| Title | Main Control Room Air Treatment System Inoperable |
| Event Description | On 5/3/2020 at 1100 EDT, Operations identified a step change in the Main Control Room ambient noise. The cause of the noise was a rise in vibrations on the Number 11 fan motor of the Main Control Room Ventilation Circulating Fan. Another step change in noise occurred and Operations swapped from the Number 11 fan motor to its redundant Number 12 fan motor, but the noise and vibrations did not improve. The two independent motors are connected to the blower shaft with belts on either end of the shaft. This entire fan and motor assembly is contained within the Main Control Room ventilation ducting and is not visible. At 1118 EDT, Operations shut off the Main Control Room Ventilation Circulating Fan due to Number 11 fan motor vibrations, declared the Main Control Room Air Treatment System inoperable, and entered the Technical Specification 3.4.5.e, 7-day action statement.
At 1750 EDT, Maintenance entered the ductwork and informed Operations that the Number 11 fan bearing had catastrophically failed and because of the extent of damage and close physical proximity to the Number 12 fan motor, jeopardized its continued operation. As a result, Operations also declared the Number 12 fan motor inoperable and determined the event was reportable as a loss of safety function per 10 CFR 50.72(b)(3)(v)(D). The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Nine Mile Point New York (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+0.63 h0.0263 days <br />0.00375 weeks <br />8.62974e-4 months <br />) | |
| Opened: | Alex Thomas 22:28 May 3, 2020 |
| NRC Officer: | Donald Norwood |
| Last Updated: | May 3, 2020 |
| 54692 - NRC Website
Loading map... | |
Nine Mile Point | |
WEEKMONTHYEARENS 546922020-05-03T21:50:0003 May 2020 21:50:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Main Control Room Air Treatment System Inoperable ENS 543642019-11-01T07:16:0001 November 2019 07:16:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray (Hpcs) System Inoperable ENS 502962014-07-22T17:43:00022 July 2014 17:43:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Diesel Generator for High Pressure Core Spray Declared Inoperable During Surveillance Testing ENS 498592014-02-27T08:30:00027 February 2014 08:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray (Hpcs) System Declared Inoperable ENS 490292013-05-14T16:15:00014 May 2013 16:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Steam Flow Isolation Capability Identified as Non-Functional ENS 487942013-02-28T18:19:00028 February 2013 18:19:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray Pump Failure ENS 486962013-01-23T20:16:00023 January 2013 20:16:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Concurrent Loss of High Pressure Reactor Makeup Systems Capability ENS 479672012-05-25T17:22:00025 May 2012 17:22:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident De-Energization of Both Divisions of Rhr Suction Line Primary Containment Isolations Valves During Testing ENS 452842009-08-23T21:50:00023 August 2009 21:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Unplanned Inoperability of the High Pressure Core Spray System ENS 442062008-05-13T12:25:00013 May 2008 12:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Loss of Offsite Power ENS 409202004-08-03T14:46:0003 August 2004 14:46:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray Rendered Inoperable Due to Faulty Test Equipment ENS 405062004-02-05T18:40:0005 February 2004 18:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Emergency Diesel Generator Ventilation Exhaust Damper Covered with Snow and Ice 2020-05-03T21:50:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_54692&oldid=3086102"