Insp Rept 50-461/89-12 on 890301-03 & 31.No Violations or Deviations Noted.Major Areas Inspected:Verification That SSER6 Required Remote Shutdown Sys Mods Installed Prior to Startup from First Refueling
ML20244D170
Person / Time
Site: Clinton 
Issue date: 04/14/1989
From: Gardner R, Neisler J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20244D169 List:
References
50-461-89-12, NUDOCS 8904210189
Download: ML20244D170 (3)


Text

_.

- - _

_ _ _ _ - - - _ _

- _ _

t

,

.

'

U.. S. flVCLEAR REGULATORY C0!iMISSION y

REGION III

,

Report No. 50-461/89012(DRS)

Docket No. 50-461'

License No. NPF-62 l

Licensee:

Illinois Power Company 500. South 27th Street Decatur, IL 62525

- Facility Name:

Clinton Power Station Inspection At:

Clinton, Illinois

- Inspection Conducted: March 1-3 and March 31, 1989

[ Date/V'ff

- Inspector:

.J. H. Neisler

-

f M\\h

' Approved By: Ronald N. Gardner, Chief k-lh-89-Plant Systems Section Date Inspection Summary Inspection on March 1-3 and March 31, 1989 (Report No. 461/89012(DRS))

Areas Inspected: Region III verification that SSER-6 required remote

' shutdown system modifications were installed prior.to startup from first refueling (37828).

Results:

No violations or deviations were identified.

$$0 kbo!K 0

@

G i

.:

_ _ _ _ _

'

.

.

DETAILS 1.

Persons Contacted Principle Licensee Employees

  • K. Baker, Supervisor, Licensing

,

  • G. Kyle, Supervising Engineer D. Sykes, Supervising Engineer R. Price, Senior Instructor, Operations C. Tewksbury, Supervising QV Specialist T. Butera, Senior QV Specialist 2.

Remote Shutdown System flodification (Closed) Open Items (461/86054-10) (461/86028-07) (SSER-6)): Verify modifications to allow use of Division II equipment for remote shutdown are implemented prior to startup from the first refueling.

a.

The inspector reviewed Field Engineering Change Notices (FECN) 1567),

15672 and 24304. These FECNs are design change documents that were implemented to effect the modifications to the Division II electrical system. The modification consisted of installing local control switches on circuit breaker doors in parallel with the existing control circuits for the following components:

Reactor Pressure Vessel Head Spray Isolation Valve RHR Pump heat exchanger 1B shell side outlet valve RHR Pump 18 suction valve.

RHR Pump 1B test return to suppression pool valve RHR heat exchanger 1B shell side inlet valve RHR heat exchanger 1B shell side bypass valve RHR Pump 1B minimum flow valve RHR heat exchanger 1B SSil outlet valve RHR heat exchanger 1B SSU inlet valve RHR Pump 1B., LPCI valve RHR shutdown cooling injection valve WS to SX header isolation valve SSU Pump Room 1B supply fan SX Pump 1B RHR Pump 1B b.

The inspector performed a walkdown inspection of the installed modification to verify that the modification had been completed in accordance with the applicable design documents. Local control switches had been braikd as specified in the design change package and ma.ntenance work request (IlllR) No. 40317.

c.

The inspector reviewed the results of acceptance testing accomplished to assure that the modification would perform as designed and would not have an adverse effect on the Division II electrical system's normal safety functions.

The test results

.

..

_ _ _ _ - _ _ - _ _ _ _ _ _.

- - - _ _ _ - _ _ - _ _ _ _ _.

.,

.

.,,.-

indicated that the installed switches would perform their remote

]

shutdown function and would not impact the normal function of the Division II system.

No violations or deviations were identified.

3.

Exit Interview The inspector met with licensee representatives listed in Paragraph 1 and summarized the scope and findings of the inspection. The inspector also discussed the likely informational content of the inspection report with

,