ET 09-0008, Additional Information Regarding Main Steam and Feedwater Isolation System (Msfis) Controls Modification

From kanterella
Jump to navigation Jump to search

Additional Information Regarding Main Steam and Feedwater Isolation System (Msfis) Controls Modification
ML090630406
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 02/17/2009
From: Garrett T
Wolf Creek
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ET 09-0008
Download: ML090630406 (46)


Text

WF CREEK TNUCLEAR OPERATING CORPORATION Terry J. Garrett Vice President Engineering February 17, 2009 ET 09-0008 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555

Reference:

1) Letter ET 07-0004, dated March 14, 2007, from T. J. Garrett, WCNOC, to USNRC
2) Letter dated May 29, 2007, from J. W. Lubinski, USNRC, to R. A. Muench, WCNOC
3) Letter ET 07-0022, dated June 15, 2007, from T. J. Garrett, WCNOC, to USNRC
4) Letter WO 07-0028, dated November 16, 2007, from T. J.

'.Garrett,-WCNOC, to USNRC

Subject:

Docket No. 50-482: Additional Information Regarding. Main Steam and Feedwater Isolation System (MSFIS) Controls Modification Gentlemen:

Reference 1 provided a license amendment request (LAR) that proposed revisions to Technical Specification (TS) 3.3.2, "Engineered Safety Feature , Actuation System (ESFAS)

Instrumentation," TS 3.7.2, "Main Steam Isolation Valves (MSIVs)," and TS 3.7.3, "Main Feedwater Isolation Valves (MFIVs)." Reference 1 proposed changes to these specifications based on a planned modification to replace the MSIVs and associated actuators, MFIVs and associated actuators, and replacement of the Main Steam and Feedwater Isolation System (MSFIS) controls.

On January 30, 2009, Wolf Creek Nuclear Operating Corporation (WCNOC) was notified of NRC staff concerns regarding an analysis of the replacement MSFIS controls to the requirements of Institute of Electrical and Electronics Engineers (IEEE) Std 603-1998, "IEEE Standard Criteria for Safety Systems for Nuclear Power Generating Stations,' and use'of IEEE Std 603-1998 in WCNOC Specification J-105A(Q) for Replacement MSFIS System. The specific NRC staff concern is that referencing IEEE Std 603-1998 in the WCNOC Specification P.O. Box 411 / Burlington, KS 66839 /Phone: (620) 364-8831 An Equal Opportunity Employer M/F/HC/VET J .

ET 09-0008 Page 2 of 3 would require an exemption to 10 CFR 50.55a, "Codes and standards," paragraph (h),

"Protections and safety systems." Paragraph (h) specifies that protection systems meet the requirements stated in either IEEE Std 279 or IEEE Std 603-1991. Specification J-105A(Q) has been revised to reference IEEE Std 603-1991 and is provided in the Enclosure.

Reference 2 identified additional documentation required by the NRC staff to complete the acceptance review of the application. Item 20 requested an analysis of all IEEE Std 603 requirements with a description of how the Field Programmable Gate Array (FPGA) MSFIS actuation controls meets these requirements. In response to this item, Enclosure 22 to Reference 3 provided an analysis of replacement MSFIS controls to the requirements of IEEE Std 603-1998. This was based on Revision 2 of Specifications J105A(Q) that referenced IEEE Std 603-1998. Reference 3 submitted a "Matrix of IEEE 7-4.3.2 Requirements to MSFIS Controls Design" to address a NRC staff request from a September 25, 2007 teleconference.

This matrix also includes cross references to the IEEE Std 603-1998 requirements. Based on discussions in a teleconference between NRC staff and WCNOC personnel on February 4, 2009, it is WCNOC's understanding that this information is not required and is therefore withdrawing Enclosure 22 to Reference 3 and Reference 4.

The documentation provided in the Enclosure does not impact the conclusions of the No Significant Hazards Consideration provided in Reference 1. In accordance with 10 CFR 50.91, a copy of the submittal is being provided to the designated Kansas State official.

This letter contains no commitments. If you have any questions concerning this matter, please contact me at (620) 364-4084, or Mr. Richard D. Flannigan at (620) 364-4117.

Sincerely, Terry J. Garrett TJG/rlt Enclosure cc: E. E. Collins (NRC), w/e T. A. Conley (KDHE), w/e V. G. Gaddy (NRC), w/e B. K. Singal (NRC), w/e Senior Resident Inspector (NRC), w/e

ET 09-0008 Page 3 of 3 STATE OF KANSAS )

COUNTY OF COFFEY )

Terry J. Garrett, of lawful age, being first duly sworn upon oath says that he is Vice President Engineering of Wolf Creek Nuclear Operating Corporation; that he has read the foregoing document and knows the contents thereof; that he has executed the same for and on behalf of said Corporation with full power and authority to do so; and that the facts therein stated are true and correct to the best of his knowledge, information and belief.

Terry earrett Vice President Engineering SUBSCRIBED and sworn to before me this S I n n e ed

/-/O"day of I-ebroru*r 1./ ,2009.

Notary P~blic GAYLE SHEPHEARD1 mNotary Public - State of KansasI My Appt. Ex,*Is 7!21/2JI J Expiration Date -1212b ,/

Enclosure to ET 09-0008 Specification J105A(Q), Rev. 5, For Replacement MSFIS System

FORM APF-05-004-01, REV 00 WVF CREEK 'r NUCLEAR OPERATING CORPORATION SPECIFICATION J- 105A(Q)

FOR REPLACEMENT MSFIS SYSTEM WOLF CREEK GENERATING STATION (WCGS)

This specificaton consists of the following documents:

1. Specification J-105A(Q), Rev. 5, Replacement MSFIS System
2. Data Sheets: None
3. Attachments:

A. Reference Drawing Package as listed inSpecification J-105A(Q) Section 4.1 D. Specification No. 10466-J-820 Rev. I Seismic Qualification Requirements for Class IE Control and Instrumentation Devices E. Drawing A4-104 Sheet I Rev. 4 Nameplate Standards H. Calculation 0620514.0 l-C-003 Rev. 0

4. Appendices:

A. Input Signals and Sources B. Power Supply Fusing and Supply to the Buyer-Supplied Status Monitor C. Modified Power Supply Fuses and Functions Assigned R. Buyer's Inspection Procedures Form APF-05-004 Documentation Submittal Requirements

=/: 18881

,, JONAL.**o REVISION DESCRIPTION: Rev. 5 changed references to IEEE 603-1991, IEEE 379-1988, and IEEE 384-1981.

J-105A(Q) REV5 SPECIFICATION NUMBER ORIGINATED VERIFIED SUPERVISOR A11ROVED/DATE RELEASED

Form APF-05-004-02, Rev. 0 REVISION STATUS SHEET SPECIFICATION NO: J-105A(Q)

SHEET LATEST SHEET LATEST SHEET LATEST SHEET LATEST SHEET LATEST SHEET LATEST REV. REV. REV. REV. REV. REV.

Cover 4 19 5 Doc Sub I 7

Rev Stat 4 20 5 i

Title 4 21 5 1 4 22 5 2 4 23 5 3 4 24 5 4 4 25 5 5 4 26 5 App. A 6 4 27 5 App. A 7 4 28 5 App. A 8 4 29 5 App. A 9 4 30 5 App. B 10 4 31 5 App. C 11 4 32 5 App. R 12 4 33 5 App. R 13 4 Doc Sub I 14 4 Doc Sub 1 2

15 4 Doc Sub I 3

16 4 Doc Sub I 4

17 4 Doc Sub 1 5

18 4 Doc Sub I 6

Page i Rev. 5

FORM APF-05-004-04, Rev. 0 SPECIFICATION FOR REPLACEMENT MSFIS SYSTEM WOLF CREEK GENERATING STATION (WCGS)

Replacement MSFIS System REV ORG ORIG VER DESCRIPTION SUPV APP/DATE RLSD W t.F CREEK F NUCLEAR OPERATING CORPORATION SIREV SPECIFICATION NIJMBE.R J-1OiA(t'O5

FORM APF-05-004-04, Rev. 0 Specification J-105A Replacement MSFIS System Table of Contents 1.0 SCOPE .............................................................................................. 3 1.2 Related Work Not Included ..................................................................... 4 2.0 OBJECTIVE........................................................................................ 4 3.0 ABBREVIATIONS.................................................................................. 4 4.0 CODES AND STANDARDS ....................................................................... S 4.1 References....................................................................  :................... 5 5.0 DESIGN REQUIREMENTS....................................................................... 6 5.1 Design Conditions............................................................................... 6 5.2 Performance Requirements........ .......................................................... 6 5.2.1 General Design Requirements ........................................................... 6 5.2.2 Modular Design............................................................................. 7 5.2.3 Response Time ............................................................................ 7 5.2.4 System Functional Requirements ..................... I.................................... 7 5.2.5 System Operation .......................................................................... 9 5.2.6 Provisions for System Test of the Safety Function .................................... 11 5.2.7 Electronics Architecture .................................................................. 12 5.3 Material Requirements ......................................................................... 13 5.4 Environmental Requirements................................................................. 13 5.5 Structural Requirements .................................................................  ;..... 13 5.5.1 Cabinets - Existing Configuration ....................................................... 13 5.5.2 Seismic Requirements .......... ;........................:.................................. 14 5.5.3 Replacement Doors........I............................................................... 15 5.6 Electrical Requirements.......................................................................* 15 5.6.1 Noise Rejection and Tolerance.......................................................... 15 5.6.2 Electrical Wiring ........................................................................... 15 5.6.3 Power Supply............................................................................. 16 5.6.4 Interconnection's........................I................................................... 17 5.6.5 Repacement Relays..................................................................... 17 5.6.6 Metal Oxide Varistors - MOVs........................................................... 17 5.6.7 Trouble Alarm............................................................................. 17 5.6.8 Fuses and Fuse Blocks.................................................................. 17 5.6.9 EMI / RFI Requirements ................................................................. 18 5.7 Instrumentation and Control Requirements ................................................. 18 5.8 Maintenance................................ ................. 18 5.9 Redundancy, Separation, and Diversity ...................................................... 18 5.9.1 Independence ............................................................................. 18 5.9.2 Isolation.................................................................................... 18 5.9.3 Separation ................................................................................ 18 5.10 Testability .................................................................................... I... 19 5.11 Interface Requirements........................................ ............*........ 19 5.12 Accessibility for Maintenance, Repair, and In-service Inspection ................... 19 5.13 Fire Protection Requirements.................................................................. 19 REV SPECIFICATO NIJ ER J-105A(O) 5 Page 1

FORM APF-05-004-04,, Rev. 0 6.0 SPARE PARTS AND SPECIAL TOOLS ....................................................... 19 6.1 Spare Parts..........................;........................................................... 19 6.1.1 Special Spare Parts....................................................................... 19 6.1.2 List .............................

