ML030290374

From kanterella
Jump to navigation Jump to search
Inservice Testing Program for Pumps & Valves - Manual Update, Sections 5.0 - 7.1
ML030290374
Person / Time
Site: Catawba  
(NPF-035, NPF-052)
Issue date: 01/21/2003
From: Gordon Peterson
Duke Power Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML030290374 (117)


Text

DUKE POWER CATAWBA NUCLEAR STATION RELIEF REQUEST Section 5.0

Relief Request 5.1 PUMP GENERIC RELIEF REQUESTS Applicability None Rev. 26 10/31/02 Page I of I Status

5.2 PUMP SPECIFIC RELIEF REQUESTS Relief Request CN-SRP-CA-01 Applicability Auxiliary Feedwater Pumps Status Revised 05/31/99 Rev. 26 10/31/02 Page 1 of 1

Catawba Units 1 and 2 Specific Relief Request Item Number:

Pump:

CN-SRP-CA-01 CA Pump IA, CA Pump 1B, CA Pump 2A, CA Pump 2B, Test Requirement:

Basis for Relief:

Oma-1988, Part 6, Section 4.6.1.2.a requires that the full scale range of the instrument shall be three times the reference value or less.

The installed process instrumentation for the CA pumps suction pressure measurement is as follows:

Local 0-160 psig (0.5% error) 0-160 psig (0.5% error)

Control Room 0-90 psig (1.12% error) 0-90 psig (1.12% error)

Test Alternative:

10/31/02 Rev. 26 The typical range of values for the suction pressure of the CA pumps during testing is 33-38 psig; therefore, the local process instrumentation on CA Pumps IA/2A and IB/2B does not meet the three times criteria.

The accuracy of the process instrumentation (0.5%) is well below the requirements specified in Oma-1988 Part 6, Table I for pressure instrumentation accuracy (2.0%).

The actual reading error at test pressure due to the process instrumentation accuracy is 2.42% (0.5%

  • 160/33). If a 0-90 psig test instrument is used (which meets the three times criteria) and it has an accuracy of 2.0%, then the reading error due to instrument accuracy would be 5.45% (2%
  • 90/33). When the requirements of Oma-1988 Part 6, Section 4.6.1.2.a and Table I are combined, the actual instrument error introduced to the test is less than the code allowable (2.42% vs. 5.45%). Using the process instrument for suction pressure data does not degrade the quality of the test, and meets the intent of the instrumentation requirements of the code.

The installed process instrumentation at both the control room and locally at the CA pumps can be used to measure CA pump suction pressure for CA Pump IA, CA Pump IB, CA Pump 2A, and CA Pump 2B tests.

CN-SRP-CA-01 Page I of 1 Section 5.2 PumD IA/2A IB/2B

Relief Request CN-GRV-01 CN-GRV-02 CN-GRV-03 CN-GRV-04 5.3 VALVE GENERIC RELIEF REQUESTS Applicability Safety/Relief Valves Tested Under Ambient Conditions (remove 10 minute hold time)

Safety/Relief Valves Tested At Other Than Ambient Conditions (reduce 10 minute hold to 5 minute hold)

Safety/Relief Valves Tested Under Ambient Conditions (Thermal Equilibrium)

Check Valve Condition Monitoring Program Status Written 05/31/99 Written 05/31/99 Written 05/31/99 Written 10/31/02 Rev. 26 10/31/02 Page 1 of I

Catawba Unit I and 2 Generic Relief Request Item Number:

Component Number (s):

Flow Diagram (s):

Function (s):

Test Requirement:

Basis for Relief:

Code Alternative:

10/31/02 Rev. 26 CN-GRV-01 All safety and relief valves tested under ambient conditions using a test medium at ambient conditions.

All applicable Provide over-pressure protection to associated systems.

OM-1, 1987 Sections 8.1.2.8 and 8.1.3.7, Time Between Valve Openings; A minimum of 10 min. shall elapse between successive openings.

This is a generic request for relief for safety and relief valves in compressible fluid service (other than steam) and liquid service applications, tested under ambient conditions using a test medium at ambient conditions.

For these valves, the requirement for verifying temperature stability (by waiting 10 min. between successive openings) is inappropriate and of no value. There is negligible affect on valve setpoint due to minor temperature deviations that might occur at these ambient conditions.

The net result of having to wait 10 minutes between successive openings is an increase in manpower and time to perform the tests and an increase in radiation exposure when located in radiation areas, without a commensurate increase in test accuracy.

Note:

This issue has been identified by the ASME Code Committees along with safety and relief valve industry experts and is reflected in a change made to the 1995 version of the code (Appendix I). In addition, NUREG -1482, 4.3.9 (6) STATES "Thermal equilibrium need not be verified for liquid service valves tested at ambient temperature using a test medium (at ambient) temperature."

For safety and relief valves tested under ambient conditions using test medium at ambient conditions, the 10 min. hold requirement between successive openings will be deleted.

CN-GRV-01 Page 1 of 1 Section 5.3

Catawba Unit 1 and 2 Generic Relief Request Item Number:

Component Number (s):

Flow Diagram (s):

Function (s):

Test Requirement:

Basis for Relief:

Code Alternative:

10/31/02 Rev. 26 CN-GRV-02 All safety and relief valves tested at other than ambient conditions.

All applicable Provide over-pressure protection to associated systems.

OM-1, 1987 Sections 8.1.1.8, 8.1.2.8 and 8.1.3.7, Time Between Valve Openings; A minimum of 10 min. shall elapse between successive openings.

This is a generic request for relief for all safety and relief valves.

The 1995 version of the code, Appendix I has adopted a 5 minute hold time for steam, compressible fluid, and water service applications rather than the 10 minute hold time. This change was based on actual test data that revealed insignificant effect on valve setpoint by reducing the hold time between successive openings to 5 minutes.

For safety and relief valves tested at other than ambient conditions, a 5 minute hold time will be used between successive valve openings.

CN-GRV-02 Page 1 of I Section 5.3

Catawba Unit 1 and 2 Generic Relief Request Item Number:

Component Number (s):

Flow Diagram (s):

Function (s):

Test Requirement:

Basis for Relief:

Code Alternative:

10/31/02 Rev. 26 CN-GRV-03 All safety and relief valves tested under ambient conditions using a test medium at ambient conditions.

All applicable Provide over-pressure protection to associated systems.

OM-1, 1987 Sections 8.1.2.4, 8.1.3.4, Temperature Stability; the temperature of the valve body shall be known and stabilized before commencing set pressure testing.

This is a generic request for relief for safety and relief valves tested under ambient conditions using a test medium at ambient conditions.

For these valves, the requirement for verifying temperature stability (by ensuring no change in measured temperature of more than 10°F in 30 minutes) is inappropriate and needlessly adds time to the test activity. Since the valves will be tested at ambient conditions, no temperature differential exists and the valves would already be considered stable per the test requirement above.

There is negligible affect on valve setpoint associated with any minor temperature deviations at these ambient conditions.

Note:

This issue has been identified by the ASME Code Committees along with safety and relief valve industry experts and is reflected in a change made to the 1995 version of the code, Appendix I, ("Verification of thermal equilibrium is not required for valves which are tested at ambient temperature using a test medium at ambient temperature").

For safety and relief valves tested under ambient conditions using test medium at ambient conditions, the Temperature Stability requirements of OM-1, 1987 Sections 8.1.2.4 and 8.1.3.4 will be replaced by the Thermal Equilibrium requirements in the 1995 edition of the code.

CN-GRV-03 Page 1 of I Section 5.3

Catawba Unit 1 and 2 Generic Relief Request Item Number:

Component Number (s):

Flow Diagram (s):

Function (s):

Test Requirement:

CN-GRV-04 All check valves in the IST Program All applicable All "active" safety functions OM-10 (OMa-1988), Sections 4.2 Category A and B valves, along Exercise Test for Check Valves.

- Inservice Test for with section 4.3.2 -

Basis for Relief:

Code Alternative:

10/31/02 Rev. 26 In NUREG 1482, Guidelines for Inservice Testing at Nuclear Power Plants, the Commission approved Owners adopting later Editions or portions thereof of the ASME Code provided those Editions or portions are approved per 10 CFR 50.55a (f)(4)(iv) and provided documentation of implementation is provided in the IST program and all conditions of Commission approval are satisfied. For this relief, the licensee is requesting to partially implement the 1995 Code Edition (ISTC, OMa-1996) to selected IST program check valves.

As an alternative to the testing or examination requirements of ISTC-35 10, ISTC-3520, ISTC-3540, and ISTC-522 1, the Owner may establish a condition monitoring program. The purpose of this program is both to improve check valve performance and to optimize testing, examination, and preventive maintenance activities in order to maintain the continued acceptable performance of a select group of check valves. The Owner may implement this program on a valve or a group of similar valves. The program shall be implemented in accordance with Appendix II, Check Valve Condition Monitoring Program.

If the condition monitoring program for a valve or valve group is discontinued, them the requirements of ISTC-5221 shall apply.

CN-GRV-04 Page I of I Section 5.3

5.4 VALVE SPECIFIC RELIEF REQUESTS Relief Request CN-SRV-FD-01 CN-SRV-VG-01 CN-SRV-VG-02 Applicability Diesel Generator Fuel Oil Regulating Valve Diesel Generator Starting Air System Diesel Generator Starting Air System Status Written 05/31/99 Written 05/31/99 Written 10/31/02 Rev. 26 10/31/02 Page 1 of I

Catawba Units 1 and 2 Specific Relief Request Item Number:

Valve:

CN-SRV-FD-01 lFD0034, IFD0074 2FD0034, 2FD0074 Flow Diagrams:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Relief:

Test Alternative:

10/31/02 Rev. 26 CN-1609-3.0, CN1609-3.1 CN-2609-3.0, CN2609-3.1 C

C Diesel Generator fuel oil regulating valve. Performs dual function of regulating fuel pressure and providing over pressure protection of the pump discharge piping.

Relief valve testing.

Dual function pressure regulating and over pressure protection valve cannot be tested per OM-I standards. The intent of relief valve testing performed per OM-I will be verified by alternate testing.

This alternate testing has been approved via Request for Relief granted by the NRC dated 12/08/98.

Diesel generator fuel oil pressure will be verified monthly during diesel generator performance test.

Affected procedures are PT/1(2)/A/4350/002A&B. This is an application of skid mounted criteria per NUREG 1482, Section 3.4.

