L-2012-332 10 CFR 50, Appendix E

'AUG 17 2012 FIPL.

U. S. Nuclear Regulatory Commission Attn.: Document Control Desk Washington, D.C. 20555-0001 Re: Turkey Point Unit 3 Docket No. 50-251 Emergency Response Data System (ERDS) Maintenance This letter is being submitted pursuant to 10 CFR 50, Appendix E, VI, 3.a, Maintaining Emergency Response Data System, for Turkey Point Unit 3 (TP3) due to several changes to the TP3 ERDS Data Point Library Reference File.

The following table contains TP3 ERDS Data Point information that requires revision to reflect Westinghouse rescaling of EPU affected NSSS and BOP system instrumentation setpoints.

TP3 ERDS DATA POINT PARAMETERS Item #

DCS Point ID Point Description Alarm/Trip Setpoint

System Description

13 SGAAVLV Steam Generator Level A Lo-Lo Rx Trip: 16%

Protection Train:

16% Reactor Trip 15 SGBAVLV Steam Generator Level B Lo-Lo Rx Trip: 16%

Protection Train:

16% Reactor Trip 17 SGCAVLV Steam Generator Level C Lo-Lo Rx Trip: 16%

Protection Train:

1 1_ 16% Reactor Trip Item #

DCS Point ID Point Description How Processed System Descriptio 19 SGAAVPV Steam Generator Pressure A 3 Input Average with 21 psig deviation...

21 psig Deviation Limit 20 SGBAVPV Steam Generator Pressure B 3 Input Average with 21 psig deviation...

21 psig Deviation Limit 21 SGCAVPV Steam Generator Pressure C 3 Input Average with 21 psig deviation...

21 psig Deviation Limit Item #

DCS Point ID Point Description Max Instrument Rang System Descriptio 22 SGAAVFWF V Feedwater Flow A SG 5.OE+6 FW flow < MS flow

@773,000 lb/Hr 23 SGBAVFWFV Feedwater Flow B SG 5.OE+6 FW flow < MS flow

@773,000 lb/Hr 24 SGCAVFWFV Feedwater Flow C SG 5.OE+6 FW flow < MS flow

_@773,000 lb/Hr Item #

DCS Point ID Point Description Alarm/Trip Setpoint 28 THA AVTP V RCS Hot Leg A Avg Temp Hi: 620'F 29 THB AVTP V RCS Hot Leg B Avg Temp Hi: 620'F 30 THC AVTP V RCS Hot Leg C Avg Temp Hi: 620'F Item #

DCS Point ID Point Description

System Description

35 PRZAVLV Pressurizer Average Level

... Hi level alarm at

__1+5%

program...

Florida Power & Light Company

/VOZ(c2 9760 SW 344 St., Florida City, FL 33035

Turkey Point Nuclear Plant L-2012-332 Docket No. 50-250 Page 2 of 2 A complete listing of the ERDS Data Points is provided in Attachment 1. The changes above have been incorporated into the TP3 ERDS Data Point Library Reference File provided in Attachment 2.

This information is being provided in compliance with 10 CFR 50, Appendix E, VI, 3.a which requires submittal of software changes to the ERDS Data Point Library within 30 days after the changes are completed. These changes were implemented for Unit 3 upon entry into MODE 4 on July 30, 2012 as part of the startup from the Unit 3 Cycle 26 refueling outage.

Should you have any questions regarding this submittal, please contact Mr. Robert J. Tomonto, Licensing Manager, at (305) 246-7327.

Very truly yours, Michael Kiley Site Vice President Turkey Point Nuclear Plant Attachments cc:

USNRC Regional Administrator, Region II USNRC Project Manager, Turkey Point Nuclear Plant USNRC Senior Resident Inspector, Turkey Point Nuclear Plant

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 1 of 3 TURKEY POINT UNIT 3 ERDS DATA POINT LIST

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 2 of 3 TP3 ERDS Data Points Item #

DCS Point ID Description 1

NIAVPRL V POWER RANGE POWER LEVEL (AVG) 2 NIAVSRL V SOURCE RANGE POWER LVL (AVG) 3 NIAVIRL V INTERMEDIATE RANGE POWER LVL (AVG) 4 N6649AVPV GAMMA-METRICS AVE OF PR (AVG) 5 N6649AVS V GAMMA-METRICS AVE OF SR (AVG) 6 RXHDLLO V REACTOR HEAD LEVEL (AUCT LOW) 7 RXPLLLO V REACTOR PLENUM LEVEL (AUCT LOW) 8 CETV CORE EXIT TEMP (AUCT HIGH) 9 SCMCETLO V SUBCOOLING (AUCT LOW) 10 RCSA AVF V RCS A AVERAGE FLOW 11 RCSB AVF V RCS B AVERAGE FLOW 12 RCSC AVF V RCS C AVERAGE FLOW 13 SGAAVLV STEAM GENERATOR LEVEL A (AVG) 14 L477 A STM GEN A WIDE RANGE LEVEL 15 SGBAVLV STEAM GENERATOR LEVEL B (AVG) 16 L487 A STM GEN B WIDE RANGE LEVEL 17 SGCAVLV STEAM GENERATOR LEVEL C (AVG) 18 L497 A STM GEN C WIDE RANGE LEVEL 19 SGA AVP V STEAM GENERATOR PRESSURE A (AVG) 20 SGBAVPV STEAM GENERATOR PRESSURE B (AVG) 21 SGCAVPV STEAM GENERATOR PRESSURE C (AVG) 22 SGAAVFWF V FEEDWATER FLOW A SG (AVG) 23 SGBAVFWF V FEEDWATER FLOW B SG (AVG) 24 SGCAVFWF V FEEDWATER FLOW C SG (AVG) 25 SGAAFWF V AUX FEEDWATER FLOW A SG U3 (TOTAL) 26 SGBAFWFV AUX FEEDWATER FLOW B SG U3 (TOTAL) 27 SGCAFWFV AUX FEEDWATER FLOW C SG U3 (TOTAL) 28 THAAVTPV RCS HOT LEG A AVG TEMP 29 THBAVTP V RCS HOT LEG B AVG TEMP 30 THCAVTPV RCS HOT LEG C AVG TEMP 31 TCA AVTPV RCS COLD LEG A AVG TEMP 32 TCB AVTP V RCS COLD LEG B AVG TEMP 33 TCC AVTP V RCS COLD LEG C AVG TEMP 34 RCSAVP V RCS AVG WR PRESSURE 35 PRZAVLV PRESSURIZER AVERAGE LEVEL 36 F122 A CHARGING FLOW 37 F932_A HHSI FLO A HL INSIDE CNTMT 38 F933_A HHSI FLO B HL INSIDE CNTMT 39 F943_A HHSI TO BORON INJ TANK 40 F605 A RHR SYSTEM FLOW 41 CHILVLL V CNTMT SUMP WATER LEVEL (AUCT HIGH)