.............................................. ......19 6.2 .Special Tools................................................................................... 20 6.2.1 Test Regime............................................................................... 20 6.2.2 Other Special Tools ...................................................................... 20 7.0 STAMPING REQUIREMENTS.................................................................. 20 8.0 FABRICATION.................................................................................... 20 8.1 Welding.......................................................................................... 20 8.2 Protective Coatings.... ......................................................................... 20 8.3 Identification.................................................................................... 20 9.0 INSTALLATION........................................................... ................ 20 10.0 TESTING .......................................................................................... 21 10.1 Seismic.................................................................................... 21 10.2 System Reliability Analysis ................................................................... 21 10.3 Components..................................................................................... 22 10.4 Actuation (Manual).......................................... 7................................... 22 10.5 Deleted ......................................................................................... 22 10.6 Environmental Qualification ................................................................... 22 10.7 EMI / REI Testing .............................................................................. 23 11.0 INSPECTION..................................................................................... 23 12.0 HANDLING, SHIPPING, AND STORAGE ...................................................... 23 12.1 Preparation for Shipment ..................................................................... 23 13.0 DOCUMENTATION REQUIREMENTS......................................................... 23 13.1 Drawings - Outline.............................................................................. 23 13.2 Assembly, Erection, and Installation.......................................................... 23 13.3 Wiring Diagrams................................................................................ 23 13.4 Logic Diagrams....................................:............................................. 23 13.5 Instruction Manuals ............................................................................ 24 13.6 Seismic Data Report and Test Procedures .................................................. 24 13.7 Engineering Performance Test Procedures and Quality Verification Reports ........... .24 ,.

13.8 Schedule ....................................................................................... 24 13.9 Inspection Requirements ..................................................................... 24 13.10 Repair Parts List............................................................................. 24 APPENDICES ........................................ I....s................................................ 25 Appendix A - Input Signals and Sources ............................................................ 25 Appendix B - Power Supply Fusing and Supply to the Buyer-Supplied Status Monitor.......... 29 Appendix C - Modified Power Supply Fuses and Functions Assigned............................ 30 Appendix R - Buyer's Inspectioni Procedures ....................................................... 31 REV SPECIFICATIOIN NUMBER I-1O5A(O) 5 Page 2

FORM APF-05-004-04, Rev. 0 1.0 SCOPE The Scope of Work is to replace various parts of the existing safety-related electronic Main Steam and Feedwater Isolation System (MSFIS) with a safety-related logic-controller-based system to perform the control functions of the Main Steam Isolation Valves (MSIVs) and Main Feedwater Isolation Valves (MFIVs). The Replacement MSFIS System will be installed in conjunction with replacement of the existing electro-pneumatic-hydraulic MSIVs and MFIVs by new MSIVs and MFIVs with system-medium actuators. The MSFIS System, existing and replacement, has two redundant subsystems located in separate cabinets:

MSFIS Channel 1 (1) located in MSFIS Cabinet SA075A MSFIS Channel IV (4) located in MSFIS Cabinet SA075B The replacement project will retain the existing cabinets, external power supply feeds, and channel separation scheme in the overall plant configuration. The replacement project will include changes to the functions by which the Replacement MSFIS System controls the replacement MSIVs and MFIVs. These changes account for the differences in the function of the existing and replacement MSIVs and MFIVs, that is, electro-pneumatic-hydraulic actuators replaced by system-medium actuators.

The existing and replacement MSFIS Systems are both considered digital in that they deal with ON-OFF inputs and outputs, and there are no analog / magnitude inputs and outputs involved. However, the systems do not have general digital computer components and characteristics such as a clock-driven central processing unit in continuous operation.

The Replacement MSFIS System project shall be worked by two suppliers; 1) Control System Supplier (Controls Seller)

2) Qualification Supplier (Qualification Seller). The Controls Seller is responsible for the selection, assembly, implementation testing, dedication, and implementation of the Replacement MSFIS System. The Qualification Seller is responsible for the Qualification of the Replacement MSFIS System supplied by the Controls Seller. The Controls Seller and the Qualification Seller shall each be a qualified I OCFR50 Appendix B vendor.

The Buyer will perform an overall independent Validation & Verification of the Replacement MSFIS System development and implementation. Final approval of the Replacement MSFIS System by the Buyer shall be required to ensure the requirements of this document have been fully satisfied.

1.1 Work Included

1. The Controls Seller's scope of work focuses on selection and production of new items for replacement of existing items, the Controls Seller is also responsible for system selection to perform the required system functions. The Qualification Seller is responsible for factors such as seismic qualification, etc., applied to the final integrated system and cabinet configuration.
2. Replacement of the existing MSFIS system components in the form of circuit cards. The existing system includes input buffer cards, valve controller module cards, and relay driver cards. These components shall be replaced by a logic-controller-based system which performs the required functions of the replacement MSIVs and MFIVs. Replacement of the racks which contain and support these circuit cards is included if required by the configuration, quantity, ambient temperature / cooling, back-plane wiring, or any other configuration aspect of the replacement circuit cards.
3. Appropriate test capability for the replacement system. The existing system's Manual Test Panel may be re-used as is, modified as appropriate, or completely replaced as required by the replacement system configuration.
4. Provide an output dry contact or equivalent in each MSFIS Cabinet for a new summary trouble alarm.
5. Replacement of the existing system power supply modules with redundant hot-swappable power supply modules.
6. Supply of new surge suppressors.

SREV

. 5 SPECIFICATION NUMBER JI-105A(O' Page 3

FORM APF-05-004-04, Rev. 0

7. Mounting hardware and wiring devices as necessary to mount the replacement components and interconnect them to each other and existing circuits.
8. Required new portable test equipment.
9. Initial stock of repair parts for twenty years' use.

Buyer acknowledges that the nature of a replacement system intended for installation in existing cabinets in the Buyer's plant is that it will consist of many small items but no unifying structure. Thus, the items are packed and shipped individually or in groups and require individual installation into the Buyer's cabinets at the Buyer's plant.

Buyer acknowledges that some of the items specified may be delivered ready for use in the form of "One lot - mounting hardware and wiring devices."

1.2 Related Work Not Included

1. Installation of Replacement MSFIS System components in the MSFIS Cabinets.
2. The replacement MSIVs and MFIVs will be supplied and installed by others.
3. Connection of field cables to the replacement MSIVs and MFIVs will be done by others.
4. New field cable required for the new summary trouble alarm.
5. The overall project will also include electrical equipment and circuit changes outside the scope of this Specification.

2.0 OBJECTIVE The plant's existing Main Steam Isolation Valves and Main Feedwater Isolation Valves have electro-pneumatic-hydraulic actuators. The existing valves have a discrete-component solid-state electronic control system to control the valve actuators and thus the valves. The valves will be replaced by new valves with system-medium actuators, rather than the electro-pneumatic-hydraulic actuators. The objective of this Specification is to procure an advanced-hardware-based control system which will have appropriate logic to control the replacement valves' system-medium actuators. The replacement'control system will be custom-selected from available hardware items so that it will not utilize nor depend upon any program software.

3.0 ABBREVIATIONS AC All Close C Close / Closed DC Direct Current ESFAS - Engineered Safety Features Actuation System FWIS - Feedwater Isolation Signal KC - Keep Closed KO - Keep Open MFIV Main Feedwater Isolation Valve MSFIS Main Steam and Feedwater Isolation Actuation System MSIS - Main Steam Isolation Signal MSIV - Main Steam Isolation Valve 0 - Open REV SPECIFICATION NUMBER J-105A(O= 5 Page 4

FORM APF-05-004-04, Rev. 0 4.0 CODES AND STANDARDS IEEE Standards IEEE Standard 279-1971, Criteria for Nuclear Power Plant Protection Systems IEEE Standard 323-1974, IEEE Standard for Qualifying Class IE Equipment for Nuclear Power Generating Stations IEEE Standard 336-2005, IEEE Standard Installation, Inspection, and Testing Requirements for Power, Instrumentation, and Control Equipment at Nuclear Facilities IEEE Standard 338-1987, IEEE Standard Criteria for Periodic Surveillance Testing of Nuclear Power Generating Station Safety Systems IEEE Standard 344-1975, IEEE Recommended Practices for Seismic Qualification of Class 1E Equipment for Nuclear Power Generating Stations IEEE Standard 352-1987, Guide for General Principles of Reliability Analysis of Nuclear Power Generating Station Safety Systems IEEE Standard 379-11988, Application of the Single Failure Criterion to Nuclear Power Generating Station Class 1E Systems IEEE Standard 383-2003, IEEE Standard or Type Test of Class IE Electric Cables, Field Splices, and Connections for Nuclear Power Generating Stations IEEE Standard 384-1981, Criteria for Independence of Class IE Equipment and Circuits IEEE Standard 420-2001, IEEE Standard for the Design and Qualification of Class 1E Control Boards, Panels, and Racks Used in Nuclear Power Generating Stations IEEE Standard 472-1974, Guide for Surge Withstand Capability Tests IEEE Standard 603-1991, Standard Criteria for Safety Systems for Nuclear Power Generating Stations Standards other than IEEE EPRI Topical Report TR-102323-R2, Guideline for Electromagnetic Interference Testing in Power Plants IEC-801-2, Electromagnetic Compatibility for Industrial-Process Measurements and Control Equipment Part 2:

Electrostatic Discharge Requirements IPCEA S-19-81, Rubber Insulated Wire and Cable for the Transmission and Distribution of Electrical Energy IPCEA S-61-402, Thermoplastic Insulated Wire and Cable for the Transmission and Distribution of Electrical Energy 4.1 References NRC Regulatory Guides Regulatory Guide 1.22, Periodic Testing of Protection System Actuation Functions Regulatory Guide 1.29, Seismic Design Classification Regulatory Guide 1.47, Bypassed and Inoperable Status Indication for Nuclear Power Plant Safety Systems Regulatory Guide 1.53, Application of the Single-Failure Criterion to Nuclear Power Plant Protection Systems Regulatory Guide 1.62, Manual Initiation of Protective Actions Regulatory Guide 1.75 Rev. 2 dated 9/78, Physical Independence of Electric Systems Regulatory Guide 1.92, Rev. 1, Combining Modal Responses and Spatial Components in Seismic Response Analysis Regulatory Guide 1.100, Rev. 1, Seismic Qualification of Electric Equipment for Nuclear Power Plants Regulatory Guide 1.118, Periodic Testing of Electric Power and Protection Systems Regulatory Guide 1.131 dated 8/77 Qualification Tests of Electric Cables, Field Splices, and Connections for Light-Water-Cooled Nuclear Power Plants Regulatory Guide 1.153, Criteria for Power, Instrumentation, and Control Portions of Safety Systems Regulatory Guide 1.180, Rev. 1, Guidelines for Evaluating Electromagnetic and Radio-Frequency Interference in Safety-Related Instrumentation and Control Systems REV SPECIFICATION NUMBER J-105A(O 5 Page 5

FORM APF-05-004-04, Rev. 0 Drawing List Wolf Creek Drawing Vendor Drawing Title Number Number J-104-00282 KAG8909 MSFIS Logic J-104-00281 KAF8909 Sh 1 Signal Flow Block Diagram J-104-00322 KAF8909 Sh 2 Signal Flow Block Diagram J-104-00323 KAF8909 Sh 3 Signal Flow Block Diagram J-104-00324 KAF8909 Sh 4 Signal Flow Block Diagram J-104-00325 KAF8909 Sh 5 Signal Flow Block Diagram J-104-00326 KAF8909 Sh 6 Signal Flow Block Diagram J-104-00327 KAF8909 Sh 7 Signal Flow Block Diagram J-104-00328 KAF8909 Sh 8 Signal Flow Block Diagram J-104-00295 KJ7316 MSFIS Power Dist 15 V DC J-104-00296 KK7316 MSFIS Power Dist 48 V DC J-104-00289 9N53 Sh I MSFIS Cabinet Assembly J-104-00303 9N53 Sh 2 MSFIS Cabinet Assembly J-104-00512 PL9N53 MSFIS Cabinet Parts List J-104-00291 R9N53 MSFIS Cabinet Installation J-104-00300 KAA7366 MSFIS Cabinet 9N53-1 Marking J-104-00299 KAL7366 MSFIS Cabinet 9N53-2 Marking J-104-00330 KH7299 Sh 1 Double Card Rack Assembly J-104-00331 KH7299 Sh 2 Double Card Rack Assembly J-104-00314 PLKH7299 Double Card Rack Parts List J-104-00332 KJ7299 Single Card Rack Assembly J-104-00315 PLKJ7299 Single Card Rack Parts List J-104-00302 7N228 Manual Test Panel Assembly J-104-00298 S7N228 Manual Test Panel Schematic J-104-00292 8N29 Power Supply Assembly / Parts List J-104-00317 6N338 Valve Control Module Assembly J-104-00320 $6N338 Valve Control Module Schematic PPS-A700/A300 Functional Description 103.225.762, Sheets System medium operated actuator for 1-R quick closing valve, Layout diagram 5.0 DESIGN REQUIREMENTS 5.1 Design Conditions No specific requirement.

