MONTHYEARML0202203122002-01-22022 January 2002 Letter, Request for Withholding Information from Public Disclosure for the Safety Analysis Report and Extended Power Uprate (MB2700 and MB2701) Project stage: Withholding Request Acceptance BSEP 01-0164, Part 2 of 2, Enclosure 3, Brunswick Steam Electric Plant, Units 1 & 2, Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate (NRC Tac Nos. MB2700 & MB2701)2002-01-24024 January 2002 Part 2 of 2, Enclosure 3, Brunswick Steam Electric Plant, Units 1 & 2, Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate (NRC Tac Nos. MB2700 & MB2701) Project stage: Response to RAI BSEP 02-0034, Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate2002-02-0101 February 2002 Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0030, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-02-0404 February 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI ML0203704172002-02-0606 February 2002 Notice of Consideration of Issuance of Amendment to Facility Operating License for Extended Power Uprate and Opportunity for Hearing Project stage: Other BSEP 02-0037, Response to NRC Request for Additional Information Re Request for License Amendments for Extended Power Uprate2002-02-13013 February 2002 Response to NRC Request for Additional Information Re Request for License Amendments for Extended Power Uprate Project stage: Response to RAI BSEP 02-0041, Response to Request for Additional Information, Request for License Amendments for Extended Power Uprate2002-02-14014 February 2002 Response to Request for Additional Information, Request for License Amendments for Extended Power Uprate Project stage: Response to RAI BSEP 02-0038, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-02-21021 February 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0046, Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate2002-02-21021 February 2002 Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate Project stage: Response to RAI ML0205400052002-02-22022 February 2002 General Electric Company, Request for Withholding Information from Public Disclosure, RAI 5-13, 5-15, 5-17b and 5-25(a), TAC Nos. MB2700 and MB2701 Project stage: RAI BSEP 02-0042, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-02-25025 February 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0048, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-02-25025 February 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0049, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-02-25025 February 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0054, Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate (NRC TAC Nos. MB2700 & MB2701)2002-03-0404 March 2002 Response to Request for Additional Information Re Request for License Amendments - Extended Power Uprate (NRC TAC Nos. MB2700 & MB2701) Project stage: Response to RAI BSEP 02-0060, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-03-0505 March 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0061, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-03-0707 March 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI ML0208007162002-03-12012 March 2002 Response to Request for Additional Information, Request for License Amendments to Extend Power Uprate Project stage: Response to RAI BSEP 02-0067, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-03-14014 March 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0065, Response to Request for Additional Information Re Request for Amendments Re Extended Power Uprate2002-03-14014 March 2002 Response to Request for Additional Information Re Request for Amendments Re Extended Power Uprate Project stage: Response to RAI BSEP 02-0068, Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate2002-03-20020 March 2002 Response to Request for Additional Information Regarding Request for License Amendments - Extended Power Uprate Project stage: Response to RAI BSEP 02-0070, Additional Information on License Amendments Re Extended Power Uprate2002-03-22022 March 2002 Additional Information on License Amendments Re Extended Power Uprate Project stage: Other BSEP 02-0071, License Condition Support Request for License Amendments Re Extended Power Uprate for Brunswick Steam Electric Plant, Units 1 & 22002-03-25025 March 2002 License Condition Support Request for License Amendments Re Extended Power Uprate for Brunswick Steam Electric Plant, Units 1 & 2 Project stage: Request ML0208805092002-03-29029 March 2002 Draft Environmental Assessment and Finding of No Significant Impact (TAC Nos. MB2700 and MB2701) Project stage: Draft Other ML0211303552002-03-29029 March 2002 Draft Safety Evaluation Proposed Extended Power