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 3 of 3 TP3 ERDS Data Points Item #

DCS Point ID Description 42 CHILVLH V CNTMT HR WATER LEVEL (AUCT HIGH) 43 R14_A**

PLANT VENT GAS ACTIVITY RAD MON 44 R6304HR A PLANT VENT GAS GAMMA HI RANGE 45 R6304FLO A PLANT VENT FLOW RATE 46 R6418HR A U3 FUEL PIT GAS GAMMA HI RANGE 47 R18 A**

LIQUID WASTE EFFLUENT RAD MON 48 R15_A CONDENSER GAS EJECTOR RAD MON 49 R6417HR A AIR EJECTOR GAS GAMMA HI RANGE 50 CHRADWV CNTMT WR RADIATION (AUCT HIGH) 51 R20 A RCS LETDOWN ACTIVITY RAD MON 52 R6426_A MAIN STM LINES GAMMA HI RANGE 53 R19_A SG EFFLUENT PROCESS RAD MON 54 CAVPRSW V CNTMT WR AVG PRESSURE 55 C HITMP V CNTMT TEMP (AUCT HIGH) 56 CH2CONC V CNTMT H2 CONCENTRATION (AUCT HIGH) 57 RWSTAVLV RWST LEVEL (AUCT LOW) 58 WS1OM_LUA WIND SPEED 10 METERS (TP) 59 WD10M LU A WIND DIRECTION 10 METERS (TP) 60 STABB SD A ESTIMATE OF ATMOS STABILITY 61 FAN3V21 A*

SPENT FUEL PIT EXHAUST FAN Digital Point

    • Common Point with Unit 4

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 1 of 62 TURKEY POINT UNIT 3 ERDS DATA POINT LIBRARY

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 2 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NI Power Rng Point ID:

NIAVPRLV Plant Spec Point Desc:

Power Range Power Level Generic/Cond Desc:

Nuclear Instr, Power Range Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

120 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

4 How Processed:

4 Input Average, w/3 % Deviation Limit Sensor Locations:

RX Vessel @ 45, 135, 225, & 315 degrees, 14'El.

Alarm/Trip Set Points:

Hi: 103% Hi-Hi Rx Trip: 108%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

3% deviation being the limit for use in calculation and Quality determination. The detector type is an excore dual ion chamber (upper-lower arrangement). Hi 103%

(Rod Stop) Hi Hi 108% (RX Trip). This instrument also inputs a 2/4 logic for a Low Power - Hi Flux Rx Trip signal at 25% power.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 3 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NI Inter Rng Point ID:

NIAVIRLV Plant Spec Point Desc:

Intermediate Range Power Level Generic/Cond Desc:

Nuclear Instr, Intermediate Range Analog/Digital:

A Engr Units/Dig States:

Amps Engr Units Conversion:

N/A Minimum Instr Range:

1.OE 11 Maximum Instr Range:

1.OE 3 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

Rx Vessel @ 90 & 270 Deg. 14' El.

Alarm/Trip Set Points:

P6: 1.001 E 10 Amps NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply

<1.OE 10 AMPS Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor quality. The average is determined from N35_A and N36_A intermediate range channel signals.

The detectors are compensated ion chambers located at the core. The P6 setpoint is 1.001 E 10 Amps. This instrument also inputs a 1/2 logic Low Power Rx trip I signal at 1.2 E 4 amps (equiv to 25% power).

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 4 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NI Source Rng Point ID:

NIAVSRLV Plant Spec Point Desc:

Source Range Power Level Generic/Cond Desc:

Nuclear Instr, Source Range Analog/Digital:

A Engr Units/Dig States:

CPS Engr Units Conversion:

N/A Minimum Instr Range:

1.OE +0 Maximum Instr Range:

1.OE +6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

Rx Vessel @ 90 & 270 Deg. 14' El.

Alarm/Trip Set Points:

Rx Trip at 1.0E5 CPS NI Detector Power Supply

>1.0E4 CPS (P6 Permissive)

Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The average is determined from N3 1_A and N32_A source range channel signals. The detectors are in the lower half of detector wells shared with the intermediate range detectors.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 5 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

N6649AVP V Plant Spec Point Desc:

Gammametrics PR Avg Generic/Cond Desc:

Nuclear Instruments, Power Rng Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

N/A Minimum Instr Range:

1.OE 8 Maximum lnstr Range:

200 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P2 Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RX Vessel @ 0 and 180 Deg. 14' El.

Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The Gammametrics Source Range Detectors are located in the same wells as the Gammametrics Power Range Detectors.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 6 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

N6649AVS V Plant Spec Point Desc:

Gammametrics SR Avg Generic/Cond Desc:

Nuclear Instruments, Source Rng Analog/Digital:

A Engr Units/Dig States:

CPS Engr Units Conversion:

N/A Minimum Instr Range:

1.OE 1 Maximum Instr Range:

1.OE +5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RX Vessel @ 0 and 180 Deg. 14' El.

Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The Gammametrics Source Range Detectors are located in the same detector wells as the Gammametrics Power Range Detectors.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 7 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

Reac VesLev Point ID:

RXPLLLO V Plant Spec Point Desc:

Reactor Upper Head Level Generic/Cond Desc:

Reactor Vessel Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

TAF Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Low Select Sensor Locations:

RX Vessel - Upper Head Alarm/Trip Set Points:

Lo-Lo: 99.99%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Reactor head water level indication consists of the lower of 2 QSPDS Trains of the top 2 sensors (1 & 2) of an eight sensor probe. Each sensor consists of a heated and an unheated thermocouple pair. The probe extends from the top of the head to the top of the fuel alignment plate. Sensor 1 is at 179" (33% indicated) above the fuel and sensor 2 is 142" (0% indicated).

