Enclosure VIII to WM 09-0001 CS Innovations Report 6002-00026, "ALS Platform Overview," Rev. 2 Non-proprietary

Non-Proprietary ALS Advanced Logic System 6002-00026 ALS Platform Overview Revision 2 Jan. 16, 2009 CS Innovations, LLC CONFIDIENTIAL AND PROPRIETARY - CLASS 4 This document is the property of and contains Proprietary Information owned by CS Innovations, LLC. It is transmitted to you in confidence and trust, and you agree to treat this document in strict accordance with the terms and conditions of the agreement under which it was provided to you.

This document may not under any circumstances be reproduced, disclosed or utilized in-whole or in-part without the written authorization of CS Innovations LLC

© 2008 CS Innovations, LLC All Rights Reserved

ALS Platform Overview Non-Proprietary CS Innovations LLC AL 1lafr Overview2 Cagdcntnofdcm ttoon-PrrprieearryCStennSovatinsLL RECORD OF CHANGES Revision Date Description of changes Made by PRE-A July 2008 Conversion from previous ALS LI Spec to new CSI format.

Steen Sorensen Removed board requirement specifications, and split it up in separate and independent documents.

1 2008-06-29 Changed content of document to Non-Proprietary Sten Sogaard 2

2009-01-12 Added section 12 and 13 regarding ALS self-test and cyber Steen Sorensen security OPEN ITEMS Item Description Status 6002-00026, Rev 2, Jan. 16, 2009 Page 2 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Table of Content 1

In tro d u c tio n........................................................................................................................................................

6

1.1 Purpose and Scope

6 1.2 O v e rv ie w...................................................................................................................................................

6 1.3 Patent Pending Technology.............................................................................................................

6 1.4 References 7

1.5 Acronyms, Units of Measure and Designations..................................................................................

8 1.6 ALS Hardware Components and Definitions............................................................................................

9 2

ALS Platform Overview....................................................................................................................................

10 2.1 ALS History.............................................................................................................................................

10 2.2 Characteristics of the ALS......................................................................................................................

11 2.3 ALS Architecture Overview.....................................................................................................................

12 2.3.1 ALS Hardware............................................................................................................................

12 2.3.2 ALS Boards.................................................................................................................................

13 2.4 ALS Operation.........................................................................................................................................

16 2.5 ALS Technology based on Solid State.............................................................................................

17 2.5.1 FPGA Devices.:...........................................................................................................................

17 2.5.2 Non-Volatile Memory (NVM )..................................................................................................

19 2.5.3 Input/Output...............................................................................................................................

19 2.6 Standards Compliance............................................................................................................................

20 2.6.1 Class 1E Safety Classification...............................................................................................

20 2.6.2 Quality Assurance.......................................................................................................................

20 2.6.3 RoHS Compliance.......................................................................................................................

20 2.6.4 IPC Standards Compliance.....................................................................................................

20 3

A L S B o a rd s......................................................................................................................................................

2 1 3.1 Core Logic Board (CLB)..........................................................................................................................

21 3.2 Service and Test Board (STB)............................................................................................................

22 3.3 Input Boards (IPB)..................................................................................................................................

23 3.4 Output Boards (OPB)..............................................................................................................................

24 3.5 Com munication Board (COM).................................................................................................................

25 3.6 Power Supply Board (PSU)....................................................................................................................

25 4

Environmental ALS Platform Qualifications................................................................................................

26 4.1 Tem perature............................................................................................................................................

26 4.2 Radiated Emissions................................................................................................................................

26 4.3 Conducted Em issions.............................................................................................................................

26 4.4 Radiated Susceptibility............................................................................................................................

26 4.5 Conducted Susceptibility.........................................................................................................................

26 4.6 S u rg e.......................................................................................................................................................

2 7 4.7 S e is m ic....................................................................................................................................................

2 7 5

ALS Rack Mechanics.......................................................................................................................................

28 5.1 Rack Mechanics......................................................................................................................................

28 5.2 ALS Slot and Card Configuration.......................................................................................................

28 5.3 ALS Rack Materials................................................................................................................................

28 5.4 ALS Front-Panel......................................................................................................................................

28 5.4.1 System LEDs...............................................................................................................................

29 5.4.2 Board Latches.............................................................................................................................

29 5.5 ALS Rear-Panel......................................................................................................................................

30 5.6 Cable Harnesses.....................................................................................................................................

31 5.7 A L S B o a rd s..........................................................................................................

3 1 6

ALS Power Management.................................................................................................................................

32 6.1 ALS Ground Domains.............................................................................................................................

32 6.1.1 5V Power Domain.......................................................................................................................

33 6.1.2 3V Power Domain.......................................................................................................................

33 6.1.3 2.5V Power Domain....................................................................................................................

33 6002-00026, Rev 2, Jan. 16, 2009 Page 3 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 7

ALS Modes and States....................................................................................................................................

34 7.1 ALS System Modes................................................................................................................................

34 7.1.1 ALS System Mode versus Local System Mode...................................................................

35 7.2 Classification of Failures.........................................................................................................................

36 7.3 Alarm Generation....................................................................................................................................

37 7.4 ALS Test Mode.......................................................................................................................................

37 8

ALS Com munication........................................................................................................................................

38 8.1 ALS Bus Facts........................................................................................................................................

38 8.2 ALS Bus Protocol....................................................................................................................................

39 8.3 ALS Bus Failure Detection and M itigation........................................................................................

40 8.3.1 ALS Bus Failure Mode Error Analysis....................................................................................

40 8.3.2 ALS Bus Failure Detection....................................................................................................

41 8.4 ALS Bus Physical Layer..........................................................................................................................

41 9

ALS Service Unit (ASU)..................................................................................................................................

42 9.1 Configuration Report...............................................................................................................................

42 10 SetPoint Configuration.....................................................................................................................................

43 10.1 SetPoint Definition..................................................................................................................................

43 10.2 Configuration Integrity.............................................................................................................................

43 11 Redundancy.....................................................................................................................................................

44 11.1 Redundancy............................................................................................................................................

44 1 1.2 B IS T........................................................................................................................................................

4 4 11.3 Inherent Self-test.....................................................................................................................................

44 12 Self-testing in ALS Platform.............................................................................................................................

45 12.1 Surveillance Testing Support...........................................................................................................

46 13 Cyber Security..................................................................................................................................................

47 13.1 Comm unication points............................................................................................................................

47 13.2 Cyber Security Fact sheet for ALS-based systems..........................................................................

48 6002-00026, Rev 2, Jan. 16, 2009 Page 4 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 4 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC Table of Tables Table 2-1 : ALS Board Types....................................................................................................................................

13 Table 2-2: Comparison between SRAM, FLASH and FUSE based FPGAs.......................................................

18 Table 7-1: ALS System M odes.................................................................................................................................

35 Table 8-1: Sim ple ALS Bus FM EA...........................................................................................................................

40 Table 12-1: Self-testing intervals in the ALS Platform........................................................................................

46 Table of Figures Figure 2-1: ALS Rack...............................................................................................................................................

12 Figure 2-3: G eneric ALS Architecture.......................................................................................................................

14 Figure 5-1: G eneric versus Custom Front Plate..............................................................

......................................... 29 Figure 5-2: ALS Rack Rear View (W olfCreek M SFIS Application)......................................................................

30 Figure 5-3: M ale Phoenix Field-Connector.........................................................................................................

30 Figure 5-4: Generic ALS Board with ALS Bus Connector. The front panel width will vary..................................

31 Figure 6-1: ALS Platform Power Dom ains........................ :................................................................................

33 Figure 7-1: ALS System M ode..... *............................................................................................................................

34 Figure 12-1: ALS Platform Self-Testing....................................................................................................................

45 6002-00026, Rev 2, Jan. 16, 2009 Page 5 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 5 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Il Introduction

1.1 Purpose and Scope

This document provides an overview of the Advanced Logic System (ALS). It is intended to be a non-proprietary overview of the ALS Platform and does not contain sensitive or proprietary information. The content is extracted from the ALS document suite, including 6000-00000, 6000-00102, 6000-00103, 6000-00104, 6000-00105, 6000-00106, and 6000-00107.

The purpose of this document is to provide an overview and general understanding of the ALS platform and how it can be used in a wide range of Nuclear Power Plant safety related I&C applications.

1.2 Overview The document is organized in the following chapters:

1) Chapter 2: ALS Platform Overview - General background information about the ALS Platform and its history
2)

Chapter 3: ALS Boards - Description of the different types of ALS Boards available

3)

Chapter 4: Environmental Qualifications - Describes EMI, Surge, Seismic and Temperature capabilities

4) Chapter 5: ALS Rack Mechanics - General Description of how the ALS Platform is constructed
5) Chapter 6: ALS Power Management - ALS Power Domains
6) Chapter 7: ALS Mode and States - Operational states of the ALS Platform
7)

Chapter 8: ALS Communication - Description of how ALS Boards communicate

8)

Chapter 9: ALS Service Unit - Service and test support equipment

9)

Chapter 10: SetPoint Configuration - ALS Configuration capabilities

10) Chapter 11: Redundancy - ALS Redundancy strategy 1.3 Patent Pending Technology The ALS Platform is a CS Innovations invention with multiple patents pending. The patents focus on key aspects of the platform ranging from the overall platform architecture to details associated with diagnostics and methods used to ensure high integrity in solid state circuits and FPGAs.

6002-00026, Rev 2, Jan. 16, 2009 Page 6 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 6 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 1.4 References

[1]

9000-00000 - CS Innovations Quality Manual, CS Innovations

[2]

NUREG 1.180 - Guidelines for Evaluating Electromagnetic and Radio Frequency Interference in Safety-Related Instrumentation and Control Systems

[3]

IEEE 344-1975 - Recommended Practice for Seismic Qualification of Class 1E Equipment

[4]

EPRI TR-102323 - Guidelines for Electromagnetic Interference Testing of Power Plant Equipment

[5]

IPC-A-610D - Acceptability of Electronics Assemblies

[6]

IPC-A-620 - Requirements and Acceptance for Cable and Wire Harness Assemblies

[7]

IPC-6012B - Qualification and Performance Specification for Rigid Printed Boards

[8]

IEEE 420-2001 - IEEE Standard for the Design and Qualification of Class 1E Control Boards, Panels, and Racks Used in Nuclear Power Generating Stations

[9]

Regulatory Guide 1.152 - Criteria for use of Computers in Safety Systems of Nuclear Power Plants, Rev 2

[10]

NIE 04 Cyber Security Program for Power Reactors, Rev 1

[11]

IEEE 603-1998, Standard Criteria for Safety Systems for Nuclear Power Generating Stations 6002-00026, Rev 2, Jan. 16, 2009 Page 7of50 6002-00026, Rev 2, Jan. 16, 2009 Page 7 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 1.5 Acronyms, Units of Measure and Designations The following table defines pertinent acronyms used in this document.

Acronym Definition ALS Advanced Logic System - CS Innovations hardware architecture platform ASU ALS Service Unit ATE ALS Test Equipment - reference the complete test harness, including the ATU ATU ALS Test Unit - independent test unit, which provides stimuli and tests ALS Racks BIST Built In Self Test includes dedicated logic for failure detection BoardlD Unique ID assigned to each board related to the physical position in the Rack CLB Core Logic Board CRC Cyclic redundancy check (CRC) is used to produce a checksum - a small, fixed number of bits

- against a block of data, such as a packet of network traffic or a block of information. The checksum is used to detect errors after transmission or storage.

EIA-485 Industry standard differential signaling protocol (formerly RS-485)

EMC Electro-Magnetic Compatibility EMI Electro-Magnetic Interference ESFAS Engineered Safety Features Actuation System FCO Full Capability Operation (System Mode)

FPGA Field Programmable Gate Array Half-duplex A half-duplex system provides for communication in both directions, but only one direction at a time (not simultaneously). Once a device begins receiving a signal, it must wait for the transmitter to stop transmitting, before replying.

IPB Input Board I&C Instrumentation and Control which may refer to both engineers and technicians MCB Main Control Board MSFIS Main Steam and Feedwater Isolation System NVM Non-Volatile Memory also known as Flash Memory technology PSU Power Supply Unit (ALS Board based power supply)

RAB Reliable ALS Bus RCO Reduced Capability Operation (System Mode)

RFI Radio Frequency Interference RPS Reactor Protection System RTL Register Transfer Level refers to coding style utilized for the ALS design STB Service & Test Board TAB Test ALS Bus TVS Transient Voltage Suppressor (Zener diode)

The following table defines pertinent units and measurements used in this document.

Unit Definition 6U 6 Rack Units (1 U = 1.75" / 44.45mm), common unit of measure used in 19" cabinets.

6HP 6 Hole Pitch (1 HP=0.2" / 5.08mm), common unit of measure used in 19" cabinets.

6002-00026, Rev 2, Jan. 16, 2009 Page 8 of 50,

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC 1.6 ALS Hardware Components and Definitions ALS Rack I Chassis I Platform Rack /

Sub-Rack A 19" cabinet mountable sub-rack. The ALS Rack is 6U tall and 16" deep. (1U=1.75").

Cables connect to the rear of the ALS rack and ALS boards are inserted from the front.

The 19" mountable sub-rack is an industry standard form factor.

2i "¸ V *fl

/

1/4 ALS Board I ALS Card /

ALS Module A daughter card assembly which can be inserted into the ALS Rack. The ALS board includes printed circuit board, back plane connectors and front plate with injector/ejector latches. The ALS boards will have different front panel with depending on the type of board, but will generally be between 6HP and 12HP. (1 HP=0.2").

+/-

Back Plane /

Back Plane Assembly The back plane assembly is mounted as the rear wall of the ALS rack and serves to interconnect the ALS boards and to connect the ALS rack with power and field signals.

Aluminum Back Plate PCB Back Plane T_**--....

PC B

Field Connector 0

K 6002-00026, Rev 2, Jan. 16, 2009 Page 9 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC 2

ALS Platform Overview The Advanced Logic System (ALS) is a new approach to safety critical control systems. The ALS is a universal platform which targets safety critical control systems, where reliability and integrity are of the highest importance.

The ALS is a logic based platform-which does not utilize a microprocessor or software for operation, but instead relies on a simple hardware architecture.

The ALS platform incorporates advanced features to allow for diagnostics, testability, and modularity. The ALS platform is designed to be at the appropriate level of complexity to achieve high reliability and integrity as well as allow enough flexibility to target multiple safety critical applications within a given plant. Diagnostics and testing capabilities are designed into the ALS platform to ensure there is a systematic approach to maintaining and testing the system.

