ENS 48794
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
18:19 Feb 28, 2013 | |
| Title | High Pressure Core Spray Pump Failure |
| Event Description | On February 28, 2013, at 1319 EST, Nine Mile Point Unit 2 (NMP2) experienced a failure of 2CSH*P2, High Pressure Core Spray System Pressure Pump. The HPCS system was currently inoperable for planned maintenance for planned pump room unit cooler maintenance with a 14 day completion time per Technical Specification 3.5.1.
Shortly after the starting of the HPCS pump as part of routine surveillance testing, the system pressure pump failed. Initial troubleshooting has found the pump motor windings to be shorted. Initial investigation identified smoke in the HPCS pump room, no indications of fire were identified. No breaker failures were identified. All other plant systems functioned as required. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Nine Mile Point New York (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+-1.3 h-0.0542 days <br />-0.00774 weeks <br />-0.00178 months <br />) | |
| Opened: | Carl Crawford 17:01 Feb 28, 2013 |
| NRC Officer: | Pete Snyder |
| Last Updated: | Feb 28, 2013 |
| 48794 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Nine Mile Point | |
WEEKMONTHYEARENS 546922020-05-03T21:50:0003 May 2020 21:50:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Main Control Room Air Treatment System Inoperable ENS 543642019-11-01T07:16:0001 November 2019 07:16:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray (Hpcs) System Inoperable ENS 502962014-07-22T17:43:00022 July 2014 17:43:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Diesel Generator for High Pressure Core Spray Declared Inoperable During Surveillance Testing ENS 498592014-02-27T08:30:00027 February 2014 08:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray (Hpcs) System Declared Inoperable ENS 490292013-05-14T16:15:00014 May 2013 16:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Steam Flow Isolation Capability Identified as Non-Functional ENS 487942013-02-28T18:19:00028 February 2013 18:19:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray Pump Failure ENS 486962013-01-23T20:16:00023 January 2013 20:16:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Concurrent Loss of High Pressure Reactor Makeup Systems Capability ENS 479672012-05-25T17:22:00025 May 2012 17:22:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident De-Energization of Both Divisions of Rhr Suction Line Primary Containment Isolations Valves During Testing ENS 452842009-08-23T21:50:00023 August 2009 21:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Unplanned Inoperability of the High Pressure Core Spray System ENS 442062008-05-13T12:25:00013 May 2008 12:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Loss of Offsite Power ENS 409202004-08-03T14:46:0003 August 2004 14:46:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Spray Rendered Inoperable Due to Faulty Test Equipment ENS 405062004-02-05T18:40:0005 February 2004 18:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Emergency Diesel Generator Ventilation Exhaust Damper Covered with Snow and Ice 2020-05-03T21:50:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_48794&oldid=85756"