Uprate License Amendments, TAC Nos. MB2700 and MB2701 Project stage: Draft Approval ML0210007332002-04-10010 April 2002 Request for Withholding Information from Public Disclosure (TAC MB2700 and MB2701) Project stage: Withholding Request Acceptance ML0212105202002-04-26026 April 2002 General Electric Co., Request for Withholding Information from Public Disclosure (TACs MB2700 and MB2701) Project stage: Withholding Request Acceptance ML0212106942002-04-26026 April 2002 General Electric Co., Request for Withholding Information from Public Disclosure Letter Dated 03/12/02 Project stage: Withholding Request Acceptance BSEP 02-0091, Response to Request for Additional Information Re Request for License Amendments Re Extended Power Uprate2002-04-26026 April 2002 Response to Request for Additional Information Re Request for License Amendments Re Extended Power Uprate Project stage: Response to RAI BSEP 02-0092, License Condition Supporting 08/09/2001 Request for License Amendments to Extend Power Uprate2002-04-29029 April 2002 License Condition Supporting 08/09/2001 Request for License Amendments to Extend Power Uprate Project stage: Request ML0213506512002-05-14014 May 2002 Environmental Assessment and Finding of No Significant Impact, an Increase in the Maximum Power Level from 2558 Mwt to 2923 Mwt Project stage: Other ML0214305512002-05-31031 May 2002 Issuance of Amendments, Revising TS to Allow an Increase in the Maximum Power Level at Each Unit from 2558 Mwt Thermal to 2923 Mwt Project stage: Approval ML0214901342002-05-31031 May 2002 General Notice - Brunswick Extended Power Uprate Project stage: Other ML0215504252002-05-31031 May 2002 Technical Specification Pages for Amendments 222 and 247 Extended Power Uprate Project stage: Other ML0214403462002-05-31031 May 2002 Non-proprietary Safety Evaluation for Extended Power Uprate Project stage: Approval 2002-03-14
[Table View] |
|
---|
Category:Letter type:BSEP
MONTHYEARBSEP 19-0012, Submittal of 2018 Sea Turtle Annual Report2019-01-17017 January 2019 Submittal of 2018 Sea Turtle Annual Report BSEP 18-0052, Annual Radiological Environmental Operating Report - 20172018-05-10010 May 2018 Annual Radiological Environmental Operating Report - 2017 BSEP 18-0051, Annual Radioactive Effluent Release Report - 20172018-04-26026 April 2018 Annual Radioactive Effluent Release Report - 2017 BSEP 18-0045, Request for License Amendment: Technical Specification 3.8.3, Diesel Fuel Oil, One-Time Extension of Main Fuel Oil Storage Tank Completion Time2018-04-25025 April 2018 Request for License Amendment: Technical Specification 3.8.3, Diesel Fuel Oil, One-Time Extension of Main Fuel Oil Storage Tank Completion Time BSEP 18-0054, Response to Request for Additional Information Regarding Inservice Inspection Program Proposed Alternative ISI-09 in Accordance with 10 CFR 50.55a(z)(1) Regarding Reactor Pressure Vessel Circumferential.2018-04-24024 April 2018 Response to Request for Additional Information Regarding Inservice Inspection Program Proposed Alternative ISI-09 in Accordance with 10 CFR 50.55a(z)(1) Regarding Reactor Pressure Vessel Circumferential. BSEP 18-0048, Response to Request for Additional Information Regarding Inservice Inspection Program Proposed Alternative ISI-09 in Accordance with 10 CFR 50.55a(z)(1) Regarding Reactor Pressure Vessel Circumferential Shell Weld Examinations2018-04-11011 April 2018 Response to Request for Additional Information Regarding Inservice Inspection Program Proposed Alternative ISI-09 in Accordance with 10 CFR 50.55a(z)(1) Regarding Reactor Pressure Vessel Circumferential Shell Weld Examinations BSEP 18-0044, Application of Dissimilar Metal Weld Full Structural Overlay - Reactor Pressure Vessel Nozzles N4A and N4D2018-04-11011 April 2018 Application of Dissimilar Metal Weld Full Structural Overlay - Reactor Pressure Vessel Nozzles N4A and N4D BSEP 18-0046, Supplement to Response to Request for Additional Information SRXB-RAI-2 Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion2018-04-10010 April 2018 Supplement to Response to Request for Additional Information SRXB-RAI-2 Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion BSEP 18-0047, Supplement to Proposed Alternative in Accordance with 10 CFR 50.55a(z)(2) for End of Interval Leakage Test2018-04-0505 April 2018 Supplement to Proposed Alternative in Accordance with 10 CFR 50.55a(z)(2) for End of Interval Leakage Test BSEP 18-0041, Request for License Amendment to Revise the Technical Specifications to Relocate the Pressure-Temperature Limit Curves to a Pressure and Temperature Limits Report2018-04-0404 April 2018 Request for License Amendment to Revise the Technical Specifications to