CN-SRV-FD-01 Page 1 of 1 Section 5.4

Catawba Units 1 and 2 Specific Relief Request Item Number:

CN-SRV-VG-O1 Valve:

Flow Diagrams:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Relief:

Alternate Testing:

10/31/02 Rev. 26 IVGOOO5, IVG0006, IVGOOO7, IVG0008,1VG0049, IVG0050, IVG005I, 1VG0052 2VG0005, 2VG0006, 2VG0007, 2VG0008, 2VG0049, 2VG0050, 2VG0051, 2VG0052 CN-1609-4.0, CN-1609-4.1 CN-2609-4.0, CN-2609-4.1 C

C These valves remain closed to prevent depressurization of the Diesel Generator Engine Starting Air Tanks.

Exercise valve (full stroke) to the position required to fulfill its function and stroke every three months.

Valves are arranged in pairs (series) to prevent depressurization of the starting air tanks. System arrangement precludes independent testing of each valve.

This alternate testing has been approved via Request for Relief granted by the NRC dated 04/13/98.

Valve pairs (VG5&7, 6&8, 49&51, 50&52) will be tested at least quarterly.

Starting Air Tank pressure decrease would indicate excessive leakage and would require Corrective action upon detection.

Both valves would be inspected for degradation and repaired as appropriate.

CN-SRV-VG-01 Page 1 of I Section 5.4

Catawba Units 1 and 2 Specific Relief Request Item Number:

CN-SRV-VG-02 Valve:

Flow Diagrams:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Relief:

Alternate Testing:

10/31/02 Rev. 26 Solenoid Valves IVG0025 through IVG0028, IVG0069 through INV0072 2VG0025 through 2VG0028, 2VG0069 through 2VG0072 Check Valves IVG0029 through IVG0032, IVG0073 through 1VG0076 2VG0029 through 2VG0032, 2VG0073 through 2VG0076 CN-1609-4.0, CN-1609-4.1 CN-2609-4.0, CN-2609-4. I Solenoid Valves - B, Check Valves - C C

These valves are normally closed and open to provide starting air to the diesel engine.

Exercise each valve (full stroke) to the position required to fulfill its function and stroke every three months.

Valves are arranged in pairs (one solenoid and one check) for each two lines to each starting air bank. The diesel can start with one line from either bank. Valves do not provide indication of position, therefore a full stroke for each valve cannot be verified.

Relief was requested based on the "skid mounted" criteria and verification of acceptable starting performance from each bank.

This alternate testing has been approved via Request for Relief granted by the NRC dated 11/18/99.

Each diesel is started once monthly to prove operability. Also, during each cold shutdown, each bank of each diesel is isolated and acceptable diesel starting performance is verified. This confirms that at least one pair of valves of each bank performs acceptably and redundancy is provided.

CN-SRV-VG-02 Page 1 of 1 Section 5.4

DUKE POWER CATAWBA NUCLEAR STATION JUSTIFICATION FOR DEFERRAL Section 6.0

6.1 VALVE JUSTIFICATION FOR DEFERRALS Justification for Applicability Status Deferral CN-CA-01 CN-CA-03 CN-CA-04 CN-CA-05 CN-CA-06 CN-CF-01 CN-CF-02 CN-CF-03 CN-CF-04 CN-CF-05 CN-FW-01 CN-FW-02 CN-IA-01 CN-KC-01 CN-KC-02 CN-KC-03 CN-KD-01 CN-NB-01 CN-NC-01 CN-NC-02 CN-NC-03 CN-ND-01 CN-ND-02 CN-ND-03 CN-ND-04 CN-ND-05 CN-NF-01 CN-NI-01 CN-NI-02 CN-NI-03 CN-NI-04 CN-NI-05 CN-NI-06 CN-NI-07 CA to Steam Generator Checks CA Pump Suction Checks CA Assured M/V from RC Checks CF to CA Nozzle Isolation Valves RN to CA Checks CF Isolations CF Checks CF to CA Checks CF Control Valves CF Bypass Control Valves FWST to ND Pump Suction Checks FW to Refueling Cavity Check Personnel Air Lock Isolation Checks KC to NCDT Hx. Isolation Valves KC to NC Pump Containment Isolations KC Containment Check Diesel Generator KD Pump Discharge Check NB Containment Check NC Containment Check Reactor Coolant System PORV Reactor Vessel Head Vents NC to ND Pump A Isolations NC to ND Pump B Isolations ND Pump discharge Checks ND Cross Connect Isolations ND Pump Supply to NV and NI Pumps Isolations NF Containment Isolation Check NV to NC Injection Isolations NV to NC Injection Check NI Pump to Cold Leg Checks NI Cold Leg Checks NI to Accumulator N2 Supply Checks Cold Leg Discharge Checks FWST to NI Pumps Check Rev. 26 10/31/02 Page I of 3 Revised 10/31/02 Revised 10/31/02 Revised 10/31/02 Revised 10/31/02 Revised 10/31/02 Revised 10/31/02 Revised 10/31/02

VALVE JUSTIFICATION FOR DEFERRALS Justification for Applicability Status Deferral CN-NI-08 CN-NI-09 CN-NI-10 CN-NI-Il CN-NI-12 CN-NI-13 CN-NI-14 CN-NI-15 CN-NI-16 CN-NI-17 CN-NI-18 CN-NI-19 CN-NI-20 CN-NI-21 CN-NI-22 CN-NI-23 CN-NI-24 CN-NI-25 CN-NM-01 CN-NS-01 CN-NS-02 CN-NS-03 CN-NV-01 CN-NV-02 CN-NV-03 CN-NV-04 CN-NV-05 CN-NV-06 CN-NV-07 CN-NV-08 CN-NV-09 CN-NV-10 CN-NV-11 CN-NV-12 FWST to NI Pumps Isolation NI Pump Recirculating Isolations NI Pump Discharge Checks NI to Hot Legs Checks NI Cold Leg Isolation NI to Cold Legs Checks ND to Cold Legs Checks ND to Cold Legs Isolation NI to Hot Legs Isolation Containment Sump Recirculating Isolations ND Train A to NV Pump Suction Isolation ND Train B to NI Pump Suction Isolation ND Train B to NI Pump Suction Check NI Pump Discharge to NC Loops Isolations NI Pumps Miniflow Isolations NI Pump Suction Isolations from ND and NV FWST to NI Train A and NV Pumps CLA Discharge Isolation Valves NM to Containment Isolation FWST to NS Pump Checks NS Spray Header Checks ND to NS Spray Header Isolations NV Letdown Containment Isolation NV to NC Pump Seals Return Header Cont. Isolation NV to VCT Outlet Isolation NV Charging Line Containment Isolation NV Pump Suction to FWST Checks NV Pump to Charging Line Checks NV Pump Miniflow Isolations NV Pumps Section from ND Checks Standby M/U Pump Cont. Header Checks NV Pumps Suction from FWST NV Letdown Orifice Outlet Valves Deleted 10/31/02 Rev. 26 10/31/02 Page 2 of 3 Revised 10/31/02 Revised 10/31/02 Revised 10/31/02 6.1

VALVE JUSTIFICATION FOR DEFERRALS Justification for Applicability Status Deferral CN-NW-01 CN-NW-02 CN-RF-01 CN-RN-01 CN-RN-02 CN-RN-03 CN-SA-01 CN-SM-01 CN-VB-01 CN-VG-01 CN-VG-02 CN-VG-03 CN-VI-01 CN-VI-02 CN-VI-03 CN-VI-04 CN-VS-01 CN-VY-01 CM-WL-01 CN-YM-01 Revised 10/31/02 Revised 10/31/02 Rev. 26 10/31/02 Page 3 of 3 NW Surge Chamber from RN Checks NW Supply to Cont. Isolation Valves Check RF to Containment Isolation Valve Checks RN-Upper Containment Vent Unit Checks RN to Lower Containment Vent. Units Supply Header Cont. Isol.

RN to Lower Containment Vent. Units Return Header Cont. Isol.

Main Steam to CAPT Checks Main Steam Containment Isolations VB Containment Isolation Valves DIG Starting Air Checks DIG Starting Air Checks DIG Control Air Checks VI Containment Header Checks VI Containment Isolation Valves N2 to NC PORV Checks N2 to NC PORV Checks VS to Unit I Containment Header Checks VY Containment Isolation Valve Checks WL Containment Isolation Valves YM Containment Isolation Checks 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-CA-01 ICA0037, ICA0041, ICA0045, ICA0049, ICA0053, ICA0057, ICA0061, ICA0065 2CA0037, 2CA0041, 2CA0045, 2CA0049, 2CA0053, 2CA0057, 2CA0061, 2CA0065 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1592-1.1 CN-2592-1.1 C

2 Opens to allow Auxiliary Feedwater (CA) System supply to the steam generators. Closes to separate Feedwater from Auxiliary Feedwater.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every three months per Oma-1988 Part 10, 4.3.2.1.

Valve closure is verified continuously by temperature monitoring.

Full stroke testing these valves during power operation would unnecessarily thermal shock the steam generators and feedwater piping.

Valves will be full stroke exercised open following each cold shutdown of greater than 30 days prior to entering Mode 2.

CN-CA-01 Page I of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-CA-03 ICA0008, ICA0010, ICA0012 2CA0008, 2CAOO10, 2CA0012 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1592-1.0 CN-2592-1.0 C

3 Close to prevent diversion of flow when the system is in operation and a Nuclear Service Water (RN) to CA swapover or Condenser Circulating Water (RC) to CA swapover has occurred.

Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-CA-03 Page I of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-CA-04 ICA0173 2CA0173 CN-1592-1.0 CN-2592-1.0 C

3 Open to allow assured makeup to Auxiliary Feedwater (CA) System from the Condenser Circulating Water (RC) System on RC to CA swapover signal, and allow RC supply to the Turbine Driven CA Pump in the event requiring use of the Standby Shutdown Facility (SSF).

Close to prevent diversion of flow when the system is in operation and Nuclear Service Water (RN) to CA swapover and RC to CA swapover has occurred.

Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix Il or Condition Monitoring.

These valves are pan of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-CA-04 Page 1 of I Section 6.1

Catawba Unit 2 Justification for Deferral Item Number:

CN-CA-05 2CA0149, 2CA0150, 2CA0151, 2CA0152 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-2592-1.1 B

2 Close on Feedwater Isolation signal and Phase "A" Containment Isolation signal.

Measure Full Stroke Time/Failed to Safe Position - Quarterly Exercise valve (full stroke) to the position required to fulfill its function every three months per OMa-1988 Part 10, 4.2.1.2. Test valve for fail safe actuation every three months per OMa-1988 Part 10, 4.2.1.6.

