| Title | Hpci Inoperable Due to Erroneous Indication on Flow Indicating Controller |
| Event Description | At 0225 EDT on September 3, 2012, with the James A. Fitzpatrick Nuclear Power Plant (JAF) operating at 93% reactor power, High Pressure Coolant Injection (HPCI) was declared inoperable due to abnormal indication on the HPCI Flow Indicating Controller (FIC). The FIC was found to be indicating a HPCI System flow rate of 700 gpm while the system was in the standby lineup. Under these conditions, the capability of the system to achieve the required flow rate cannot be assured.
This failure meets NRC 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> reporting criterion 10CFR50.72(b)(3)(v)(D). Reactor Core Isolation Cooling (RCIC) and other Emergency Core Cooling Systems (ECCS) remain operable. The NRC Resident Inspector has been notified.
The improper HPCI flow indication was determined to be due to minor air intrusion following restoration of the system after maintenance. The flow transmitter for the HPCI system was repeatedly vented with no air observed. The HPCI system has been restored to a normal standby line-up and is OPERABLE as of 9/4/2012 at 1415 EDT. The NRC Resident Inspector has been notified. R1DO (Conte) notified. |
| Where | |
|---|---|
| FitzPatrick New York (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+1.25 h0.0521 days <br />0.00744 weeks <br />0.00171 months <br />) | |
| Opened: | John Walkowiak 07:40 Sep 3, 2012 |
| NRC Officer: | Dong Park |
| Last Updated: | Sep 4, 2012 |
| 48270 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (93 %) |
| After | Power Operation (93 %) |
FitzPatrick | |
WEEKMONTHYEARENS 571202024-05-09T20:29:0009 May 2024 20:29:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Inoperable ENS 558712022-04-29T16:51:00029 April 2022 16:51:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (HPCI) Inoperable ENS 555932021-11-18T22:02:00018 November 2021 22:02:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Inoperable Due to Isolation Valve Failure to Automatically Open ENS 546572020-04-10T07:00:00010 April 2020 07:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Injection System Declared Inoperable ENS 526642017-04-04T11:35:0004 April 2017 11:35:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Inadvertently Isolated During Conduct of Maintenance Surveillance ENS 516132015-12-18T22:22:00018 December 2015 22:22:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Both Trains of Containment Atmosphere Dilution System Inoperable ENS 509792015-04-12T22:00:00012 April 2015 22:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Temporary Loss of Control Room Envelope Boundary ENS 505322014-10-13T23:35:00013 October 2014 23:35:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Injection Degraded Accident Mitigation Capability ENS 502102014-06-18T19:45:00018 June 2014 19:45:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Hpci Room Cooling ENS 496602013-12-18T20:00:00018 December 2013 20:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Safety Function for the Hpci Suction Automatic Low Cst Level Swap Over Inoperable ENS 484102012-10-16T11:00:00016 October 2012 11:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Shutdown Cooling Isolation Capability Lost ENS 482702012-09-03T06:25:0003 September 2012 06:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Erroneous Indication on Flow Indicating Controller ENS 482582012-08-30T16:15:00030 August 2012 16:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Failed Pressure Control Valve ENS 463552010-10-23T04:45:00023 October 2010 04:45:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable Due to Power Supply Failure ENS 450082009-04-22T15:21:00022 April 2009 15:21:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Inoperable ENS 429642006-11-04T23:10:0004 November 2006 23:10:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable 2024-05-09T20:29:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_48270&oldid=423652"