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 8 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

RXPLLLOV Plant Spec Point Desc:

Reactor Plenum Water Level Generic/Cond Desc:

Reactor Vessel Plenum Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

TAF Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Low Select Sensor Locations:

Rx Vessel-Plenum Above Core Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Reactor plenum water level indication consists of the lower of 2 QSPDS Trains of the lower 6 sensors (3-8) of an eight sensor probe. Each sensor consists of a heated and an unheated thermocouple pair. Sensor locations above the fuel from top to bottom (i.e.,

sensors 3-8) are 128", 98", 69", 55", 40", and 24" respectively. Indicated levels are 81%, 58%, 40%,

28%, 16%, and 0% respectively.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 9 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

Temp Core Ex Point ID:

CET V Plant Spec Point Desc:

Core Exit Temperature Generic/Cond Desc:

Highest Temp At Core Exit Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

2300 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Hi Select Sensor Locations:

Inside Reactor Vessel-Core Exit Area Alarm/Trip Set Points:

Lo: 540°F Hi: 650°F NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Signals originate from 2 QSPDS (Qualified Safety Parameter Display System) Channel Trains selecting the higher of 2 calculated representative core exit thermocouple (CET) temperatures. The representative CET temperature is the average of the highest eight valid CETs for that Train.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 10 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

Sub Margin Point ID:

SCMCETLOV Plant Spec Point Desc:

Subcooling Generic/Cond Desc:

Sat Temp - Highest CET Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

- 2100 Maximum Instr Range:

700 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Low Select Sensor Locations:

Core Exit Channels Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Signals originate from 2 QSPDS (Qualified Safety Parameter Display System) Channel Trains selecting the lower of 2 calculated subcooled margins. The QSPDS subcooled margin calculation for each Train uses a representative CET temperature input (based on statistical analyses) as measured against saturation temperature for existing RCS pressure.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 11 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

RCSA AVF V Plant Spec Point Desc:

RCS A Average Flow Generic/Cond Desc:

RCS Loop A Coolant Flow Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

1% = 895 gpm Minimum Instr Range:

0 Maximum Instr Range:

120 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/6 % Deviation Limit Sensor Locations:

RCS Lower Loop Piping Alarm/Trip Set Points:

Lo: 104% LoLo Rx Trip: 90%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

6% deviation (5370 gpm) being the limit for use in averaging calculation and for Quality determination.

The flow is based on a differential pressure developed by a flow elbow located in the main coolant loop.

100% flow: - 89,500 gpm. Lo RCS Flow Rx Trip at

-90%. Minimum DNB flow: 104%.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 12 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

RCSBAVF V Plant Spec Point Desc:

RCS B Average Flow Generic/Cond Desc:

RCS Loop B Coolant Flow Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

1% = 895 gpm Minimum Instr Range:

0 Maximum Instr Range:

120 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/6 % Deviation Limit Sensor Locations:

RCS Lower Loop Piping Alarm/Trip Set Points:

Lo: 104% LoLo Rx Trip: 90%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

6% deviation (5370 gpm) being the limit for use in averaging calculation and for Quality deterrination.

The flow is based on a differential pressure developed by a flow elbow located in the main coolant loop.

100% flow: - 89,500 gpm. Lo RCS Flow Rx Trip at

-90%. Minimum DNB flow: 104%.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 13 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

RCSC AVFV Plant Spec Point Desc:

RCS C Average Flow Generic/Cond Desc:

RCS Loop C Coolant Flow Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

1% = 895 gpm Minimum Instr Range:

0 Maximum Instr Range:

120 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/6 % Deviation Limit Sensor Locations:

RCS Lower Loop Piping Alarm/Trip Set Points:

Lo: 104% LoLo Rx Trip: 90%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation NO For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

6% deviation (5370 gpm) being the limit for use in averaging calculation and for Quality determination.

The flow is based on a differential pressure developed by a flow elbow located in the main coolant loop.

100% flow: - 89,500 gpm. Lo RCS Flow Rx Trip at

-90%. Minimum DNB flow: 104%.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 14 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

SG LEVEL 1/A Point ID:

SGAAVL V Plant Spec Point Desc:

Steam Generator Level A Generic/Cond Desc:

Steam Generator A Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

1% = 112.5 GALLONS Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

U-Tubes Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/10% Deviation Limit Sensor Locations:

SG Vessel A 30' 6" El Alarm/Trip Set Points:

Lo-Lo Rx Trip: 16% Lo: 35% Hi 68% Hi-Hi: 80%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation NO For DP Transmitters Level Reference Leg:

WET Unique System Desc:

10 % deviation being the limit for use in calculation and quality determination.

0%

= 16,250 gal 100% = 27,500 gal The lower tap is 8" above the top of the tube bundle.

Protection Train: 16 % Reactor Trip, 80 % Turbine Trip

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 15 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

L477_A Plant Spec Point Desc:

Steam Generator A Wide Rng Level Generic/Cond Desc:

Steam Generator A WR Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

See Description Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

Tubesheet Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Containment 30' 6" El Alarm/Trip Set Points:

Lo: 40% Hi: 93%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:

WET Unique System Desc:

0% = 750 gal 100% = 27,500 gal Percent to gal conversion is:

0-52 %: 187 gal / %

52-73 %: 274 gal / %

73-100%: 417gal/%.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 16 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

SG LEVEL 2/B Point ID:

SGBAVL_V Plant Spec Point Desc:

Steam Generator Level B Generic/Cond Desc:

Steam Generator B Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

1% = 112.5 GALLONS Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

U-Tubes Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/1 0% Deviation Limit Sensor Locations:

SG Vessel B 30' 6" El Alarm/Trip Set Points:

Lo-Lo Rx Trip: 16% Lo: 35% Hi 68% Hi-Hi: 80%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

Wet Unique System Desc:

10 % deviation being the limit for use in calculation and quality determination.

0%

= 16,250 gal 100% = 27,500 gal The lower tap is 8" above the top of the tube bundle.

Protection Train: 16 % Reactor Trip, 80 % Turbine Trip.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 17 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

L487_A Plant Spec Point Desc:

Steam Generator B Wide Rng Level Generic/Cond Desc:

Steam Generator B WR Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

See Description Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

Tubesheet Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Containment 30' 6" El Alarm/Trip Set Points:

Lo: 40% Hi: 93%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:.