2.1 ALS History United States Nuclear Power Plants (USNPPs) have been facing significant challenges with replacing their existing safety related I&C systems. The original manufacturers of the existing equipment are in most cases either out of business or no longer support the product lines. The USNPPs has been faced with two approaches to replacing their safety related I&C systems 1) Reverse engineer the existing system and maintain the system as obsolescence and failures occur. 2) Replace the system with a Commercial-Off-The-Shelf system (COTS). Both of these approaches have a number of issues to contend with. The reverse engineered approach is a short term fix for a long term problem. This approach offers no benefit from advancements in the areas of system integrity, diagnostics, and testability. The COTS approach is typically a much more complex system, as it was designed for more complex industrial control applications. Since the COTS target is complex commercial controls systems the COTS platforms are rapidly advancing. This situation significantly shortens the obsolescence cycle of the product and creates issues with configuration control of the installed systems.

In late 2003 Wolf Creek Nuclear Generating Station was faced with the situation described above. Wolf Creek had an immediate need to replace one of the RPS/ESFAS safety related I&C Systems due to reliability and obsolescence issues. Based on this need and the fact that no viable solutions existed in the market place, Wolf Creek began working towards a new approach. In early 2004 Wolf Creek partnered with CS Innovations on a new approach to replacing safety related I&C systems. As a result of this partnership the ALS architecture was proposed, by CS Innovations, as a general control platform to target the USNPPs Safety Related I&C System retrofit market.

The ALS is designed as a universal control system platform, but specifically targets Class 1 E Reactor Protection Systems (RPS) and Engineered Safety Features Actuations Systems (ESFAS). The ALS architecture solves the issues associated with both the reverse engineered and COTS approaches described above. The ALS provides advanced diagnostics and testability features which improve the plant I&C personnel's ability to perform surveillance testing and well as diagnose failures should they occur. System integrity is greatly increased over the exiting systems; by eliminating single point vulnerabilities with the ability to identify and address any failure within the system without causing plant transient. The reliability of the system increases due to the simplicity of the ALS architecture and incorporating a repeatable advanced design process for system development. Issues associated with future obsolescence are solved by incorporating a simplified board level design and maintaining proven logic in an abstracted form in the event the underlying hardware is required to be updated in the future. This eliminates the issue of essentially starting from scratch with each update. In addition to solving the above issues, the ALS provides benefits in the area of common spares and common training for station personnel. These benefits are realized -by the ability of the ALS to be installed as a common platform which all safety related I&C systems can be based upon.

The ALS platform has been fully designed, built, tested. This included all environmental qualification testing. The ALS meets and exceeds all areas within the EMI/RFI and seismic testing. This high level of environmental robustness ensures the ALS can be installed in all of the environments the existing safety related I&C systems reside.

CS Innovations has incorporated a very robust design, build, and test process. This process is constructed to be highly repeatable and allows CS Innovations to design, build, test and install safety related I&C applications based on the ALS Platform.

6002-00026, Rev 2, Jan. 16, 2009 Page 10 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 10 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 2.2 Characteristics of the ALS Integrity through dedicated Failure Detection and Isolation The ALS incorporates advanced failure detection and isolation techniques. The operation of the system is deterministic in nature and allows the system to monitor itself for validation of the desired function. The ALS implements advanced failure detection and mitigation in the active path, to avoid unintended plant events, and in the passive path to ensure inoperable systems cannot remain undetected. Undetected failures could cause an unintended plant event or prevent the system from performing its intended safety function, the ALS advanced failure detections prevents this situation. The ALS platform is based on autonomous boards working together. The system utilizes advanced logic to perform distributed control where no single failure will result in an erroneous plant event while maintaining the ability to perform the intended safety function.

Reliability Reliability is one of the key aspects of a safety critical control system. The ALS incorporates several characteristics to achieve a high level of reliability. The ALS is both an analog and digital platform based on solid-state devices, such as opto-couplers, FPGAs, line drivers, and FET power transistors. The ALS utilizes proven FPGA technology to support a higher-level of integration. The higher level of integration removes discrete logic components and reduces overall system hardware requirements, i.e. fewer racks, boards, and relays. Reducing the complexity of the system has several benefits with regards to reliability and availability. A simpler system directly translates into increased reliability by incorporating fewer components. Another benefit is lower power dissipation which increases the overall system life and ensures a high level of system availability.

The ALS does not utilize a microprocessor and therefore has no software component for the operation of the system.

The concern for software common mode failures is eliminated by incorporating a full hardware system which only uses proven design practices and methodologies for implementation of the hardware.

Advanced Diagnostics The ALS supports advanced diagnostics features, such as LiveView and BlackBox using the ALS Service Unit (ASU). The ASU is a dedicated piece of test equipment which can be connected to the ALS rack during diagnostics or testing by plant personnel. LiveView is a non-intrusive diagnostics tool which allows plant personnel to access detailed status and configuration information of the system while the system is online. The BlackBox function provides post event analysis information about the system to plant personnel for evaluation of the event after it has occurred.

Universal Platform The ALS is highly customizable to support a wide variety of safety system applications. The ALS architecture is scalable allowing for a single system upgrade up to full set of safety system upgrades using the same ALS platform.

The system can be upgraded to support additional requirements which are added to the application after it has been deployed in the field. The ALS technology platform supports many additional features compared to the older relay, ECL or TTL systems, including increased testability, advanced diagnostics, increased integrity and reliability.

Maintainability Long term maintainability is an important piece of the ALS Platform. Component obsolescence is a challenge to all electronics, especially if the components are one of a kind with only a single source. The obsolescence mitigation strategy for the ALS platform is to use industry standard components with a wide customer base. This helps ensuring availability of the components and increases the likelihood of second sources being available. Furthermore the FPGA logic is described at an abstracted level with allows for easy retargeting in the event the underlying hardware is required to be updated in the future.

Common Spare Parts The ALS Platform is designed to allow for common spare parts between different ALS systems. This plays an important role in the long term maintainability of the platform and eases training and logistics requirements for the plant personnel.

6002-00026, Rev 2, Jan. 16, 2009 Page 11 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Plafform Overview Non-Proprietary CS Innovations LLC 2.3 ALS Architecture Overview 2.3.1 ALS Hardware An application implemented using the ALS platform typically consists of one or more ALS racks and an assembly panel which incorporates terminal blocks, fuse holders and other field interface hardware.

The ALS rack is an industry standard 19" sub-rack and can be mounted in a wide variety of existing 19" cabinets.

The ALS boards are designed to a CS Innovations proprietary standard for size and shape of the board. This proprietary standard ensures only ALS boards will fit into the ALS rack, which is critical for ensuring the integrity of the safety system.

Each rack contains a number of boards which is dependent on the particular safety application as well as the type of boards that are fitted into the rack. An ALS rack will typically contain 6-14 boards.

A number of ALS racks can be chained together through an expansion bus if more boards are needed for a specific application. The internal bus system architecture allows for up to 62 boards to be connected in up to six different racks. Generally the racks must be located within 50 feet of one another.

Figure 2-1 shows a typical ALS rack configuration with the following parts:

M (#1) Sub-rack mountable in a 19" rack M (#2) Core Logic Board W (#3) Service and Test Board 0

(#4 - #9) A number of 10-boards (up to 12)

M (#10) power supply boards a

(#11) Application name-plate W Customized back panel and (#12) back plate w/ interconnects for cabling Figure 2-1: ALS Rack An ALS rack may be powered directly from the Class 1 E power source to a redundant pair of current-sharing internal power supply boards (DC-DC converters). The power supply boards ensure a stable internal ALS rack voltage of 5V.

Each power supply board is capable of supplying the ALS rack with sufficient power to continue un-interrupted operation should one of the power supply boards fail.

6002-00026, Rev 2, Jan. 16, 2009 Page 12 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 2.3.2 ALS Boards The ALS Platform is based on a combination of generic ALS boards; which can be retargeted either directly or after a simple configuration, and dedicated ALS boards; where the FPGA logic has been configured for a specific application. Examples of such ALS boards are listed below:

Table 2-1: ALS Board Types Board Type Configuration Description Core Logic Board (CLB)

Dedicated Board 1 Responsible for control related activities and primary communication in the system. See Section 3.1.

Input Board (IPB)

Generic Configurable 2 Responsible for conditioning, sensing and filtering of field input signals. See Section 3.2.

Output Board (OPB)

Generic Configurable 2 Responsible for controlling and conditioning of field output signals. See Section 3.3.

Service & Test Board (STB)

Generic Configurable 2 Provides diagnostics and monitoring capability to the ALS platform. See Section 3.4.

Communication Board (COM)

Generic Configurable 2 Provides secure communication links to external systems.

See Section 3.5.

Power Supply Unit (PSU)

Generic 3 Generates supply voltages from external power source.

See Section 3.6.

1) 2)

FPGA is configured with application specific logic.

Generic board, with configuration capability. Note: precautions to avoid incorrect configurations..

3)

Generic board without configuration capability.

X2 X1 Figure 2-2: Generic ALS Board Figure 2-2 shows a typical FPGA based ALS board. The Logic Circuit includes the voltage conditioning, FPGA and bus communication circuits. Generally all FPGA based ALS boards have identical components in the logic circuit area. The Channel Circuit area will vary with board type, this is the area where input channel conditioning or output drive channels are located.

6002-00026, Rev 2, Jan. 16, 2009 Page 13 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Communication RAB/TAB - Board communication is supported using two different types of independent serial data structures; RAB: Reliable ALS Bus TAB: Test ALS Bus The RAB is used for all data transfers between ALS boards during normal system operation, and the TAB is used for integrity monitoring, diagnostics and test information. Figure 2-3 below illustrates a generic ALS architecture with a total of 9 boards (simple ALS systems will have fewer boards and not include all board types). The boards communicate over the ALS Back Plane using RAB and TAB busses. The CLB is master on the RAB and the STB is master on the TAB. The RAB/TAB bus architecture is a simple differential EIA-485, point-to-point, master-slave communication protocol with a CS Innovation proprietary communication protocol and standard cyclic redundancy checks (CRC) protection to ensure the integrity of the communicated information between two boards. There will normally only be one TAB bus, but there may be multiple RAB busses if additional redundancy is required. Chapter 8 describes the ALS Communication in more detail.

CORE LOGIC BOARD LOGI FUNCTIONS IPOWER SUPPLY BOARD INPUT BOARDA

-E*OTU OR INPUT BOARD OUTPUT BOARD ICh OUT #1 IN #316 S

OUT #16 CTRL+ON FIILTER CTRL+ES FITRCTRL CTRL-SENSE CODTN I

SERVICE & TEST BOARD COMMUNICATION BOARD ASUJ Figure 2-3: Generic ALS Architecture Note: Figure 2-3 is an example only. A minimum system may only include a CLB, /PB, OPB, STB and PSU, a total of 6 boards. More complex systems may include multiple CLBs,/IPBs OBPs, COMs, STBs and PSUs in order to provide redundancy.

6002-00026, Rev 2, Jan. 16, 2009 Page 14 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Common Components/Design - Component reuse and circuit design reuse is a key aspect of the ALS platform design. This improves long term reliability and maintainability, but also gives the ALS boards a common look and feel. Generally the ALS board utilizes the following standard components:

FPGA - handles all communications, control and integrity activities, and self-test functions

" Voltage regulators and monitors - ensures stable local board voltages Local oscillator - ensures a stable local timing reference Non-Volatile Memory (NVM) - stores all configuration information EIA-485 - differential communication transceiver used for serial communication links.

In addition to the components above, all 10 boards incorporate dedicated 10 channels which typically include opto-coupler, TVS, and MOV devices for isolation and protection Configurable Boards - The ALS Boards have a dedicated FLASH devices to store application specific SetPoints.

The SetPoint configuration is stored in an external Non-Volatile Memory (NVM) and local copies are maintained /

utilized within the FPGA. The configuration memory is particularly important for I/O boards, where the configuration memory allows for board reuse and common spare parts. Precautions have been made in the ALS platform to ensure that an incorrectly configured I/O board cannot cause unintended plant event if inserted into a rack.

System Mode - The ALS Platform utilizes a System Mode concept to control and indicate the overall capability of the ALS system. The System Mode is communicated between all boards within the rack as a part of the integrity information passed between the boards, it also provides easy to interpret diagnostics information to the plant personnel. The System Mode will during operation be in one of the following four modes; Full Capability Operation (FCO), Reduced Capability Operation (RCO), HALT mode, or (RESET) mode.

FCO - Full Capability Operation: The ALS platform is operating in a normal mode of operation, and is ready to perform the intended safety function. All circuits are 100% functional and operational. Input channels are updated and evaluated and are in accordance with expected values. Output channels are controlled in the manner for which they are intended, all feed-back information is as expected, and the Core Logic is fully functional.

RCO - Reduced Capability Operation: The ALS platform has detected one or more problems and indicates that it operates in reduced mode of operation. The failures have been isolated to prevent the failures from propagating through the system and causing unintended plant events. The ALS rack may perform specific actions depending of the location of failure, based on customer requirements. These actions include:

o " Entering a partial trip condition o

Enter a failsafe condition o

Performing a trip o

Provide detailed status indication (operability indication to control room)

The system continues to perform as specified and all unaffected circuits will continue to perform their function. Input channels are updated and evaluated. Output channels are controlled in the way they were intended. The Core Logic is fully functional. The ALS platform alarm is active to show that maintenance is required.

HALT mode indicates that a serious failure has been detected in the ALS platform and that it has entered a failsafe state. In this mode the ALS is inoperable and not capable of performing the intended safety function.

The actual failsafe condition of outputs is configurable using SetPoints. All operations will stop and the system (i.e. all boards) enters a fail-safe state. Input boards continue as usual, except they do not respond to RAB requests. The front-panel LEDs continue to be updated. Output boards are placed in a fail-safe state, where all outputs will enter their configured fail safe mode which can be: "Fail-as-is" or "Fail-as-defined". All RAB Communication has seized when the ALS is in HALT. The HALT mode is also the power up condition of the ALS platform.

RESET mode is a transitory state which is only entered when the CLB's reset switch is toggled. The RESET mode informs all ALS boards that the system will attempt to enter FCO mode and resume full operation. If failures persist the ALS platform will automatically degrade its System Mode to the proper level.

More details about the System Mode can be found in chapter 7.

6002-00026, Rev 2, Jan. 16, 2009 Page 15 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Redundancy - All critical logic modules within the FPGAs are implemented with redundancy. The logic module redundancy is established such that it provides error detection and mitigation to the rest of the system.

