COUNT PERCENT PRIMARY SPEED GOOD HOURS 8315 94.92%
BACKUP SPEED GOOD HOURS 8147 93. 00%
BACKUP SPEED HOURS USED 442 5.05%
TOTAL AVAILABLE SPEED HOURS 8757 99. 97%
PRIMARY DIRECTION GOOD HOURS 8315 94.92%
BACKUP DIRECTION GOOD HOURS 8147 93.00%
BACKUP DIRECTION HOURS USED 442 5.05%
TOTAL AVAILABLE DIRECTION HOURS 8757 99.97%
PRIMARY (266-26') DELTA TEMP HOURS 5274 60.21%
BACKUP (300-26') DELTA TEMP HOURS 8142 92.95%
BACKUP DELTA TEMP HOURS USED 3482 39.75%
TOTAL AVAILABLE DELTA TEMP HOURS 8756 99.95%
LEVEL 2 JOINT DATA RECOVERY: 8756 99.95%