WET Unique System Desc:

0% = 750 gal 100% = 27,500 gal Percent to GAL conversion is:

0-52 %: 187 gal / %

52-73 %: 274 gal / %

73-100 %: 417 gal/%

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 18 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

SG LEVEL 3/C Point ID:

SGCAVL V Plant Spec Point Desc:

Steam Generator Level C Generic/Cond Desc:

Steam Generator C Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

1% = 112.5 gallons Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

U-Tubes Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/10% Deviation Limit Sensor Locations:

SG Vessel C 30' 6" El Alarm/Trip Set Points:

Lo-Lo Rx Trip: 16% Lo: 35% Hi 68% Hi-Hi: 80%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

Wet Unique System Desc:

10 % deviation being the limit for use in calculation and quality determination.

0%

= 16,250 gal 100% = 27,500 gal The lower tap is 8" above the top of the tube bundle.

Protection Train: 16 % Reactor Trip, 80 % Turbine Trip.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 19 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A.

NRC ERDS Parameter:

NL Point ID:

L497 A Plant Spec Point Desc:

Steam Generator C Wide Rng Level Generic/Cond Desc:

Steam Generator C WR Water Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

See Description Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

Tubesheet Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Containment 30' 6" El Alarm/Trip Set Points:

Lo: 40% Hi: 93%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:

WET Unique System Desc:

0% = 750 gal 100% = 27,500 gal Percent to GAL conversion is:

0-52 %: 187 gal /%

52-73 %: 274 gal/ %

73-100 %: 417 gal/%

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 20 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

SG PRESS 1/A Point ID:

SGA AVPV Plant Spec Point Desc:

Steam Generator Pressure A Generic/Cond Desc:

Steam Generator A Pressure Analog/Digital:

A Engr Units/Dig States:

psig Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

1400 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

.3 Input Average w/21 psig Deviation limit Sensor Locations:

SG A Steam Line before MSIV Alarm/Trip Set Points:

Lo: 614 psig Hi: 1085 psig NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

21 psig deviation being the limit for use in calculation and for Quality determination.

ESF actuation signals:

SG pressure 100 psig < steam header pressure SG pressure of < 614 psig

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 21 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

SG PRESS 2/B Point ID:

SGBAVP_V Plant Spec Point Desc:

Steam Generator Pressure B Generic/Cond Desc:

Steam Generator B Pressure Analog/Digital:

A Engr Units/Dig States:

psig Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

1400 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/21 psig Deviation limit Sensor Locations:

SG B Steam Line before MSIV Alarm/Trip Set Points:

Lo: 614 psig Hi: 1085 psig NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

21 psig deviation being the limit for use in calculation and for Quality determination.

ESF actuation signals:

SG pressure 100 psig < steam header pressure SG pressure of< 614 psig

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 22 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

SG PRESS 3/C Point ID:

SGC AVPV Plant Spec Point Desc:

Steam Generator Pressure C Generic/Cond Desc:

Steam Generator C Pressure Analog/Digital:

A Engr Units/Dig States:

psig Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

1400 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average w/21 psig Deviation limit Sensor Locations:

SG C Steam Line before MSIV Alarm/Trip Set Points:

Lo: 614 psig Hi: 1085 psig NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

N/A Temperature Compensation As-Is For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

21 psig deviation being the limit for use in calculation and for Quality determination.

ESF actuation signals:

SG pressure 100 psig < steam header pressure SG pressure of< 614 psig

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 23 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

MN FD FL 1/A Point ID:

SGAAVFWF V Plant Spec Point Desc:

Feedwater Flow A SG Generic/Cond Desc:

Steam Generator A Mn Feedwater Fl Analog/Digital:

A Engr Units/Dig States:

Lb/Hr Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

5.OE +6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

Upstream FW Regulating Valve Alarm/Trip Set Points:

See Description NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes poor quality. Protection Train instrumentation has 2 separate channels of input to a reactor trip signal when:

Feedwater flow < Steam Flow @ 773,000 lb/Hr coincident SG level of -10%

Feedwater < Steam Flow alarm @ 500,000 lb/Hr

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 24 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

MN FD FL 2/B Point ID:

SGBAVFWFV Plant Spec Point Desc:

Feedwater Flow B SG Generic/Cond Desc:

Steam Generator B Mn Feedwater Fl Analog/Digital:

A Engr Units/Dig States:

lb/Hr Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

5.OE +6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

Upstream FW Regulating Valve Alarm/Trip Set Points:

See Description NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation NO For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes poor quality. Protection Train instrumentation has 2 separate channels of input to a reactor trip signal when:

Feedwater flow < Steam Flow @ 773,000 lb/Hr coincident SG level of -10%

Feedwater < Steam Flow alarm @ 500,000 lb/Hr

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 25 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

MN FD FL 3/C Point ID:

SGCAVFWF V Plant Spec Point Desc:

Feedwater Flow C SG Generic/Cond Desc:

Steam Generator C Mn Feedwater Fl Analog/Digital:

A Engr Units/Dig States:

lb/Hr Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

5.OE +6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

Upstream FW Regulating Valve Alarm/Trip Set Points:

See Description NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes poor quality. Protection Train instrumentation has 2 separate channels of input to a reactor trip signal when:

Feedwater flow < Steam Flow @ 773,000 lb/Hr coincident SG level of -10%

Feedwater < Steam Flow alarm @ 500,000 lb/Hr

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 26 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

AX FD FL 1/A Point ID:

SGAAFWFV Plant Spec Point Desc:

Aux Feedwater Flow A SG Generic/Cond Desc:

Steam Generator A Aux FW Flow Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

600 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Sum Sensor Locations:

Aux FW lines Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation NO For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Total AFW flow is the sum of Train One and Train Two to each SG. The aux feed is supplied by 3 steam driven pumps which discharge to 2 redundant trains.

Each train supplies flow to both Units and may feed any of the SGs. Administratively, pump A is aligned to Train One and pumps B and C to Train Two. The 2 condensate storage tanks are the normal water supplies to the AFW pumps.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 27 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

AX FD FL 2/B Point ID:

SGBAFWF V Plant Spec Point Desc:

Aux Feedwater Flow B SG Generic/Cond Desc:

Steam Generator B Aux FW Flow Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

600 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Sum Sensor Locations:

Aux FW lines Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation NO For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Total AFW flow is the sum of Train One and Train Two to each SG. The aux feed is supplied by 3 steam driven. pumps which discharge to 2 redundant trains.