2.4 ALS Operation Signal flow in the ALS rack is simple and straight forward. This section outlines the basic principles of ALS operation.

Refer to the generic ALS architecture shown in Figure 2-3. The actual number and type of input and output boards/channels is dependent on the particular application system requirements. The fundamental ALS operation remains the same regardless of the application specific aspects.

The ALS operation is accomplished by a fundamental cycle with three phases, the cycle is explained below:

(1) Sampling Field Inputs - On a given input board there will be a number of input channels each responsible for conditioning, sensing, filtering, and sampling the field inputs. In the event an input channel changes due to a field input change (i.e. contact transition from open to close) the signal conditioning circuit will detect this transition and change state. Each channel is described with state information and integrity information. If a channel fails self-test it will be marked as invalid in the integrity information. The CLB retrieves the state and integrity information during the regular polling of data from the input board.

(2)

Performing Logic Decisions - Input state and integrity information are retrieved from the input boards and are stored in the input register bank in the CLB. When all input data is present the application specific Core Logic circuit within the CLB will perform its logic function. Based on the current state of the system, input states and integrity information, the CLB will determine a new output state for all outputs. The application specific logic functions consist of timers, random logic gates, FSMs, 2/4-voters, etc. The decision making process is instantaneous. All system level integrity and data checks are performed during this phase of operation.

The results of the application specific logic circuit are stored in an output register bank within the CLB FPGA and from there the information is transmitted to the output boards.

(3)

Driving Field Outputs - The output boards receive information from the CLB. The digital circuits will immediately drive the signal conditioning circuit and perform the intended output function.

The cycle above, (1) Sampling Field Inputs (2) Performing Logic Decisions (3) Driving Field Outputs, repeats every System Frame.

6002-00026, Rev 2, Jan. 16, 2009 Page 16 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 16 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 2.5 ALS Technology based on Solid State The ALS is a hardware-based architecture which utilizes a minimal set of hardware to implement a system with high reliability and integrity. The system incorporates self-test capability for detection and mitigation of the effects of failures within or external to the system. This section describes the hardware technologies utilized in the ALS. This section also lists the characteristics for each technology and provides comparisons to alternate technologies. In the discussion which follows the ALS boards are split into 3 sections:

INPUT/OUTPUT (SOLID STATE 1/0):

Input/Output channels.

A CONTROL (FPGA):

The control logic in each ALS board is implemented in a FPGA using synchronous clocked Moore Finite State Machines.

SETPOINTS (NVM FLASH):

Settings such as input channel filter constants are stored in a NVM.

2.5.1 FPGA Devices INPUT I OUTPUT SOLID STATE SETPOINTS-FLASH SOLID STATE I

CONTROL - FPGA SOLID STATE The key component in the ALS design is an FPGA. An FPGA is a semiconductor device containing programmable logic components and programmable interconnects. The programmable logic components can be programmed to duplicate the functionality of basic logic gates such as AND, OR, XOR, NOT. These logic components can be combined into more complex combinational functions such as decoders or simple math functions. In most FPGAs, these programmable logic components (or logic blocks, in FPGA parlance) also include a simple memory element in the form of a flip-flop. Many FPGAs also include dedicated memory blocks which can be combined to form more complex memories.

A hierarchy of programmable interconnects allows the logic blocks of an FPGA to be interconnected as needed by the system designer, somewhat like an on-chip programmable breadboard. These logic blocks and interconnects can be programmed after the manufacturing process by the customer/designer (hence the term "field programmable", i.e. programmable in the field) so that the FPGA can perform whatever logical function is required.

The logic design is based on schematic capture and/or VHDL code for the FPGA implementation. Schematic capture tools have been utilized for many years in the electronics design industry and have reached a mature state. VHDL was originally developed at the request of the US Department of Defense in order to document the behavior of the ASICs that supplier companies were including in equipment. That is to say, VHDL was developed as an alternative to huge, complex manuals which were subject to implementation-specific details. VHDL implementation offers the capability of simulating system behavior in a deterministic and iterative manner using simple test benches. Register Transfer Level (RTL) descriptions are a method of capturing the behavior of a digital circuit.

Dedicated test-benches and test systems are developed to test the final logic circuits. Faults can be injected in a controlled environment and verify proper error detection and expected response. A test plan with regression test suites utilizing well-defined golden test vectors is incorporated in the overall testing of the FPGA design.

6002-00026, Rev 2, Jan. 16, 2009 Page 17 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Several families of FPGAs are available today. The table below identifies the high-level characteristics of the three major types of FPGAs:

Table 2-2: Comparison between SRAM, FLASH and FUSE based FPGAs Description SRAM FLASH FUSE Typical use-case Commercial, High Volume Military & Space Military & Space Technology Standard CMOS CMOS with FLASH Special FUSE (typical deep-submicron) technology technology many additional process steps Prone to SEU (Single Event Upset)

Very sensitive to SEU.

Insensitive to SEU.

Immune to SEU.

SRAM devices prone to Immune to neutrons Immune to neutrons neutron induced configuration errors Prone to SEL (Latchup)

Very susceptible Less susceptible Less susceptible Configuration Integrity (Bit flipping)

Susceptible Leakage issue Fuse defects, electron migration, weak oxide Configuration Retention time Until loss of power 20-50 years Indefinite (20-50 years)

(Temp < 700C)

Device Configuration Lock Transferred at startup FlashLock FuseLock (Intruders capability to change (Possible to modify setup)

(Impossible)

(Impossible) content)

Security Transferred at startup FlashLock FuseLock (Read-back of content)

(None)

(Impossible)

(Impossible)

Development friendliness Fast and easy Optimal Slow and difficult The ALS utilizes a FLASH-based FPGA type. The FLASH-based FPGA provides the best characteristics for the applications targeted by ALS. The SRAM-based FPGAs are prone to SEU and SEL which is a critical characteristic which makes this type of FPGA not viable for the applications for which the ALS is targeted.

The FLASH-based and FUSE-based FPGAs are similar type devices. Each of the two types has particular failure mechanisms. The ALS technology is designed to detect and isolate the failure mechanisms of each if they occur.

This is done by implementing redundancy, where the control logic is duplicated into two independent logic modules which are continuously monitored. If a mismatch is detected between the redundant modules the failing ALS board will be isolated from the remaining system.

Radiation-hard FPGA options are available but are not typically required for the ALS target applications.

2.5.1.1 FPGA Technology - FPGA vs. ASIC The ALS system is based on using FPGAs to implement the control functions. An alternative to FPGAs are ASICs (Application Specific Integrated Circuits). ASICs are typically used for complex digital devices such as processors, graphics controllers, or for very high volume consumer products where the high NRE (Non-Recurring Engineering) costs but low unit prices are favorable compared to the low NRE but high unit cost FPGAs. Due to the widespread use of ASICs in consumer products, where there are constant pressures to decrease cost and increase speed and processing power, the ASICs are constantly evolving. Unit price reductions are done by reducing the size of the transistors used in the ASIC. The size of the transistors in ASIC verbiage is referred to as "Technology" (examples "0.35um Technology" or "90nm Technology"). The dimension refers to the width of the gate in the transistors. The ASIC foundries are typically geared towards specific Technologies, and are required to undergo rebuilding or major renovations when changing "Technology". This constant upgrading of the foundries poses another obstacle for low volume, long life applications like the ALS where future designs might be forced into a new Technology because of availability of compatible foundries. For an ASIC to change technology it must undergo the same design and validation flow it underwent when it was originally design and will incur similar NRE costs. Every time the technology is reduced it causes the NRE costs to increase and at the same time increases the minimum yearly volume for ASICs to be a viable solution. This trend has made the market more favorable for FPGA based designs which has slowly moved into low and medium volume products. FPGAs are built in the same foundries as the ASICs and are subjected to the same design, validation and production costs as the ASICs. But, since a single FPGA device can be used by many customers, the FPGA vendors are able to achieve yearly volume in millions of unit quantities. Using 6002-00026, Rev 2, Jan. 16, 2009 Page 18 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ASICs for a low volume application like the ALS system will result in a limited test-base where fundamental IC design issues such as thin oxide-layers, bad metallization or chemical residues can be difficult to detect.

The ability to leverage the design, validation, and quality control performed by the FPGA vendors has made FPGAs popular in end products such as military, space, and aerospace products. The FPGAs used in ALS are manufactured by Actel. Actel has focused on the military/space/aerospace product segment where high reliability, robust QA processes and procedures, and long product cycles are important.

2.5.1.2 Solid-State Technology Issues Radiation Effects such as ionizing radiation can cause unwanted effects in semiconductor devices. Energetic protons, neutrons, heavy ions, and alpha particles can strike sensitive regions of the transistor, causing various failures, or Single Event Effects (SEE), such as:

Single Event Upsets (SEUs) which occur when high-energy ionizing particles, such as heavy ions, alpha particles or protons, irradiate a circuit or pass through an integrated circuit causing a disruption in the system logic (CMOS memory element changes content).

Single Event Latch-Up (SEL) which is a condition that causes loss of device functionality due to a single-event-induced high current state (occasional short circuit between power and ground). A SEL may or may not cause permanent device damage, but requires power strobing of the device to resume normal device operations.

SRAM cells are susceptible to neutron-induced errors where they change state in an unpredictable and uncontrollable way. Since SRAM cells are used to control the configuration of SRAM-based FPGA, a neutron-induced error could result in an unpredictable change in functionality of an SRAM-based FPGA and result in complete system failure. Independent and comprehensive reports from industry neutron-effects experts iRoC Technologies, determines that SRAM-based devices are susceptible to functional failure when exposed to neutron radiation. Failure rates are significant even when exposed to the naturally-occurring background neutron radiation present at ground level. On the contrary, the fuse and Flash based FPGAs are immune to the effects of neutron radiation.

Because of the incompatible characteristics described above, SRAM-based FPGAs are not utilized in the ALS.

2.5.2 Non-Volatile Memory (NVM)

The ALS boards have an on-board SetPoint memory where local settings are stored. Examples of such settings are Input Channel Filter Setting and Input Channel Normally Open / Normally Close. The SetPoint memory eliminates the need for using DIP switches or a Jumper Array to select these settings.

Storing the SetPoint information in a NVM memory offers several advantages over a DIP switch solution. The NVM contents are protected with a CRC checksum, which will detect and alert if any changes to the information has occurred. The DIP switch solution does not have this protection and could be accidentally modified during board installation or maintenance.

The ALS implements a high level of integrity for the data stored in the NVM. The ALS boards are designed to read out the NVM contents only at power-up. After power-up the ALS boards hold an internal copy of SetPoint settings within the FPGA. While the ALS is running the NVM contents will be tested at regular intervals to ensure there are no data integrity issues. If a data integrity issue is found, the ALS will actuate the plant alarm system to indicate an ALS board requires maintenance. In this case the ALS remains fully functional until the next power cycle.

2.5.3 Input / Output The input and output channels are all designed for high reliability and integrity. The ALS is almost exclusively designed from solid state components. Solid state components have a very long life; however surge voltages, high temperatures, mishandling, overstressing, or manufacturing defects can reduce this life expectancy. The ALS channels are designed with the primary goal of avoiding such situations by building in margins in the design itself and providing early'detection and mitigation capabilities for such problems. The ALS design also focuses on the power consumption and power loss of the system, which has been minimized in all components to ensure that all solid state components remain at low temperatures.

6002-00026, Rev 2, Jan. 16, 2009 Page 19 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 19 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 2.5.3.1 Input Channels The input channels on the ALS boards are based on isolated solid-state devices. The input channels include self-test capability which continuously verifies all components within the channel are operational. During self-test, all components in the channel are tested to ensure full functionally. High isolation is maintained by utilizing opto-isolators. The input channels are protected against ESD and surge voltages using Transient Voltage Suppressors (TVS). The opto-isolators are used in a way which maximizes the life expectancy of the device.

2.5.3.2 Output Channels The output channels, similar to the input channels, are based on isolated solid-state devices. Using solid-state devices vs. electro-mechanical relays offers several advantages particularly when long life and the ability to handle inductive loads is required. Output channels also include self-test capability and for some channel types provides redundancy and other specialized test features to ensure the channel is operational. The output channels are protected against ESD and surge voltages using Metal Oxide Varistors (MOV).

2.6 Standards Compliance 2.6.1 Class 1E Safety Classification The ALS Platform is designed and implemented to meet all requirements of a Class 1 E Safety System, reference IEEE 420-2001.

2.6.2 Quality Assurance The ALS Platform is designed and manufactured under CS Innovations' Quality Assurance Program, Reference 9000-00000.

2.6.3 RoHS Compliance Because the reliability properties of lead free is still unknown the ALS Platform is not design to be lead free or RoHS compliant. The ALS Platform will transition to RoHS once the reliability has been proven.

2.6.4 IPC Standards Compliance The ALS Platform has been designed and manufactured to meet the following requirements:

IPC-A-610D Class III requirements.

IPC-6012B Class III requirements.

IPC-A-620 Class III requirements.

6002-00026, Rev 2, Jan. 16, 2009 Page 20 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC 3ALS Boards This chapter describes the 6 primary board types available in the ALS Platform

1) CLB - Core Logic Board
2)

IPB - Input Board

3) OPB - Output Board
4) STB - Service and Test Board
5)

COM - Communication Board

6)

PSU - Power Supply 3.1 Core Logic Board (CLB)

The CLB contains all the application specific core logic circuits, which define and control the operation of a given system. The CLB controls all sequencing within the ALS system. The CLB issues requests to input boards to provide field input information as required, makes decisions based on received inputs, and commands the output boards to drive a specific output state to the field devices. The CLB is the primary decision making board in the ALS system, it has no direct field input or output capability except for the directly coupled alarm output. An ALS system will utypically contain a single CLB, but may have two if redundancy is needed.

Core Logic - The core logic is customizable based on the requirements of a given application and can contain any type of digital building blocks which can be generated from a NAND2 device, such as AND/ORJXOR-gates, Flip Flops (D, JK, SR). These building blocks can then be combined to form more complex logic such as, counters, timers, multiplexers, comparators or Finite State Machines (FSMs).

The core logic is implemented in the FPGA and the typical size of the core logic module is less than 5K gates (NAND2).

SetPoint Configuration - The CLB has a dedicated FLASH device to store application specific SetPoints used by the design. The SetPoint configuration is stored in an external Non-Volatile Memory (NVM) and local copies are maintained / utilized within the FPGA. Typically only parameters which are requested by the customer to be adjustable are included in the SetPoint configuration, otherwise they will be hardcoded.

Examples of such configuration SetPoints are: sequencer delays, time constants and trigger-points.