Relocate the Pressure-Temperature Limit Curves to a Pressure and Temperature Limits Report BSEP 18-0043, Application of Dissimilar Metal Weld Full Structural Overlay - Reactor Pressure Vessel Nozzles N4A and N4D2018-03-31031 March 2018 Application of Dissimilar Metal Weld Full Structural Overlay - Reactor Pressure Vessel Nozzles N4A and N4D BSEP 18-0035, Response to Request for Additional Information Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion2018-03-29029 March 2018 Response to Request for Additional Information Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion BSEP 18-0042, Cycle 22 Core Operating Limits Report (COLR)2018-03-27027 March 2018 Cycle 22 Core Operating Limits Report (COLR) BSEP 18-0040, Proposed Alternative in Accordance with 10 CFR 50.55a(z)(1) for End of Interval Leakage Test2018-03-23023 March 2018 Proposed Alternative in Accordance with 10 CFR 50.55a(z)(1) for End of Interval Leakage Test BSEP 18-0039, Proposed In-Service Inspection Alternative for Application of Dissimilar Metal Weld Full Structural Overlay - Nozzles N4A and N4D2018-03-19019 March 2018 Proposed In-Service Inspection Alternative for Application of Dissimilar Metal Weld Full Structural Overlay - Nozzles N4A and N4D BSEP 18-0034, Corrected Affidavit Relating to the Request for License Amendment Regarding Core Flow Operating Range Expansion2018-03-16016 March 2018 Corrected Affidavit Relating to the Request for License Amendment Regarding Core Flow Operating Range Expansion BSEP 18-0032, Additional Testing Information Relating to the Request for License Amendment Regarding Core Flow Operating Range Expansion2018-03-14014 March 2018 Additional Testing Information Relating to the Request for License Amendment Regarding Core Flow Operating Range Expansion BSEP 18-0026, Additional Information Regarding Proposed Alternative in Accordance with 10 CFR 50.55a(z)(1) for Reactor Pressure Vessel Nozzle-to-Vessel Weld Examination2018-03-0707 March 2018 Additional Information Regarding Proposed Alternative in Accordance with 10 CFR 50.55a(z)(1) for Reactor Pressure Vessel Nozzle-to-Vessel Weld Examination BSEP 18-0014, Fifth 10-Year Inservice Testing Program Plan2018-02-19019 February 2018 Fifth 10-Year Inservice Testing Program Plan BSEP 18-0021, Response to Request for Additional Information Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion (CAC Nos. MF8864 and MF8865). Without Proprietary Enclosure2018-02-0505 February 2018 Response to Request for Additional Information Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion (CAC Nos. MF8864 and MF8865). Without Proprietary Enclosure BSEP 18-0017, Revision to Radiological Emergency Response Plan and Implementing Procedure2018-01-30030 January 2018 Revision to Radiological Emergency Response Plan and Implementing Procedure BSEP 18-0015, Inservice Inspection Program Proposed Alternative ISI-09 in Accordance with 10 CFR 50.55a(z)(1) Regarding Reactor Pressure Vessel Circumferential Shell Weld Examinations2018-01-23023 January 2018 Inservice Inspection Program Proposed Alternative ISI-09 in Accordance with 10 CFR 50.55a(z)(1) Regarding Reactor Pressure Vessel Circumferential Shell Weld Examinations BSEP 18-0013, Supplement to Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control2018-01-23023 January 2018 Supplement to Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control BSEP 18-0001, Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements2018-01-23023 January 2018 Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements BSEP 18-0012, Application to Revise Technical Specifications to Adopt TSTF-208, Revision 0, Extension of Time to Reach Mode 2 in LCO 3.0.32018-01-23023 January 2018 Application to Revise Technical Specifications to Adopt TSTF-208, Revision 0, Extension of Time to Reach Mode 2 in LCO 3.0.3 BSEP 18-0009, 2017 Sea Turtle Annual Report2018-01-15015 January 2018 2017 Sea Turtle Annual Report BSEP 17-0098, Application to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems, and Components (Sscs) for Nuclear Power Reactors2018-01-10010 January 2018 Application to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems, and Components (Sscs) for Nuclear Power Reactors BSEP 17-0119, Snubber Program Plan for Fifth 10-Year Interval Inservice Testing Program2018-01-10010 January 2018 Snubber Program Plan for Fifth 10-Year Interval Inservice Testing Program BSEP 17-0115, Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control2018-01-0404 January 2018 Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control BSEP 17-0110, Seventh Six-Month Status Report in Response to June 6, 2013, Commission Order Modifying Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Conditions2017-12-20020 