ENS 49859
ENS Event | |
|---|---|
08:30 Feb 27, 2014 | |
| Title | High Pressure Core Spray (Hpcs) System Declared Inoperable |
| Event Description | On February 24th at 0400 [EST], the Division 3 diesel (HPCS diesel) was declared inoperable for planned maintenance. Technical Specification (TS) 3.8.1 condition B was entered with a required action to restore the diesel to operable status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. Shortly after starting the diesel for post maintenance testing, operations observed erratic voltage regulator operation. The diesel was secured at 1621 on 2/24/14 before completing the required post maintenance operability test and troubleshooting is ongoing.
At 0330 on 2/27/14, the High Pressure Core Spray System (HPCS) was declared inoperable and TS 3.5.1 condition B was entered. With the HPCS system declared inoperable, TS 3.8.1 condition B was exited in accordance with the following note modifying TS 3.8.1: 'Division 3 AC electrical power sources are not required to be OPERABLE when High Pressure Core Spray (HPCS) System is inoperable.' The HPCS system is a single train system that is discussed in Chapters 6 and 15 of the Final Safety Analysis Report. The unplanned inoperability of the HPCS system is reportable in accordance with 10 CFR 50.72(b)(3)(v)(D) as, 'Any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to: (D) Mitigate the consequences of an accident.' The condition has been entered into the NMP corrective action program as CR-2014-001623. The NRC Resident Inspector has been notified.
The NMP Unit 2 Division 3 diesel testing was completed satisfactorily. The licensee declared the Division 3 diesel and HPCS systems operable at 1013 EST on 2/27/14 and exited TS 3.8.1 and 3.5.1. The licensee has notified the NRC Resident Inspector. Notified the R1DO (DeFrancisco). |
| Where | |
|---|---|
| Nine Mile Point New York (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+-4.88 h-0.203 days <br />-0.029 weeks <br />-0.00668 months <br />) | |
| Opened: | Carl Crawford 03:37 Feb 27, 2014 |
| NRC Officer: | Jeff Rotton |
| Last Updated: | Feb 27, 2014 |
| 49859 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Nine Mile Point | |
WEEKMONTHYEARENS 546922020-05-03T21:50:0003 May 2020 21:50:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Main Control Room Air Treatment System Inoperable ENS 543642019-11-01T07:16:0001 November 2019 07:16:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray (Hpcs) System Inoperable ENS 502962014-07-22T17:43:00022 July 2014 17:43:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Diesel Generator for High Pressure Core Spray Declared Inoperable During Surveillance Testing ENS 498592014-02-27T08:30:00027 February 2014 08:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray (Hpcs) System Declared Inoperable ENS 490292013-05-14T16:15:00014 May 2013 16:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Steam Flow Isolation Capability Identified as Non-Functional ENS 487942013-02-28T18:19:00028 February 2013 18:19:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray Pump Failure ENS 486962013-01-23T20:16:00023 January 2013 20:16:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Concurrent Loss of High Pressure Reactor Makeup Systems Capability ENS 479672012-05-25T17:22:00025 May 2012 17:22:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident De-Energization of Both Divisions of Rhr Suction Line Primary Containment Isolations Valves During Testing ENS 452842009-08-23T21:50:00023 August 2009 21:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Unplanned Inoperability of the High Pressure Core Spray System ENS 442062008-05-13T12:25:00013 May 2008 12:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Loss of Offsite Power ENS 409202004-08-03T14:46:0003 August 2004 14:46:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray Rendered Inoperable Due to Faulty Test Equipment ENS 405062004-02-05T18:40:0005 February 2004 18:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Emergency Diesel Generator Ventilation Exhaust Damper Covered with Snow and Ice 2020-05-03T21:50:00 | |