RAB Communication - The CLB is a RAB master and is the initiator of all communication on a RAB bus. All communication performed on a RAB bus is performed in a predetermined sequence also known as a System Frame.

During the System Frame all inputs are acquired, all new outputs are determined and written to output boards.

During operation the System Frame is repeated at a fixed rate (typically 10ms).

The inherent architecture (protocol and implementation) detects any RAB communication failure. The CLB maintains a status of all RAB communication, when communication does fail, due to a CRC failure, loss of packet or similar defect, the system will retry the transmission 1 time. An unsuccessful retry will result in the failing board being removed from the list of active boards and the system alarm being actuated. When a board has been removed from the list of active board no further accesses will be attempted without acknowledgement by plant personnel. Data (or the lack there of) from the failing communication will be isolated (not used) and will not cause any further effects.

TAB Communication - The CLB is a slave on the TAB and will respond with the requested diagnostic and integrity information. The information is collected in a non-intrusive manner and does not affect the on-going operation of the system.

Examples of diagnostics from the CLB are inputs and outputs to the core logic module, as well as any internal node that is of interest to a certain application (e.g. states in a state machine or the count of a counter).

6002-00026, Rev 2, Jan. 16, 2009 Page 21 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC System Mode - The CLB maintains the System Mode which is used to control the run capability of the ALS system, and to provide easy to interpret diagnostics information to plant personnel.

Alarm - The CLB has a dedicated and independent alarm circuit to control and generate an isolated alarm output.

Two types of failures can cause the alarm to be actuated:

Application related failures - The Core Logic within the CLB can be configured to generate alarms if inputs to the ALS are invalid. Examples of such failures are redundant inputs not being consistent or valve position indicators indicating both open and close.

System related failures - caused by failures within the ALS circuitry such as failures on the RAB bus, supply voltages out of specified range or blown fuses, device or circuit failures.

Note: a redundant Alarm circuit similar to the CLB alarm circuit is located on the STB.

3.2 Service and Test Board (STB)

The STB provides several advanced on-line and off-line maintenance features such as; integrity monitoring and diagnostics.

The monitoring and diagnostic capabilities support fast system installation and post-installation test during the installation phase, accurate troubleshooting in the event a failure or an unintended plant event occurred during normal operation, as well as general I&C maintenance during outages and while the system is on-line.

Diagnostics - The two key features provided by the STB are LiveView and BlackBox:

LiveView - is a run-time diagnostics feature which provides a live-view of all important signals within the ALS. Signals include information transferred between input/output boards and the CLB (on the RAB), as well as important internal Core Logic signals and health information for all the boards in the ALS rack. The LiveView feature is available while the system is both on-line and off-line and provides the real-time information with 1O0uS resolution.

BlackBox - is a run-time logging and post-event off-line diagnostics feature which provides the plant personnel with information about the sequence of events in the past. The BlackBox circuit continuously records information transmitted on the RAB. When a change in the system occurs the information is stored into an NVM, which allows for high resolution analysis of pre-event conditions, event sequence and post events. In a typical ALS rack application the BlackBox information is stored for the previous 18 months of operation up to and including the most recent information.

The STB gathers information and records it for either real-time retrieval or retrieval at a later time. The information recorded by the STB is retrieved by plant personnel using the ALS Service Unit (ASU).

The diagnostics features are implemented in a passive and non-intrusive manner and do not affect ALS system performance. All communication (information gathering) is (a) performed on the TAB, and does therefore not interfere with I/O information flowing on the RAB and (b) the STB only retrieves information from the other boards. It does not write to or attempt to control other boards. The hardware implementation prevents any interference from the TAB to the system operation.

TAB Communication - The STB is master on the TAB and initiates all requests on the bus.

Communication on the TAB is controlled and synchronized to a System Frame. During each System Frame all boards within the system will be accessed one or more times. Information gathered on the TAB is made available to the BlackBox recorder and ASU interface (should the ASU be connected).

RAB Communication - The STB is slave on the RAB and will respond with the information when the CLB requests it.

Alarm - The STB includes an ALARM output which is normally wired in series with the alarm output from the CLB.

Similarly to the CLB the STB will generate an alarm if failures are detected with the ALS platform.

6002-00026, Rev 2, Jan. 16, 2009 Page 22 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ASU Interface - The STB provides an access port, which allows the ASU to attach to the ALS rack. The ASU is not attached during normal operation. It is only attached and utilized by plant personnel for maintenance and troubleshooting activities. The alarm circuit is actuated immediately when an ASU is plugged into the ALS rack.

An ALS system typically contains one STB. The ALS system will operate without the board; however the absence of the board will remove the advanced diagnostics features provided by the board.

SetPoint Configuration - The STB has a dedicated FLASH device to store application specific SetPoints used by the design. The SetPoint configuration is stored in an external Non-Volatile Memory (NVM) and local copies are maintained / utilized in the FPGA.

3.3 Input Boards (IPB)

IPBs are responsible for conditioning, sensing, filtering, and sampling field inputs. IPBs are typically dedicated to a specific input type, such as 24V or 48V digital inputs, 4-2OmA analog inputs, 0-1iv analog inputs, or thermo-couple inputs.

The IPB provides a front panel indication which shows the status of a particular input using an LED. The ALS design allows for both generic IPB front-panels as well as customized front panels where each channel LED is marked with a descriptive text such as sensor ID.

An ALS rack may require multiple IPBs to support a particular application. The number of IPBs in the ALS rack is related to the number of channels and/or the type of field inputs required. A particular IPB can provide a number of input channels - typically between 4 and 32 channels. The input channel itself can be simple with minimal circuitry to measure a digital signal, or can contain more complex feedback measuring and test circuitry to ensure channel integrity.

Input Channels - An input channel consists of two key circuits - the analog signal conditioning circuit and a digital circuit.

The analog circuit is responsible for converting analog voltages or currents into digital representation and is also referred to as signal conditioning circuitry.

The digital portion of the channel is located in the FPGA and performs all channel control, sample & hold, integrity checks, self-testing, and digital filtering functions. All digital channel circuits, RAB communication, and channel integrity are implemented with redundant logic within the FPGA. The redundancy and self test circuits ensures the detection of any single failure on the board is isolated from the rest of the ALS rack in a controlled manner.

Generally all input channels are galvanic isolated from the ALS logic and can withstand 15 0 0 VAC. The input channels may also be individually isolated or isolated into groups with common reference.

SetPoint Configuration - The IPB has a dedicated FLASH device to store application specific SetPoints used by the design. The SetPoint configuration is stored in an external Non-Volatile Memory (NVM) and local copies are maintained / utilized in the FPGA. The amount of SetPoint information stored is between 0-80 bytes. The input conditioning configuration such as filter time and normal open/normal close configuration is stored in the SetPoint memory.

RAB/TAB Communications - The IPB's are slave devices on the RAB and TAB busses and will respond as required by the masters. The IPB's will automatically acquire the input condition and make it available on the busses.

Integrity information is provided with each input channel and allows the CLB to mitigate failures on channel basis.

The IPB's expects to be accessed in every System Frame, if the IPB detects no access for a duration of time it will automatically time-out and enter HALT.

Integrity - The IPB's maintains integrity information for all input channels which are passed to the CLB together with channel data. Other failures will cause the IPB to either enter RCO mode to HALT mode depending on the severity.

The IPB can detect communication failures on the RAB or TAB and is responsible for isolating the board from further communication on the RAB until the failure(s) has been removed.

6002-00026, Rev 2, Jan. 16, 2009 Page 23 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 3.4 Output Boards (OPB)

OPBs are responsible for controlling and conditioning actuators, indicators, relays and field output devices. OPBs are typically dedicated to a specific output type, such as 24-48VDC digital outputs, relay outputs capable of switching 125VAC analog signals, high inductive solenoid loads, or resistive devices.

OPBs are named according to the type of signal conditioning they provide: ALS-4xx where 'xx' designates the output type and number of channels available. The OPB provides a front panel indication' which shows the status of a particular output with an LED. The ALS design allows for both generic OPB front-panel indications as well as customized front panel indications by mapping the LED indication to application specific field outputs.

An ALS rack may require multiple OPBs to support a particular application. The number of OPBs in the ALS rack is related to the number of outputs and/or the type of field devices the ALS rack is interfaced to. A particular OPB can provide a number of output channels - typically between 1 and 16 channels. The output channel itself can be simple with minimal circuitry to switch a relay, or it can be more complex such as a FET driver channel with feedback measuring and test circuitry to ensure channel integrity.

Output Channels - An output channel consists of two key circuits - a digital circuit and the analog signal conditioning circuit.

The analog circuit is responsible for signal conditioning from digital 3.3V control voltage levels into the desired output function, (i.e. switching to an analog voltage, switching a relay or solid-state-contact or a high-power FET transistor). The analog circuit is responsible for all integrity sensing and feedback loops, which provide information about the state of the output circuit.

The digital portion of the channel is located in the FPGA and performs all channel control, integrity checks, self-testing and any necessary digital filtering. All digital channel circuits, RAB communication, and channel integrity are implemented with redundant logic within the FPGA. The redundancy ensures, in the event of a device failure, the failure is detected and the board is isolated from the rest of the ALS rack.

Note: ALS has the capability of driving field devices directly from the rack without the use of interposing relays. This is accomplished with the use of well protected FET transistor devices and a specific isolation scheme.

Output channels are divided up into groups - typically one to four groups. Each group uses a common ground and provides galvanic isolation from the other groups, as well as the digital portions of the board. The galvanic isolation typically withstands a minimum 1500Vac. Channels and/or groups of channels can typically be configured to perform the intended function (Normally Open/Normally Closed or Fail Safe modes).

RAB/TAB Communications - The OPB communicates over the RAB and the TAB as requested. The OPB is a slave device on the both the RAB and the TAB. All OPBs are slave devices with limited intelligence. The OPBs are dedicated to driving or actuating a field output every time a request is made, and the on-board intelligence is limited to the capability of the integrity monitor or redundancy scheme to decide if a failure has been detected. The OPB does not have the capability of broadcasting the failure to the rest of the ALS rack. The CLB will detect the failure and handle all broadcast responsibilities. The OPB can detect communication failures on the RAB or TAB and is responsible for isolating the board from further communication on the RAB until the failure(s) has been removed.

SetPoint Configuration - The OPB has a dedicated FLASH device to store application specific SetPoints used by the design. The SetPoint configuration is stored in an external Non-Volatile Memory (NVM) and local copies are maintained / utilized in the FPGA. The amount of SetPoint information stored is between 0-80 bytes.

Channels and/or groups of channels can typically be configured to perform the intended function (Normally Open/Normally Closed or filter time constants). This application specific information is stored in the board NVM.

Integrity - The OPB incorporates a FailSafe feature which allows the OPB to autonomously assume a predefined FailSafe state upon a system failure. The fail safe state for a particular OPB is defined during the system design cycle. There are three states for each of the independent channels of a board. The states are; 1) Fail-As-Is, 2) Fail-As-Defined-Open, 3) Fail-As-Defined-Closed.

6002-00026, Rev 2, Jan. 16, 2009 Page 24 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 3.5 Communication Board (COM)

The COM provides a reliable communication link in and out of a ALS Rack. The COM may be used to establish an isolated and reliable communication link between two ALS systems. This may be used in larger ALS systems where an input conditioning ALS rack may be placed close to the source of the signals. This is common practice when the inputs are analog signals such a thermocouples. The input conditioning ALS rack may then communicate the digitized data over a communication link to a processing cabinet where the actual decision making and output generation takes place.

The communication boards may also be configured for One-Way Communication which may be used for communicating detailed status and configuration information to non-safety equipment. This may be plant computers or plant historians. By implementing the communication link as an isolated one-way link a Class 1 E barrier may be maintained.

RAB/TAB Communications - The COM is a slave device on the both the RAB and the TAB and will only communicates over the RAB and the TAB as requested.

Communications Link - The behavior of the communication link will depend on its configuration.

1) It may be configured to repeat all RAB and TAB communication on the Comm Link.
2)

It may selectively collect data transmitted on the RAB and TAB and send at regular interval.

3) It may received data directly from the CLB and only send it when directed by the CLB.

The communication links are isolated from ALS logic and capable of 1500VAC. The communication board may include multiple communication links. The communication links will typically be: EIA-232, EIA-422 or EIA-485 type connections.

SetPoint Configuration - The COM has a dedicated FLASH device to store application specific SetPoints used by the design. The SetPoint configuration is stored in an external Non-Volatile Memory (NVM) and local copies are maintained / utilized in the FPGA.

3.6 Power Supply Board (PSU)

The PSU's are used to generate a regulated local supply to be used by all ALS boards in the rack. The PSU can be connected directly to a Class 1 E power source. A redundant pair of PSUs are utilized in ALS racks to provide load sharing and redundancy, which ensures a stable internal rack voltage both long term but also in the event of a single power supply failure. Each of the PSUs are capable of supplying the ALS rack with sufficient power to continue un-interrupted operation should the other PSU fail.

The PSU is hot-swappable and can be replaced while the system is operational. The PSU contains built in diagnostics to detect an under-voltage. The PSU provides an energized NO contact to indicate the failure to the rest of the ALS rack.

The PSUs may also be used to generate other voltages such as 24V or 48V to be used to drive external components such as fan-out relays or breaker trip coils.

6002-00026, Rev 2, Jan. 16, 2009 Page 25 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 25 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 4

Environmental ALS Plafform Qualifications This chapter describes the environmental capabilities of the ALS Platform and which requirements it has been designed to meet. The basis for setting the Environmental Qualification requirements was the guidance provided in EPRI TR-102323 Rev 2 and the requirements listed in NUREG RG 1.180.

4.1 Temperature The ALS Platform is designed to operate in a mild environment, such as control rooms or electrical equipment rooms, with an operational temperature of 0°C to 500C and relative humidity: 20 to 80% (Non-condensing)

Storage Temperature conditions is: -100 C to 60'C. Relative Humidity: 20 to 80% (Non-condensing).

4.2 Radiated Emissions The ALS Platform was qualified to the following MIL-STD-461E tests.

RIaescripatien Ite I RE101 Radiated emissions (Low Frequency)

System (Rack)

RE102 Radiated emissions (High Frequency)

System 4.3 Conducted Emissions The ALS Platform was qualified to the following MIL-STD-461E tests.

Conducten emin MM F

Pwem I CE101 Conducted emissions (Low Frequency)

Power leads CE102 Conducted emissions (High Frequency)

Power leads 4.4 Radiated Susceptibility The ALS Platform was qualified to be able to withstand the following MIL-STD-461E and IEC-61000 tests.