December 2017 Seventh Six-Month Status Report in Response to June 6, 2013, Commission Order Modifying Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Conditions BSEP 17-0121, Post-Examination Documentation and Comments for Operator Retake Initial Examination2017-12-14014 December 2017 Post-Examination Documentation and Comments for Operator Retake Initial Examination BSEP 17-0120, Withdrawal of Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension..2017-12-12012 December 2017 Withdrawal of Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension.. BSEP 17-0118, Supplement to Response to Request for Additional Information Regarding Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel..2017-12-0707 December 2017 Supplement to Response to Request for Additional Information Regarding Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel.. BSEP 17-0117, Response to Request for Additional Information (Probabilistic Risk Assessment and Human Performance Branches) Regarding Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1 AC Sources..2017-12-0606 December 2017 Response to Request for Additional Information (Probabilistic Risk Assessment and Human Performance Branches) Regarding Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1 AC Sources.. BSEP 17-0116, Response to Request for Additional Information Regarding Request for Risk- Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of ..2017-12-0404 December 2017 Response to Request for Additional Information Regarding Request for Risk- Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of .. BSEP 17-0104, Proposed Alternative in Accordance with 10 CFR 50.55a(z)(1) for Reactor Pressure Vessel Nozzle-to-Vessel Weld Examination2017-11-29029 November 2017 Proposed Alternative in Accordance with 10 CFR 50.55a(z)(1) for Reactor Pressure Vessel Nozzle-to-Vessel Weld Examination BSEP 17-0111, Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension of Surveillance Requirements2017-11-28028 November 2017 Request for Risk-Informed Exigent License Amendment - Technical Specification 3.8.1, AC Sources Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension of Surveillance Requirements BSEP 17-0109, Response to Request for Additional Information Regarding Request for Emergency License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel Generator Completion Times And.2017-11-24024 November 2017 Response to Request for Additional Information Regarding Request for Emergency License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel Generator Completion Times And. BSEP 17-0108, Request for Emergency License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension of Surveillance Requirements2017-11-22022 November 2017 Request for Emergency License Amendment - Technical Specification 3.8.1, AC Sources - Operating, One-Time Extension of Emergency Diesel Generator Completion Times and Suspension of Surveillance Requirements BSEP 17-0017, Submittal of Request for License Amendment for Performance-Based Fire Protection Alternative for Thermal Insulation Material2017-11-15015 November 2017 Submittal of Request for License Amendment for Performance-Based Fire Protection Alternative for Thermal Insulation Material BSEP 17-0100, Fifth 10-Year Inservice Testing Interval2017-11-0202 November 2017 Fifth 10-Year Inservice Testing Interval BSEP 17-0089, Updates to Request for License Amendment Regarding Core Flow Operating Range Expansion2017-11-0101 November 2017 Updates to Request for License Amendment Regarding Core Flow Operating Range Expansion BSEP 17-0093, Response to Request for Additional Information Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion2017-11-0101 November 2017 Response to Request for Additional Information Regarding Request for License Amendment Regarding Core Flow Operating Range Expansion BSEP 17-0078, Request for License Amendment - DC Sources - Operating Surveillance Requirement (SR) 3.8.4.52017-10-0303 October 2017 Request for License Amendment - DC Sources - Operating Surveillance Requirement (SR) 3.8.4.5 BSEP 17-0076, Registration for Use of General License Spent Fuel Casks2017-09-0606 September 2017 Registration for Use of General License Spent Fuel Casks BSEP 17-0081, Revision to Radiological Emergency Response Plan Implementing Procedures2017-09-0505 September 2017 Revision to Radiological Emergency Response Plan Implementing Procedures BSEP 17-0039, Submittal of Response to Inspection Report 05000324/2015404 and 05000325/2015404, Dated March 30, 2015, Inspection of Interim Cyber Security Milestones 1-7 and Target Set Requirements2017-08-15015 August 2017 Submittal of Response to Inspection