5.2 Performance Requirements 5.2.1 General Design Requirements

a. The MSFIS provides 125 Volt DC outputs to energize or de-energize control solenoids to operate and test the plant MSIVs and MFIVs.

REV SPECIFICATION NUMBER .- 105A(O) 5 Page 6

FORM APF-05-004-04, Rev. 0

b. The MSFIS is divided into two actuation channels. Each of the two independent actuation channels monitors system inputs and, by means of logic matrices, energizes / de-energizes the required solenoids in the required sequence for the appropriate valve operations.
c. The MSFIS System is comprised of solid-state components.
d. The Replacement MSFIS System shall not involve software such as an application program for a digital computer in the hardware in place during plant operation. However, software is permitted in portable test equipment which is completely disconnected from the Replacement MSFIS System at the conclusion of testing.
e. The Controls Seller shall configure the MSFIS control logic matrices to develop output states and output sequences in accordance with Appendix C and Sections 5.2.5 and 5.2.6 of this specification.

5.2.2 Modular Design Interchangeability shall be provided and demonstrated for all similar modules or components.

Items designed to be removable from the equipment, such as assemblies, subassemblies, electrical parts, modules, and hardware, shall be replaceable physically and electrically with corresponding items without drilling, bending, filing, fabricating, or using undue force. Hot swap capability shall be included for the logic-controller-based system circuit cards. Hot swap capability includes the requirement that the controlled equipment shall not cause a plant transient. Further the redundant train shall not lose the capability to continue plant operation and shall continue to perform it's safety-related function, closure of the MSIVs and MFIVs when required by input conditions.

The replacement of parts, when accomplished in a manner prescribed by the Controls Seller, shall not cause the equipment to depart from the original specified performance.

5.2.3 Response Time The overall response time of the Replacement MSFIS System specified herein shall be less than or equal to 100 milliseconds for an input signal step change. The Replacement MSFIS System is contained within the cabinets SA075A and SA075B, from field terminal block input to field terminal block output.

5.2.4 System Functional Requirements

a. System Input Signals The MSFIS shall accept input signals (in the form of contact conditions) from control switches located on the Main Control Board and from output relays in the Engineered Safety Features Actuation System. Appendix A tabulates the inputs for each subsystem of the MSFIS.
1) The existing MSFIS System configuration obeys the plant's separation criteria by use of two separate MSFIS Cabinets, one for each Channel. The Controls Seller shall use the existing MSFIS Cabinets and Channels to continue adherence to these criteria. Incoming signal Channel assignments are specified in Appendix A.
2) The System inputs from the control switches will all be momentary (>1 OOmS), and shall be sealed-in as necessary inside the Replacement MSFIS System logic circuits.
3) The contacts from ESFAS will be normally closed, and will open to cause an operation. The remaining input contacts will be normally open, and will close to cause an operation.

I REV SPECIFICATION NUMBER J-105A(O) 1 5 Page 7

FORM APF-05-004-04. Rev. 0 4)ý The Controls Seller shall determine the voltage and current ratings of the buffer input circuits based on the power supplies as required under Section 5.6.3 and also subject to the maximums of NEMA ICS-5 P300 .ratings and the minimums required to keep the contacts clean and function in-a nuclear plant instrument cabinet room with unshielded cables connecting the remotely located input contacts to the system.

b. System Logic Matrices The logic matrices shall adhere to the requirements of channel independence and separation required by Appendix A.
c. System Output Signals
1) Actuation Outputs The MSFIS shall energize / de-energize the MSIV *andMFIV actuator solenoids in accordance with the logic requirements of Sections 5.2.5 and 5.2.6. The output signals shall adhere to the requirements of channel independence and separation required by Appendix A.

The outputs shall provide sufficient voltage to energize the actuator solenoids. The specifications for the actuator solenoids are as follows.

Nominal Line Supply Voltage. 125VDC Supply Voltage Tolerance +12% / -28%

Coil Resistance 97.6 Ohm @ 20-C Inductance 40 - 60 Henry Nominal Current 1.28A @ 20-C Nominal Power Consumption. 160 Watt @ 20'C

2) Status Outputs In addition to the actuation outputs, one status output shall be provided for each actuation.

train for each valve. This status output is shown in Appendix B. The MSFIS System status output will supply 125 Volt DC power to an input relay at the Status Panel if both of the following are true: a) 125 Volt DC power is available downstream of the individual power supply fuses for solenoid MVI (2), and b) there is no test in progress in the MSFIS System logic. The output to the Status Panel shall be able to handle a 125VDC, <25mA load.

3) Annunciator The MSFIS shall provide outputs to the plant Annunciator system as described in section 5.6.7. The annunciator outputs shall be able to handle a 125VAC, <25mA load.

4), ESFAS Test Circuits The MSFIS shall provide one output for each actuation train for each valve to the ESFAS test circuitry, as described in section 5.2.6. These outputs shall be able to handle an 11 8VAC,

<500mA load.

IREV SPECIFICATION NUMBER J-105A(O) 5 Page 8

FORM APF-05-004-04. Rev. 0 5.2.5. System Operation In response to command signals from various sources, the MSFIS shall energize and de-energize sets of output terminals in accordance with the requirements set forth below. These outputs will be connected by the Buyer to control solenoids in the actuators of the Main Steam Isolation Valves and the Main Feedwater Isolation Valves.

For illustrative purposes, the functional description document for these actuators is included in this specification. Reference will be made to the operation of these actuators and of their component parts; such references are solely for the purposes of discussion.

The Replacement MSFIS System shall measure actual System outputs, compare the outputs to the required output states, and alarm any discrepancies. See section 5.6.7.

The responsibility of the Controls Seller shall be limited to energizing and de-energizing the system outputs as specified.

Note that the actuators are divided into two "sides," and that each side is controlled by three solenoids labeled MV1, MV3, and MV5 for one side, and MV2, MV4, and MV6 for the other side. The three MSFIS outputs associated with each side of each valve are likewise identified as outputs MV1, MV3, and MV5 for one side, and MV2, MV4, and MV6 for the other side.

There must be no connection nor communication of information within the MSFIS between the controls for the two sides of any valve. The states of the outputs for the two sides of a valve must be completely independent of one another. This separation is accomplished by assigning the two "sides" of each valve to opposite Channels MSFIS Cabinets.

a. Output States and Commands
1) Output States There are three output states for each valve actuator; 1) CLOSE, 2) KEEP CLOSED, and 3)

OPEN. The normal state (during normal plant operations) for each MSIV and FWIV is OPEN. The required output to each solenoid for all three of the valve actuator states is shown below.

Outputs to Outputs to MSIV / MFIV MSIV / MFIV MV1, 3,5 Side MV2, 4,6 Side Output State Symbol MV1 MV3 MV5 MV2 MV4 MV6 CLOSE C KEEP CLOSED KC + +

OPEN 0 + + + +

Key: + = energized

- = de-energized The fail safe output state shall be defined as maintaining the current output state when a failure is identified

2) Commands There are four commands; 1) All Close, 2) ESFAS, 3) Close, and 4) Open.

The All Close command is generated from the ALL CLOSE pushbutton hand switch on the Main Control Board (separate switches for MSIVs and MFIVs). The All Close command shall REV SPECIFICATION NUMBER .- 105A(O) .

Page 9

FORM APF-05-004-04, Rev. 0 place the CLOSE output state for all four valves for the respective switch, MSIV or MFIV.

The output state shall remain CLOSE for 60sec +/- 1sec after All Close command was initiated. After the 60sec time delay the output shall be changed to KEEP CLOSED.

The ESFAS command is generated from the Solid State Protection System. The Solid State Protection System provides the inputs to the MSFIS from a separate slave relay for each the MSIVs and MFIVs. Each slave relay provides four contacts into.the MSFIS, one contact for each valve. The four contacts from a particular slave relay for either the MSIVs or MFIVs shall be evaluated using 2-out-of-4-voting. The 2-out-of-4 vote shall be required for a valid ESFAS command. The ESFAS command shall place the CLOSE output state on all four valves of the particular system MSIV or MFIV. Note: Under Normal Operating conditions the four ESFAS commands will come in at the same time, as they are derived from the same slave relay coil. The output state shall remain CLOSE for 60sec +/- 1sec after the ESFAS command was initiated. After the 60sec time delay the output shall be changed to KEEP CLOSED.

The Close command is defined as a close signal to one valve, MSIV or MFIV, initiated by the valve's assigned individual NORMAL-CLOSE-OPEN pushbutton hand switch on the Main Control Board. The Close command shall place the CLOSE output state for the particular valve associated with the NORMAL-CLOSE-OPEN pushbutton hand switch that was actuated. The output state shall remain CLOSE for 60 sec +/- 1 sec after the Close command was initiated. After the 60sec time delay the output shall be changed to KEEP CLOSED.

The Open command is defined as an open signal to one valve, MSIV or MFIV, initiated by the valve's assigned individual NORMAL-CLOSE-OPEN pushbutton hand switch on the Main Control Board. The Open command shall place the OPEN output state for the particular valve associated with the NORMAL-CLOSE-OPEN pushbutton hand switch that was actuated.

b. Command Priorities
1) The command priorities are as follows when the MSFIS system is in OPERATE mode (see section 5.2.6 for OPERATE mode).

All Close, Close, and ESFAS have equal priority. The Open command will be ignored while the All Close, Close, or ESFAS command(s) are present. Further the Open command will be ignored until the CLOSE to KEEP CLOSE time delay has expired.

2) The command priorities are as follows when the MSFIS system is in BYPASS mode (see section 5.2.6 for BYPASS mode).

All Close, Close, ESFAS, and Open commands shall not cause a change in system outputs while the system is in BYPASS mode.