Each train supplies flow to both Units and may feed any of the SGs. Administratively, pump A is aligned to Train One and pumps B and C to Train Two. The 2 condensate storage tanks are the normal water supplies to the AFW pumps.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 28 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

AX FD FL 3/C Point ID:

SGCAFWF V Plant Spec Point Desc:

Aux Feedwater Flow C SG Generic/Cond Desc:

Steam Generator C Aux FW Flow Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

600 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Sum Sensor Locations:

Aux FW lines Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Total AFW flow is the sum of Train One and Train Two to each SG. The aux feed is supplied by 3 steam driven pumps which discharge to 2 redundant trains.

Each train supplies flow to both Units and may feed any of the SGs. Administratively, pump A is aligned to Train One and pumps B and C to Train Two. The 2 condensate storage tanks are the normal water supplies to the AFW pumps.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 29 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

HL TEMP 1/A Point ID:

THAAVTP V Plant Spec Point Desc:

RCS Hot Leg A Avg Temp Generic/Cond Desc:

Steam Generator A Inlet Temp Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

750 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RCS Hot Leg A Piping 14' El Alarm/Trip Set Points:

Lo: 540'F Hi: 620'F NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The sensors are platinum RTDs which are located in wells in the main coolant loops.

The loop T-Hot signals are also inputs to the Qualified Safety Parameter Display System.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Attachmnent 2 Page 30 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

HL TEMP 2/B 1

-3 Point ID:

THB AVTP V Plant Spec Point Desc:

RCS Hot Leg B Avg Temp Generic/Cond Desc:

Steam Generator B Inlet Temp Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

750 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RCS Hot Leg B Piping 14' El Alarm/Trip Set Points:

Lo: 540OF Hi: 620'F NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The sensors are platinum RTDs which are located in wells in the main coolant loops.

The loop T-Hot signals are also inputs to the Qualified Safety Parameter Display System.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Attachmnent 2 Page 31 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

HL TEMP 3/C Point ID:

THCAVTP V Plant Spec Point Desc:

RCS Hot Leg C Avg Temp Generic/Cond Desc:

Steam Generator C Inlet Temp Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

750 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RCS Hot Leg C Piping 14' El Alarm/Trip Set Points:

Lo: 540'F Hi: 620'F NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The sensors are platinum RTDs which are located in wells in the main coolant loops.

The loop T-Hot signals are also inputs to the Qualified Safety Parameter Display System.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 32 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CL TEMP 1/A Point ID:

TCAAVTP V Plant Spec Point Desc:

RCS Cold Leg A Avg Temp Generic/Cond Desc:

Steam Generator A Outlet Temp Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

750 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RCS Cold Leg A Piping 14' El Alarm/Trip Set Points:

Lo: 540'F H: 555°F NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The sensors are platinum RTDs which are located in wells in the main coolant loops.

The loop T-Cold signals are also inputs to the Qualified Safety Parameter Display System.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 33 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CL TEMP 2/B Point ID:

TCBAVTPV Plant Spec Point Desc:

RCS Cold Leg B Avg Temp Generic/Cond Desc:

Steam Generator B Outlet Temp Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

750 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RCS Cold Leg B Piping 14' El Alarm/Trip Set Points:

Lo: 540'F H: 555°F NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The sensors are platinum RTDs which are located in wells in the main coolant loops.

The loop T-Cold signals are also inputs to the Qualified Safety Parameter Display System.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 34 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CL TEMP 3/C Point ID:

TCCAVTPV Plant Spec Point Desc:

RCS Cold Leg C Avg Temp Generic/Cond Desc:

Steam Generator C Outlet Temp Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

750 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RCS Cold Leg C Piping 14' El Alarm/Trip Set Points:

Lo: 540'F Hi: 5557F NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. The sensors are platinum RTDs which are located in wells in the main coolant loops.

The loop T-Cold signals are also inputs to the Qualified Safety Parameter Display System.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 35 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

RCS PRESSURE Point ID:

RCSAVP V Plant Spec Point Desc:

RCS Pressure WR Generic/Cond Desc:

Reactor Coolant System Pressure Analog/bigital:

A Engr Units/Dig States:

psig Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

3000 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

RCS Loop A & B Hot Legs 14' El Alarm/Trip Set Points:

Lo: 1910 psig Hi: 2310 psig NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

RCS pressure is the average of 2 inputs (P404 & P406).

5 % Deviation check meaning the value at which point becomes Poor Quality.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 36 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

PRZR LEVEL Point ID:

PRZ AVLV Plant Spec.Point Desc:

Pressurizer Average Level Generic/Cond Desc:

Primary System Pressurizer Level Analog/Digital:

A Engr Units/Dig States:

Engr Units Conversion:

1% = 84.5 gallons Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

Compix Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Average Sensor Locations:

PRZ Vessel 30' El Alarm/Trip Set Points:

Lo: 14% Hi: 92%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation No For DP Transmitters Level Reference Leg:

Wet Unique System Desc:

The pressurizer average level is calculated using 5 minute rolling averages of 3 redundant sensors. The instrument range of 0-100% is equivalent to 600-9050 gallons. Protection Channel inputs include: PZR Hi-Level Rx trip (2/3 at 91%), Lo-Lo level alarm at 6%,

PZR heaters Off and letdown isolate at 14.4%, Hi level alarm at +5% program, and Lo level alarm at -5%

program.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 37 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

RCS CHG/MU Point ID:

F122_A Plant Spec Point Desc:

Charging Flow Generic/Cond Desc:

Primary System Charging/MU Flow Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

150 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Charging Pumps Discharge Header Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Charging flow is provided by 3 electrically driven positive displacement pumps. The discharge is to a common header (where the flow is measured) and provides cooled RCP seal water flow and re-heated flow that can be directed to loops A cold leg, C hot leg, or to the pressurizer auxiliary spray line. Charging flow rate is normally controlled by pressurizer level.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 38 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

F932_A Plant Spec Point Desc:

HHSI Flo A HL Inside Containment Generic/Cond Desc:

High Press SI Flow To HL A Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

600 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

I How Processed:

N/A Sensor Locations:

On SI line to Hot Leg A 14' El Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

FT-932 measures HHSI flow to the loop A hot leg.

HHSI is provided by 2 electrically driven pumps. The water supply is the Unit 3 RWST. The discharge of each pump is directed to a common discharge header to the A and/or B hot legs. Note: The Unit 3 & 4 RWSTs may be cross-connected and Unit 3 & 4 HHSI pumps discharge headers may be cross-connected.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 39 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

F933_A Plant Spec Point Desc:

HHSI Flo B HL Inside Containment Generic/Cond Desc:

High Press SI Flow To HL B Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

600 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

On SI line to Hot Leg B 14' El Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

FT-933 measures HHSI flow to loop A and/or B hot legs. HHSI is provided by 2 electrically driven pumps.