Stroke time valve (full stroke) every three months per OMa-1988 Part 10,4.2.1.8.

The Westinghouse D-5 steam generator design requires these valves to be used for a portion of the main Feedwater flow during power operation. Closing these valves at 100% power would isolate this flow, possibly resulting in preheater damage.

These valves will be:

exercised (full stroke) during cold shutdown, tested for fail safe actuation during cold shutdown, and stroke timed tested during cold shutdown.

CN-CA-05 Page I of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-CA-06 ICA0291, ICA0292 2CA0291, 2CA0292 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1592-1.0 CN-2592-1.0 C

3 These valves are normally closed. The valves shall open on CA to RN switchover to permit RN Header A(B) flow to the Turbine Driven CA Pump Number 1(2).

Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-CA-06 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-CF-01 ICF0033, ICF0042, ICF0051, ICF0060 2CF0033, 2CF0042, 2CF0051, 2CF0060 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1591-1.1 CN-2591-1.1 B

2 Isolates main feedwater piping from the steam generators upon receipt of a feedwater isolation signal.

Measure Full Stroke Time/Failed to Safe Position - Quarterly Exercise valve (full stroke) to the position required to fulfill its function, observe fail-safe operation, and stroke time every 3 months.

Closing these valves during power operation is considered impractical from an operating viewpoint.

Closure would isolate feedwater to the steam generator which may result in a severe transient in the steam generator, possibly causing a unit trip.

Valve will be exercised (full stroke) to the position required to fulfill its function, fail-safe operation verified, and stroke timed during cold shutdown.

CN-CF-01 Page 1 of 1 Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-CF-02 Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 ICF0031, ICF0040, ICF0049, ICF0058 2CF0031, 2CF0040, 2CF0049, 2CF0058 CN-1591-1.1 CN-2591-1.1 C

2 These valves are normally open and must close to prevent blowdown of the corresponding steam generator in the event of a feedwater line rupture.

Full Stroke Closed - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-CF-02 Page I of I Section 6.1

Catawba Unit 2 Justification for Deferral Item Number:

CN-CF-03 2CF0166, 2CF0167, 2CF0168, 2CF0169 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 25 CN-2591-1.1 C

2 These valves are normally open and must close to prevent diversion of auxiliary feedwater flow to the feedwater system via the feedwater bypass line following a feedwater isolation signal.

Full Stroke Closed - Quarterly Exercise the valve to the position required to fulfill its function every three (3) months.

Closing these valves would require removing the unit from service and reducing reactor power to less than three percent.

During each refueling one of the four check valves will be disassembled, inspected and the disk mechanically exercised.

The next refueling, a different valve will be disassembled. All four valves will be tested within a four refueling time period. Should any one valve fail to stroke acceptably, the remaining three valves will also be disassembled.

CN-CF-03 Page 1 of I Section 6.1 Valve:

Catawba Units I and 2 justification for Deferral Item Number:

Valve:

CN-CF-04 lCF0028, lCF0037, lCF0046, ICF0055 2CF0028, 2CF0037, 2CF0046, 2CF0055 CN-1591-1.1 CN-2591-1.1 Flow Diagram:

Code Category:

ASME Class:

B 3

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Control valves normally modulated by the Digital Feedwater Control System (DFCS) to maintain proper steam generator water level. Automatic closure will occur upon transfer to the auxiliary shutdown panel, an inboard doghouse Hi-Hi water level, or a feedwater isolation signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function every 3 months.

Closing these valves during power operation is considered impractical from an operating viewpoint. Closure would reduce feedwater to the steam generators which may result in a severe transient in the steam generator, possibly causing a unit trip.

Valves will be exercised (full stroke) to the closed position and stroke timed during cold shutdown.

CN-CF-04 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-CF-05 ICF0030, ICF0039, 1CF0048, ICF0057 2CF0030, 2CF0039, 2CF0048, 2CF0057 Flow Diagram:

Code Category:

ASME Class:

CN-1591-1.1 CN-2591-1.1 B

ANSI B31.1 (Class F)

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Bypass control valves normally modulated by the Digital Feedwater Control System (DFCS) to maintain proper steam generator water level. Automatic closure will occur upon transfer to the auxiliary shutdown panel, an inboard doghouse Hi-Hi water level, or a feedwater isolation signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function every 3 months.

Closing these valves during power operation is considered impractical from an operating viewpoint.

Closure would reduce feedwater to the steam generators which may result in a severe transient in the steam generator, possibly causing a unit trip.

Valves will be exercised (full stroke) to the closed position and stroke timed during cold shutdown.

CN-CF-05 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral CN-FW-01 IFW0028, IFW0056 2FW0028, 2FW0056 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1571-1.0 CN-2571-1.0 C

2 Opens on flow from Refueling Water Storage Tank to suction of Residual Heat Removal Pumps.

Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-FW-01 Page I of I Section 6.1 Item Number:

Valve:

Catawba Units 1 and 2 JTustification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-FW-02 IFW0005 2FW0005 CN-1571-1.0 CN-2571-1.0 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (Full Stroke) to the position required to fulfill its function every 3 months.

System does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate testing during refueling.

CN-FW-02 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-IA-01 IIACV5340, lIACV5350, IIACV5360, IIACV5370, IIACV5380. IIACV5390 21ACV5340, 2IACV5350, 21ACV5360, 2IACV5370, 2IACV5380, 21ACV5390 CN-1499-IAI.01 CN-2499-IAI.01 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-IA-01 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-KC-O1 IKC320A, IKC332B, IKC333A 2KC320A, 2KC332B, 2KC333A CN-1573-1.3 CN-2573-1.3 Flow Diagram:

Code Category:

ASME Class:

B 2

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Isolates flow to the reactor coolant drain tank heat exchanger upon receipt of a high containment pressure signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of one of these valves in the closed position during testing would inhibit the flow path through the reactor coolant drain tank heat exchanger. This would result in boiling of the water in the reactor coolant drain tank resulting in excess heat in containment.

This increased heat load could cause unit shutdown due to exceeding Tech Spec containment temperature limits.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-KC-01 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-KC-02 IKC0338B, IKC0424B, IKC0425A 2KC0338B, 2KC0424B, 2KC0425A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1573-1.3 CN-2573-1.3 B

2 Isolates flow to the reactor vessel support coolers, reactor coolant pump motor bearing coolers, and reactor coolant pump thermal barriers, upon receipt of a high-high containment pressure signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of these valves in the closed position during testing would inhibit flow to the reactor vessel support coolers, reactor coolant pump motor bearing coolers, and reactor coolant pump thermal barriers. This action could result in unit shutdown and possible damage to the vessel and reactor coolant pumps.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-KC-02 Page 1 of 1 Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-KC-03 IKC0047, IKC0279, IKC0340 2KC0047, 2KC0279, 2KC0340 CN-1573-1.3 CN-2573-1.3 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its safety function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-KC-03 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral CN-KD-01 1KDO006, IKDO021 2KD0006, 2KD0021 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31102 Rev. 26 CN-1609-1.0 CN-2609-1.0 C

3 Opens on diesel engine start to pass cooling water flow from the diesel generator engine driven jacket water circulation pump.

Full Stroke Open/Close - Quarterly Exercise valve (full stroke) to the position required to fulfill its function every 3 months.

Valve design does not provide any indication of position.

Valves will be verified to operate during monthly Tech Specs Diesel Test (PT/iIA14350102A, B - Diesel Generator A, B Operability Test)

(PT/21A/4350/02A, B - Diesel Generator A, B Operability Test) by verifying proper cooling is supplied during diesel run.

In addition, the valves will be disassembled (as required by IE Bulletin No. 83-03) during each refueling and the mechanical integrity of the valve internals verified.

CN-KD-01 Page 1 of I Section 6.1 Item Number:

Valve:

Catawba Units I and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NB-01 INB0262 2NB0262 CN-1556-2.0 CN-1556-2.0 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every three (3) months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-NB-O1 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NC-01 INC0057 2NC0057 CN-1553-1.1 CN-2553-1.1 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-NC-O1 Page 1 of I Section 6.1

Justification for Deferral CN-NC-02 INCO032B, INCO034A, INCO036B 2NC0032B, 2NC0034A, 2NC0036B Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1553-1.1 CN-2553-1.1 B

I Reactor Coolant System PORV opens to relieve pressure for the primary system.

Measure Full Stroke Time/Failed to Safe Position - Quarterly Stroke time and observe fail-safe operation every three (3) months.

PORVS do not serve a safety function when unit is at operating temperature and pressure. PORVs protect the Reactor Coolant System from over pressurization during LTOP conditions l(2)NCO032B &

1(2)NCO034A only. Also according to NRC Branch Technical Position RSB5-2 the full stroke exercise should take place during cold shutdown vs. quarterly during power operations due to the high probability of sticking open.

Tech Spec prevents Catawba from performing the surveillance test in Modes I and 2.

Stroke time testing and fail-safe observation will be performed at cold shutdown for 1(2)NCO032B, 1(2)NCO034A, & I(2)NCO036B; and in all cases prior to entering LTOP conditions in accordance with Generic Letter 90-06 for 1(2)NCO032B & I(2)NCOO34A. Testing will not be required more often than once per quarter as defined in Oma-1988 Part 10,4.2.1.1.

CN-NC-02 Page I of I Section 6.1 Catawba Units 1 and 2

Catawba Units 1 and 2 Justification for Deferral CN-NC-03 INCO250A, INC0251B., INC0252B, INC0253A 2NC0250A, 2NC025 IB, 2NC0252B, 2NC0253A CN-1553-1.1 CN-2553-1.1 Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 B

1 Reactor vessel head vent.

Measure Full Stroke Time - Quarterly Stroke time test in accordance with Oma-1988 Part 10, 4.2.1.1.

Opening these valves at full pressure could cause damage to the valve seating surfaces. A reactor coolant leak could be caused.

Valve will be cycled and timed during cold shutdown.