REV SPECIFICATION NUMBER .- 105A(OF _ 5 Page 10

FORM APF-05-004-04, Rev. 0 5.2.6 Provisions for System Test of the Safety Function The existing MSFIS System includes provision to permit complete testing of the safety function (ESFAS command) of each actuation train for each valve. The Replacement MSFIS System shall also have such provision for complete testing of the safety function of each actuation train for each valve.

Overlapping of test schemes may be utilized in order to ensure complete coverage of the test program. It shall be possible to conduct all tests during plant operation. Performance of fully automatic system tests shall not interfere with the system's operation during presence of any actuation input.

Controls Seller shall provide three test types or detection capabilities to verify the proper operation of the Replacement MSFIS System to perform the intended safety function. The three types of tests or detection capabilities shall be;

1) Manual System Test:
a. Ability to manually test required inputs and/or outputs required to perform the safety function
2) Manually Initiated Automatic Test:
a. Ability to manually initiate automatic test(s) and/or detection capabilities which monitor or test the ability of the system to perform the required safety function.
3) Automatic Exception Detection:
a. The system shall be designed such that the system is fully deterministic and shall automatically detect improper operation of the system's ability to perform the required safety function.

All system test and detection capabilities shall be validated & verified by Buyer.

The MSFIS test circuits shall provide one contact set for each actuation train for each valve. The contacts shall be open for normal operation and shall close at the appropriate test step as described below. These contacts will be used to enable test circuits in the Safeguards Test Cabinets to verify proper transmission and to verify the response to the ESFAS command.

a. BYPASS / OPERATE Mode Selection
1) Selection Means shall be provided to select BYPASS or OPERATE mode for each actuation train for each valve. The selection of BYPASS shall maintain the valve in the as found condition and shall not cause a change in system outputs.. The selection of BYPASS shall only impact the particular actuation train and particular valve for which the BYPASS is selected. Except as indicated in the following paragraph, each change in mode shall require a positive manual action such as pushing a button, flipping a switch, or turning a switch (releasing a pushbutton or switch is not considered to be positive action, and shall cause no change in mode).

The actuation train for a particular side of a particular valve shall enter BYPASS mode upon command. There shall be one exception to this, which is the situation where the output state is CLOSE and the 60 sec delay is active, in this situation the CLOSE state must be completed and the 60 sec time complete prior to entering the BYPASS mode.

2) Indication An indicating light /LED shall be provided for each actuation train for each valve. This light

/ LED shall be "ON" whenever BYPASS mode is in effect.

REV SPECIFICATION NUMBER l-105A(O1 5 Page 11

FORM APF-05-004-04, Rev. 0

3) BYPASS Mode Initiation Upon initiation of BYPASS mode for a particular actuation train for a particular valve, the following must be accomplished:

a) Latch the actuation outputs to the as found state.

b) De-energize the status output.

c) Light the BYPASS mode indicator light / LED d) Close the test contacts described in Section 5.2.6 to enable the test circuits in ESFAS.

To prevent accidental valve operation, "a" must occur prior to "d."

4) Return to OPERATE Mode Upon return to OPERATE mode, the -following must be accomplished:

a) Open the test contacts (see Section 5.2.6).

b) Unlatch the actuation outputs, extinguish the BYPASS mode indicating light/LED, and release the status output.

b. Testing of Replacement MSFIS System
1) Controls Seller may modify or replace the existing Manual Test Panel as necessary to effectively interface with the Replacement MSFIS System logic-controller-based system and meet all specified requirements.
2) Provisions for testing of the Replacement MSFIS may include portable test equipment and capability to temporarily connect the portable test equipment to the Replacement MSFIS System during performance of testing.

5.2.7 Electronics Architecture

a. Existing Configuration The attached drawing package depicts the existing electronic architecture. The Cabinet Assembly drawing 9N53 Sheets 1 and 2 depicts double card rack AI with 32 card positions as part number 3 and single card rack A2 with 16 card positions as part number 4. Double card rack Al is further detailed on drawing KH7299. Single card rack A2 is further depicted on drawing KJ7299.

The signal flow block diagram drawings KAF8909 Sheets 1 through 8 depict the location of every card in the card racks in the lower corners of the rectangles depicting the cards. The signal flow block diagrams also depict the card terminal numbers for all functions except power supply. Some card positions in the card racks are left vacant.

The three types of cards are input buffer, valve control module, and output relay driver. Drawing

$6N23I depicts a schematic of the input buffer cards. Drawing $6N232 depicts a schematic of the output relay driver cards. Drawing $6N338 depicts a schematic of the valve control module cards.

These schematic drawings depict the card terminal numbers for all functions, including power supply.

REV SPECIFICATION NUMBER .--105A(O . 5 Page 12

FORM APF-05-004-04, Rev. 0 The signal flow block diagram drawings KAF8909 Sheets 1 through 8 depict signal flow between the circuit cards and to and from the output relays and cabinet terminal blocks. These drawings also depict wiring harnesses and connector and pin numbers. Interconnections are discussed further in Section 5.6.4.

b. Replacement MSFIS System Configuration The replacement MSFIS System shall be an advanced-hardware-based solid-state control system which will receive defined inputs and develop defined outputs as specified to control the valves. The Replacement MSFIS System shall include the overall electronic functions of input buffers, system logic, and then output relay drivers. However, the Controls Seller shall configure the system, logic elements, circuit cards, and interconnections to perform the required system functions and meet all requirements such as sufficient drive capacity for the actuator solenoids.

Controls Seller may choose to re-use the existing card racks and interconnecting wiring to any extent feasible or to replace it all.

In each Cabinet, Controls Seller shall place the operating logic for the four MSIVs on a separate system from the system where the MFIV logic is placed.

5.3 Material Requirements No specific requirement.

5.4 Environmental Requirements The MSFIS cabinets are located in the Control Room equipment cabinet area, which will normally be air conditioned; however, the system and components shall be selected to function continuously at ambient temperatures ranging from 65°F to 84°F at a relative humidity from 20 to 70 percent.

5.5 Structural Requirements 5.5.1 Cabinets - Existing Configuration The existing MSFIS System is contained in two independent cabinets, one cabinet for each separation group.

The drawings included in this specification document the existing cabinets' physical arrangement. These drawings are the best available information in document form, but there is no guarantee of their accuracy.

Controls Seller is responsible for field measurement of all factors affecting interface of the replacement equipment with the existing equipment not replaced. Buyer can arrange access to the cabinets for Controls Seller's personnel to observe the cabinets and perform measurements. The cabinets are energized and in operation except during brief, precisely scheduled "maintenance window" periods during plant outages. Access can be arranged during operation or during a maintenance window. Such access will be under close supervision, and Controls Seller's personnel shall take precautions to prevent injury to themselves and also to prevent damage to, or inadvertent operation of, the equipment in the cabinets.

I REV SPECIFICATION NUMBER J-10A(O' 5J Page 13

FORM APF-05-004-04, Rev. 0 The existing cabinets to house the MSFIS are freestanding NEMA 12 enclosures, and they conform to the seismic qualifications of Attachment D. The cabinets are 90 inches high and 30 inches deep. Each cabinet is 24 inches wide with at least 19-inch doors. Each cabinet has a lock, and one key opens all cabinet locks. Cabinets were designed for stitch welding to imbedded floor channels. The bottom angle of the equipment has been stitch welded on the outside of the cabinet along the front and rear to concrete-imbedded channels that protrude 1 inch outside the cabinet face.

Flush or semi-flush panel-type hinged doors with resilient gasketing have been used on the cabinets.

Doors are equipped with a handle, latch, and lock sufficiently strong to hold the door in alignment when closed.

Door panels on the front and back are clear Lexan 1/4 inch thick.

Doors have hinges that permit them to swing approximately 180 degrees, are easily removed, and have sufficient members to ensure rigidity and prevent weaving or warping.

Mechanisms are provided in order to maintain cabinet doors in the open position during testing and maintenance.

Requirements for replacement doors are stated in Section 5.5.3.

Channel identification is required throughout the system.

Engraved nameplates shall be used to identify all cabinets. Colors for the nameplates shall be white letters on a red background in Channel I / Cabinet SA075A and black letters on a yellow background in Channel IV I Cabinet SA075B. Nameplates for non-safety-related Groups 5 and 6 items in both cabinets shall have white letters on a black background. See Attachment E for details of nameplates.

Cabinets have been designed to permit both top and bottom cable entry.

5.5.2 Seismic Requirements Seismic requirements shall be in accordance with Attachments D and H, IEEE 323, IEEE 344, Regulatory Guide 1.100, and the damping values of Regulatory Guide 1.92. Seismic qualification may be performed by test or analysis, or a combination thereof.

The MSFIS is designated as Seismic Category I and shall be selected, configured, and analyzed accordingly.

Actual shake tests of components, assemblies, subassemblies, and systems shall be performed in accordance with Attachment H.

Equipment procured under this Specification J-105A isdesignated Qf-lI with respect to Attachment D Section 3, that is, the equipment shall remain functional before, during, and after an OBE or an SSE.

Further notes on application of Attachments D:

a. The name Bechtel Power Corporation shall be understood to be the Buyer, Wolf Creek Nuclear Operating Corporation.
b. The names Supplier and Bidder shall be understood to be the Qualification Seller.

REV SPECIFICATION NIJMBER J-105AO 5 _

Page 14

FORM APF-05-004-04, Rev. 0 Prior to testing, test procedures shall be submitted for Buyer's approval. Buyer shall be notified of all tests and offered the opportunity to witness the tests. All test anomalies shall be promptly reported to the Buyer and resolution sought before continuation of testing.

5.5.3 Replacement Doors The Controls Seller may provide replacement doors for the existing cabinets to pass the EMI / RFI requirements. The replacement doors shall include hinges, latches, and latch operating rods and handles which meet the seismic requirements of Section 5.5.2. Welding shall not be required to mount the hinges and latch provisions of the replacement doors.

5.6 Electrical Requirements 5.6.1. Noise Rejection and Tolerance The Replacement MSFIS System shall comply with the EMI IRFI requirements of EPRI TR-102323 as modified by Regulatory Guide 1.180. Testing is specified in Section 10.7. The Controls Seller's scope of work includes any required corrective action.

5.6.2 Electrical Wiring

a. Wiring within the cabinet enclosure shall be suitable for a general-purpose, non-hazardous location.
b. Wiring shall be so arranged that instruments or devices may be removed and / or serviced without undue disturbance.
c. No wiring shall be routed across the face or rear of an instrument, junction box, or other device in a manner that will prevent or hinder the opening of covers or obstruct access to leads, terminals, devices, or instruments.
d. Wiring shall be installed as shown on the Controls Seller's wiring diagrams. During installation, wiring that is found to be in nonconformance with the wiring diagrams shall be reworked at the Controls Seller's cost. Any wire that is disconnected as a result of rework shall be completely removed from the system.
e. All wiring to field terminal blocks, except coaxial and triaxial, shall be made with solder-less ring-tongue, compression-type connectors with insulated ferrules.
f. Where wiring must cross sharp metal edges, protection in the form of grommets or similar devices shall be provided. Wires shall be grouped in bundles and secured with nonflammable, nonmetallic tie bands.
g. Wiring shall not cross a panel door opening or be fixed to a panel door.
h. Internal wiring shall be identified with the Controls Seller's wire number at each termination to field terminal blocks by means of a plastic sleeve or similar perm anent-type marker.
1. All wiring shall be subject to Buyer's approval.