The water supply is the Unit 3 RWST. The discharge of each pump is directed to a common discharge header to the A and/or B hot legs. Note: The Unit 3 & 4 RWSTs may be cross-connected and Unit 3 & 4 HHSI pumps discharge headers may be cross-connected.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 40 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

HPSI FLOW Point ID:

F943_A Plant Spec Point Desc:

HHSI Flo To BIT To Cold Legs Generic/Cond Desc:

High Press SI Flow To Cold Legs Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

1000 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

SI line upstream of Discharge Header MOVs Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

FT-943 measures total HHSI flow to loops A, B, and C cold legs. HHSI is provided by 2 electrically driven pumps. The water supply is the Unit 3 RWST. The discharge of each pump is directed to a common discharge header to the 3 cold legs. Note: The Unit 3

& 4 RWSTs may be cross-connected and Unit 3 & 4 HHSI pumps discharge headers may be cross-connected.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 41 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

LP SI FLOW Point ID:

F605_A Plant Spec Point Desc:

RHR System Flow Generic/Cond Desc:

Lo Pressure SI Flow Analog/Digital:

A Engr Units/Dig States:

gpm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

8500 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

RHR/SI Header to Cold Legs (in RHR HX Room)

Alarm/Trip Set Points:

Hi: 7000 gpm NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation No For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

FT-605 measures the Residual Heat Removal (RHR) flow. RHR is provided by 2 RHR pumps. Each pump discharges to its own associated heat exchanger. Flow from the heat exchangers are combined into a single header for penetration into containment. Flow in this header is measured by FT-605, flow is then directed to loops A, B, and C cold legs. This flow signal also actuates a low flow alarm annunciator at 3000 gpm.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 42 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CTMNT SMP NR Point ID:

CHILVLLV Plant Spec Point Desc:

CNTMT LR Sump Water Level Generic/Cond Desc:

Containment Sump Lo-Range Level Analog/Digital:

A Engr Units/Dig States:

Inches Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

369 Zero Point

Reference:

-18' 8" El Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Hi Select w/ 5% Deviation check Sensor Locations:

Containment Sump Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Containment sump level is the highest of the two sump level channels. Each channel consists of 5 segment, float and reed switch level column. The level column starts at the -18'8" elevation (i.e., below sea level) and covers 30'9" of level. The conversion from inches to gallons is non-linear. Note: The elevation between 12' and 14'3" is not covered by the containment sump or containment level transmitters.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 43 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CTMNT SMP WR Point ID:

CHILVLH V Plant Spec Point Desc:

CNTMT HR Water Level Generic/Cond Desc:

Containment Sump Hi-Range Level Analog/Digital:

A Engr Units/Dig States:

Inches Engr Units Conversion:

N/A Minimum Instr Range:

397 Maximum Instr Range:

487.5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Hi Select Sensor Locations:

Containment Floor 14' El & Above Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Containment level is the highest of the 2 containment level channels. Each channel consists of a float and reed switch level column. The level column starts at the 14'3" elevation and covers 7'6" of level. The conversion from inches to gallons is non-linear. Note:

The elevation between 12' and 14'3" is not covered by the containment sump or containment level transmitters.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 44 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

R14-A Plant Spec Point Desc:

Plant Vent Gas Activity Generic/Cond Desc:

Radioactivity Of A Released Gas Analog/Digital:

A Engr Units/Dig States:

cpm Engr Units Conversion:

N/A Minimum Instr Range:

10 Maximum Instr Range:

1 E6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Top Of Plant Vent Stack Alarm/Trip Set Points:

Determined By Radiochemist NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

R-14 is installed inside the plant vent. It consists of 4 thin-walled Gieger-Mueller tube detectors arranged across the plant vent stack diameter. The 4 detectors operate in parallel, are Beta-Gamma sensitive in the range of 5E-7 to 1 E4 Ci/cc, and have a check source.

R-14 alarm will automatically close the Gas Decay Tank discharge valve upon actuation. Note: cpm to uCi/cc conversion factor is 2E8 ml/cc at sample flow rate.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 45 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

EFF GAS RAD Point ID:

R6304HRA Plant Spec Point Desc:

Plant Vent Gas Gamma Hi Range Generic/Cond Desc:

Radioactivity Of Released Gases Analog/Digital:

A Engr Units/Dig States:

uCi/cc Engr Units Conversion:

N/A Minimum Instr Range:

1.OE1 Maximum Instr Range:

1.0E5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

1 How Processed:

Data Link Sensor Locations:

Auxiliary Building Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

An Eberline SPING Unit provides Plant Vent High Range Noble Gas Activity. The detector type is a Geiger-Mueller tube, uncompensated with a check source. The plant vent stack is the normal discharge path for: Unit 3 & 4 containment purge, auxiliary building exhaust and Unit 4 SFP. Note: Unit 3 SFP exhaust is through a dedicated stack.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 46 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

R6304FLOA Plant Spec Point Desc:

Plant Vent Flow Rate Generic/Cond Desc:

Plant Vent Stack Flow Rate Analog/Digital:

A Engr Units/Dig States:

cfm Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

1.5E+5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

1 How Processed:

Data Link Sensor Locations:

Plant Vent Stack Near Top Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Plant vent flow is provided by transmitter FT-6584 which measures the differential pressure across a flow orifice installed in the plant vent stack. The signal is processed by an optional analog to digital channel

(#10) on the Plant Vent SPING unit. Note: Loss of plant vent flow channel will not affect the calibration of the plant vent high range gas monitor which is based on a fixed sample flow rate.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 47 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

R6418HRA Plant Spec Point Desc:

U3 Fuel Pool Gas Gamma Hi Rng Generic/Cond Desc:

Radioactivity Of Released Gases Analog/Digital:

A Engr Units/Dig States:

uCi/cc Engr Units Conversion:

N/A Minimum Instr Range:

1.OEI Maximum Instr Range:

1.0E+5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

1 How Processed:

Data Link Sensor Locations:

U3 Spent Fuel Pool Vent Stack Alarm/Trip Set Points:

Determined By Radiochemist NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