CN-NC-03 Page 1 of I Section 6.1 Item Number:

Valve:

Flow Diagram:

Catawba Units 1 and 2 Justification for Deferral CN-ND-01 INDOOO1B, IND0002A 2NDOOO1B, 2ND0002A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1561-1.0 CN-2561-1.0 A

1 Valves open to provide suction to Residual Heat Removal Pump A during normal unit cooldown.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

These valves have been provided with an interlock which prevents their opening when Reactor Coolant System pressure is above approximately 425 PSIG.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-ND-01 Page 1 of I Section 6.1 Item Number:

Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

IND0036B, INDO037A 2ND0036B, 2ND0037A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Valves open to provide suction to Residual Heat Removal Pump B during normal unit cooldown.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

These valves have been provided with an interlock which prevents their opening when Reactor Coolant System pressure is above approximately 425 PSIG.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-ND-02 Page I of I Section 6.1 Valve:

CN-ND-02 CN-1561-1.1 CN-2561-1.1 A

I

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-ND-03 IND0010, 1ND0044 2NDOO10, 2ND0044 Flow Diagram:

Code Category:

ASME Class:

Function:

CN-1561-1.0, CN-1561-1.1 CN-2561-1.0, CN-2561-1.1 C

2 Residual heat removal pump discharge check valve.

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Full Stroke Open/Close - Quarterly Exercise check valve (Full Stroke) to the position required to fulfill its function every 3 months.

These valves can only be full stoke tested with the residual heat removal pump operating at full flow in recirculation to the refueling water storage tank. To do this requires closing one of the cold leg injection cross-tie valves and opening the manual valve (IND0033)

(2ND0033) leading back to the FWST. Based on Engineering and Westinghouse evaluation this renders both trains of ND inoperable.

This is not allowed by Technical Specification in Modes 1-3 since both trains are required to be operable. Technical Specification requires one train of ND to be operable in Mode 4.

These valves will be exercised (Partial Stroke) by operating the residual heat removal pump in minimum flow mode every 3 months. These valves will be exercised (Full Stroke) during cold shutdown.

CN-ND-03 Page 1 of 1 Section 6.1

Catawba Units I and 2 Justification for Deferral CN-ND-04 IND0032A, IND0065B 2ND0032A, 2ND0065B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1561-1.0, CN-1561-1.1 CN-2561-1.0, CN-2561-1.1 B

2 Cross connect cold leg injection flow path from the two trains of residual heat removal.

Measure Full Stroke Time - Quarterly Exercise valve (Full Stroke) to the position required to fulfill its function and stroke time every 3 months.

Based on Engineering and Westinghouse evaluation, closing one of these valves renders both trains of residual heat removal inoperable.

This is not allowed by Technical Specification in Modes 1-3 since both trains are required to be operable. Technical Specification requires one of train of ND to be operable in Mode 4.

Valves will be exercised (Full Stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-ND-04 Page I of I Section 6.1 Item Number:

Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-ND-05 IND0028A 2ND0028A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1561-1.0 CN-2561-1.0 B

2 Residual Heat Removal pump supply to NV and NI pumps.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Opening valve provides flow path from FWST to suction of centrifugal charging pumps.

This could result in a plant transient due to an increase in RCS Boron inventory.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-ND-05 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NF-01 INF0229, INF0235 2NF0229, 2NF0235 CN-1558-2.0 CN-2558-2.0 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-NF-01 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-01 INI0009A, INIOOIOB 2NI0009A, 2NI0010B Flow Diagram:

Code Category:

ASME Class:

CN-1562-1.0 CN-2562-1.0 B

2 Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Opens to allow flow from centrifugal charging pump reactor coolant loop cold leg.

Measure Full Stroke Time - Quarterly Exercise valve (Full Stroke) to the position required function and stroke time every 3 months.

discharge to to fulfill its Exercising these valves quarterly during power operations would result in flow of non-preheated water through the injection lines and thermal shocking of the injection nozzles.

Valve will be exercised (Full Stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NI-01 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

CN-1562-1.0 CN-2562-1.0 C

2 Opens on flow from the Centrifugal Charging Pumps.

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Full Stroke Open - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Using a centrifugal charging pump to provide flow to (INI0012)

(2NI0012) would result in injecting borated water into the Reactor Coolant System through the cold leg injection lines. This would result in thermal shock to the reactor coolant piping. During cold shutdowns exercising this valve could result in a

low temperature overpressurization of the reactor coolant system.

Exercise check valve (full stroke) to the position required to fulfill its function at refueling.

CN-NI-02 Page I of 1 Section 6.1 CN-NI-02 INI0012 2NI0012

Catawba Units 1 and 2 Justification for Deferral CN-NI-03 IN10015, INI0017, IN10019, INI0021, IN10351, IN10352, INI0353, IN10354 2NI0015, 2NI0017, 2NI0019, 2NI0021, 2NI0351, 2NI0352, 2NI0353, 2NI0354 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.0 CN-2562-1.0 C

I These valves open on flow from the Centrifugal Charging Pumps.

Full Stroke Open - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Operating these valves would require using a centrifugal charging pump to provide flow which would result in injecting borated water into the Reactor Coolant System thereby causing thermal shock to the reactor coolant piping.

During cold shutdowns exercising this valve could result in a low temperature overpressurization of the reactor coolant system.

Exercise check valve (full stroke) to the position required to fulfill its function at refueling.

CN-NI-03 Page 1 of I Section 6.1 Item Number:

Valve:

Catawba Units 1 and 2 Item Number:

Valve:

Justification for Deferral CN-NI-04 INI0060, IN10071, IN10082, IN10094 2NI0060, 2NI0071, 2NI0082, 2NI0094 CN-1562-1.1 CN-2562-1.1 Flow Diagram:

Code Category:

ASME Class:

A,C 1

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Opens on flow from the cold leg accumulators, safety injection pumps or residual heat removal pumps to provide flow to the reactor coolant system cold legs.

Valves are classified as Pressure Isolation Valves (PIVs) and are therefore required to close.

Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-NI-04 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NI-05 INI0048, 1NI0471, IN10485 2NI0048, 2NI047 1, 2NI0485 CN-1562-1.1 CN-2562-1.1 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-NI-05 Page I of I Section 6.1

Justification for Deferral Item Number:

CN-NI-06 IN10059, 1N10070, IN10081, IN10093 2NI0059, 2NI0070, 2NI0081, 2NI0093 CN-1562-1.1 CN-2562-1.1 Flow Diagram:

Code Category:

ASME Class:

A, C I

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Opens on flow from the cold leg accumulators to provide flow to the reactor coolant system cold legs.

Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-NI-06 Page 1 of I Section 6.1 Catawba Units 1 and 2 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NI-07 INI0101 2NI0101 CN-1562-1.2 CN-2562-1.2 C

2 Opens to provide flow from refueling water storage tank to safety injection pumps suction.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valves cannot be full stroke exercised during power operation since the only full flow flowpath discharges into the reactor coolant system.

Safety injection pump discharge pressure (-1520 psig) cannot overcome reactor coolant system pressure. During cold shutdown this valve cannot be full stroke exercised since this could result in a low temperature overpressurization of the reactor coolant system.

Exercise check valve (partial stroke) to the position required to fulfill its function every 3 months and exercise check valve (full stroke) to the position required to fulfill its function during refueling.

CN-NI-07 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-NI-08 INIOIOOB 2NIO100B CN-1562-1.2 CN-2562-1.2 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Provides suction for both trains of safety injection pumps from the refueling water storage tank.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of this valve in the closed position during testing would render both trains of safety injection pumps inoperable.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NI-08 Page I of 1 Section 6.1 B

2

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NI-09 IN10147B 2NI0147B CN-1562-1.2 CN-2562-1.2 B

2 Valve is normally open to provide miniflow path to the refueling water storage tank.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of this valve in the closed position during testing would result in loss of miniflow path for both trains of safety injection pumps. This would result in pump damage due to dead heading the safety injection pumps in the event of a safety injection signal with reactor coolant pressure above 1520 psig (Safety Injection Pump Discharge Pressure).

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NI-09 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-10 INIO116, IN10148 2NI01 16. 2N10148 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.2 CN-2562-1.2 C

2 Opens on flow from the safety injection pumps to the reactor coolant cold legs or hot legs.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valves cannot be full or partial stroke exercised during power operation since the only flowpath discharges into the reactor coolant system.

Safety injection pump discharge pressure (-1520 psig) cannot overcome reactor coolant system pressure. During cold shutdown these valves cannot be full or partial stroke exercised since this could result in a low temperature overpressurization of the reactor coolant system.

Exercise check valve (full stroke) to the position required to fulfill its function at refueling.

CN-NI-10 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-I I IN10124, INI0126, INI0128, IN10134, INI0156, INI0157, INI0159, IN10160 2NI0124, 2NI0126, 2NI0128, 2NI0134, 2NI0156, 2NI0157, 2NI0159, 2NI0160 Flow Diagram:

Code Category:

ASME Class:

CN-1562-1.2 CN-2562-1.2 A,C I

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 These valves open to provide hot leg recirculation flow from the safety injection pumps.

These valves serve as an inside containment isolation valve and are required to close if not in hot leg recirculation to prevent breach of containment.

These valves are also classified as Pressure Isolation Valves (PIVs) and are required to close per Technical Specification.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valves cannot be full or partial stroke exercised during power operation since the only flowpath discharges into the reactor coolant system.

Safety injection pump discharge pressure (-1520 psig) cannot overcome reactor coolant system pressure. During cold shutdown these valves cannot be full or partial stroke exercised since this could result in a low temperature overpressurization or the reactor coolant system.

Exercise check valve (full stroke) to the position required to fulfill its function at refueling.

CN-NI-11 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2

.Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.3 CN-2562-1.3 B

2 Valve is normally open to provide cold leg injection flow from both trains of safety injection pumps.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of this valve in the closed position during testing would result in loss of cold leg injection flow from the safety injection pumps rendering both trains of safety injection inoperable.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NI-12 Page I of 1 Section 6.1 CN-NI-12 IN10162A 2NI0162A

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-13 IN10165, INI0167, INI0169, IN10171 2NI0165, 2NI0167, 2NI0169, 2NI0171 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.3 CN-2562-1.3 A, C I

Valves open on cold leg injection flow from the safety injection pumps.

Valves are classified as Pressure Isolation Valves (PIVs) and are therefore required to close.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valves cannot be full or partial stroke exercised during power operation since the only flowpath discharges into the reactor coolant system.

Safety Injection Pump Discharge Pressure (-

1520 psig) cannot overcome reactor coolant system pressure. During cold shutdown these valves cannot be full or partial stroke exercised since this could result in a low temperature overpressurization of the reactor coolant system.

Exercise check valve (full stroke) to the position required to fulfill its function at refueling.