IREV.

SPECIFICATION NUMBER J-105MO) 5 Page 15

FORM APF-05-004-04, Rev. 0 5.6.3 Power Supply

a. Sources Two separate sources currently supply nominal 125 Volt DC power, one to each MSFIS Channel /

Cabinet. These redundant supplies are used throughout the plant, and complete physical and electrical isolation shall be maintained between them within the Controls Seller's equipment.

The incoming voltage level on all power supply modules will be a nominal 125 Volts DC, normally operated at 135 Volts DC. The designed operating range of the existing 125 Volt DC System is 140 Volts DC to 105 Volts DC.

b. Replacement Power Supply Modules In the existing configuration, each cabinet has two output voltage levels, nominal 48 Volts DC and nominal 15 Volts DC. For the Replacement MSFIS System, the Controls Seller shall provide replacement power supply modules rated at DC voltage level(s) appropriate to feed all of the electrical loads in the Replacement MSFIS System plus any components retained from the existing design. The replacement power supplies shall have an input voltage operating range of 105VDC - 140VDC. The Controls Seller shall also determine whether any separate supplies are required at a given voltage level to separate electronic circuits from the effects of high-current switched loads.

The existing 125 Volt DC System has the capability to deliver a short circuit current of 11,070 Amperes. All electrical protective devices provided by the Controls Seller shall be capable of clearing this short circuit current.

Each voltage level in each cabinet shall have a pair of redundant and parallel power supply modules and capability to shift all load to one module in case of failure of the other one. Each pair of redundant power supply modules shall have provision for hot replacement "swapping" of one module while the other continues in service. Hot replacement by front-pull-out is preferred, but other configurations may be considered. Controls Seller may choose to modify or totally replace the existing power supply rack. Final configuration of the power supply rack and final configuration of the provisions for hot replacement are subject to Buyer's approval.

Each replacement power supply module shall have sufficient capacity to supply all assigned loads with 15% spare capacity while the redundant power supply module is out of service. The system shall have the capability ("health") to detect loss of each power supply module's capability to assume the full load assigned to the redundant pair. Loss of any power supply module's capability ("health") shall be one of the inputs to the Replacement MSFIS System's new summary trouble alarm circuit. Each pair of redundant power supply modules shall have provision for load sharing whenever both are in service and both have no failure detected.

Drawings of the existing power supply distribution scheme are attached as a reference for power supply module capacity. Drawings J-104-00295 and J-104-00296 show the existing power supply scheme before replacement by the redundant power supply modules with hot replacement capability.

Drawing J-104-00296 shows the existing distribution of 48 Volts DC power to the output relays as well as to the existing electronic control system. Drawing J- 104-00295 shows that the only existing use of 15 Volts DC power is to feed the electronic controller cards of the existing MSFIS System.

c. Outputs The system outputs shall be fused as shown in Appendix B.

REV SPECIFICATION NUMBER I-105A(O' 5 Page 16

FORM APF-05-004-04, Rev. 0

d. Operation The MSFIS shall operate as required with the stated power supply without producing spurious actuation or failure to produce a required response to accident conditions.

5.6.4 Interconnections Controls Seller shall provide wiring harnesses as required to interconnect all equipment provided. Controls Seller may re-use existing connectors and wiring harnesses connected to cabinet terminal blocks and components not replaced. The Signal Flow Block Diagrams and the Schematic of the Manual Test Panel provide information about the existing connectors and wiring harnesses. Wrap-type terminals are not permitted on new connectors / wiring harnesses. The connectors of the existing wiring harnesses have been identified as ITT Cannon type DL5, Zero Insertion Force (ZIF) 96-pin connectors with polarizing posts. The polarizing post orientation is defined on the assembly drawings for the Card Racks and Manual Test Panel. If Controls Seller uses new connectors, the connectors shall be a type which will meet seismic and noise requirements as specified elsewhere in the specification.

5.6.5 Replacement Relays N/A 5.6.6 Metal Oxide Varistors - MOVs N/A 5.6.7 Trouble Alarm

a. Controls Seller shall develop a summary trouble alarm in each system cabinet. The alarm shall provide a normally-open, open-to-alarm dry contact or equivalent. The alarm shall be wired to spare points on an existing terminal block in each cabinet. Buyer will provide a field cable and connect the trouble alarm to the plant annunciator.
b. The following items are suggested as a minimum list of conditions which should be alarmed:

Any DC power supply module loss of capability Any circuit card removed Any external test apparatus is connected to the system Any output sequence incomplete

c. The trouble alarm logic shall include a means to indicate which trouble condition caused the alarm.

The indication shall be displayed at the MSFIS Cabinet.

5.6.8 Fuses and Fuse Blocks Distribution of 125 Volt DC power to the output solenoid valves is shown in Appendix B. The distribution scheme includes separate assigned fuses for each output solenoid valve in the field.

Additional nominal 3.2 ampere fuses and fuse blocks are required to meet this requirement. Appendix C shows the existing and modified fuse functions and number assignments. The scope of work REV SPECIFICATION NUMBER .-105A(O) = 5 Page 17

FORM APF-05-004-04, Rev. 0 includes procurement, location, seismic qualification, and all other pertinent factors for the additional fuses and fuse blocks.

The fuses and fuse blocks described in the previous paragraph and Appendix C are in addition to any fuses and fuse blocks that may be required by section 5.6.3 Power Supply or any other specific requirement or by good practice in the selection and configuration of the Replacement MSFIS System.

5.6.9 EMI RFI Requirements The Replacement MSFIS Systema shall comply with the EMI / RFI requirements of EPRI TR-102323 as modified by Regulatory Guide 1.180. Testing is specified in Section 10.7. The Controls Seller's scope of work includes any required corrective action.

5.7 Instrumentation and Control Requirements No specific requirement.

5.8 Maintenance No specific requirement. See also section 5.12, Accessibility for Maintenance and section 6.2, Special Tools.

5.9 Redundancy, Separation, and Diversity 5.9.1 Independence Separation Groups (trains) are be electrically and physically isolated from each other so that events (including faults) affecting one element do not affect the others in any way. Independence is provided between redundant elements to preclude any interaction between different separation groups during maintenance or as a result of channel malfunction.

The Controls Seller shall provide electrical isolation and physical separation to develop the required independence on the Replacement MSFIS System.

5.9.2 Isolation N/A 5.9.3 Separation

a. Physical separation shall be in accordance with IEEE 384 as modified by Regulatory Guide 1.75.
b. Equipment for one actuation channel or one measurement channel shall be separated physically by a barrier from any other actuation channel or measurement channel. The wiring and terminal block arrangement within a given cabinet or isolated compartment shall allow for a minimum physical separation of six inches or use of fireproof barriers. Suitable means to implement IEEE 384 are contained in IEEE 420. Wiring separated by barriers shall maintain a 1-inch separation (or an equivalent of thermal insulation) between the barrier and the wire.

REV SPECIFICATION NUMBER J-105A(O) . 5 Page 18

FORM APF-05-004-04, Rev. 0

c. Wiring of any separation group shall be separated from any other group except as permitted by IEEE Standard 384 and except that Group 5 and Group 6 wiring do not have to be separated from each other, but must be separated from the other groups.

5.10 Testability No specific requirement. See also section 5.2.b, Provision for System Test.

5.11 Interface Requirements See section 5.2.4.

5.12 Accessibility for Maintenance, Repair, and In-service Inspection No specific requirement. See also section 6.2, Special Tools.

5.13 Fire Protection Requirements The Main Steam Isolation Valve, Main Feedwater Isolation Valves, and MSFIS System are required to function as part of the 10CFR50 Appendix R Safe Shutdown design. However, there are no specific requirements on the Replacement MSFIS System from the plant's Appendix R requirements. The existing and replacement MSFIS Systems meet the requirements of the plant's channel and group separation scheme.

6.0 SPARE PARTS AND SPECIAL TOOLS 6.1 Spare Parts 6.1.1 Special Spare Parts Due to the specialized nature of the equipment supplied under this Specification, the following provisions are required:

a. Per Section 1.1 item 9, the initial stock of spare parts included in the basic scope shall be the quantity of each item reasonably estimated as necessary for twenty years' consumption. The initial stock of spare parts is the responsibility of the Controls Seller.
b. Controls Seller shall maintain the documentation, tooling, personnel expertise, access to materials, and any other necessary factor to enable the Controls Seller to produce additional spare parts items, within a reasonable lead time and at a reasonable price. Parts shall be provided as Commercial Grade items.

Controls Seller shall maintain this capability for the foreseeable future.

6.1.2 List A list of all repair parts and replaceable modules for the Replacement MSFIS System is required as part of the project documentation in Section 13.10.

REV SPECIFICATION NUMBER J-105A(OQ 5 Page 19

FORM APF-05-004-04, Rev. 0 6.2 Special Tools 6.2.1 Test Regime Controls Seller shall develop a portable test regime for use during production and prototype testing. After-Controls Seller Testing is completed, Controls Seller shall turn over the test regime to the Buyer.

The test regime shall have the capability to test the complete Replacement MSFIS System from input to final output. This test regime is intended to perform complete system flrctional<testing or individual card by card testing.

6.2.2 Other Special Tools Controls Seller shall provide to Buyer one set of any special tools required for maintenance or testing of the Replacement MSFIS System. Special tools are defined as tools not commonly available to the trade, involving non-standard dimensions, offsets, or shapes, specialized tools for holding parts in place for assembly, or specialized handling and lifting tools. The special tools also include electrical test equipment involving non-standard ranges of parameters or signals formats. The special tool scope also includes submittal of test or calibration procedures or set-point documents, if required by the configuration of any special tools. If no special tools are required, then no special tools need be supplied.

7.0 STAMPING REQUIREMENTS All engineering documents developed specifically for this project shall be stamped by a Kansas Professional Engineer. It is anticipatedthat all documents developed specifically for this project will be Wolf Creek internal design documents.

Therefore, it is not anticipated that the design documents from both the Controls Seller and the Qualification Seller will be developed specifically for this project, as the Replacement MSFIS System is not unique to Wolf Creek.

8.0 FABRICATION' 8.1 Welding No specific requirement.

8.2 Protective Coatings No specific requirement.

8.3 Identification No specific requirement.

9.0 INSTALLATION Installation and work planning will be performed by the Buyer. However, Controls Seller shall provide documentation regarding assembly and installation of the replacement MSFIS. See Section 12.

REV SPECIFICATION NUMBER J-105A(Q _ 5 Page 20

FORM APF-05-004-04, Rev. 0 10.0 TESTING For the Replacement MSFIS System, the Controls Seller shall meet the requirements for all testing, inspection, quality assurance, documentation, and equipment preparation for shipment set forth here. Prior to shipment, the assembled and wired equipment shall be tested at the factory in the presence of the Buyer. In consideration of the Replacement MSFIS System scope, the system configuration to be tested and the scope of testing is defined below.

10.1 Seismic Required seismic tests are specified in Section 5.5.2 and the Attachments. Test documentation is specified in Section 13.6.