An Eberline SPING Unit provides the Unit 3 Spent Fuel Pit High Range Noble Gas Activity. The detector type is a Geiger-Mueller tube, uncompensated with a check source. The Unit 3 spent fuel pit exhaust is through a dedicated stack. The flow rate is -18,500 cfm when the exhaust fan is running. Note: Use point FAN3V21 A as an indication of fan running.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 48 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

EFF LIQ RAD Point ID:

R18-A Plant Spec Point Desc:

Liquid Release Gross Activity Generic/Cond Desc:

Radioactivity Of Released Liquid Analog/Digital:

A Engr Units/Dig States:

cpm Engr Units Conversion:

N/A Minimum Instr Range:

10 Maximum Instr Range:

1.0E+6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Liquid Release Line In Aux Bldg Alarm/Trip Set Points:

Determined By Radiochemist NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

R-18 monitors liquid waste release activity in the waste discharge header upstream of the liquid release isolation valve RCV-0l18. The detector is a sodium iodide scintillation tube, lead shielded against background. The alarm setpoint is plant condition dependent and set by the Radiochemist. The liquid waste control valve (RCV-18) auto isolates on a high activity alarm. Note: the cpm to uci/cc conversion factor is 2.96E7 ml-cpm at 100 gpm.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 49 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

R15iA Plant Spec Point Desc:

Condenser Air Ejector (PRMS)

Generic/Cond Desc:

Condenser Air Ejector Rad Analog/Digital:

A Engr Units/Dig States:

cpm Engr Units Conversion:

N/A Minimum Instr Range:

10 Maximum Instr Range:

1.0E+6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Turbine Deck Alarm/Trip Set Points:

Determined By Radiochemist NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

R-15, the Condenser Air Ejector Monitor uses a thin wall Geiger-Mueller tube detector. The detector is located in the air ejector exhaust manifold and uses lead shielding against background. The alarm setpoint is plant condition dependent and is determined by the Radiochemist.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 50 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

COND A/E RAD Point ID:

R6417HR A Plant Spec Point Desc:

Air Ejector Gas Gamma Hi-Rng Generic/Cond Desc:

Condenser Air Ejector Rad Analog/Digital:

A Engr Units/Dig States:

uCi/cc Engr Units Conversion:

N/A Minimum Instr Range:

1.OE1 Maximum Instr Range:

1.0E+5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

1 How Processed:

Data Link Sensor Locations:

Turbine Deck Alarm/Trip Set Points:

Determined By Radiochemist NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

M/A Unique System Desc:

An Eberline SPING Unit provides the Air Ejector Plant Vent Hi-Range Noble Gas Activity. The detector type is a Gieger-Mueller tube, uncompensated with a check source.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 51 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CNTMT RAD Point ID:

CHRADWV Plant Spec Point Desc:

Containment Radiation (WR)

Generic/Cond Desc:

Radiation Level In Containment Analog/Digital:

A Engr Units/Dig States:

R/Hr Engr Units Conversion:

N/A Minimum Instr Range:

1.0 Maximum Instr Range:

1.0E+8 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Hi Select w/ 5 % Deviation limit Sensor Locations:

Rx Bldg @ 25' & 64' El Alarm/Trip Set Points:

Hi: 1.3E4 R/Hr Hi-Hi: 1.3E5 R/Hr NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

CNTMT RAD is the higher of 2 channel inputs (RAD63 11 A and RAD63 11 B). Both use ion chamber detectors. RAD63 11A is located inside containment on the 25' level near the personnel hatch and RAD631 lB is near the 64' level on the SG shield wall near the pressurizer ARMS channel R-2. These channels have 2 Hi Alarm setpoints, the first one activating an annunciator.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 52 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

RCS LTDN RAD Point ID:

R20OV Plant Spec Point Desc:

RCS Letdown Line Activity Generic/Cond Desc:

Rad Level Of The RCS Letdown Analog/Digital:

A Engr Units/Dig States:

mR/Hr Engr Units Conversion:

N/A Minimum Instr Range:

1.0 Maximum Instr Range:

1.0E+5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

RCS letdown piping upstream of HX Alarm/Trip Set Points:

Hi 5.0E+4 mR/Hr NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Low Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

R-20 provides reactor coolant letdown line activity.

The monitor is located on the letdown line, outside of containment and upstream of the non-regenerative heat exchanger. The monitor is external to the piping system and far enough from the coolant loop that a 40 second transient time is provided for N16 gamma decay. The detector is a Geiger-Mueller tube.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 53 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

N/L Point ID:

R6426 A Plant Spec Point Desc:

Main Stm Lines Gamma Hi Rng Generic/Cond Desc:

Main Steam Lines Radioactivity Analog/Digital:

A Engr Units/Dig States:

uCi/cc Engr Units Conversion:

N/A Minimum Instr Range:

1.0EI Maximum Instr Range:

1.0E+5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

I How Processed:

Data Link Sensor Locations:

Main Steam Sample lines Alarm/Trip Set Points:

Determined By Plant Radiochemist NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

RAD6426-Main Steam Line High Range Gamma is measured by the Eberline DAM-1. Detector type is a Gieger-Mueller Tube with no compensation. Note:

sample lines from all 6 SGs run simultaneously through the detector. To identify a ruptured SG, manual isolation valves must be operated.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 54 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

R19-A Plant Spec Point Desc:

Stm Gen Liquid Sample Activity Generic/Cond Desc:

SG Blowdown Radioactivity Analog/Digital:

A Engr Units/Dig States:

cpm Engr Units Conversion:

N/A Minimum Instr Range:

10 Maximum Instr Range:

1.0E+6 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

Auxiliary Bldg N-S Hallway Alarm/Trip Set Points:

Determined By Radiochemist NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

10 Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Detector type - Scintillation. Located in the combined SG sample line. R-19 provides for auto closure of all 3 (Unit 3) SG sample lines, all 3 blowdown flow control valves, and both (2) blowdown tank drain valves. High Alarm setpoint is determined by Radiochemist based on plant conditions.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 55 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CTMNT PRESS Point ID:

CAVPRSW V Plant Spec Point Desc:

Containment Pressure (WR)

Generic/Cond Desc:

Containment Pressure Analog/Digital:

A Engr Units/Dig States:

psig Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

180 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

South Penetration Room Alarm/Trip Set Points:

Hi: 20 psig Hi-Hi: 55 psig NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. Containment pressure transmitters provide containment Hi and Hi-Hi actuation of the ESFAS circuitry at 4 psig and 20 psig respectively. Hi containment pressure actuates Safety Injection, while the Hi-Hi pressure coincident with the Hi pressure will actuate containment sprays and Phase B Containment Isolation.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 56 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

CTMNT TEMP Point ID:

CHITMPV Plant Spec Point Desc:

Containment Temperature Generic/Cond Desc:

Containment Temperature Analog/Digital:

A Engr Units/Dig States:

OF Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

300 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

3 How Processed:

3 Input Hi Select Sensor Locations:

Containment El 58' @ 120' Intervals Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

As-Is Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

The containment temperature is the average of 3 channels (TE6700, TE6701, and TE6702). Each channel uses platinum RTD. TE6700 is located near the 3B Normal Containment Cooler, TE6701 is located near the 3C Normal Containment Cooler, TE6702 is located near the 3C Emergency Containment Filters.