RS101 Radiated Susceptibility (Low Frequency)

System (Rack)

IEC 61000-4-3 Radiated immunity (High Frequency)

System IEC 61000-4-6 Radiated immunity (High Frequency)

Power / Signal leads IEC 61000-4-8 Radiated immunity (High Frequency)

System IEC 61000-4-9 Pulse magnetic field immunity System IEC 61000-4-10 Damped oscillatory magnetic field immunity System 4.5 Conducted Susceptibility The ALS Platform was qualified to be able to withstand the following MIL-STD-461E and IEC-61000 tests.

1 1

Cnescriptien Item

(

CS101 Conducted Susceptibility (Low Frequency)

Power Lead Lines 6002-00026, Rev 2, Jan. 16, 2009 Page 26 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 4.6 Surge The ALS Platform was qualified to be able to withstand the following IEC-61000 tests.

Test Description

Item IEC61000-4-2 Electrostatic Discharge (ESD) Immunity Case & Cables IEC61000-44 Electrical Fast Transient Immunity (EFT/B)

Power / Signal leads IEC61000-4-5 Surge Immunity Power leads IEC61000-4-12 Ring Wave immunity Power / Signal leads IEC61000-4-16 Conducted, common-mode immunity 4.7 Seismic The ALS Platform was qualified to handle seismic events according to IEEE 344-1975. The ALS Platform remained operational during and after all seismic tests.

6002-00026, Rev 2, Jan. 16, 2009 Page 27 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 27 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 5

ALS Rack Mechanics 5.1 Rack Mechanics The ALS Platform is based on 19" (482.6mm) Sub-Racks, 6U (266mm) tall and 400mm deep. The sub-racks are an industry standard products following IEC 60297-3-101. For easy insertion and ejection the ALS Boards are configured with IEC 60297-3-102 style injector/ejector handles and IEC 60297-3-103 style card guides.

The combination of Injector/Ejector handles, card guides and general rack mechanics ensures ESD safe insertion of ALS boards.

The ALS rack is fully enclosed with perforated top and bottom panels. All 6 sides of the rack is electrically connected and grounded to chassis ground. Chassis ground is provided through a single earthing lug on the back of the ALS rack. The ALS Platform rack is IP20 rated against foreign objects and water.

Connectors - All cable harnesses are securely attached to the rear of the ALS rack using industrial grade plug connecters.

Weight - A fully configured ALS Platform rack will typically weigh less than 20kg.

Cooling - The ALS Platform is designed to rely on natural convection in the cabinet and with no internal fans.

5.2 ALS Slot and Card Configuration The ALS rack has the capacity to support 14 boards maximum, assuming each ALS board is 6 HP wide (1.2").

Component height and front plate indication requirements may require that certain types of ALS board to be wider.

Each opening in the ALS rack which can accommodate an ALS board is referred to as an ALS Slot. The ALS Slots are not designed to be interchangeable; the combination of back plane connectors, their locations and optional keying ensures that only the correct type of ALS board can be inserted into a given slot. In addition to this the ALS logic will also verify that the inserted board contains proper configuration before allowing it to become an active part of the system.

Unused slots in the ALS rack are covered with generic filler plates to maintain an IP20 rating.

5.3 ALS Rack Materials The ALS rack is implemented in a lightweight and durable construction, suitable for rugged environments and long life expectancy. The ALS rack is made from aluminum alloys with a combination of alodine or anodized finishes.

The side plates are made from solid aluminum with a yellow alodine finish.

The top and bottom covers are made from perforated aluminum with a yellow alodine finsish.

The rear plate is made from solid aluminum with anodized finish. The rear plate will typically be customized for each application to provide an optimal combination of cable connectors.

5.4 ALS Front-Panel All ALS boards are design with a generic front plate, this front plate is application independent and can be reused across may designs. To aid I&C technicians and to improve general serviceability the front plate may be modified with application specific designators. This includes adding description labels to input and output channels matching the equipment or component tagging nomenclature used at the particular plant.

To ensure long term durability and readability all text are engraved and painted black. Figure 5-1 shows how ALS board front plates can be customized to provide application specific information directly on the front plate.

6002-00026, Rev 2, Jan. 16, 2009 Page 28 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Generic Front Plate Customized Front Plate 0

  • SL-3W ALS-30H1 Qem)

OPWR 0 FA.

0 FAL 0

msOESr" 00,.0 000" OrOwn

  • o

.' z 20,2 00,,

0 Figure 5-1: Generic versus Custom Front Plate 5.4.1 System LEDs All ALS boards include 3 common system LEDs. The System LED's are located identically on all ALS boards and are used for easy diagnostics of the system.

The ALS System LEDs are the following:

Syte_

EDIniato Type__

Colors S~tye Decito Green Solid The board is powered - Both latches are locked PWR Board power indicator Yellow Solid The board is powered - One latch is locked Off Solid None of the latches have been locked Green Blink 1Hz The board is running in FCO mode Board running Yellow Blink 1Hz The board is running in RCO mode indicator Off Solid The board has stopped execution and is in HALT mode Red Solid The board has experienced and detected a failure FAIL Board fail indicator Off Solid The board has not detected any failures 5.4.2 Board Latches Boards are fastened and secured to the rack using dedicated ergonomically injector/ejector handles, referred to as board latches.

One latch is located on the top and another is located on the bottom of the front-plate to secure the board in the rack.

The latches are IEC 60297-3-102 compatible board latches used for supporting hot-swaping of board while providing ESD precautions and alignment pins. The latches includes a microswitch which allows the ALS board to enter a safe state before the board is ejected.

Both OPEN (not inserted in rack)

Board without power Off Both OPEN (inserted in rack)

Board will be powered, but in HALT mode Off One OPEN, One CLOSED Board will be operational Yellow Both CLOSED Board will be operational Green 6002-00026, Rev 2, Jan. 16, 2009 Page 29 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 5.5 ALS Rear-Panel The ALS rear-panel is made with 4mm Anodized Aluminum. The text is engraved with a black or blue background as shown in the table below. Figure 5-2 shows the rear side of ALS rack showing Cable Connectors and labels.

Figure 5-2: ALS Rack Rear View (WolfCreek MSFIS Application)

All permanent rack connections are made using cable harnesses connecting to the back panel. The connectors used by the ALS Platform are Phoenix Contact Variocon style connectors. The Variocon connectors are modular connectors where each module can be selected to provide a optimal combination of voltage/current capability and connector density. The Variocon connector shells can accommodate between 2-5 modules where each module includes between 2 and 8 connections.

Poitos_

icueeml PictreMale

§UL Nom.

600V / 20A 2

6kV Surge AWG 10-30 S"250V

/ 10A 6

IIII 2.5kV Surge AWG 14-30 300V / 10A 8

loll 2.5kV Surge AWG 14-30 Figure 5-3: Male Phoenix Field-Connector The Earthing connection (Chassis Ground) is located in lower-left corner of the rear-panel.

6002-00026, Rev 2, Jan. 16, 2009 Page 30 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 30 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 5.6 Cable Harnesses Cable harnesses are built to specifications and will vary from application to application.

5.7 ALS Boards ALS boards are designed to fit directly into an ALS platform rack. The ALS boards connects to the back plane using DIN41612 style connectors. All components, switches and LEDs are mounted directly on the printed circuit board (PCB) which allows for easy removal of the front plate.

13.965 4.

9.168 FPGA IL Figure 5-4: Generic ALS Board with ALS Bus Connector. The front panel width will vary The intelligence on each board is located in the FPGA. The FPGA contains the communication controllers (RAB and TAB), registers, NVM interface and all other auxiliary logic as well as board specific logic (input channel logic). All ALS boards use the same FPGA, however each of the FPGAs contain a different board build functionality.

A key design goal for the ALS platform was to reduce the number of different components used on the ALS boards by striving to reuse sub-circuits. This reduces the part number count used in the ALS platform and helps to mitigate obsolescence issues. All common sub-circuits are located identical on all ALS boards.

6002-00026, Rev 2, Jan. 16, 2009 Page 31 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 31 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC 6ALS Power Management The ALS power management architecture is based on a two-step conversion approach to supply circuits with power:

Centralized power is fed to the ALS platform rack where a DC/DC or AC/DC converter generates a stable 5V ALS rack power from the available cabinet power. Typically the cabinet power will be a Class 1 E 125V power feed.

o Input:

125Vdc plant (90Vdc-15OVdc) o Output: 5Vdc ALS supply voltage (Common 5V for all boards in the ALS rack)

Distributed (local) DC-DC voltage regulation and filtering on each ALS board is used to generate the required stable voltages for the digital domains:

o Input:

5Vdc ALS supply voltage o

Output: 5Vdc (Filtered / Regulated) o Output: 3Vdc (Filtered / Regulated) o Output: 2.5Vdc (Filtered / Regulated)

Figure 6-1 shows a typical ALS platform with the different voltage domains.

6.1 ALS Ground Domains The ALS has three fundamental types of ground domains:

Chassis Ground - referred to as CGND Digital Ground - referred to as DGND, used for ALS Logic circuits Isolated Field Ground - An ALS rack may have many individually isolated field ground domains.

Chassis ground (CGND) is the overall cabinet earth ground. Chassis ground is typically supplied to the cabinet from a plant grounding system using heavy gauge copper wires to a distribution point within the cabinet. The ALS Platform rack are grounded directly to this ground distribution point.

All conductive parts of the ALS rack (chassis) are connected to CGND to provide effective EMI characteristics.

Furthermore, all board card guides are connected to CGND to ensure early grounding of PCB boards while boards are being inserted by CSI or I&C technicians.

Digital ground (DGND) is a local ALS ground reference generated by the central 5V DC-DC converters on the redundant power supply boards within the rack.

All digital ALS circuits (FPGA's bus communication devices, 3V/2.5V-voltage regulators, etc.) are referenced to DGND.

Isolated Ground is used for field signal condition circuits. The isolated ground is usually supplied by the field input or output device and enters the ALS rack together with the field signals. Examples of isolated ground references are:

Digital field input boards with isolated channel power Field output drive channels with high-power isolated drive circuits 6002-00026, Rev 2, Jan. 16, 2009 Page 32 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC 6.1.1 5V Power Domain The 5V board supply voltage is supplied to each ALS board through the ALS Bus backplane connector and is described in the following sections.

Filtering - Upon entry onto the ALS board the 5V is fused, filtered and overvoltage protected. The fuse ensures that catastrophic failures on a ALS board cannot disrupt the rack power. The filtering is done to avoid noise propagating from the ALS back-plane (transients, etc) to the board itself and also to avoid noise coming from the the ALS board to the ALS back-plane.

Each ALS board provides it's own protection circuit to ensure no damage is caused to any of the on-board components in the case of transients coming from the back-plane.

Supervisor - The 5V voltage supervisor is utilized by the FPGA to provide direct monitoring capability of the 5V supply voltage.

6.1.2 3V Power Domain The 3V domain is primarily utilized to power the FPGA I/O-ring and associated components.

Supervisor - The 3V voltage supervisor is utilized by the FPGA to provide direct monitoring capability of the 3V supply voltage.

6.1.3 2.5V Power Domain The 2.5V domain is dedicated to provide a stable FPGA core voltage.

Supervisor - The 2.5V voltage supervisor is utilized for Power-On Reset of the FPGA logic.

ALS Platform U

U, z

Isolated Ground 1 Isolated Ground 2 Isolated Ground 3 DU-IL Rack Power Feed (e.g. Class 1E 125Vdc)

Figure 6-1: ALS Platform Power Domains 6002-00026, Rev 2, Jan. 16, 2009 Page 33 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC This chapter describes the ALS Modes and States and includes the following concepts: ALS System Mode, Classification of Failures, Alarm Generation and ALS Test Mode.

7.1 ALS System Modes The Core Logic Board (CLB) maintains the ALS platform's "System Mode", which defines the operational state of the ALS system. The System Mode can be "FCO", "RCO", "HALT" or "RESET". Figure 7-1 and Table 7-1 define the 4 System Modes.

FCO, RCO and HALT are the 3 primary modes of operation. FCO is the ideal situation which indicates no errors are present within the system, RCO indicates that non-vital error(s) have occurred, the ALS will disregard information from the failing units but otherwise continue to perform its function, HALT means a serious error has occurred and all functions have stopped in the rack. RESET is a transitory state only entered when plant personnel toggle the reset switch on the CLB front panel in order to clear all latched errors. The classification of failures (non-vital and vital) can be found in section 7.2.

N N

Power-on SYSTEM RESET toggle switch held in RESET Position Figure 7-1: ALS System Mode 6002-00026, Rev 2, Jan. 16, 2009 Page 34 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC Table 7-1: ALS System Modes FCO Full Capability Operation (FCO) mode:

FCO is the normal mode of operation for the ALS rack. It indicates that all circuits are 100% functional and that the ALS rack is ready to perform the intended safety function.

Input channels are continuously updated, and BIST values are in accordance with expected values.

Output channels are controlled in the manner in which they were intended, and BIST values are as expected.

Core Logic circuit is fully functional.

i RCO Reduced Capability Operation (RCO) mode:

The ALS rack operates in RCO mode when one or more failures have been detected within the ALS system. The failures have been isolated and all other functions continue to perform their intended function.

The failures can be simple channel related failures with one or more individual failing channels. The failures can also represent a more complex set of failures have occurred on a particular ALS board and the entire board has been removed from operation. The failed functions or boards are not longer used by the CLB to determine the desired output state.

If an ALS board is removed from the ALS rack, after two failed accesses the CLB will enter RCO mode and stop accessing the board.

HALT mode indicates the ALS rack is inoperable and not capable of performing the safety function.

Vital failures have occurred and the ALS rack is forced into HALT mode. The rack will also enter HALT at power-up or when CLB is initially inserted in the rack.

All operation is halted and all boards within the ALS system are forced to a FailSafe state:

HALT 0

All input channels are updated. BIST engines continue to monitor the channel circuitry.

a All output channels are placed in a FailSafe state, where all outputs are either force to"Fail-as-is' or 'Fail-as-defined' - depending on their SetPoint configuration. BIST engines continue to monitor channel circuitry.

E Core Logic circuit is in HALT mode.

HALT is also referred to as the FailSafe state.

RESET mode indicates manual action is being taken by the plant personnel to confirm (and clear) existing alarm conditions in order to (re-)start the system in a normal mode of operation.

The ALS rack is inoperable and not capable of performing the safety function while in RESET mode.

All operations will stop and the system (i.e. all boards) is forced to a FailSafe state:

RESET 0

All input channels are updated. BIST engines continue to monitor the channel circuitry.