10.2 System Reliability Analysis 10.2.1 The Buyer will perform failure-mode-and-effects analysis and reliability predictions. The final report of analysis-and-reliability data will be in accordance with IEEE 352.

The failure-mode-and-effects analysis will be presented in tabular form and shall list the following for each module, component or element:

a. Descriptive name of each element
b. A concise statement of the function performed by the element C. A statement of the possible failure modes such as open, short circuit, high voltage, or burnout applicable for that element
d. The failure mechanism(s) for each failure mode
e. The effect of each postulated failure on the system performance
f. Method of detection for component failure 10.2.2 Components and modules used in the manufacture of the actuation system shall exhibit a quality consistent with the nuclear power plant 40-year-life objective of minimum maintenance and low failure rate.

10.2.3 Scope of the analysis shall be limited to the elements of the MSFIS required to perform the safety-related functions shown in Appendix A.

10.2.4 The basis for module reliability estimates shall follow the method described in MIL-HDBK-217B, December 1974, Section 4.5, Part Class and Part Type technique.

10.2.5 The Buyer will incorporate into an MSFIS reliability analysis the module reliability prediction values obtained by calculation.

10.2.6 The Buyer will assume that the time from the detection of a failure to normal after repair is eight hours, and shall list the reference(s) used in his analysis.

10.2.7 For the purposes of this analysis, the Buyer will use a MTBF value of twenty years for each channel of DC power supplied to the MSFIS.

10.2.8 The Buyer will provide a reliability analysis defining the system unreliability, assuming one system challenge a year, for both manual testing on a 30-day schedule and for automatic testing.

I REV SPECIFICATION NUMBER J-105A(QI 5 Page 21

FORM APF-05-004-04, Rev. 0 10.2.9 The Buyer will also supply a failure effects analysis arranged according to type of failure or effect and shall list the possible causes for each failure.

10.2.10 The Controls Seller shall rnot substitute any alternate or equivalent components in the system that would degrade the system reliability as approved by the Buyer in the Failure Modes and Effects Analysis or on the Reliability Analysis. If a change or modification must be made, for any reason, the Controls Seller shall advise the Buyer of the impact on these analyses (including quantitative impact on the Reliability Analysis) and shall obtain Buyer approval before implementing the change. A revised copy of the respective report, incorporating the revised analysis, must then be completed prior to final acceptance of the change. The Buyer reserves the right to require that complete revisions to the analyses be presented prior to determining the acceptability of a proposed change.

10.3 Components 10.3.1 Replacement MSFIS System components shall be tested in accordance with the Controls Seller's standard test procedure.

10.3.2 All Controls Seller wiring outside of the card rack shall be given a dielectric test in accordance with NEMA Standard Publication ICS- 1-2000. The dielectric testing shall be performed by the Qualification Seller.

10.3.3 Wiring tests shall include point-to-point continuity tests.

10.3.4 The Controls Seller shall be responsible for proper preparation of instruments and devices that may be damaged by high-voltage tests.

10.4 Actuation 10.4.1 The Controls Seller shall submit, for Buyer's approval, the proposed factory acceptance test procedures to demonstrate compliance with the functional requirements of this Specification. The procedures shall be approved by Buyer prior to the completion of system fabrication and assembly.

10.4.2 The MSFIS equipment shallundergo a complete functional test that shall prove the correct performance according to the specification of each individual module of the sensor and actuation channels. Tests shall be initiated in manual mode, applying simulated signals at the input terminals.

10.4.3 The MSFIS equipment shall be tested at the input terminals by applying all possible trip.combinations as input signals for all possible system states.

10.4.4 Each actuation interface shall be individually tested through manual inputs and through the relative actuation logic.

10.5 Deleted 10.6 Environmental Qualification The environment at the equipment location is considered MILD with respect to the Equipment Qualification (EQ) program. Thus, the equipment is not subjected to the EQ program. However, the equipment's environment is stated in Section 5.4, and the equipment is required to operate in that environment for its 40 year lifetime. The 40 year lifetime of the equipment assumes buyer performs both corrective and preventative maintenance of the system as specified by both the Control Seller and the Qualification Seller*

REV SPECIFICATION NUMBER J-105A(O) 1 5 Page 22

FORM APF-05-004-04, Rev. 0 10.7 EMI / RFI Testing Testing shall be conducted to demonstrate compliance with the EMI / RFI requirements of EPRI TR-102323 as modified by Regulatory Guide 1.180. Testing may be performed on a suitable structure in a laboratory environment, or the final installed configuration in Buyer's plant, or an appropriate combination or these configurations.

11.0 INSPECTION Inspection requirements are specified in Appendix R.

12.0 HANDLING, SHIPPING, AND STORAGE 12.1 Preparation for Shipment 12.1.1 The equipment shall not be prepared for shipment or shipped before the Buyer has either inspected the equipment or waived inspection.

12.1.2 Handling, shipping, and storage procedures shall be in accordance with ANSI N45.2.2, Level B. The Buyer shall review the Controls Seller's procedures prior to shipment.

13.0 DOCUMENTATION REQUIREMENTS The following types of documentation shall be submitted for engineering and quality verification. Controls Seller's and Qualification Seller's failure to comply with these requirements may result in order cancellation or withholding of payment until compliance is established:

13.1 Drawings - Outline Drawings providing external envelope, including lugs, center line(s), location of center of gravity, location and size for electrical cable, conduit, fluid, and other service connections, isometrics, and details related to foundations and mountings.

13.2 Assembly, Erection, and Installation Detailed written procedures, instructions, and drawings required to erect or install material or equipment.

13.3 Wiring Diagrams Drawings which show the schematic wiring and connection information for electrical items.

13.4 Logic Diagrams Drawings which show all the functional capabilities of the system, including all alarm, testing, bistable, bypass, coincidence logic, interface logic, and actuation logic.

REV SPECIFICATION NIUMBER J-105 A(OQ 5 Page 23

FORM APF-05-004-04, Rev. 0 13.5 Instruction Manuals Instruction Manuals shall contain, as a minimum, a discussion of the theory of operation of the system and its components, copies of all interface and assembly drawings and parts lists, all written procedures, instructions, and drawings required for operation, maintenance, storage, and handling to ensure proper operation and to prevent any damage or deterioration during storage and handling at the job site.

13.6 Seismic Data Report and Test Procedures Seismic requirements are stated in Section 5.5.2 and the Attachments. Required documentation discussed in Section 5.5.2 and the Attachments, including test procedures and analytical or test data which provide physical response information on an item, material, component, or system in relation to the conditions imposed by the stated seismic criteria of Attachment D shall be submitted for review or for record.

13.7 Engineering Performance Test Procedures and Quality Verification Reports Engineering performance test procedures and quality verification reports of electrical tests, including continuity checks, channel actuation tests, system checks with and without imposed single failures, system tests with temperature and / or power supply variances, and all other test requirements of Section 10.

13.8 Schedule The Controls Seller shall furnish a complete schedule forecasting engineering, fabrication, and testing, 60 days after the receipt of the purchase order.

13.9 Inspection Requirements All inspection requirement details are described by Appendix R.

13.10 Repair Parts List A list of all repair parts and replaceable modules for the Replacement MSFIS System in the Controls Seller's scope beyond commonly available "commodity" items. The list shall state for each item the name, Controls Seller's part number, unit price, recommended quantity to stock for five years' use, and lead time for additional production. This document shall also include ordering information and shipping options.

REV SPECIFICATION NUMBER J-105A(UO 5 Page 24

FORM APF-05-004-04, Rev. 0 APPENDICES Replacement MSFIS System Appendix A -, Input Signals and Sources AB-HV MSIV for Steam Generator A SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3,5 1 ALL CLOSE AC AB-HS-80 Group I contact*

ALL CLOSE AC ESFAS (MSIS) Group I**

CLOSE C AB-HIS-14 Group I C contact OPEN 0 AB-HIS-14 Group I 0 contact MV2,4,6 4 ALL CLOSE AC AB-HS-79 Group IV contact*

ALL CLOSE AC ESFAS (MSIS) Group IV**

CLOSE C AB-HIS-14 Group IV C contact OPEN 0 AB-HIS-14 Group IV 0 contact AB-HV MSIV for Steam Generator B SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3,5 4 ALL CLOSE AC AB-HS-79 Group IV contact*

ALL CLOSE AC ESFAS (MSIS) Group IV**

CLOSE C AB-HIS-17 Group IV C contact OPEN 0 AB-HIS-17 Group IV 0 contact MV2,4,6 I ALL CLOSE AC AB-HS-80 Group I contact*

ALL CLOSE AC ESFAS (MSIS) Group I**

CLOSE C AB-HIS- 17 Group I C contact OPEN 0 AB-HIS-17 Group I 0 contact.

  • AB-HS-79, AB-HS-80, AE-HS-80, and AE-HS-81 each provide signals to four valves. One set of contacts is provided in each switch.
    • A separate MSIS or FWIS signal is provided for each separation group for each valve.

Page Al of 4 I REV SPECIFICATION NUMBER J-105A(O) 5 Page 25

FORM APF-05-004-04, Rev. 0 Replacement MSFIS System:

Appendix A - Input Signals and Sources AB-HV MSIV for Steam Generator C SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3, 5 1 ALL CLOSE AC AB-HS-80 Group I contact*

ALL CLOSE AC ESFAS (MSIS) Group I**

CLOSE C AB-HIS-20 Group I C contact OPEN 0 AB-HIS-20 Group I 0 contact MV2,4,6 4 ALL CLOSE AC AB-HS-79 Group IV contact*

ALL CLOSE AC ESFAS (MSIS) Group IV**

CLOSE C AB-HIS-20 Group IV C contact OPEN 0 AB-HIS-20 Group IV 0 contact AB-HV-1 1 - MSIV for Steam Generator D SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3, 5 4 ALL CLOSE AC AB-HS-79 Group IV contact*

ALL CLOSE AC ESFAS (MSIS) Group IV**

CLOSE C AB-HIS-1 1 Group IV C contact OPEN 0 AB-HIS-1 1 Group IV 0 contact MV2,4,6 1 ALL CLOSE AC AB-HS-80 Group I contact*

ALL CLOSE AC ESFAS (MSIS) Group I**

CLOSE C AB-HIS-1 1 Group I C contact OPEN 0 AB-HIS-I 1 Group I 0 contact Page A2 of 4 SPECIFICATION NUMBER J-105A(O9 5 Page 26

FORM APF-05-004-04, Rev. 0 Replacement MSFIS System Appendix A - Input Signals and Sources AE-FV MFIV for Steam Generator A SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3,5 1 ALL CLOSE AC AE-HS-80 Group I contact*

ALL CLOSE AC ESFAS (FWIS) Group I**

CLOSE C AE-HIS-39 Group I C contact OPEN 0 AE-HIS-39 Group I 0 contact MV2,4,6 4 ALL CLOSE AC AE-HS-81 Group IV contact*

ALL CLOSE AC ESFAS (FWIS) Group IV**

CLOSE C. AE-HIS-39 Group IV C contact OPEN 0 AE-HIS-39 Group IV 0 contact AE-FV MFIV for Steam Generator B SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3,5 4 ALL CLOSE AC AE-HS-81 Group IV contact*

