IR 05000306/1980003

From kanterella
Jump to navigation Jump to search
Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in IE Insp Rept 50-306/80-03
ML19309F676
Person / Time
Site: Prairie Island 
Issue date: 04/08/1980
From: Fiorelli G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Gilberts D
NORTHERN STATES POWER CO.
Shared Package
ML19309F677 List:
References
NUDOCS 8004300334
Download: ML19309F676 (2)


Text

MC M

,

f ucm'g

<,9 UNITED STATES

['~

/(f[ g NUCLEAR REGULATORY COMMISSION

$004300 930-g-

/. c REGION lli

{

'

o, 799 ROOSEVELT ROAD

%***.*o GLEN ELLYN,ILLINOls 60137 APR 8 460

-

Docket No. 50-282 Docket No. 50-306 Northern States Power Company ATTN:

Mr. Dennis E. Gilberts Vice President Power Production and System Operation 414 Nicollet Mall Minneapolis, MN 55401 Gentlemen:

k Thank you for your letter dated March 12, 1980, responding to the item of noncompliance which we brought to your attention in Inspection Report No.

l 50-306/80-03 forwarded by our letter dated February 16, 1980.

Our inspector examined Westinghouse Electric Corporation letter dated December 14, 1979, recommending that operating plants should, at their earliest convenient time, perform dye penetrant tests at those pressurizer safe-end nozzle areas not inspected during the last twelve months. This recommendation was based on problems being indentified in these areas at other operating' plants. Northern States Power Company Procedure NSP-PT-1, Revision 1, is the procedure you used to control the quality of this liquid penetrant examination. This procedure requires developer shall be applied after penetrant removal and a 5 minute maximum drying time. Our inspector observed your examiner clean, apply and remove the penetrant on one nozzle, then move over and clean, apply and remove penetrant on a second nozzle. The procedure your examiner used resulted in an approximate 30 minute drying time on the first nozzle and over a 10 minute drying time on the second nozzle prior to applying the developer. This is in violation of your procedure requirements and is the basis for our item of noncompliance.

At no time during this inspection was our inspector informed these areas were going to be refinished and a re-examination performed.

l l

,

/

i

.

--

. __

. __ _----- ---

,_

i

.h O

Northern States Power Compiny-2-l

.

l We will examine the records of your re-examination of these nozzles during

-

l a subsequent inspection.

Your cooperation with us is appreciated.

Sincerely, I

i G. Fiorelli, Chief Reactor Construction and Engineering Support Branch cc:

Mr. F. P. Tierney, Jr.,

Plant Manager l

cc w/ltr dtd 3/12/80:

i Central Files (

Reproduction Unit NRC 20b l

PDh Local PDR NSIC TIC John W. Ferman, Ph.D.,

Nuclear Engineer, MPCA l

l l

.

.

d

.. - -

...

-

-