All output channels are placed in FailSafe state, where all outputs are either force to 'Fail-as-is' or

'Fail-as-defined' - depending on their SetPoint configuration. BIST engines continue to monitor channel circuitry.

Core Logic circuit is in RESET mode.

7.1.1 ALS System Mode versus Local System Mode The ALS platform provides two levels of System Modes; The top level is the Global System mode distributed by the CLB to the ALS slave board during each RAB access, at a lower level all ALS boards maintains a Local System Mode. The Local System Mode will ideally track the ALS System Mode, but it allows the individual boards to autonomously enter RCO or HALT as soon as the failure is discovered. As soon as the detected failure has been transmitted to the CLB, the CLB will adjust the system mode accordingly.

6002-00026, Rev 2, Jan. 16, 2009 Page 35 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC System Mode Facts:

System Mode is the global mode of operation for the entire ALS system (ALS system referrers to all boards within a rack controlled by the CLB).

System Mode is based solely on 'ALS System Integrity' information, such as device operation, power supply operation, redundancy checks and is 100% independent of the application related core logic circuits.

The System Mode is based on integrity information retrieved from all ALS boards in the system during the process of communicating I/O-data between ALS I/O-boards and the CLB using the RAB bus.

System Mode will initially be HALT mode when the system powers up or when the CLB board is inserted into the rack.

The System Mode 'master-copy' is physically located in a register within the integrity monitor module in the CLB. Local replicas of the System Mode are maintained by each ALS-board within the slave integrity monitor module.

System Mode is communicated to all ALS boards in the system during transactions on the RAB.

Important note:

The System Mode is an indicator of the health of the ALS hardware platform. If BIST engines have detected an issue in non-vital circuits the system is forced into a reduced capability mode of operation (RCO), and if BIST engines detect issues related to vital circuitry the system is forced into HALT mode.

Whether the system can perform it's safety related function or not is not related to the System Mode, but instead related to application specific circuits located within the Core Logic circuits Example: WCGS MSFIS system has a alarm linked directly to the System Mode, and has independent STATUS signals to provide indication of the capability of the system to perform its intended safety function.

7.2 Classification of Failures This section defines the failure states used in the CLB decision process to determine the System Mode of operation.

The ALS boards are also capable of monitoring the local System Mode from board integrity. The terms are used to define the class of failures a system will observe:

Fatal Fatal failures refer to a severe type of failure, which compromises the control function of the system, and the concept of SYSTEMMODE is no longer valid. The most obvious fatal failure is the complete loss of input power to the ALS rack - the result is loss of all system functionality and status indication.

Vital failures refer to the class of errors which affect the overall system and possibly degrade the performance to a degree, where the overall system performance and integrity is compromised. The occurrence of one or more vital failures will result in loss of ALS integrity Vital and maintenance is required immediately.

The system will immediately enter HALT mode, if a vital error is detected and boards will enter the predefined FailSafe state.

Non-vital failures refer to the class of errors, which do not affect the overall system performance or integrity of the system. Following one or more non-vital failures, the ALS Non-vital platform is still operable and the integrity of the system has not been compromised, but requires maintenance to operate as specified.

The system will immediately enter RCO mode, if a non-vital error is detected.

Undetectable failures refer to the class of errors, which do not affect the overall system Undetectable performance or general integrity of the system. Examples of undetectable failures are LED related circuit failures (wiring, failed LED, driver). The rack front-panel provides wrong indication, but the system will perform the function as specified.

6002-00026, Rev 2, Jan. 16, 2009 Page 36 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 7.3 Alarm Generation The dedicated alarm generation/indication from ALS rack is implemented using redundant Solid State Relays (SSR).

The alarm is designed to be CLOSED during normal operation and OPEN to indicate a failure.

There are two sources for alarm within an ALS rack:

Application related alarms, which is associated to the application logic System related alarms, which is generated in the integrity monitor circuits protecting the integrity of the board.

The alarm generation circuit is located on 2 independent boards:

CLB (ALS-101 boards)

STB (ALS-201 boards)

The alarm connections points are independent, but can be wired together in series on the back-panel.

7.4 ALS Test Mode TESTMODE is a special feature available to CS Innovations engineering teams to allow access to test circuits within the ALS platform. TESTMODE is a special mode which basically provides access to otherwise hidden and inaccessible registers in the ALS boards, without actually probing or forcing external voltages onto boards.

Access to TESTMODE is restricted and requires a specific set of conditions to be valid in order for a board to enter TESTMODE. This ensures no faulty signals or defects on the board can cause sensitive information to change without notice in the background.

TESTMODE is only active when explicitly enabled from an external device using special tools (ATU) provided by CS Innovations. Standard PCs are not able to establish connections to an ALS board. A series of "checks" as well as the proprietary TAB protocol ensures that a ALS board will never enter TESTMODE when in a ALS Rack.

6002-00026, Rev 2, Jan. 16, 2009 Page 37 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 37 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 8

ALS Communication The ALS architecture is based on reliable and high integrity communication between boards. The bus architecture is a unique feature to the ALS platform with an advanced fault detection and mitigation strategy designed not only to provide reliable communication of information, but also to detect and handle faulty components in the communication link itself.

The dedicated and efficient bus implementation is achieved using industry standard differential EIA-485 hardware, a dedicated, simple and efficient communication protocol and a small optimized embedded controller implemented using redundancy.

Two separate and independent communication busses are implemented:

Reliable ALS Bus (RAB) - is the primary communication bus within the ALS platform. The RAB is dedicated to transfer safety related signal information between the boards, i.e. IPBs -- CLB and CLB --

OPBs. The RAB is the primary bus used for communication during normal operation (not in HALT mode).

The RAB data always includes:

o DATA - The actual I/O-information o

INTEGRITY - The associated health information to a DATA I/O-point.

Test ALS Bus (TAB) - is the secondary communication bus within the ALS platform. The TAB is dedicated to transfer run-time diagnostics information to the STB in the background without affecting the main system operation, as well as off-line test and configuration tasks with the ATU. During normal operation the TAB interface supports the diagnostics and LiveView features, where the STB collects integrity information from all ALS boards in the system and stores the information in the BlackBox or transfers the information to an ASU (if attached). While off-line the TAB is the only interface, where CS Innovations test equipment (ATU) has access to write configuration (SetPoint) information to the board NVMs. TAB communications are performed asynchronously in the background without affecting RAB communication.

The RAB and the TAB interfaces utilize equivalent design and implementation, as well a similar protocol and packet format, see section 8.2.

The RAB and TAB interfaces are the only means of communication between ALS boards and all information shared between boards is transferred using these two interfaces.

All transfers over the busses are validated for integrity utilizing checksums. If the checksum does not match the expected, then the data packet is not utilized.

ALS bus communication is handled by simple, dedicated communication circuits on each board (section 8.4) in conjunction with digital circuits within the FPGA device.

8.1 ALS Bus Facts Dedicated Bus Topology:

Linear bus topology with all devices connected to a low-speed differential EIA-485 wire-pair. The back-plane provides the main wire-pair with a terminator at each end. All nodes (ALS-boards) are connected to the linear bus thru back plane connectors.

Master-slave protocol with 1 master and many slaves on each bus:

Access scheme:

a.

RAB transactions with I/O data are point-to-point communication initiated by the master, with slaves responding with valid data when requested. Response is immediate.

Half-duplex communication protocol between two devices. The bus provides for communication in both directions, but only one direction at a time (not simultaneously).

6002-00026, Rev 2, Jan. 16, 2009 Page 38 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Reliability and High Integrity:

Two-way communication, which utilizes a request-and-response protocol for transactions meaning all communication is acknowledged (except Broadcasts).

The packet payload (I/O-data information) is protected by cyclic redundancy check (CRC). Packets are ignored, if the CRC is invalid, which again leads to the payload being discarded and the information not used.

Integrity information collected in the I/O-channels is transferred along with I/O-data. This enables the CLB to make decisions based on valid information and take appropriate action only if invalid channel information is available. If boards become un-available (due to board removal or vital failures) then data and the integrity gets invalidated within the CLB.

High noise immunity due to dedicated EIA-485 differential wire-pair, implemented with short wire length and high drive capability.

Fault Isolation:

Bus protocol avoids bus contention, can detect unintended bus contention, and will isolate boards with failing devices.

Instant detection of communication failure (invalid data) and communication loss (indicating a failing unit).

Spoof-proof communication ensures instantaneous detection of interference from invalid or failing boards.

Advanced, Deterministic Protocol:

( ("n i~rntfa rncnnng timr= whinh ln*i^uilc thac \\

ttm fn h%/= rifg-hrminktiri rw-rtinn timen fnr 2nln inni it ctntg U

U changes.

Guaranteed response time enable detection of lost or failing devices.

Guaranteed packet synchronization, with instant detection of synchronization loss.

8.2 ALS Bus Protocol This section specifies the ALS Bus (RAB and TAB) protocol. The protocol is a set of rules that governs communications between devices (ALS boards). These rules include guidelines that regulate the network characteristics such as access method, fault detection, fault isolation, physical topology, physical layer, and speed of data transfers. All CRC calculations will be based on a CCITT standard polynomial.

A RAB master (CLB) requests accesses to the slaves in a round robin fashion at a fixed rate determined by the RAB System Frame Timing. The RAB master will read information from all appropriate input boards and write information to all appropriate outputs boards once every ALS System Frame.

6002-00026, Rev 2, Jan. 16, 2009 Page 39 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 39 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 8.3 ALS Bus Failure Detection and Mitigation This section describes the general detection of ALS bus failures and the actions taken to ensure high system reliability. In normal operation the ALS platform will detect any failure on the ALS bus (RAB or TAB). In addition to being able to detect any failure, care is taken in defining the protocol to ensure that a secondary failure cannot occur as a result of a primary bus failure. Having multiple layers of error detection and mitigation techniques results in a highly reliable bus where all failures or errors will be detected and handled appropriately.

8.3.1 ALS Bus Failure Mode Error Analysis The following RAB communication failures can be detected and isolated - see the simple FMEA in Table 8-1.

Table 8-1: Simple ALS Bus FMEA Causes Failure Mechanism Detection Mechanism Mitigation Defective crystal or loss of synchronization SYNC detector (On ALS board)

RETRY then FAILSAFE FPGA device defect:

Redundant bus circuit (within FPGA)

RETRY then Defective flash cell FAILSAFE Logic gate failure I/O pad defect Clock or voltage distribution Hardware Redundant channel disagrees with primary channel External circuitry defect:

CRC-check and implicit encoding of information RETRY then Defective EIA-485 driver FAILSAFE Bus-termination circuit Loose connector Bad soldering Broken wire or Tin whisker Spoofing by defective ALS board CRC check and implicit encoding of information RETRY then External FAILSAFE System Induced noise on communication line CRC check and implicit encoding of information RETRY then FAILSAFE Read or Write transaction failed:

CRC check and implicit encoding of information RETRY then CRC received on ALS bus does not Note: Received data is not used.

FAILSAFE compare to calculated CRC Packet Incomplete transmission error e

No response from slave Read or Write requests to undefined ALS Action will only occur on slave address match FAILSAFE slave addresses and CRC OK TAB failures will be detected and mitigated in a similar fashion. The only exception is that the TAB will not force the board into HALT Mode, but instead will detect the failure and ensure no valid response is issued. A failure of the TAB interface is not considered vital to the ALS rack, even though it is an essential part of the system. TAB communication failures will only affect debugging and diagnostics. This approach allows the system keep running as long as possible, while still preserving point-to-point integrity.

6002-00026, Rev 2, Jan. 16, 200g Page 40 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 40 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 8.3.2 ALS Bus Failure Detection Both the RAB and TAB interfaces provide a layered failure detection scheme. This layered failure detection scheme is designed to detect any possible failure that can occur on the communication bus, the communication devices, or the communication logic circuits within the FPGA.

Four detection schemes are responsible for detecting a communication failure:

Redundancy failure detection Synchronization failure detection CRC failure detection Protocol failure detection Note: Detection and reaction of Redundancy and Synchronization failures are instantaneous Detection of CRC or Protocol failures will likely not be instantaneous (payload data will be transferred before the CRC is calculated) but the reaction will be instantaneous. The Rx will not allow the data to propagate 8.4 ALS Bus Physical Layer The physical layer for ALS Bus (RAB and TAB) is implemented with standard EIA-485 devices.

EIA-485 specifies a 2-wire, bidirectional, differential line, half-duplex data transmission, multipoint communication standard. Up to 32 transmitters and 32 receivers may be interconnected in any combination, including one driver and multiple receivers (multi-drop), or one receiver and multiple drivers.

6002-00026, Rev 2, Jan. 16, 2009 Page 41 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 41 of 50

ALS Platform Overview Non-Proprietary CS Innovations LILC 9

ALS Service Unit (ASU)

The ALS Service Unit (ASU) is the primary tool used when accessing a particular ALS system in operation. The ASU provides plant personnel access to advanced features of the ALS system such as system diagnostics, post-trip analysis, monitoring real-time operation, and initiating various run-time tests. The advanced diagnostics capabilities enable fast and efficient system setup and troubleshooting. The ASU is a standard laptop running the dedicated ASU software application. It is connected to the ALS-201 STB board of an ALS rack through a USB connection.

The main features of the ASU are:

State Information: Features monitoring of real-time operation, including all I/O signals as well as detailed status information from internal debugging registers. The advanced monitoring capabilities enable fast system diagnostics and troubleshooting.

System and Board Information: Provides detailed information about the static parameters of an ALS system, including board FPGA programming, board build information, and board set-point configurations.

Black Box: The ASU facilitates retrieving and presenting the black box information, thereby enabling plant personnel to inspect the ALS system's reaction to a past event. This feature significantly helps reduce the time it takes to pinpoint the cause of problem situations.

Testing: Various surveillance tests can be initiated using the ASU.

The ASU operation is passive and non-intrusive, i.e. it cannot modify the system configuration, nor can it override any of the safety-related functionality within the ALS. All communication initiated by the ASU takes place on the TAB bus. No RAB interruption can occur, effectively leaving the safety operations of the ALS system unaffected.

9.1 Configuration Report The ASU can generate a configuration report for the ALS system. This configuration report includes:

Build Information - similar to information written on labels on the board and the PCB silk-screen. It is stored in the NVM for more reliable traceability, and it offers an efficient way to retrieve information. This information is static and only programmed once by CS Innovations personnel. The Build Information will typically include: Board Serial Number, Board Part Number, Board Revision Number, Build Date, FPGA Part Number, and FPGA Revision Number.