ALL CLOSE AC ESFAS (FWIS) Group IV**

CLOSE C AE-HIS-40 Group IV C contact OPEN 0 AE-HIS-40 Group IV 0 contact MV2,4,6 1 ALL CLOSE AC AE-HS-80 Group I contact*

ALL CLOSE AC ESFAS (FWIS) Group I**

CLOSE C AE-HIS-40 Group I C contact OPEN 0 AE-HIS-40 Group I 0 contact Page A3 of 4 REV SPECIFICATION NUMBER J-1O5A(O) I 5 Page 27

FORM APF-05-004-04, Rev. 0 Replacement MSFIS System Appendix A - Input Signals and Sources AE-FV MFIV for Steam Generator C SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3,5 1 ALL CLOSE AC AE-HS-80 Group I contact*

ALL CLOSE AC ESFAS (FWIS) Group I**

CLOSE C AE-HIS-41 Group I C contact OPEN 0 AE-HIS-41 Group 1 0 contact MV2,4,6 4 ALL CLOSE AC AE-HS-81 Group IV contact*

ALL CLOSE AC ESFAS (FWIS) Group IV**

CLOSE C AE-HIS-41 Group IV C contact OPEN 0 AE-HIS-41 Group IV 0 contact AE-FV MFIV for Steam Generator D SEP SIDE GRP COMMAND SIGNAL SOURCE MV1, 3,5 4 ALL CLOSE AC AE-HS-81 Group IV contact*

ALL CLOSE AC ESFAS (FWIS) Group IV**

CLOSE C AE-HIS-42 Group IV C contact OPEN 0 AE-HIS-42 Group IV 0 contact MV2,4,6 1 ALL CLOSE AC AE-HS-80 Group I contact*

ALL CLOSE AC ESFAS (FWIS) Group I**

CLOSE C AE-HIS-42 Group I C contact OPEN 0 AE-HIS-42 Group I 0 contact Page A4 of 4 REV SPECIFICATION NUMBER J1-05A(O) .

Page 28

FORM APF-05-004-04. Rev. 0 Appendix B - Power Supply Fusing and Supply to the Buyer-Supplied Status Monitor ON ¶~TEwAL

,SUPPLIEO L.H I TO SOLEJKO1O MV 1(2)

I POWEtR Von TO SOt.*EOIO MV3(4)

TO SOLVE140 MV5(6)

NOTE:

THE ARRANGEMENT SHOWN IS TO BE DUPLICATED FOR EACH ACTUATION TRAIN FOR EACH MSIV AND MFIV: T oULrMlyLr CONTACT ARRANGIEMENTFOR A I'FIV HAS BEEN SHOWN AS AN E-XAMPILE.

3 AMPERE NOMINAL RATING Page D1 of I REV SPECIFICATION NUMBER J-105A(O)

Page 29"

FORM APF-05-004-04, Rev. 0 Replacement MSFIS System Appendix C - Modified Power Supply Fuses and Functions Assigned SA075A Separation Group I Circuits / Fuses / Functions Valve Existing Fuses / Functions Modified Fuses Functions MSIV I Fl 11,2 Sol A + Status Panel Input Relay Fl 11,2 Sol MVI + Status Panel Input Relay F113,4 Sol B + Sol C + Sol D F113,4 Sol MV3 F 115,6 Sol MV5 MSIV 2 Fl 15, 6 Sol A + Status Panel Input Relay Fl 17,8 Sol MV2 + Status Panel Input Relay Fl17,8 Sol B+SolC+Sol D F119,20 Sol MV4 F121,2 Sol MV6 MSIV 3 F 119,20 Sol A + Status Panel Input Relay F123,4 Sol MVI + Status Panel Input Relay F121,2 Sol B + Sol C + Sol D F125,6 Sol MV3 F127,8 Sol MV5 MSIV 4 F123,4 Sol A + Status Panel Input Relay F129,30 Sol MV2 + Status Panel Input Relay F125,6 Sol B + Sol C + Sol D. F131,2 Sol MV4 F133,4 Sol MV6 MFIV I F151,2 Sol A + Status Panel Input Relay F151,2 Sol MVI + Status Panel Input Relay F153,4 Sol B+Sol C+Sol D F153,4 Sol MV3 F155,6 Sol MV5 MFIV 2 F155,6 Sol A + Status Panel Input Relay F157,8 Sol MV2 + Status Panel Input Relay F157,8 Sol B + Sol C + Sol D F159,60 Sol MV4 F161,2 Sol MV6 MFIV 3 F 159,60 Sol A + Status Panel Input Relay F163,4 Sol MVI + Status Panel Input Relay F161,2 Sol B + Sol C + Sol D F165,6 Sol MV3 F 167,8 Sol MV5 Sol A + Status Panel Input Relay F169,70 Sol MV2 + Status Panel Input Relay MFIV 4 F163,4 F165,6 Sol B + Sol C+ Sol D F171,2 Sol MV4 F173,4 Sol MV6 SA075B Separation Group 4 Circuits / Fuses / Functions Valve Existing Fuses / Functions Modified Fuses / Functions MSIV I F411,2 Sol A + Status Panel Input Relay F411,2 Sol MV2 + Status Panel Input Relay F413,4 Sol B + Sol C +-Sol D F413,4 Sol MV4 F415,6 Sol MV6 MSIV 2 F415,6 Sol A +-StatusPanel Input Relay F417,8 Sol MVI + Status Panel Input Relay F417,8 Sol B + Sol C + Sol D F419,20 Sol MV3 F421,2 Sol MV5 MSIV 3 F419,20 Sol A + Status Panel Input Relay F423,4 Sol MV2 + Status Panel Input Relay F421,2 Sol B + Sol C + Sol D F425,6 Sol MV4 F427,8 Sol MV6 MSIV 4 F423,4 Sol A + Status Panel Input Relay F429,30 Sol MVI + Status Panel Input Relay F425,6 Sol B + Sol C + Sol D F431,2 Sol MV3 F433,4 Sol MV5 MFIV I F451,2 Sol A + Status Panel Input Relay F451,2 Sol MV2 + Status Panel Input Relay F453,4 Sol B + Sol C + Sol D F453,4 Sol MV4 F455,6 Sol MV6 MFIV 2 F455,6 Sol A + Status Panel Input Relay F457,8 Sol MVI + Status Panel Input Relay F457,8 Sol B + Sol C +/- Sol D F459,60 Sol MV3 F461,2 Sol MV5 MFIV 3 F459,60 Sol A + Status Panel Input Relay F463,4 Sol MV2 + Status Panel Input Relay F461,2 Sol B 4 Sol C + Sol D F465,6 Sol MV4 F467,8 Sol MV6 MFIV 4 F463,4 Sol A + Status Panel Input Relay F469,70 Sol MVI + Status Panel Input Relay F465,6 Sol B + Sol C + Sol D F471,2 Sol MV3 I F473,4 Sol MV5 Page El of I I REV SPECIFICATION NUMBER J-105A(Om 5 Page 30

FORM APF-05-004-04, Rev. 0 Replacement MSFIS System Appendix R - Buyer's Inspection Procedures 1.0 SCOPE This appendix details the responsibilities with regard to the inspection of material / equipment covered by this Specification and outlines the activities to be performed by the Buyer's inspector all in accordance with General Conditions, Clause 6, titled, Inspection.

2.0 RESPONSIBILITY The prime responsibility for inspection of all material and work rests with the Controls Seller. The inspection or its waiver by the Buyer does not relieve the Controls Seller and the Qualification Seller of any obligations or responsibility to perform in accordance with all requirements of the Specification.

3.0 ACCESS The Buyer's representative shall be given free access to the Controls Seller's and Qualification Seller's, and their sub-supplier's manufacturing facilities to inspect and report on work in all phases of selection, manufacture, examination, or testing.

4.0 INSPECTION POINTS 4.1 Inspection observations on material produced under this Specification shall include, but not be limited to, the witness andhold points listed in Paragraph 4.2 and 4.3.

4.2 Witness Points Witness points are defined as critical steps in manufacturing and testing where the Controls Seller and Qualification Seller is obligated to advise the inspector 5 days in advance of the start of the operation so that it may be witnessed by the inspector. However, the work may proceed past the witness point if the inspector is not available at the appointed time.

The following activities are classified as witness points and will be witnessed on a first-operation basis for each approved procedure and periodically thereafter.

a. Wire dielectric test
b. Wiring Page RI of 2 REV SPECIFICATION NUMBER J-105A(O 1 Page 31

FORM APF-05-004-04, Rev. 0

c. Component testing 4.3 Hold Points Hold points are defined as critical steps in manufacturing and testing where the Controls Seller and Qualification Seller is obligated to advise the inspector 5 days in advance of the operation so that is may be witnessed by the inspector. The Controls Seller or the Qualification Seller shall not proceed with the work past the hold point except by written waiver (agreement by the inspector).

The following activities are classified as hold points and will be witnessed or performed by the inspector for each item manufactured:

a. Functional / performance testing.
b. Final inspection of materials for construction, dimensions, general workmanship, cleanliness, marking, tagging, and preparation for shipment.

c.. Review and sign-off of supplier's quality verification documents for completeness and accuracy.

d. Release for shipment.

5.0 ACCEPTANCE (

The Buyer's release of any material furnished by the Controls Seller or Qualification Seller, or their subcontractor's shall not imply acceptance of the material or in any way relieve the Controls Seller or Qualification Seller of their responsibility. Final acceptance of all materials is made at the job site.

Page R2 of 2 I REV SPECIFICATION NUMBER 5-105AO.

Page 32

Form APF-05-004-03, Rev. 1 A

DOCUMENTATION SUBMITTAL REQUIREMENTS Specification Number J-105A Rev.. 1 Sheet 1 of 7 A. The following documentation shall be submitted to WCNOC within 60 days after the issuenace of the Controls Seller P0 for the Replacement MSFIS System DOCUMENT SPECIFICATION TYPE & QTY CATEGORY PARAGRAPH COPIES DESCRIPTION AND REMARKS NUMBER REFERENCE REQUIRED 5.0 13.8 1 hc Schedule of Engineering, Fab'n, Test, and Delivery B. The following documentation shall be submitted to WCNOC prior to start of manufacture of production items for WCNOC Engineering review and approval:

DOCUMENT SPECIFICATION TYPE & QTY CATEGORY PARAGRAPH COPIES DESCRIPTION AND REMARKS NUMBER REFERENCE REQUIRED 1.1 13.1 1 elec + hc Outline Drawings 1.5 13.4 1 elec + 1 hc Control Logic diagram 1.2 13.2 1 elec + 1 hc Assembly Drawings 1.4 13.3 1 elec + I hc Wiring Diagrams 7.0 13.6 1 elec + 1 hc Seismic Test Procedures for review 8.0 10.2.1 1 elec + 1 hc Preliminary FMEA and Reliability Analysis C. The following documentation shall be submitted to WCNOC prior to shipment for WCNOC Engineering review and approval:

DOCUMENT SPECIFICATION TYPE & QTY CATEGORY PARAGRAPH. COPIES DESCRIPTION AND REMARKS NUMBER REFERENCE REQUIRED 7.0 13.6 1 hc Seismic Test Data Reports 26.0 10.4.1 and 13.7 1 elec + 1 hc Performance Test Procedures and Reports aka FAT 28.0 12.1.10 1 elec + 1 hc Handling, Shipping, and Storatge Procedures D. The following documentation shall be submitted to WCNOC with shipment of the item. Prior WCNOC Engineering review and approval is not required:

DOCUMENT SPECIFICATION TYPE & QTY CATEGORY PARAGRAPH COPIES DESCRIPTION AND REMARKS NUMBER REFERENCE REQUIRED 2.0 13.10 1 elec +.1 hc Repair Parts List - 20 Years' Consumption 4;0,.1, .2,.3,.4 13.5 8 hc Instruction Manual 8.0 10.2.1 1 elec + 1 hc Final FMEA and Reliability Analysis

Form APF-05-004-03, Rev. 1 A

DOCUMENTATION SUBMITTAL REQUIREMENTS Specification Number J-105A Rev. .1 Sheet 2 of 7 DOCUMENT CATEGORY DEFINITIONS FOR FORM APF-05-004-03 (E) Engineering Documents - This term comprises procedures, drawings, specifications, QA plans, prototype qualification test reports, and other similar documents that require approval prior to use of the document in the design, fabrication, installation or other work process. The term is also applied to price lists and instructional documents'for handling, storage, maintenance, etc., that are informational interest only to engineering.