CHITMPV provides an input to DEGCNTMTV alarm @ 140 OF.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 57 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

H2 CONC Point ID:

CH2CONCV Plant Spec Point Desc:

CTMT Hydrogen Concentration Generic/Cond Desc:

Containment Atmosphere H2 Conc Analog/Digital:

A Engr Units/Dig States:

% H2 Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

10 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Hi Select w/ 5 % Deviation check Sensor Locations:

Aux Bldg Basement Alarm/Trip Set Points:

4%

NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

AS-IS Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Two channels of instrumentation are provided, the highest which is reported. A % H2 signal is developed by comparing the thermal conductivity of a reference sample with the conductivity of a sample after removing any nitrogen. The system provides a high H2 annunciator alarm at 7.5%, Low and Hi Cell Failure, Calibration Gas Low Pressure, Reagent Gas Low Pressure, and Low Analyzer Flow Alarm.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 58 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

RWST LEVEL Point ID:

RWSTAVL V Plant Spec Point Desc:

RWST (Unit 3) Average Level Generic/Cond Desc:

Borated Water Storage Tank Level Analog/Digital:

A Engr Units/Dig States:

gal Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

335,000 gals Zero Point

Reference:

TNKBOT Reference Point Notes:

N/A PROC or SENS:

P Number of Sensors:

2 How Processed:

2 Input Average w/ 5 % Deviation check Sensor Locations:

Ground Level by RWST Alarm/Trip Set Points:

See Description NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

AS-IS Temperature Compensation N/A For DP Transmitters Level Reference Leg:

DRY Unique System Desc:

5 % Deviation check meaning the value at which point becomes Poor Quality. Each RWST level loop consists of a Rosemount DP transmitter and Foxboro Modules to provide alarm and indication functions. Alarms provided are: Lo-Lo Level at 60,000 gallons, Low Level at 155,000 gallons, Tech Spec Min Level at 322,000 gallons and Hi Level at 333,000 gallons.

Note: the RWST is the Borated Water Storage Tank.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 59 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

WIND SPEED Point ID:

WS10MLUA Plant Spec Point Desc:

10 Meter Wind Speed (T.P.)

Generic/Cond Desc:

Wind Speed At Reactor Site Analog/Digital:

A Engr Units/Dig States:

mph Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

100 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

10 Meter Tower I Mile SW of Plant Alarm/Trip Set Points:

Hi: 75 mph Hi-Hi: 90 mph NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

0 Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Wind Speed meteorological data is gathered by instruments mounted on a 10 meter tower. The data (a 15 minute running average) is transmitted by radio to the plant and is received by the Campbell Scientific equipment located in the Plant Computer Room.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 60 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

WIND DIR Point ID:

WD1OMLUA Plant Spec Point Desc:

10 Meter Wind Direction (T.P.)

Generic/Cond Desc:

Wind Direction At Reactor Site Analog/Digital:

A Engr Units/Dig States:

0 (Degrees)

Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr Range:

540 Zero Point

Reference:

N/A Reference Point Notes:

0 And 360 Are North. Switch Pt 180 PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

10 Meter Tower 1 Mile Sw Of Plant Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

0 Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Wind direction is provided by instruments mounted on a 10 meter tower. The data (a 15 minute running average) is transmitted by radio to the plant and is received by the Campbell Scientific equipment located in the Computer Room. The 10 Meter Tower is located 1 mile SW of the site. Note: Wind is coming from direction reported by the instrument, with 0 and 360 being North.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 61 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

STABB CLASS Point ID:

STABB SD A Plant Spec Point Desc:

Estimate Of Atmos Stability Generic/Cond Desc:

Air Stability At A Reactor Site Analog/Digital:

A Engr Units/Dig States:

df/mm Engr Units Conversion:

N/A Minimum Instr Range:

-5 Maximum Instr Range:

15 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

60 Meter Tower 7 Miles SSW Of Plant Alarm/Trip Set Points:

N/A NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

-5 Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Atmospheric stability is developed by taking the difference between the temperature at the 10 meter and 60 meters. The difference is multiplied by 2 to obtain the change per 100 meters altitude. A 15 minute running average data transmitted by radio telemetry to a Campbell Scientific receiver in the Plant Computer Room.

Turkey Point Nuclear Plant Docket No. 50-250 L-2012-332 Page 62 of 62 TP3 DATA POINT LIBRARY REFERENCE FILE Date:

08/07/2007 Reactor Unit:

TP3 Data Feeder:

N/A NRC ERDS Parameter:

NL Point ID:

FAN3V21_A Plant Spec Point Desc:

U3 SFP Exhaust Vent Flow Generic/Cond Desc:

U3 Fuel Pool Exhaust Vent Flow Analog/Digital:

D Engr Units/Dig States:

N/A Engr Units Conversion:

N/A Minimum Instr Range:

ON Maximum Instr Range:

OFF Zero Point

Reference:

N/A Reference Point Notes:

Use With RAD6418-3 For Release Rate PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

MCC-3C Alarm/Trip Set Points:

Annunciator Alarm On Fan Trip NI Detector Power Supply N/A Cut-off Power Level:

NI Detector Power Supply N/A Turn-On Power Level:

Instrument Failure Mode:

Off Temperature Compensation N/A For DP Transmitters Level Reference Leg:

N/A Unique System Desc:

Auxiliary contact of Brkr-30769-3 for Unit 3 Spent Fuel Pool Exhaust Fan used to indicate flow through spent fuel pool exhaust stack. See RAD6418-3. Note the flow will be about 18,500 cfm with the fan running.