CN-NI-13 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-14 INI0175, INI0176, INI0180, IN10181 2NI0175. 2NI0176. 2NI0180. 2NI0181 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.3 CN-2562-1.3 A,C I

Valves open on cold leg injection from the residual heat removal pumps.

Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-NI-14 Page 1 of I Section 6.1 Valve:

Catawba Units I and 2 Justification for Deferral Item Number:

CN-NI-15 INI0173A, IN10178B 2NI0173A. 2NI0178B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.3 CN-2562-1.3 B

2 Each valve isolates two of the four cold leg injection flow paths from the residual heat removal discharge crossover line.

Measure Full Stroke Time - Quarterly Exercise (Full Stroke) to the position required to fulfill its function and stroke time every 3 months.

Based on Engineering and Westinghouse evaluation, closing one of these valves renders both trains of residual heat removal inoperable.

This is not allowed by Technical Specification in Modes 1-3 since both trains are required to be operable. Technical Specification requires one train of ND to be operable in Mode 4.

Valves will be exercised (Full Stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NI-15 Page I of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.2 CN-2562-1.2 B

2 Opens to align hot leg injection during recirculation phase following safety injection actuation.

Measure Full Stroke Time - Quarterly Exercise valve (Full Stroke) to the position required to fulfill its function and stroke time every 3 months.

Based on Engineering and Westinghouse evaluation, in order for a train of ND to be operable to perform its ECCS function, it must be able to discharge into all four cold leg injection lines. This is in the event of single train failure.

With this additional valve open, one ND pump could then be aligned to all four cold leg injection paths plus two hot leg paths during an ECCS actuation.

Valve will be exercised (Full Stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NI-16 Page I of I Section 6.1 CN-NI-16 INI0183B 2NI0183B

Catawba Units 1 and 2 Justification for Deferral CN-NI-17 INI0184B, IN10185A 2NI0184B. 2NI0185A Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.3 CN-2562-1.3 B

2 Opens to provide flow from the Containment Sump to the suction of Residual Heat Removal and Containment Spray Pumps during post accident recirculation phase.

Measure Full Stroke Time - Quarterly Exercise valve (Full Stroke) to the position required to fulfill its function and stroke time every 3 months.

To prevent water from entering lower containment when cycling these valves, piping downstream must be drained. This results in making one train of ECCS inoperable for an extended period of time until completion of the test, refilling the piping and realignment of isolation valves. Also, the large amount of potentially contaminated water that must be drained is a major Health Physics and Radwaste Chemistry problem.

Valve will be exercised (Full Stroke) to the position required to fulfill its function and stroke time during Cold Shutdown.

CN-NI-17 Page 1 of I Section 6.1 Item Number:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-18 INI0332A, IN10333B 2N10332A, 2NI0333B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10131/02 Rev. 26 CN-1562-1.2 CN-2562-1.2 B

2 Aligns discharge of ND Pump IA to suction of NI and NV Pumps.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

If one of these valves were to fail in the open position during testing, the FWST would be aligned to the suction of the charging pumps. This could result in an increase in RCS Boron inventory and could result in plant shutdown.

Valve will be exercised (full stroke) to the position required to fulfill its safety function and stroke timed during cold shutdown.

CN-NI-18 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NI-19 INI0136B 2NI0136B CN-1562-1.2 CN-2562-1.2 B

2 Valve is opened for the recirculation phase of ECCS operation to allow flow from the residual heat removal pumps to the safety injection pumps.

Measure Full Stroke Time - Quarterly Exercise valve (Full Stroke) to the position required to fulfill its function and stroke time every three months.

Based on Engineering evaluation, opening this valve during power operation could degrade ND system flow in the event of a Large Break LOCA.

Valve will be exercised (Full Stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NI-19 Page 1 of I Section 6.1

Catawba Units I and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NI-20 INI0342 2NI0342 CN-1562-1.2 CN-2562-1.2 C

2 Opens to provide suction to the safety injection pumps from residual heat removal pump (IB) (2B) discharge during the recirculation phase following safety injection actuation.

Closes if Train A ND recirculation is in service via the NI pump suction header and Train B ND is shutdown and depressurized.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valve cannot be full stroke exercised during power operation since the only full flow flowpath discharges into the Reactor Coolant system.

Safety injection pump discharge pressure (approximately 1520 psig) cannot overcome Reactor Coolant System pressure.

Valve cannot be full stroke exercised during cold shutdown since this could result in a cold overpressurization of the Reactor Coolant System.

Valve cannot be partial stroke exercised during power operation since the valve lineup would require opening (INI0136B) (2NI0136B). If an accident would occur with (INI0136B) (2NI0136B) open, injection flow would be diverted from both trains of the ND system.

Exercise check valve (partial stroke) to the position required to fulfill its function at cold shutdown. Exercise check valve (full stroke, open &

close) to the position required to fulfill its function at refueling.

CN-NI-20 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-21 INI0121A, INI0152B 2NI0121A, 2NI0152B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Alternate Testing & Frequency:

10/31/02 Rev. 26 CN-1562-1.2 CN-2562-1.2 B

2 Valves 1(2)NIO121A and 1(2)NI0152B are motor operated gate valves on the discharge side of NI Pump A and B to NC Loops B&C and A&D, respectively.

The valves are normally closed during the injection phase and cold leg recirculation phases of ECCS operation to prevent diversion of flow via the NC hot legs.

Measure Full Stroke Time - Quarterly Exercise valve full-stroke to position required to fulfill its function and stroke time every three months per Oma-1988 Part 10, 4.2.1.1.

Exercising the valves in modes 1-3 can result in challenging NI pump discharge relief valves and overpressurization of NI piping due to reactor coolant leakage pressurizing piping downstream.

These valves will be exercised (full-stroked) to position to fulfill its function and stroke timed during cold shutdown.

CN-NI-21 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

CN-NI-22 INI0144A, 2NI0144A CN-1562-1.2 CN-2562-1.2 B

2 Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Valves NI0144A are motor operated valves on the NI Pump B miniflow line. The valves are open during the injection mode when the NI Pumps are operating.

During the recirculation mode, when the NI Pumps are taking suction from the containment sump (via the ND System), the valves are closed to isolate the miniflow line. Closure of the valves prevents the possibility of introducing reactor coolant water into the FWST and diversion of flow from the NC System. The valves are also interlocked with valves ND0028A & N10136B such that they can not be opened unless valves ND0028A and NI0136B are closed.

Measure Full Stroke Time - Quarterly Exercise valve full-stroke to position required to fulfill its function and stroke time every three months per OMa-1988 Part 10, 4.2.1.1.

If N10144A was closed for testing and of a loss of offsite power with the loss of Train A diesel generator as the single failure occurred, the valve could not be reopened which would result in a loss of both NI pumps.

These valves will be exercised (full-stroked) to position to fulfill its function during cold shutdown.

CN-NI-22 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-NI-23 INI0334B, 2NI0334B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.2 CN-2562-1.2 B

2 Provides flowpath from B Train of Residual Heat Removal to B Train of Chemical and Volume Control, and from A Train of Residual Heat Removal to A Train of Safety Injection.

Measure Full Stroke Time - Quarterly Stroke time test in accordance with Oma-1988 Part 10,4.2.1.1.

Closing this valve during power operation degrades both trains of Safety Injection. With the single failure of Train B diesel generator, Train A of Safety Injection, which is provided suction from Residual Heat Removal via N10334B or N10136B, would be inoperable (since N10136B is normally closed).

Train B of Safety Injection would already be inoperable due to the single failure.

Valve will be cycled and stroke timed tested during cold shutdown.

CN-NI-23 Page 1 of 1 Section 6.1

Catawba Units 1 and 2 Justification for Deferral CN-NI-24 INI0103A, 2NI0103A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Alternate Testing & Frequency:

10/31/02 Rev. 26 CN-1562-1.2 CN-2562-1.2 B

2 Provides flow from the Refueling Water Storage Tank to the A Train Safety Injection Pump suction. This valve also provides a flow path from the B Train Residual Heat Removal Pump to the A Train Safety Injection Pump and both Centrifugal Charging Pumps.

Measure Full Stroke Time - Quarterly Exercise valve full-stroke to position required to fulfill its function and stroke time every three months per Oma-1988 Part 10, 4.2.1.1.

Closing this valve during power operations degrades both trains of the Chemical and Volume Control System. In the event of a loss of offsite power with the loss of the Train A Diesel Generator as the single failure when the valve was closed, B Train NV would be lost for sump recirculation mode of operation. Train A NV would already be inoperable due to the single failure.

These valves will be exercised to the position to fulfill their function during cold shutdown.

CN-NI-24 Page 1 of I Section 6.1 Item Number:

Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NI-25 INI0054A, INI0065B, INI0076A, INI0088B 2NI0054A, 2NI0065B, 2NI0076A, 2NI0088B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1562-1.1 CN-2562-1.1 B

2 Valve is administratively open with power removed during normal operation. Some accidents require closure of these valves to prevent injecting nitrogen into the NC System.

Measure Full Stroke Time - Quarterly Exercise valve full stroke to the position required to fulfill its function and stroke time every three months per OMa-1988 Part 10, 4.2.1.1.

Valves cannot be full or partial stroke exercised during power operations since closure of any of the four valve violates TS 3.5.1.

These valves will be exercised (closed) to the position to fulfill their function during refueling.

CN-NI-25 Page I of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NM-O1 INM0424, INM0425 2NM0424, 2NM0425 CN-1572-1.0 CN-2572-1.0 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate testing during refueling.

CN-NM-OI Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NS-01 INS0004, INS0021, INS0098, INS0099 2NS0004, 2NS0021, 2NS0098, 2NS0099 Flow Diagram:

Code Category:

ASME Class:

CN-1563-1.0 CN-2563-1.0 C

2 Function:

Valves open to provide flow from the refueling the spray headers.

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 water storage tank to Full Stroke Open/Close - Quarterly Adoption of the 1995 ASME OM Code, specifically Appendix II or Condition Monitoring.

These valves are part of the Condition Monitoring Program. Based on the maintenance history, the testing interval has been extended.

Additional information can be obtained from the Condition Monitoring database.

CN-NS-01 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NS-02 Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 INS0013, INS0016, INS0030, INS0033, INS0041, INS0046 2NS0013, 2NS0016, 2NS0030, 2NS0033, 2NS0041, 2NS0046 CN-1563-1.0 CN-2563-1.0 C

2 Opens to flow from the containment spray and residual heat removal pumps to the containment spray headers.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

To full or partial stroke these valves flow from the containment spray or residual heat removal pumps would have to be initiated. This would result in spraying water through the spray nozzles into containment.