(V) Quality Verification Documents - This term comprises material test reports, heat treatment charts, welding reports, NDE results, performance test reports, etc.,

which demonstrate or certify conformance to the technical or inspections requirements of the procurement documents.

1.0 DRAWINGS (E) 1.1 Outline Dimensions, Services and Foundation/Mounting Details - Drawings providing external envelope, including lugs, center line(s), location and size for electrical cable, conduit, fluid and other service connections, isometrics and details related to foundations and mountings.

1.2 Assembly Drawings - Detailed drawings indicating sufficient information to facilitate assembly of the component parts of an equipment item.

1.3 Shop Detail Drawings - Drawings which provide sufficient detail to facilitate the fabrication or manufacture of the equipment item. This includes but is not limited to, spool drawings, heat exchanger internal details, internal piping and wiring, cross-sectional details and architectural details.

Form APF-05-004-03. Rev. 1 A

DOCUMENTATION SUBMITTAL REQUIREMENTS Specification Number J-1 05A Rev. .1 Sheet 3 of 7 DOCUMENT CATEGORY DEFINITIONS FOR FORM APF-05-004-03 1.4 Wiring Diagrams - Drawings which show the schematic wiring and connection information for electrical items.

1.5 Control Logic Diagrams - Drawings which show the paths which input signals must follow to accomplish the required responses.

1.6 P & IDs - Piping and instrumentation diagrams which show piping system details and the basic control elements.

2.0 PARTS LIST AND COST (E) - Exploded view with identified parts and recommended spare parts for one year's operation with unit cost.

3.0 COMPLETED DATA SHEETS (E) - Information provided by a supplier on data sheets furnished by WCNOC which states serial number, operating ranges, etc., of equipment that the supplier intends to deliver to satisfy the specification requirements.

4.0 INSTRUCTIONS (E) 4.1 Erection/Installation - Detailed written procedures, instructions, and drawings required to erect or install material or equipment.

4.2 Operating - Detailed written instructions describing how an item or system should be operated.

4.3 Maintenance - Detailed written instructions required to disassemble, reassemble and maintain items or systems in an operating condition.

4.4 Site Storage and Handling - Detailed written instructions which define the requirements and time period for lubricating, rotating, heating, lifting or other handling requirements to prevent damage or deterioration during storage and handling at jobsite.

5.0 SCHEDULES ENGINEERING AND FABRICATION/ERECTION (E) - Bar charts, critical path methods, etc., which chronologically detail the sequence of activities.

6.0 QUALITY ASSURANCE MANUAL PROCEDURES (E) - The documents which describe the planned and systematic measures that are used to assure that structures, systems and components will meet the requirements of the procurement documents.

Form APF-05-004-03, Rev. 1 A

DOCUMENTATION SUBMITTAL REQUIREMENTS.

Specification Number J-105A Rev.. 1 Sheet 4 of 7 DOCUMENT CATEGORY DEFINITIONS FOR FORM APF-05-004-03 7.0 SEISMIC DATA REPORT (E) - The analytical or test data which provides physical response information on an item, material, component or system in relation to the conditions imposed by the stated seismic criteria.

8.0 ANALYSIS AND DESIGN REPORT (E) - The analytical data (stress, electrical loading, fluid dynamics, etc.) which assures that an item satisfies specified requirements.

9.0 ACOUSTIC DATA REPORT (E) - The noise, sound and other vibration data required by specification which is the audible range and above the seismic frequency.

10.0 SAMPLES (E) - A representative sample of the material to be used or a representative data package which will be submitted for the items purchased as required in the specification.

11.0 MATERIAL DESCRIPTION (E) - The technical data describing a material which a supplier proposes to use for a specific order. This usually applies to architectural items, e.g., metal siding, decking, doors, paints, and coatings.

12.0 WELDING PROCEDURES AND QUALIFICATION (E) AND VERIFICATION REPORTS (V) -. The welding procedure specification and supporting welding procedure qualification test records required for welding hard facing, overlay,'

brazing and soldering. A verification report of welds performed includes the identification of the qualified welders, and the procedures used, and certification that the welders were qualified.

13.0 WELD ROD CONTROL PROCEDURES (E) AND VERIFICATION REPORTS (V) -

The procedures for controlling issuance, handling, storage and traceability.

Verification report(s) for weld rod are defined as certified material test reports which include the requirements defined by the code and material specification imposed by the procurement documents.

Form APF-05-004-03, Rev. 1 A

DOCUMENTATION SUBMITTAL REQUIREMENTS Specification Number J-105A Rev. .1 Sheet 5 of 7 DOCUMENT CATEGORY DEFINITIONS FOR FORM APF-05-004-03 14.0 REPAIR PROCEDURES (E) AND MAJOR REPAIR VERIFICATION REPORTS (V) -

The procedures for controlling material removal and replacement by welding, brazing, etc., subsequent thermal treatments, and final acceptance inspection.

Verification reports may include weld repair locations (maps), material test reports for filler metal, pre-and-post-weld heat treatment records, NDE records, etc. The resolution of whether a repair is major or not is a WCNOC responsibility.

15.0 CLEANING AND COATING PROCEDURES (E) AND VERIFICATION REPORTS (V) - The procedures for removal of dirt, grease or other surface contamination and includes application of protective coatings. Verification reports include certification of visual examination for surface preparation, surface profile, materials, etc.,

humidity data, temperature data and coating thickness data as required by the procurement documents.

16.0 HEAT TREATMENT PROCEDURES (E) AND VERIFICATION REPORTS (V) - The procedures for controlling temperature, time at temperature as a function of thickness, furnace atmosphere, cooling rate and method, etc. Verification reports normally include furnace charts or similar records which identify and certify the item(s) treated, the procedure used, furnace atmosphere, time at temperature, cooling rate, etc. Verification data may be in either narrative or tabular form.

17.0 CERTIFIED MATERIAL PROPERTY REPORTS (V) 17.1 CMTR (Certified Material Test Reports) -These reports include all chemical, physical, mechanical and electrical property test data required by material specification and applicable codes. This is applicable to cement, concrete, metals, cable jacket materials, rebar, rebar splices, etc. The certified MTR shall include a statement of conformance that the materials meet the specification requirements.

17.2 Impact Test Data - Results of any Charpy or drop weight tests including specimen configuration, test temperature and fracture data.

17.3 Ferrite Data - Report of the ferrite percentage for stainless steel materials used, including castings and welding filler metals as deposited.

17.4 Material Certificate of Compliance - Verification document which certifies conformance to the requirements of the applicable material specification.

17.5 Electrical Property Reports - Report of electrical characteristics, e.g., dielectric, impedance, resistance, flame test, corona, etc.

Form APF-05-004-03, Rev. 1 A

DOCUMENTATION SUBMITTAL REQUIREMENTS Specification Number J-105A Rev.. 1 Sheet 6 of 7 DOCUMENT CATEGORY DEFINITIONS FOR FORM APF-05-004-03 18.0 CODE COMPLIANCE (V) - Verifying documents (such as data Forms U-I, N-2, State, etc.) which are prepared by the manufacturer or installer and certified by the Authorized Code Inspector.

19.0 UT - ULTRASONIC EXAMINATION PROCEDURES (E) AND VERIFICATION REPORTS (V) - Method of detection and examination results of presence and certain characteristics of discontinuities and inclusions in materials by the use of high frequency acoustic energy.

20.0 RT - RADIOGRAPHIC EXAMINATION PROCEDURES (E) AND VERIFICATION REPORTS (V) - Method of detection and examination results of presence and certain characteristics of discontinuities and inclusions in materials by x-ray or gamma ray exposure of photographic film.

21.0 MT - MAGNETIC PARTICLE EXAMINATION PROCEDURES (E) AND VERIFICATION REPORTS (V) - Method of detection and examination results of surface (or near surface) discontinuities in magnetic materials by distortion of an applied magnetic field.

22.0 PT - LIQUID PENETRANT EXAMINATION PROCEDURES (E) AND VERIFICATION REPORTS (V) - Method of detection and examination results of surface discontinuities in materials by application of a penetrating liquid in conjunction with suitable developing techniques.

23.0 EDDY CURRENT EXAMINATION PROCEDURES (E) AND VERIFICATION REPORTS (V) - Method for detection and examination results of discontinuities in material by distortion of an applied electromagnetic field.

24.0 PRESSURE TEST - HYDRO, AIR, LEAK, BUBBLE OR VACUUM TEST PROCEDURE (E) AND VERIFICATION REPORTS (V) - Method for evaluating the structural and mechanical adequacy or integrity by application of differential pressure and report of the test results.

25.0 INSPECTION PROCEDURE (E) AND VERIFICATION REPORTS (V) -

Organized process followed for the purpose of determining that specified requirements (dimensions, properties, performance results, etc.) are met.

Documented findings resulting from an inspection are included in the verification report.

Form APF-05-004-03, Rev. 1 AJ DOCUMENTATION SUBMITTAL REQUIREMENTS V

Specification Number J-105A Rev. .1 Sheet 7 of 7 DOCUMENT CATEGORY DEFINITIONS FOR FORM APF-05-004-03 26.0 PERFORMANCE TEST PROCEDURES (E) AND VERIFICATION REPORTS (V) - Tests performed to demonstrate that functional design and operational parameters are met'and the report of the test results.

26.1 Mechanical Tests, e.g., pump curves, valve stroking, load, temperature rise, calibration, environmental, etc.

26.2 Electrical Tests, e.g., load, impulse, overload, continuity, voltage, temperature rise, calibration, saturation, loss, etc.

27.0 PROTOTYPE TEST REPORT (E AND V) - Report of a test which is performed on a standard or typical example of equipment, material or item, and is not required for each item produced in order to substantiate the acceptability of equal items. This normally includes tests which may, or could be expected to, result in damage to the item(s) tested.

28.0 SUPPLIER SHIPPING PREPARATION PROCEDURE (E) - The procedure used by the supplier to prepare finished materials or equipment for shipment from his facility to the jobsite.