SetPoint Configuration - The application specific configuration of the ALS boards. It is stored in the NVM to enhance reliability and robustness as well as to have a more reliable traceability, and it offers an efficient way to retrieve information about a board configuration using the ASU. The set-point information is configured by CS Innovations during board dedication for use in a particular application. The set-point configuration is static in nature, and it is only supposed to be programmed once by CS Innovations personnel. However, the set-point configuration can be modified using the ALS Test Equipment if changes to the system application parameters if desired. The ASU can retrieve the SetPoint Configuration, but cannot modify the SetPoints.

6002-00026, Rev2, Jan. 16, 2009 Page 42 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 42 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC 1 0 SetPoint Configuration The ALS platform has the capability of configuring each board to support application specific functions. The configuration is facilitated with the use of a non-volatile memory (NVM) device attached to the FPGA device, and a small sequencer within the FPGA to read information stored in the NVM and place it in local registers within the FPGA.

SetPoint information is local to a board. Individual ALS boards have their own configuration memory where information local to the board is stored. SetPoint information consists of local settings, such as channel setup, sequencer setup, timing setup, build information, etc.

SetPoint configuration is stored in the NVM using the ATU and the TAB bus.

10.1 SetPoint Definition ALS defines SetPoints as local values related to an ALS board, which can be either set or cleared, activated or de-activated, enabled or disabled, a trip value, a timing value.

Examples of SetPoints are:

Channel Enable/Disable Channel NO/NC Type Channel Filter Timing Temperature Trip Values Timing Delays (used in timers / sequencers)

FAILASDEFINED (Mode and State values)

BoardlD SetPoint Build information 10.2 Configuration Integrity The traditional approach to set-point implementation on PCBs has been the use of jumpers, DIP-switches or 0O resistors.

The ALS approach to maintain set-points is to store them as bits in a non-volatile memory device (a serial-FLASH device), also referred to as the SetPoints FLASH or the SetPoint NVM.

Information stored in the SetPoint NVM is protected by CRC Redundancy which ensures instant detection of failures in the NVM.

6002-00026, Rev 2, Jan. 16, 2009 Page 43 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 43 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 11 Redundancy The ALS Platform uses a combination implementation and test strategies in order to maintain its high integrity status. These strategies are covered by the pending ALS Patents. This chapter describes the 3 primary implementation and test strategies:

Redundancy Built In Self Test (BIST)

Inherent Self-Test The testing will typically be performed automatically by the ALS system without the need for interaction by plant personnel and may replace the need for regular surveillance testing at the plant.

11.1 Redundancy All ALS FPGAs are all implemented with redundant digital logic. This is to protect the ALS board against a type of failure which can potentially occur over time as a result of manufacturing defects, radiation damage or flash cell charge degradation. This section exclusively focuses on how the redundancy is implemented internal to the ALS FPGAs. Other levels of redundancy such as the redundant input or outputs, or application level redundancy are not covered in this section. Difference between the redundant circuits will cause the ALS to take appropriate action. The redundancy implementation will detect any deviation between the redundant circuits before a possible erroneous signal can propagate to the remainder of the system.

11.2 BIST The Built-In-Self-Test (BIST) is used for exercising all critical functions within a board. This is done to ensure that latent failures cannot build up in the system and make the system inoperable without the knowledge of plant personnel. The BIST will typically apply input stimuli on the inputs to a sub-circuit and validate the correct response on the output.

11.3 Inherent Self-test Inherent Self-test is a method for implementing high integrity directly into the logic circuits by constructing it in a way that latent STUCK-AT or OPEN failures will be instantly detected. An example of inherent self-testing is a serial communication link with CRC protection.

6002-00026, Rev 2, Jan. 16, 2009 Page 44 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC ALS Platform Overview Non-Proprietary CS Innovations LLC The ALS Platform is designed to eliminate the need for surveillance testing of installed ALS Systems. In most safety related applications the ALS platform will be operating a steady state where it is waiting for trip conditions or shutdown commands. Some of these conditions and commands may only occur during refueling; others may in best case scenarios never occur. To claim operability it is necessary to test these dormant commands at a regular basis.

Historically it has been done with surveillance testing which involved plant personnel placing the system into a bypassed or partial tripped stated and then testing the critical functions. The ALS platform has been designed to eliminate the need for surveillance testing with a combination of redundancy and self-testing which automatically and transparently verifies the critical functions of system.

The ALS Platform self-test strategy is based on 4 simple and effective steps:

Detect: The ALS Platform detects failures in its circuits or connected field devices either by running non-intrusive background tests on a regular interval, or by redundancy.

Mitigate: The circuits causing the failure will be isolated before the failure is allowed to propagate to other systems.

Announce: The detected failure is announced using the ALS rack alarm which will typically tie into a master control board alarm. Other application specific indicators may also be added to the system to give a more detailed status indication to the control room, such as indicating in which function the failure occurred and to show if the system remains operable.

React: The failure will be announced using the system alarm and by other application specific means. The ALS system may also be designed so a failure in a sub-circuit causes the system to enter a specific state, such as a partial trip or bypass.

The critical functions in a particular application are defined by the customer and become key requirements when specifying the application specific ALS system. Generally a critical function will be the system's ability to drive its output channels to a predefined state when a specified set of inputs events occur, such as digital inputs being activated or analog input going beyond a threshold.

The self-testing of the ALS platform can be divided up into segments as shown on Figure 12-1. The figure shows the path needed to be tested to verify a typical critical function is operational. The following sections will describe the self-test strategy in each of these segments.

04JT f POWd +- WOWu Ouut +- FWe IP

+ W/U

.->R/

R MB

- RW I

I I

I Figure 12-1: ALS Platform Self-Testing Field-*Input: The capability of testing the connection to a field input is determined by the customer's application/equipment and the particular ALS input board. If the field input supports self-test, the ALS board will determine the integrity of the wiring and perform an application specific action in case of failure. A simple example of this is a 4-2OmA current loop where a wire break will be detected, mitigated and reacted and annunciated accordingly.

Input--RAB: The generic ALS input boards are designed to automatically detect circuit failures between the input channels and the ALS Bus. This is done with a combination of redundancy and self-test. The input channels typically include a self-test circuit where the channel are disconnected from the field input and tested. These tests are done in a way that the test time does not affect the response time of the system. Such self-tests will normally occur every 10-15 minutes and on every change of state of the input, see Table 12-1. The logic inside the FPGAs on the input boards is protected with the standard ALS dual-core redundancy.

6002-00026, Rev 2, Jan. 16, 2009 Page 45 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC RAB-4RAB: The ALS Bus communication is protected with redundancy and timeout detectors. The ALS bus communication is protected by CRC checksum and by the way the data packets are constructed. Any error on the ALS bus are immediately detected and handled appropriately. The failure detection mechanism on the ALS bus ensures that any one board cannot cause an unannounced and failure.

1) If the CLB fails the slave boards will detect a timeout event an all enter their fail-safe state. The redundant alarm in the STB will ensure that the failure is announced, even if the CLB is not capable of doing so.
2)

If an ALS slave board fails, the CLB will detect the failure and perform a predetermined action.

The ALS bus implementation and protocol inherently ensure that no 'stuck-at' failures can occur in the ALS system without detection.

CLB: The logic function is application specific. They are typically based on state machines and other basic building blocks. A self-test strategy will be designed specifically to ensure no hidden failures in the critical functions. The FPGA logic inside the CLB is protected by the standard dual-core redundancy.

RAB-4RAB: Save as above.

RAB-4Output: The generic ALS output boards are designed to automatically detect circuit failures between the ALS Bus and the output channel. This is done with a combination of redundancy and self-tests, see Table 12-1.

Output--Field: The capability of testing the connection to a field device is determined by the customer's equipment and the particular ALS output board. If the field device supports self-test, the ALS board will determine the integrity of the wiring and component and perform an application specific action in case of failure. The field testing may be a combination of wire-break, current, and voltage detection.

Table 12-1: Self-testing intervals in the ALS Platform Description ALS Board Test Interval Digital Input Channel ALS-301 15 minutes interval Change of state High Integrity Output Channel ALS-411 1 minute interval Change of state Extended test every 30 minutes Digital Output Channel ALS-401 Continuous LED's All FPGA based ALS boards 1 second interval NVM (used for storing SetPoints)

All FPGA based ALS boards 1 Hour interval ALS Bus All FPGA based ALS boards Every communication FPGA Logic All FPGA based ALS boards Continuous Voltage Supervisors on local voltage domains.

All ALS Boards Continuous Failures related to the FPGA, the busses, and the analog channels will be detected, and the effects will be mitigated and managed according to the application specifications - see Table 8-1.

12.1 Surveillance Testing Support The ALS system can be specified to support surveillance testing as need by the application. Typical plant applications require that the ALS system or functions inside the system can be placed in bypass or partial trip. While a function or system is in bypass the associated inputs or outputs may be tested, but only if support for this have been built into the system as design time.

Surveillance Test enabled outputs may be toggled either by using the ASU interface or by toggle switches mounted on a panel in the cabinet. Inputs may be monitored by the state of the front panel LED or by using the ASU.

The surveillance testing supported by the ALS system is decided by the customer and will communicated to CS Innovations in their requirements specification or purchase order.

6002-00026, Rev 2, Jan. 16, 2009 Page 46 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 46 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 13 Cyber Security The ALS Platform is designed and implemented to meet the intent of the Regulatory Guide 1.152, Revision 2 [9], as well as the considerations done in NEI 04-04 revision 1 [10]. Special emphasis was placed on making a very robust design, which could not be compromised by any Cyber security risks.

Special emphasis was placed on cyber security throughout the life cycle, with special emphasis on ensuring the ALS concepts and ALS design basis was solid, as well as the actual Design & Implementation. This process was tested and validated by the V&V group.

The guidance provided within Regulatory Positions 2.1-2.9 of Regulatory Guide 1.152 Rev. 2 is met. ALS has implemented an acceptable method that can be used by licensees or applicants to assist in the protection of digital computers used within safety systems from cyber threat.

A separate and Wolf Creek MSFIS specific Cyber Security evaluation was done in the MSFIS Safety Assessment document, Reference 6101-00006. In the document Chapter 7 covers different types of malicious alterations.

13.1 Communication points The cyber security principles of avoidance, detection and mitigation strategy on which the ALS platform is designed and implemented are the base principles of a hardwired logic. design, which cannot change runtime.

The ALS platform has a very limited communication interface due the nature of the hardware implementation. Inputs and outputs are typically dedicated simple analog/digital signal conditioning channels without the capability to perform any type of communication.

The following boards are not credible cyber security threats due to their lack of any communication capability:

Control logic boards, referred to as ALS-lxx boards Analog/Digital inputs boards, referred to as ALS-3xx boards Analog/Digital outputs boards, referred to as ALS-4xx boards Power supply boards, referred to as ALS-9xx boards The following board has a potential credible cyber security threat:

0 Service & Test Board, referred to as ALS-2xx boards The Service & Test Boards support simple interfaces, which are capable of communicating with the ALS Service Unit (ASU) through a simple Universal Serial Bus (USB) connection.

The Service & Test Boards are designed and implemented to aid plant personnel during maintenance and diagnostics by providing visibility of the internal ALS system's status, state, health and configuration information, without affecting the safety related function.

ALS does not support advanced communication ports and protocols, such as IEEE 802.x protocols, IEEE 802.3 Ethernet, IEEE 802.11 Wireless LAN, IEEE 802.15 Wireless PAN, etc.

6002-00026, Rev 2, Jan. 16, 2009 Page 47 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 47 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC 13.2 Cyber Security Fact sheet for ALS-based systems The following list serves as a fact sheet regarding the ALS platform and postulated cyber security concerns:

The 'ALS Service Unit (ASU)' has the following characteristics:

The ASU is a dedicated piece of test equipment, intended as an "External Non Safety-related Equipment' The ASU can be connected to the ALS rack during diagnostics or when surveillance testing is performed by plant personnel The ASU is not a fixed mounted device. Plant personnel will bring the ASU to the cabinets when there is a need to use the test equipment The ASU cannot be connected to the ALS rack without causing an MCB alarm.

The ASU cannot in any way permanently alter the behavior of an ALS rack. When the ASU is disconnected, the rack is restored to its normal operation.

The ASU connects to the ALS rack through a simple USB connection on the ALS-2xx Service & Test Board which will allow the ASU to request information to be transmitted over the TAB bus. ALS-2xx boards are responsible for controlling the TAB bus communication. The ASU can only request information to be sent over the TAB bus and cannot in any direct or indirect way affect the safety related data communication on the RAB bus.

" The ASU is a standard battery powered Windows XP based laptop.

" The ASU executes the dedicated CS Innovations software package, which includes the dedicated ASU software application.

" The ASU uses the proprietary and non-disclosed CS Innovations communications protocol to communicate with the ALS rack. Without the correct protocol the connection cannot be established or maintained.

Even if the ASU software was maliciously modified, it would not be able to gain further access into the ALS rack. The limitations in the ASU as described in the above bullets are set by the ALS-2xx hardware capabilities.

The 'ALS Platform' has the following characteristic:

ALS is a hardware-based system that does not have a software component and therefore no Real-Time Operating System (RTOS), no Dynamic Link Libraries (DLL), no run-time libraries, no device drivers, etc.

This means that typical issues related to software implementations cannot occur. Software related problems include, but are not limited to the following issues:

o Malicious program fragments with intended security logic leaks, backdoors into an OS, time bomb code fragments, virus infiltrations, worm's infiltrations, Trojan horses, hacker intrusion attempts, data storms, etc.

The 'ALS boards' have the following characteristic with respect to cyber security:

The FPGA runtime content cannot be modified by an operator/intruder.

o The FPGA image is fixed and cannot be modified in-part or in-full without a complete re-flashing.

o Re-flashing the FPGA image requires the removal of the board from the ALS rack which would immediately cause an MCB alarm.

o The new FPGA image should be implemented and communication based on CS Innovations proprietary HDL source-core, otherwise the board would be rejected by the system.

6002-00026, Rev 2, Jan. 16, 2009 Page 48 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 48 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC The runtime SetPoints stored in the onboard NVM cannot be modified by an operator/intruder.

o The SetPoints image is fixed and cannot be modified in-part or in-full without a complete re-flashing.

o Re-flashing the SetPoints image within the NVM would require the removal of the board from the ALS rack which would cause an MCB alarm.

o Re-flashing the SetPoints can only be done by inserting the board into the CS Innovations proprietary ALS Test Unit (ATU). The new image should be implemented based on CS Innovations proprietary SetPoints format. If the SetPoints are not using the right format or passing the CRC checks, then the board will enter HALT and remain in and idle state and not start up.

o Programming Valid SetPoints intended for a different system into an ALS board is possible, but it would be detected either by the ALS system itself, or through review of the generated SetPoints report, which clearly indicate the programmed SetPoints configuration.