During each refueling one of the six check valves will be disassembled and the disk will be mechanically exercised.

The next refueling a different valve in this group will be disassembled and so on, such that all six valves will be tested within a six refueling time period. Should any one valve fail to stroke acceptably, the remaining five valves will also be disassembled.

CN-NS-02 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NS-03 INS0038B, INS0043A 2NS0038B, 2NS0043A CN-1563-1.0 CN-2563-1.0 B

2 Residual Heat Pump A (and B) to Containment Spray Header Containment Isolation Valve.

Measure Full Stroke Time - Quarterly Stroke time test in accordance with Oma-1988, Part 10, 4.1.1.1.

If an accident occurred with one of these valves open, injection flow would be diverted from both trains of the ND System.

Valves will be exercised (full stroke) to the position required to fulfill its function and stroke timed during Cold Shutdown.

CN-NS-03 Page 1 of 1 Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NV-01 INVO015B 2NVO015B CN-1554-1.0 CN-2554-1.0 A

2 Valves closes to isolate flow to the letdown heat exchanger.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of this valve in the closed position during testing would result in loss of pressurizer level control and could result in plant shutdown.

Valve will be exercise (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NV-01 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-NV-02 INVO089A, INVO091B 2NVO089A, 2NVO09IB Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.0 CN-2554-1.0 B

2 These valves isolate the return flow path from the reactor coolant pump seal water supply.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Closure of one of these valves during power operation would increase backpressure on the seals, reducing leakoff flow and lifting relief valve 1(2)NV0087 to divert leakoff to the PRT. Damage to RCP seals could result.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NV-02 Page 1 of I Section 6.1

Catawba Units I and 2 Justification for Deferral Item Number:

CN-NV-03 INVOI88A, INVOI89B 2NV0188A, 2NV0189B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.1 CN-2554-1.1 B

2 Valves close to isolate the volume control tank (normal charging supply) upon receipt of a safety injection signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill itsfunction and stroke time every 3 months.

Closure of one of these valves during normal unit operation would isolate the normal suction for the charging pumps. Alternate suction paths would result in increasing the reactor coolant system boron inventory and could result in plant shutdown. In addition, seal water for the reactor coolant pumps would inhibited. This may result in damage to the reactor coolant pump seals.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NV-03 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NV-04 INVO312A, INVO314B 2NV0312A, 2NV0314B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.2 CN-2554-1.2 B

2 Valves close to isolate the charging line to the Reactor Coolant System upon receipt of a safety injection signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Closure of one of these valves during power operation would isolate charging flow to the Reactor Coolant System. This could result in loss of pressurizer level control and cause plant shutdown.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NV-04 Page I of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NV-05 INV0254 2NV0254 CN-1554-1.7 CN-2554-1.7 C

2 Valve opens on flow from the refueling water storage tank to suction of the centrifugal charging pumps.

Valve serves as a backup to, and must close to prevent over pressurization of the FW System piping if up stream isolation valves NV0252A and NV0253B are open and the charging pump suction is pressurized from one of the alternate sources.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valve cannot be full or partial stroke exercised during power operation as this would increase the reactor coolant system boron inventory and possibly cause plant shutdown.

This valve cannot be full stroke exercised during cold shutdown since this could result in a cold overpressurization of the reactor coolant system.

Exercise check valve (partial stroke) to the position required to fulfill its function at cold shutdown. Exercise check valve (full stroke) to the position required to fulfill its function at refueling.

CN-NV-05 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral CN-NV-06 INV0270, INV0290 2NV0270, 2NV0290 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.7 CN-2554-1.7 C

2 Open to provide flow from the centrifugal charging pumps to the normal charging line or Cold Leg Injection Header.

Closes to prevent overpressurization of the charging pump suction header from opposite train operating pump back through idle same train pump.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valves cannot be full stroke exercised during power operation. The only full flow flowpath is through the Cold Leg Injection Header into the reactor coolant system. This would cause an increase in reactor coolant system boron inventory and possibly cause plant shutdown.

Valves cannot be full stroke exercised during cold shutdown since this could result in a cold overpressurization of the reactor coolant system.

Exercise check valve (partial stroke) to the position required to fulfill its function every 3 months. Exercise check valve (full stroke) to the position required to fulfill its function at refueling.

CN-NV-06 Page 1 of I Section 6.1 Item Number:

Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NV-07 INVO202B, INVO203A 2NV0202B, 2NV0203A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.6 CN-2554-1.6 B

2 Valves can be closed to isolate the centrifugal charging pump miniflow line during cold leg injection phase following a LOCA.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of one of these valves in the closed position during test would isolate the centrifugal charging pumps miniflow line. This path must remain open in the event of a LOCA until the operator verifies a primary side break at which time the valves are closed. In the event of a secondary side break, the miniflow path must remain open in order to prevent possible dead heading and damaging the centrifugal charging pumps.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NV-07 Page I of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-NV-08 INV0813 2NV0813 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.7 CN-2554-1.7 C

2 Opens to provide suction to the centrifugal charging pumps from residual heat removal pump discharge during the recirculation phase following safety injection actuation.

Closes if Train B ND is in recirculation via NI pump suction header and Train A ND is shutdown and depressurized.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valve cannot be full stroke exercised during power operation since the only full flow flowpath discharges into the Reactor Coolant System.

This would cause an increase in Reactor Coolant System boron inventory and possibly cause plant shutdown. Valve cannot be partial stroke exercised during power operation. Use of the partial stroke flowpath (through the miniflow line to the seal water heat exchanger) would: I) Cause an increase in the boron concentration in the volume control tank which is the normal source of makeup water for the positive displacement charging pump. This would cause an increase in the Reactor Coolant System boron inventory and possibly cause plant shutdown. 2) Cause the return path for the reactor coolant pump seal water to be deadheaded due to the miniflow path pressure. This would result in reduced seal cooling, diversion of seal leakoff to the PRT, and cause possible pump damage. Valve cannot be full stroke exercised during cold shutdown since this could result in a low temperature overpressurization of the Reactor Coolant System.

Exercise check valve (partial stroke) to the position required to fulfill its function during cold shutdown and exercise check valve (full stroke open & close) to the position required to fulfill its function during refueling.

CN-NV-08 Page 1 of I Section 6.1

Catawba Units 1 and 2 Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Justification for Deferral CN-NV-09 INVO090, INV0874 2NV0090, 2NV0874 CN-1554-1.8 CN-2554-1.8 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-NV-09 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NV-10 INVO252A, INVO253B 2NV0252A, 2NV0253B CN-1554-1.7 CN-2554-1.7 Flow Diagram:

Code Category:

ASME Class:

B 2

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Aligns refueling water storage tank (FWST) to the suction of the centrifugal charging pumps upon receipt of a safety injection signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

If one of these valves were to fail in the open position during testing, the FWST would be aligned to the suction of the charging pumps. This would result in an increase in RCS Boron inventory and could result in a plant shutdown.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-NV-10 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NV-I1 INVOOIOA, INVO011A, INVO013A 2NVOOIOA, 2NVOO1 1A, 2NVO013A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.0 CN-2554-1.0 B

2 These valves must automatically close to isolate containment upon receipt of a Pressurizer Low Level signal, if either valve I(2)NVOOO1A or 1(2)NVO002A closes, upon receipt of a Phase A Containment Isolation Signal (ST), or on a concurrent failure of the PD pump and both centrifugal charging pumps.

These valves are cross-interlocked with valves 1(2)NVOOOIA and 1(2)NVO002A such that they will automatically close if either 1(2)NVOOOIA or I(2)NVO002A is not in the "Open" position. These valves can be operated from the Auxiliary Shutdown Panel, and cannot be opened unless valves 1(2)NVOOO1A and 1(2)NVO002A are both open.

Measure Full Stroke Time/Failed to Safe Position - Quarterly Stroke time and observe fail-safe operation every three (3) months.

Letdown header relief valve I(2)NVO014 has experienced lifting and subsequent seat leakage as a result of pressure transients during orifice swaps for stroke time testing of valves I(2)NVO01OA, l(2)NVOOIIA, and 1(2)NVO013A.

Leakage past 1(2)NVO014 is considered Reactor Coolant (NC) system leakage. This leakage directly impacts Technical Specification.

Based on the above, testing of these valves is impractical and non conservative during power operation.

Valves l(2)NVOOIOA, 1(2)NVOOIIA, and I(2)NVO013 will be stroke time tested and fail-safe operation verified during cold shutdown.

CN-NV-I I Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NV-12 INVOOOIA, 1NVO002A 2NVOOO1A, 2NVO002A Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1554-1.0 CN-2554-1.0 B

I Valves closes to isolate flow to the letdown heat exchanger.

Measure Full Stroke Time/Failed to Safe Position - Quarterly Exercise valve (full stroke) to the position required to fulfill its function, observe fail-safe operation, and stroke time every 3 months.

Failure of this valve in the closed position during testing would result in loss of pressurizer level control and could result in plant shutdown.

Also causes letdown pressure transient, refer to CN-NV-I I Deferral.

Valve will be exercise (full stroke) to the position required to fulfill its function, fail-safe operation verified, and stroke timed during cold shutdown.

CN-NV-12 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-NW-01 INW0006, INW0063 2NW0006, 2NW0063 CN-1569-1.0 CN-2569-1.0 C

2 Open to provide flow from Nuclear Service Water System to the containment valve injection water surge chambers.

Full Stroke Open - Quarterly Exercise valve (full stroke) to the position required to fulfill its function every 3 months.

Operating these valves would result in placing raw water in the NW System.

Exercise check valve (full stroke) to the position required to fulfill its function at refueling (NW surge chamber can be drained and isolated at this time.)