Report 05000324/2015404 and 05000325/2015404, Dated March 30, 2015, Inspection of Interim Cyber Security Milestones 1-7 and Target Set Requirements BSEP 17-0071, ISFSI - Registration for Use of General License Spent Fuel Casks2017-08-15015 August 2017 ISFSI - Registration for Use of General License Spent Fuel Casks BSEP 17-0064, Application of Dissimilar Metal Weld Full Structural Overlay on Reactor Pressure Vessel Nozzle N92017-07-10010 July 2017 Application of Dissimilar Metal Weld Full Structural Overlay on Reactor Pressure Vessel Nozzle N9 BSEP 17-0060, Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control.2017-06-29029 June 2017 Application to Revise Technical Specifications to Adopt TSTF-542, Reactor Pressure Vessel Water Inventory Control. 2019-01-17
[Table view] |
Text
CP&L CP&L AProgress Energy Company JohnPresident Vice S.Keenan Brunswick Nuclear Plant APR 2 6 2002 SERIAL: BSEP 02-0091 TSC-2001-09 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2 DOCKET NOS. 50-325 AND 50-324/LICENSE NOS. DPR-71 AND DPR-62 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION REGARDING REQUEST FOR LICENSE AMENDMENTS - EXTENDED POWER UPRATE (NRC TAC NOS. MB2700 AND MB2701)
Ladies and Gentlemen:
On August 9, 2001 (i.e., Serial: BSEP 01-0086), Carolina Power & Light (CP&L) Company requested a revision to the Operating Licenses (OLs) and the Technical Specifications for the Brunswick Steam Electric Plant (BSEP), Units 1 and 2. The proposed license amendments increase the maximum power level authorized by Section 2.C.(1) of OLs DPR-71 and DPR-62 from 2558 megawatts thermal (MWt) to 2923 MWt. Subsequently, on April 23, 2002, during a meeting with the Advisory Committee On Reactor Safeguards Thermal-Hydraulic Phenomena Subcommittee, CP&L was requested to provide additional information regarding the evaluation of the limiting 10 CFR 50, Appendix R event performed in support of the extended power uprate amendment request. The response to this request for additional information is enclosed.
Please refer any questions regarding this submittal to Mr. Edward T. O'Neil, Manager - Regulatory Affairs, at (910) 457-3512.
Sincerely, John S. Keenan MAT/mat P.OBox 10429 Southport, NC 28461
> 910,457.2496
> 910.457T2803
Document Control Desk BSEP 02-0091 / Page 2
Enclosure:
Response to Request for Additional Information (RAI) 26 C. J. Gannon, having been first duly sworn, did depose and say that the information contained herein is true and correct to the best of his information, knowledge and belief; and the sources of his information are officers, employees, and agents of Carolina Power & Light Company.
Notary (Seal)
My commission expires: /
' im cc: U. S. Nuclear Regulatory Commission, Region II ATTN: Mr. Luis A. Reyes, Regional Administrator Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 Atlanta, GA 30303-8931 U. S. Nuclear Regulatory Commission ATTN: Mr. Theodore A. Easlick, NRC Senior Resident Inspector 8470 River Road Southport, NC 28461-8869 U. S. Nuclear Regulatory Commission (Electronic Copy Only)
ATTN: Ms. Brenda L. Mozafari (Mail Stop OWFN 8G9) 11555 Rockville Pike Rockville, MD 20852-2738 U. S. Nuclear Regulatory Commission ATTN: Mr. Mohammed Shuaibi (Mail Stop OWFN 8H4A) 11555 Rockville Pike Rockville, MD 20852-2738 Ms. Jo A. Sanford Chair - North Carolina Utilities Commission P.O. Box 29510 Raleigh, NC 27626-05 10 Mr. Mel Fry Director - Division of Radiation Protection North Carolina Department of Environment and Natural Resources 3825 Barrett Drive Raleigh, NC 27609-7221
BSEP 02-0091 Enclosure Page 1 of 2 ENCLOSURE BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2 DOCKET NOS. 50-325 AND 50-324/LICENSE NOS. DPR-71 AND DPR-62 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION REGARDING REQUEST FOR LICENSE AMENDMENTS - EXTENDED POWER UPRATE (NRC TAC NOS. MB2700 AND MB2701)
Response to Request for Additional Information (RAI) 26 Back2round On August 9, 2001 (i.e., Serial: BSEP 01-0086), Carolina Power & Light (CP&L) Company requested a revision to the Operating Licenses (OLs) and the Technical Specifications for the Brunswick Steam Electric Plant (BSEP), Units 1 and 2. The proposed license amendments increase the maximum power level authorized by Section 2.C.(1) of OLs DPR-71 and DPR-62 from 2558 megawatts thermal (MWt) to 2923 MWt. Subsequently, on April 23, 2002, during a meeting with the Advisory Committee On Reactor Safeguards Thermal-Hydraulic Phenomena Subcommittee, CP&L was requested to provide additional information regarding the evaluation of the limiting 10 CFR 50, Appendix R event performed in support of the extended power uprate amendment request. The response to this RAI follows.