The Reliable ALS bus (RAB) and safety critical path components cannot be affected, altered or manipulated.

o All safety related information passed between boards in the ALS system is hardwired and cannot be modified or tampered by any outside intervention.

o RAB communication is controlled by a hardwired sequencer located within the ALS-lxx Core Logic Boards. The communication is fixed and cannot be modified, interrupted or stopped by any outside intervention.

o Unexpected RAB accesses to an ALS board, e.g. wrong address, write to read-only register or read from a write-only register, will cause the ALS board to enter a HALT condition and ignore all further communication attempts.

The safety path RAB is isolated from the Test ALS bus (TAB) and the ASU interface.

o The TAB is used to transfer all non-safety information such as integrity monitoring, diagnostics, and test data used for maintenance and troubleshooting diagnostics.

o The TAB is used to support a series of ASU initiated actions:

ASU initiated self-test, such as force a board to perform a LED, NVM, or 10 channel test ASU accesses the status and health information BlackBox accesses the status and health information o

The TAB communication runs asynchronously, independent, and separate from the RAB o

The ASU interface has access to see boards through the TAB o

The ASU interface has no access to the RAB or the safety path Communication isolation and independence considerations related to DI&C-ISG-04.

ALS racks do not require communication with any External Safety-related Equipment.

o ALS maintains 100% isolation, separation and independence to external Safety-related Equipment.

ALS racks do not require communication with any External Non safety-related Equipment.

o ALS maintains 100% isolation, separation and independence to external Non Safety-related Equipment.

ALS racks do not require communication between divisions and equipment configuration maintains a separate Class 1E circuit per Division.

o ALS maintains 100% isolation, separation and independence between divisions/channels.

Note: Systems can be implemented which violate the above statements if the application requires it. This is typically not desirable or recommended and would likely violate staff positions set forth in DI&C-ISG-04.

6002-00026, Rev 2, Jan. 16, 2009 Page 49 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 49 of 50

ALS Platform Overview Non-Proprietary CS Innovations LLC Connecting an ASU to an ALS rack will typically have the following consequences:

Standard access restrictions and administrative requirements would be imposed by the plant based on the application requirements that includes the following:

o Access restrictions to get access to the equipment room where ALS racks typically are located o

Access restrictions to get access to the ASU units with the proprietary software Main control board (MCB) annunciation from the cabinet (if the application requires a cabinet alarm)

Main control board (MCB) annunciation from the ALS rack What cannot be accomplished or changed in a running ALS system by an operator/intruder?

o The FPGA content or the intended operation of the system cannot be changed o

The SetPoints or the configuration of the system cannot be changed 0

What can be accomplished or changed in a running ALS system by an operator/intruder?

o Obtain system information, such as board configuration and status information o

Obtain the content of the BlackBox.

o Initiate simple self tests which do not affect the safety path such as force the board to perform a LED test, NVM test, or 10 channel tes). Note, typically the output tests would be controlled in such a way that it cannot affect the application, e.g. typically manual action such as placing parts of the system in BYPASS is required to toggle an output.

Removal of the ASU connection from the ALS rack or a simple loss of connection will immediately result in the ALS going back to normal operation in the way it was before the ASU was connected to the ALS system.

In accordance with IEEE Std 603-1991 [11] the ALS platform is designed to prevent unauthorized electronic access to safety systems and data via network connections and maintenance equipment. Access via maintenance equipment is limited to those times the maintenance equipment is actually being used for maintenance. Additionally, the design of the ALS platform ensures no electronic path exists by which a person can make unauthorized changes to the ALS system or display erroneous plant status information to the operators.

The ALS platform is designed to ensure that no changes can be made to the system while installed, and advanced

'detection and mitigation techniques typically seen in software based systems are therefore not needed or implemented.

The ALS integrity cannot be compromised through unintentional operator handling, or through attempted malicious alterations of the system function or the system configuration. The ASU and the ALS-2xx Service and Test Board cannot modify any component within the ALS rack, which will change, interrupt or impair the safety path.

6002-00026, Rev 2, Jan. 16, 2009 Page 50 of 50 6002-00026, Rev 2, Jan. 16, 2009 Page 50 of 50

Vendor Submittal Approval ALS CLASS 1E CONTROLS VENDOR SUBMITTAL APPROVAL Name/Description Document Date Vendor Comments

  1. /Rev Submitted Name ALS Platform Overview 6002-00026 1/16/2009 CS Reviewed the revised portions Innovations Approver Signature Approval Date

,~L~ 1'-

~1/16/2009 Wolf Creek Nuclear Operating Corporation PO Box 411 1550 Oxen Lane, NE Burlington, KS 66839 Revision 1 Page I of I

Enclosure XXVIII to WM 09-0001 CS Innovations Letter 9100-00025, "Application for Withholding Proprietary Information from Public Disclosure" Non-proprietary

Ref. 9100-00025 CS INNOVATIONS LLC CS INNOVATIONS Direct phone: 480-612-2040 9150 E. DEL CAMINO, SUITE 110 Fax:

623-505-1055 SCOTTSDALE, AZ, 85258 e-mail:

steen@cs-innovation.com U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Our ref: 9100-00025 January 16, 2009 APPLICATION FOR WITHHOLDING PROPRIETARY INFORMATION FROM PUBLIC DISCLOSURE

Subject:

(CS Innovations LLC Confidential and Proprietary) 6002-00003 - ALS VV Plan, dated January 5"h 2009 6002-00004 - ALS EQ Plan, dated January 13"' 2009 6002-00010 - ALS Platform Requirements Specification, dated January 15'h 2009 6002-00011 - ALS Platform Specification, dated January 140 2009 6002-00031 - ALS Diversity Analysis, dated January 13"h 2009 6002-10101 - ALS-101 Requirements Specification, dated January 15"h 2009 6002-10102 - ALS-101 Hardware Specification, dated January 15"h 2009 6002-20101 - ALS-201 Requirements Specification, dated January 151h 2009 6002-20102 - ALS-201 Hardware Specification, dated January 15'h 2009 6002-30101 - ALS-301 Requirements Specification, dated January 15"h 2009 6002-30102 - ALS-301 Hardware Specification, dated January 15"' 2009 6002-40101 - ALS-401 Requirements Specification, dated January 1 5 th 2009 6002-40102 - ALS-401 Hardware Specification, dated January 15"1 2009 6002-41101 - ALS-411 Requirements Specification, dated January 15"h 2009 6002-41102 - ALS-411 Hardware Specification, dated January 15"' 2009 6002-90501 - ALS-905 Requirements Specification, dated January 15"' 2009 6002-90502 - ALS-905 Hardware Specification, dated December 9 1h 2008 6002-00206 - NTS Temperature Test Report, dated January 16"' 2009 6002-00207 - CSI ESD Test Report, dated January 16"' 2009 6002-00208 - CSI Isolation Test Report, dated January 16"' 2009 6101-00200 - MSFIS V&V Report, dated January 16"' 2009 9006-00008 - Return for Material Repair Procedure, revision 0.

The proprietary information for which withholding is being requested in the above referenced report is further identified in Affidavit 9100-00024 signed by the owner of the proprietary information, CS Innovations LLC. The affidavit, which accompanies this letter, sets forth the basis on which the information may be withheld from public

Ref: 9100-00025 disclosure by the Commission and addresses with specificity the considerations listed in paragraph (b)(4) of 10 CFR Section 2.390 of the Commission's regulations.

Accordingly, this letter authorizes the utilization of the accompanying affidavit by the Wolf Creek Nuclear Operating Corporation.

Correspondence with respect to the proprietary aspects of the application for withholding or the CSI affidavit should reference this letter, 9100-00025, and should be addressed to Steen D. Sorensen, President & CEO, CS Innovations LLC, 9150 E. Del Camino, Suite 110, Scottsdale, AZ, 85258.

Very truly yours, Steen D. Sorensen President & CEO

Ref-9100-00024 AFFIDAVIT State of Arizona County of Maricopa Before me, the undersigned authority, personally appeared Steen D. Sorensen, who, being by me duly sworn according to law, deposes and says that he is authorized to execute this Affidavit on behalf of CS Innovations LLC (CSI), and that the averments of fact set forth in this Affidavit are true and correct to the best of his knowledge, information, and belief:

Steen D. Sorensen, President & CEO Sworn to and subscribed before me this _ff6&day of A... -7.i.56 -

Page 1 of 4

Ref. 9100-00024 (1) 1 am President & CEO, CS Innovations LLC (CSI), and as such, I have been specifically delegated the function of reviewing the proprietary information sought to be withheld from public disclosure in connection with nuclear power plant licensing and rule making proceedings, and am authorized to apply for its withholding on behalf of CSI.

(2) I am making this Affidavit in conformance with the provisions of 10 CFR Section 2.390 of the Commission's regulations and in conjunction with the CSI "Application for Withholding" accompanying this Affidavit.

(3) I have personal knowledge of the criteria and procedures utilized by CSI in designating information as a trade secret, privileged or as confidential commercial or financial information.

(4) Pursuant to the provisions of paragraph (b)(4) of Section 2.390 of the Commission's regulations, the following is furnished for consideration by the Commission in determining the information sought to be withheld from public disclosure should be withheld.

(i)

The information sought to be withheld from public disclosure is owned and been held in confidence by CSI.

(ii)

The information is of a type customarily held in confidence by CSI and not customarily disclosure to the public. CSI has a rational basis for determining the types of information customarily held in confidence by it and, in that connection, utilizes a system to determining when and whether to hold certain types of information in confidence. The application of that system and substance of that system constitutes CSI policy and provides the rational basis required.

Under that system, information is held in confidence if it falls in one or more of several types, the release of which might result in the loss of an existing or potential competitive advantage, as follows:

(a) The information reveals the distinguishing aspects of a process (or component structure, tool, method, etc.) where prevention of its use by any of CSI's competitors without license from CSI constitutes a competitive economic advantage over other companies.

(b) It consists of supporting data, including test data, relative to a process (or component, structure, tool, method, etc.) the application of which data secures a competitive economic advantage, e.g. by optimization or improved marketability.

Page 2 of 4

Ref: 9100-00024 (c) Its use by a competitor would reduce his expenditure of resources or improve his competitive position in the design, manufacture, shipment, installation, assurance of quality, or licensing a similar product.

(d) It reveals costs or price information, production capacities, budget levels, or commercial strategies of CSI, its customers or suppliers.

(e) It reveals aspects of past, present, or future CSI or customer funded development plans and programs of potential commercial value to CSI.

(f) It contains patentable ideas, for which patent protection may be desirable.

There are sound policy reasons behind the CSI system which include the following:

(a) The use of such information by CSI gives CSI a competitive advantage over its competitors. It is, therefore, withheld from disclosure to protect the CSI competitive position.

(b) It is information that is marketable in many ways. The extent to which such information is available to competitors diminishes the CSI ability to sell products and services involving the use of the information.

(c) Use by our competitor would put CSI at a competitive disadvantage by reducing his expenditure of resources at our expense.

(d) Each component of proprietary information pertinent to a particular competitive advantage is potentially as valuable as the total competitive advantage. If competitors acquire components of proprietary information, any one component may be the key to the entire puzzle, thereby depriving CSI of a competitive advantage.

(e) The CSI capacity to invest corporate assets in research and development depends upon the success in obtaining and maintaining a competitive advantage.

(iii)

The information is being transmitted to the Commission in confidence and, under the provisions of 10 CFR Section 2.390, it is to be received in confidence by the Commission.

(iv)

The information sought to be protected is not available in public sources or available information has not been previously employed in the same original manner or method to the best of our knowledge and belief.

Page 3 of 4

Ref: 9100-00024 (v)

The proprietary information sought to be withheld in this submittal is that which is appropriately marked (Confidential and Proprietary) in the following documents:

6002-00003 - ALS VV Plan, dated January 5th 2009 6002-00004 - ALS EQ Plan, dated January 13"' 2009 6002-00010 - ALS Platform Requirements Specification, dated January 15'h 2009 6002-00011 - ALS Platform Specification, dated January 141h 2009 6002-00031 - ALS Diversity Analysis, dated January 13"h 2009 6002-10101 - ALS-i01 Requirements Specification, dated January 15"1 2009 6002-10102 - ALS-101 Hardware Specification, dated January 151' 2009 6002-20101 - ALS-201 Requirements Specification, dated January 15"1 2009 6002-20102 - ALS-201 Hardware Specification, dated January 15"' 2009 6002-30101 - ALS-301 Requirements Specification, dated January 15'h 2009 6002-30102 - ALS-301 Hardware Specification, dated January 15th 2009 6002-40101 - ALS-401 Requirements Specification, dated January 15th 2009 6002-40102 -ALS-401 Hardware Specification, dated January 15'h 2009 6002-41101 -ALS-41 I Requirements Specification, dated January 15"h 2009 6002-41102 -ALS-411 Hardware Specification, dated January 151h 2009 6002-90501 -ALS-905 Requirements Specification, dated January 15th 2009 6002-90502 - ALS-905 Hardware Specification, dated December 9 th 2008 6002-00206 -NTS Temperature Test Report, dated January 16th 2009 6002-00207 - CSI ESD Test Report, dated January 16th 2009 6002-00208 - CSI Isolation Test Report, dated January 16th 2009 6101-00200 - MSFIS V&V Report, dated January 16th 2009 9006-00008 - Return for Material Repair Procedure, revision 0.

The information is provided in support of a submittal to the Commission, being transmitted by the Wolf Creek Nuclear Operating Corporation and Application for Withholding Proprietary Information from Public Disclosure, to the Document Control Desk.

This information is part of that which will enable CSI to:

(a) Provide a replacement MSFIS Controls for Wolf Creek Generating Station.

Further this information has substantial commercial value as follows:

(a) The information requested to be withheld reveals the distinguishing aspects of a methodology which was developed by CSI.

Public disclosure of this proprietary information is likely to cause substantial harm to the competitive position of CSI.

The development of the technology described in part by the information is the result of applying the results of many years of experience in an intensive CSI effort and the expenditure of a considerable sum of money.

In order for competitors of CSI to duplicate this information, similar technical programs would have to be performed and a significant manpower effort, having the requisite talent and experience, would have to be expended.

Further the deponent sayeth not.

Page 4 of 4