CN-NW-01 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NW-02 Valve:

INW0017, INW0021, INW0024, INW0027, INW0037, INW0040, INW0043, INW0047, INWOOSO, INW0070, INW0074, INW0077, INW0080, INW0086, INW0089, INW0092, INW0095, INW0098, INW0101, INW0107, INW0109, INWOIII, INW0114, INW0120, INW0121, INW0123 through INW0133, INW0135, INW0136, INW0138, INW0139, INW0140, INW0141, INW0147, INW0148, INW0159, INW0160, INW0163, INW0164, INW0168, INW0169, INW0171, INW0172, INW0178, INW0179, INW0183, INW0184, INW0188, INW0189, INW0196, INW0197, INW0201, INW0202, INW0205, INW0206, INW0209, INW0210, INW0213, INW0214, INW0218, INW0219, INW0223, INW0224, INW0230, INW0231, INW0240, INW0241, INW0245, INW0246 2NW0017,2NW0021,2NW0024,2NW0027,2NW0037,2NW0040, 2NW0043,2NW0047,2NW0050,2NWOO70,2NW0074,2NW0077, 2NWOO8O,2NW0086,2NW0089,2NW0092,2NW0095,2NW0098, 2NWOlOl, 2NW0107,2NW0109,2NWOI 11, 2NWOI 14,2NW0120, 2NW0121,2NW0123 through 2NW0133,2NW0135,2NW0136, 2NW0138,2NW0139,2NW0140,2NW0141,2NW0147,2NWOl48, 2NW0159,2NW0160,2NW0163,2NWOI64,2NW0168,2NW0169, 2NW0171,2NW0172,2NW0178,2NW0179,2NW0183,2NW0184, 2NW0188,2NW0189,2NW0196,2NWOI97,2NW0201,2NW0202, 2NW0205,2NW0206,2NW0209,2NW0210,2NWO2l3,2NW0214, 2NW0218,2NW0219,2NW0223,2NW0224,2NW0230,2NW0231, 2NW0240,2NW0241,2NW0245,2NW0246 Flow Diagram:

CN-1569-1.0 CN-2569-1.0 Code Category:

C ASME Class:

2 Function:

These valves open to supply containment valve injection water to certain containment isolation valves.

10/31/02 CN-NW-02 Rev. 26 Page I of 2 Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-NW-02 (Continued)

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Full Stroke Open - Quarterly Exercise check valve (full stroke) to the position required to fulfill its functions every 3 months.

Normal plant conditions will not allow these check valves to operate since the valves fed by the NW System are in systems which are normally pressurized with flow passing through them.

To operate the check valves normal system pressures would have to be bled off in order to allow NW pressure to open the check valves. This is not possible during normal plant operation.

Valves will be full stroked open each refueling outage.

CN-NW-02 Page 2 of 2 Section 6.1

Catawba Units I and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-RF-01 IRF0392, IRF0448 2RF0392, 2RF0448 CN-1599-2.2 CN-2599-2.2 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-RF-01 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-RN-01 IRN0405, IRN0438, IRN0485 2RN0405, 2RN0438, 2RN0485 CN-1574-2.8, CN-1574-2.2 CN-2574-2.2, CN-2574-2.7 A,C 2

Provides containment isolation Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-RN-01 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-RN-02 IRN0437B 2RN0437B Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1574-2.8 CN-2574-2.2 B

2 This valve closes on a high-high containment pressure signal to isolate the supply header to lower containment.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke every 3 months.

Failure of this valve in the closed position during testing would result in loss of nuclear service water flow to the reactor coolant pump motor coolers. This would result in unit shutdown and possible damage to the reactor coolant pumps.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

CN-RN-02 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-SA-01 ISA0003, ISA0006 2SA0003, 2SA0006 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1593-1.1 CN-2593-1.1 C

2 Closes to prevent steam flow reversal in the event of a loss of steam generator.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months per Oma-1988 Part 10,4.3.2.1.

Check valve reverse flow test per GL 89-04.

System design does not provide any indication for verifying valve position. No means exist to test for valve closure.

Verification of ability to prevent reverse flow will be performed during refueling. During each refueling one of the two check valves will be disassembled and the disk will be mechanically exercised. The next refueling the other valve will be disassembled, such that both valves will be tested within a two refueling time period. Should any one valve fail to stroke acceptably, the remaining valve will also be disassembled.

CN-SA-01 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-SM-01 ISMOOO1, ISM0003, ISM0005, ISM0007 2SMOOO1, 2SM0003, 2SM0005, 2SM0007 CN-1593-1.0 CN-2593-1.0 Flow Diagram:

Code Category:

ASME Class:

B 2

Main steam isolation valves.

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Measure Full Stroke Time/Failed to Safe Position - Quarterly Exercise valve (full stroke) to the position required to fulfill its function, stroke time, and verify fail safe actuation every 3 months.

Closure of these valves during power operation could introduce a severe transient in the main steam lines which could cause a unit trip.

Valves will be exercised (full stroke) to the position required to fulfill its function, stroke timed, and fail safe actuation verified during startup after cold shutdown.

CN-SM-01 Page 1 of I Section 6.1 Function:

Catawba Units I and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-VB-01 IVB0085 2VB0085 CN-1605-3.2 CN-2605-3.2 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-VB-01 Page 1 of 1 Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-VG-01 IVG0015, IVG0016, IVG0029, IVG0030, IVG0031, IVG0032, IVG0059, IVG0060, IVG0073, IVG0074, IVG0075, IVG0076 2VG0015, 2VG0016, 2VG0029, 2VG0030, 2VG0031, 2VG0032, 2VG0059, 2VG0060, 2VG0073, 2VG0074, 2VG0075, 2VG0076 Flow Diagram:

Code Category:

ASME Class:

Function:

CN-1609-4.0, CN-1609-4.1 CN-2609-4.0, CN-2609-4.1 C

3 Open to supply starting air to Diesel Generators.

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

No method exists of directly verifying valve movement. Failure of one valve to operate will result in increase in start time of diesel generator during performance of monthly Tech Spec Surveillance Requirement.

Valve will be verified to operate during monthly Tech Spec Diesel Test (PT/i/A/4350/02A,B Diesel Generator A, B Operability Test)

(PT/2/A/4350/02A,B Diesel Generator A, B Operability Test) by verifying diesel starts within required time. In addition, during cold shutdown, a test will be performed which verifies the diesel is able to start within required time with one starting air tank disabled at a time.

The test will be performed twice, first with one bank disabled, then with the opposite bank disabled.

CN-VG-OI Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-VG-02 IVG0025, IVG0026, IVG0027, IVG0028, IVG0069, IVG0070, IVG0071, 1VG0072 2VG0025, 2VG0026, 2VG0027, 2VG0028, 2VG0069, 2VG0070, 2VG0071, 2VG0072 Flow Diagram:

Code Category:

ASME Class:

Function:

CN-1609-4.0, CN-1609-4.1 CN-2609-4.0, CN-2609-4.1 B

3 Open to supply starting air to Diesel Generators Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months. Verify remote position indication every 2 years.

Valve design does not provide any indication of position. Failure of this valve to perform its required function will result in increase in start time of Diesel Generator during performance of monthly Tech Spec Surveillance Requirement.

Valves will be verified to operate during monthly Tech Spec Diesel Test (PT/I/A/4350/02A, B - Diesel Generator A, B Operability Test)

Test (PT/2/A/4350/02A, B - Diesel Generator A, B Operability Test) by verifying diesel starts within required time. In addition, during cold shutdown a test will be performed which verifies the diesel is able to start within required time with one starting air bank disabled at a time.

The test will be performed twice, first with one bank disabled, then with the opposite bank disabled.

CN-VG-02 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-VG-03 IVG0133, IVG0134, IVG0135, IVG0136 2VG0133, 2VG0134, 2VG0135, 2VG0136 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1609-4.0, CN-1609-4.1 CN-2609-4.0, CN-2609-4.1 C

3 Opens during diesel operation to provide air to the engine control panel.

Closes if starting air tank is depressurized to prevent diversion of air from the opposite starting air tank to the control panel.

Full Stroke Open/Close - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

Valve design does not provide any indication of position.

connections are not available to facilitate individual valve testing.

Test During each refueling, one of the four check valves will be disassembled and the disc mechanically exercised. The next refueling, a different valve will be disassembled, and so on, such that all four valves will be tested within a four refueling time period. Should any one valve fail to stroke acceptably, the remaining three valves will also be disassembled.

CN-VG-03 Page 1 of I Section 6.1 Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-VI-01 IVI0079 2VI0079 CN-1605-1.4 CN-2605-1.5 A,C 2

Provides containment isolation Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-VI-01 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

CN-VI-02 1VI0077B 2VI0077B CN-1605-1.4 CN-2605-1.5 Flow Diagram:

Code Category:

ASME Class:

A 2

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 Provides containment isolation. Closes upon receipt of a containment high-high pressure signal.

Measure Full Stroke Time - Quarterly Exercise valve (full stroke) to the position required to fulfill its function and stroke time every 3 months.

Failure of this valve in the closed position during testing would result in loss of instrument air supply to valves and controls within containment.

This would result in loss of normal reactor coolant letdown, containment ventilation unit controls, normal air supply to the power operated relief valves, etc., thereby possibly causing unit shutdown.

Valve will be exercised (full stroke) to the position required to fulfill its function and stroke timed during cold shutdown.

Leak rate performance testing will be performed at refueling.

CN-VI-02 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral CN-VI-03 IVI0367, IVI0368 2VI0367, 2VI0368 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1605-1.14 CN-2605-1.5 C

N,A Close to prevent reverse flow of nitrogen from cold leg accumulator when supplying PORV's from safety air source.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during cold shutdown by stroking the PORV's using the safety air source.

CN-VI-03 Page 1 of I Section 6.1 Item Number:

Valve:

Catawba Units 1 and 2 Justification for Deferral Item Number:

CN-VI-04 IVI0369, IVI0370 2VI0369, 2VI0370 Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-1605-1.14 CN-2605-1.5 C

N,A Open to provide flowpath for nitrogen from cold leg accumulator when supplying PORV's from safety air source.

Full Stroke Open - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve operation when passing flow.

Verify proper valve operation during cold shutdown by stroking the PORV's using the safety air source.

CN-VI-04 Page I of I Section 6.1 Valve:

Catawba Units I and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-VS-01 IVS0056 2VS0056 CN-1605-2.1 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function ever 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-VS-01 Page 1 of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-VY-01 IVY0016 2VY0016 CN-1559-1.0 CN-2559-1.0 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-VY-01 Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-WL-01 IWLA022, 1WL0321, IWL0806, IWL0868 2WLA022, 2WL0321, 2WL0806, 2WL0868 CN-1565-2.6, 2.4, 2.0,2.1 CN-2565-2.6, 2.4, 2.0,2.1 A, C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-WL-0I Page I of I Section 6.1

Catawba Units 1 and 2 Justification for Deferral Item Number:

Valve:

Flow Diagram:

Code Category:

ASME Class:

Function:

Test Requirement:

Basis for Deferral:

Test Alternative & Frequency:

10/31/02 Rev. 26 CN-YM-01 IYM0121 2YM0121 CN-1601-3.1 CN-1601-3.1 A,C 2

Provides containment isolation.