NRC Ouestion 26-1 Table 6-5, "Appendix R Fire Event Evaluation Results," of NEDC-33039P, "Safety Analysis Report for Brunswick Steam Electric Plant Units 1 and 2 Extended Power Uprate," dated August 2001 (i.e., the Power Uprate Safety Analysis Report (PUSAR)) shows that the peak cladding temperature (PCT) for this event increases from < 1200'F to 1468°F under extended power uprate (EPU) conditions. Please explain the large increase in PCT for this event.
Response to NRC Question 26-1 The Appendix R event in question involves a shutdown from outside of the main control room.
The fuel heatup analysis was performed using the SAFERPGESTR-LOCA analysis model. To minimize the scope of required reviews, the preferred EPU approach was to maintain the existing cases, methods, and assumed operator action times when evaluating Appendix R events, provided the acceptance criteria were met. For this event, the acceptance criterion of a PCT
< 1500'F was met using the pre-EPU assumptions. The inputs and assumptions for this event include:
"* A fire occurs in the main control room at time zero.
"* The fire results in a reactor scram and loss-of-offsite power (LOOP) at time zero.
BSEP 02-0091 Enclosure Page 2 of 2
- There is a concurrent loss of feedwater at time zero, with a five second pump coast-down, due to the LOOP.
- The Reactor Core Isolation Cooling (RCIC) system is not credited for vessel inventory makeup (i.e., this assumption is a conservatism beyond what is required to meet Appendix R requirements).
For a shutdown from outside of the main control room, operators are dispatched to local control provisions in the Diesel Generator Building and the Reactor Building. With no high pressure injection available, core cooling is accomplished by vessel depressurization followed by low pressure injection. However, the depressurization cannot be started until an EDG is running to provide power to the low pressure system. At 40 minutes into the event, an EDG will have been started as needed to allow the operators in the Reactor Building to open the three Safety/Relief Valves (SRVs) with local controls.
The increased PCT for the Appendix R event is caused by the increased decay heat associated with EPU. The increased decay heat for EPU results in a lower predicted reactor water level at the assumed 40 minute operator action time. This results in a deeper core uncovery following depressurization and a higher fuel heatup. There is more steam generation due to the increased decay heat for EPU, which results in a longer period of vessel depressurization before the low pressure makeup system can inject. This delay in makeup injection also results in a higher fuel heatup for EPU. The increase in PCT shown for the BSEP EPU Appendix R event is consistent with the Appendix R results for other BWR/4 EPU projects.
Nominal input and modeling assumptions can be used in analyzing the Appendix R fire event.
However, for ease of performing the analysis, the conservative system modeling assumptions from the SAFER ECCS-LOCA performance analysis were used in the Appendix R event analysis. The system modeling conservatisms include (1) no high pressure makeup, (2) ECCS performance characteristics (i.e., minimum flow rates as functions of vessel pressure, maximum valve stroke times, etc.), and (3) the use of SRVs at the rated steam flow capacity (i.e., 90% of the tested capacity). Because of the extremely low likelihood of the event combined with the conservatisms of the evaluation, CP&L determined that the reduced margin to the acceptance limit is acceptable.