Full Stroke Closed - Quarterly Exercise check valve (full stroke) to the position required to fulfill its function every 3 months.

System design does not provide any indication for verifying valve closure upon flow reversal.

Verify valve closure during performance of leak rate test during refueling.

CN-YM-0 1 Page 1 of I Section 6.1

DUKE POWER CATAWBA NUCLEAR STATION SUPPLEMENTAL TEST PROGRAM Section 7.0

Catawba Nuclear Station Supplemental Testing Program - Valves 10/31/2002 Interval 2, Revision 26 Valve Flow Diagram ASME Active Valve Actuator JOD Pl Test Test Type Test Relief Class Category Type Type Description Direction Request CA - Auxiliary Feedwater System ICAK360 CN-1499-CA10 00 C

Yes C

Self Actuated None No FS Full-Stroke Exercise Open to Closed None Self Actuated Self Actuated Self Actuated Self Actuated Self Actuated Self Actuated Self Actuated None None None None None None None No No No No No No No FS FS FS FS FS FS FS Full-Stroke Exercise Full-Stroke Exercise Full-Stroke Exercise Full-Stroke Exercise Full-Stroke Exercise Full-Stroke Exercise Full-Stroke Exercise Open to Closed Open to Closed Open to Closed Open to Closed Open to Closed Open to Closed Open to Closed None None None None None None None Section 7.1 Page /

2CAK360 ICAK361 2CAK361 ICAK400 2CAK400 ICAK401 2CAK401 CN-2499-CA 10 CN-1499-CAIO CN-2499-CAI 0 CN-1499-CA7 CN-2499-CA7 CN-1499-CA7 CN-2499-CA7 00 00 00 00 00 00 00 Yes Yes Yes Yes Yes Yes Yes ICAK440 CN-1499-CA7 00 C

Yes C

Self Actuated None No Catawba Nuclear Station - Supplemental Testing Prgram for Valves Interval 2. Revision 26

Valve Fow Diagram ASME Active Valve Actuator JOD PI Test Test Type Test Relief Class Category Type Type Description Direction Request ICAK560 CN-1499-CA7 00 C

Yes C

Self Actuated None No FS 2CAK560 ICAK56I 2CAK56 I ICAK600 2CAK600 ICAK601 2CAK60 I ICAK640 2CAK640 ICAK641 2CAK641 CN-2499-CA7 00 CN-1499-CA7 00 CN-2499-CA7 00 CN-1499-CA7 00 CN-2499-CA7 00 CN-1499-CA7 00 CN-2499-CA7 00 CN-1499-CAI0 00 CN-2499-CAIO 00 CN-1499-CAIO 00 CN-2499-CAI0 00 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes C

Self Actuated None No FS Full-Stroke Exercise Open to Closed Catawba Nuclear Station - Supplemental Testing Prgram for Valves None Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No FS FS FS FS FS FS FS FS FS FS Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Full-Stroke Exercise Open to Closed Section 7 1 None None None None None None None None None None None

Valve Flow Diagram ASME Active Valve Actuator JOD Pi Test Test Type Test Relief Class Category Type Type Description Direction Request KC-Component Cooling System IKC0313 CN-1573-1.3 112 C

Yes C

Self Actuated None No RV Safety and Relief Valve Closed to Open None CN-2573-1.3 112 CN-1573-1.3 BI CN-2573-1.3 BI CN-1573-1.7 KIO CN-2573-1.7 KIO CN-1573-1.7 H8 CN-2573-1.7 H8 CN-1573-1.7 K4 CN-2573-1.7 K4 CN-1573-1.7 H2 C

C C

C C

C C

C C

Yes C

Yes C

Yes C

Yes C

Yes C

Yes C

Yes C

Yes C

Yes C

Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No RV RV RV RV RV RV RV RV RV Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open 2KC0313 I KC0330 2KC0330 I KC0355 2KC0355 I KC0361 2KC0361 I KC0374 2KC0374 I KC0380 Section 7.1 Catawba Nuclear Station - Supplemental Testing Prgram for Valves C

Yes C

Self Actuated None No None None None None None None None None None

Valve Flow Diagram ASME Active Valve Actuator JOD PI Test Test Type Test Relief Class Category Type Type Description Direction Request RV Safety and Relief Valve Closed to Open None 2KC0380 CN-2573-1.7 H2 C

Yes C

Self Actuated None No RV Safety and Relief Valve Closed to Open None 1 KC0386 CN-1573-1.4 H 12 C

Yes C

Self Actuated None No RV Safety and Relief Valve Closed to Open None 2KC0386 CN-2573-1.4 H 12 C

Yes C

Self Actuated None No RV Safety and Relief Valve Closed to Open None I KC0392 CN-1573-1.4 KIO 2KC0392 CN-2573-1.4 KIO I KC0404 CN-1573-1.4 H6 2KC0404 CN-2573-1.4 H6 IKC0410 CN-1573-1.4 14 2KC0410 CN-2573-1.4 14 IKC0814 CN-1573-1.5 Gl C

Yes C

C C

C C

C C

Yes Yes Yes Yes Yes Yes Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No RV RV RV PV RV RV RV Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open MOVATS/VOTES -

Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open 2KC0814 CN-2573-I.5 61 C

Yes C

Self Actuated None No RV Safety and Relief Valve Closed to Open None Catawba Nuclear Station - Supplemental Testing Prgram for Valwve None None None None None None None Section 7.1

Valve Flow Diagram ASME Active Valve Class Category Actuator JOD PI Test Type Type NB - Boron Recycle System INB0331 CN-1556-2.0 G8 C

2NB0331 CN-2556-2.0 G7 C

Yes C

Yes C

Self Actuated None No Self Actuatcd Nonc No RV RV Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Section 7.1 Catawba Nuclear Station - Supplemental Testing Prgram for Valves Test Type Description Test Direction Relief Request None None

Valve Flow Diagram ASME Active Valve Class Category NF - Ice Condenser Refrigeration System INF0895 CN-1558-2.6 G2 C

Yes C

S 2NF0895 CN-2558-2.6 G2 C

Yes C

S Actuator JOD PI Test Test Type Test Relief Type Type Description Direction Request Self Actuated None No Self Actuated None No RV RV Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open None None Section 7.1 Catawba Nuclear Station - Supplemental Testing Prgra.n for Valves

Valve Flow Diagram ASME Active Valve Actuator JOD PI Test Test Type Test Relief Class Category Type Type Description Direction Request NI - Safety Injection System IN10125 CN-1562-1.2 H04 I

2NI0125 CN-2562-1.2 H04 I

INl0129 CN-1562-1.2 J03 1

2NIO129 CN-2562-1.2 J03 1

lN10481 CN-1562-1.2 D12 C

2NIO481 CN-2562-1.2 E12 C

Yes Yes Yes Yes Yes Yes AC AC AC AC C

C Self Actuated No Self Actuated No Self Actuated No Self Acluated No Self Actuated None No Self Actuated None No FS FS FS FS RV RV Full-Stroke Exercise Closed to Open Full-Stroke Exercise Closed to Open Full-Stroke Exercise Closed to Open Full-Stroke Exercise Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Section 7.1 Catawba Nuclear Station - Supplemental Testing Prgram for Valhs None None None None None None

Valve Flow Diagram ASME Active Valve Actuator JOD PI Test Test Type Test Relief Class Category Type Type Description Direction Request NV - Chemical & Volume Control System INVOOOIA CN-1554-1.0 HOI I

Yes B

Air Yes SFT Failed to Safe 2NVOOOIA CN-2554-1.0 H02 I

Yes B

Air Yes SFT Failed to Safe INVOOO2A CN-1554-I.O H02 I

Yes B

Air Yes SFT Failed to Safe 2NVO002A CN-2554-1.0 H02 I

Yes B

Air Yes SFT Failed to Safe Position Open to Closed Position Open to Closed Position Open to Closed Position Open to Closed Catawba Nuclear Station - Supplemental Testing Prgran for Valves None None None None Section 7.1

Valve Flow Diagram ASME Active Valve Actuator JOD PI Test Test Type Test Relief Class Category Type Type Description Direction Request RN - Nuclear Service Water System IRN0499 CN-1574-2.3 J4 C

Yes C

Self Actuated None No RV Safety and Relief Valve Closed to Open None 2RN0499 IRN0807 2RN0807 IRN0815 2RN0815 I RN0823 2RN0823 I RN0861 2RN0861 I RN0863 Yes C

Self Actuated None No Yes C

Self Actuated None No Yes C

Self Actuated None No Yes C

Self Actuated None No Yes C

Self Actuated None No Yes C

Self Actuated None No Yes C

Self Actuated None No Yes C

Self Actuated None No Yes C

Self Actuated None No CN-2574-2.3 J4 CN-1574-2.3 J7 CN-2574-2.3 17 CN-1574-2.3 J9 CN-2574-2.3 J9 CN-1574-2.3 J12 CN-2574-2.3 J12 CN-1574-2.8 JI CN-2574-2.7 E3 CN-1574-2.8 D9 Catawba Nuclear Station - Supplemental Testing Prgrarn for Valves RV RV RV RV RV RV RV RV RV Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open None None None None None None None None None Self Actuated None No Section 7.1 Yes C

Valve now Diagram ASME Active Valve Actuator JOD PI Test Test Type Test Relief Class Category Type Type Description Direction Request RV Safety and Relief Valve Closed to Open None 2RN0863 CN-2574-2.2 K9 C

Yes C

Self Actuated None No RV Safety and Relief Valve Closed to Open None Catawba Nuclear Station - Supplenwental Tes'till lPrgrant far Vahlves Section 7Z.

Valve Flow Diagram ASME Active Valve Actuator JOD PI Test Test Type Test Relief Class Category Type Type Description Direction Request WL - Liquid Waste Recycle System IWL0462 CN-1565-2.0 H3 C

Yes 2WL0462 CN-2565-2.0 H3 C

Yes IWL0826 CN-1565-2.4 HIO C

Yes 2WL0826 CN-2565-2.4 HIO C

Yes IWLA033 CN-1565-2.6 K8 C

Yes 2WLA033 CN-2565-2.6 H7 C

Yes C

C C

C Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No Self Actuated None No RV RV RV RV RV RV Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Safety and Relief Valve Closed to Open Section 7.1 Catawba Nuclear Station - Supplemental Testing Prgram for Valves None None None None None None