05000482/LER-2010-013, Regarding Potential Safe Shutdown Unanalyzed Condition Identified During Post-Fire Safe Shutdown Circuit Analysis

From kanterella
(Redirected from 05000482/LER-2010-013)
Jump to navigation Jump to search
Regarding Potential Safe Shutdown Unanalyzed Condition Identified During Post-Fire Safe Shutdown Circuit Analysis
ML110250333
Person / Time
Site: Wolf Creek 
Issue date: 01/17/2011
From: Rich Smith
Wolf Creek
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
WO 11-0003 LER 10-013-00
Download: ML110250333 (5)


LER-2010-013, Regarding Potential Safe Shutdown Unanalyzed Condition Identified During Post-Fire Safe Shutdown Circuit Analysis
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(x)
4822010013R00 - NRC Website

text

WLF CREEK NUCLEAR OPERATING CORPORATION January 17, 2011 Russell A. Smith Plant Manager WO 11-0003 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Subject: Docket No. 50-482: Licensee Event Report 2010-013-00, "Potential Safe Shutdown Unanalyzed Condition Identified during Post-Fire Safe Shutdown Circuit Analysis" Gentlemen:

The enclosed Licensee Event Report (LER) is being submitted pursuant to 10 CFR 50.73(a)(2)(ii)(B) regarding an unanalyzed condition that could potentially affect post fire safe shutdown equipment at Wolf Creek Generating Station.

This letter contains no commitments. If you have any questions concerning this matter, please contact me at (620) 364-4156, or Mr. Gautam Sen at (620) 364-4175.

Sincerely, Russell A. Smith RAS/rlt Enclosure cc:

E. E. Collins Jr (NRC), w/e G. B. Miller (NRC), w/e B. K. Singal (NRC), w/e Senior Resident Inspector (NRC), w/e P.O. Box 411 / Burlington, KS 66839 / Phone: (620) 364-8831 An Equal Opportunity Employer M/F/HC/VET tj

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 10/31/2013 (10-2010)

Estimated burden per response to comply with this mandatory collection request: 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />.

Reported lessons learned are incorporated into the licensing process and fed back to industry. Send comments regarding burden estimate to the Records and FOlAIPrivacy Service Branch (T-5 F52),

U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by LICENSEE EVENT REPORT (LER) internet e-mail to infocollects@nrc.gov, and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202, (3150-0104), Office of Management and Budget, Washington, DC 20503.

If a means used to (See reverse for required number of impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required digits/characters for each block) to respond to, the information collection.

3. PAGE WOLF CREEK GENERATING STATION 05000 482 1 OF 4

,. TITLE Potential Safe Shutdown Unanalvzed Condition Identified durinq Post-Fire Safe Shutdown Circuit Analysis

5. EVENT DATE 1
6. LER NUMBER 1

7.

8. OTHER FACILITIES INVOLVED MONT DAY YEAR HI YEAR SEQUENTIAL NUMBER REV IMONTH NAME DOCKET NUMBER 05000 11 18 2010 2010 013 00 FACILITY NAME DOCKET NUMBER 1

105000 I

I-

9. OPERATING MODE Mode 1
10. POWER LEVEL 100%
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR§: (Check all that apply)

El 20.2201 (b)

El 20.2201(d)

El 20.2203(a)(1)

El 20.2203(a)(2)(i)

El 20.2203(a)(2)(ii)

El 20.2203(a)(2)(iii)

El 20.2203(a)(2)(iv)

El 20.2203(a)(2)(v)

El 20.2203(a)(2)(vi)

El 20.2203(a)(3)(i)

El 20.2203(a)(3)(ii)

E] 20.2203(a)(4)

El 50.36(c)(1)(i)(A)

[1 50.36(c)(1)(ii)(A)

El 50.36(c)(2)

El 50.46(a)(3)(ii)

El 50.73(a)(2)(i)(A)

El 50.73(a)(2)(i)(B)

[I 50.73(a)(2)(i)(C)

El 50.73(a)(2)(ii)(A)

El 50.73(a)(2)(ii)(B)

El 50.73(a)(2)(iii)

El 50.73(a)(2)(iv)(A)

[E 50.73(a)(2)(v)(A)

El 50.73(a)(2)(v)(B)

El 50.73(a)(2)(v)(C)

El 50.73(a)(2)(v)(D)

El 50.73(a)(2)(vii)

El 50.73(a)(2)(viii)(A)

El 50.73(a)(2)(viii)(B)

El 50.73(a)(2)(ix)(A)

El 50.73(a)(2)(x)

El 73.71(a)(4)

El 73.71(a)(5)

El OTHER Specify in Abstract below or in NRC Form 366A

12. LICENSEE CONTACT FOR THIS LER zACILITY NAME TELEPHONE NUMBER (include Area Code)

Gautamn Sen, Manager Regulatory. Affairs 1 (620) 364-4175CAS YTMCMOET MANU-REPORTABLE CAS YTMCOMPONEN MANUI-REPORTABLE FACTURER TO EPIX

CAUSE

T T

FACTURER TO EPIX

14. SUPPLEMENTAL REPORT EXPECTED
15. EXPECTED MONTH DAY YEAR SUBMISSION [I YES (If yes, complete 15. EXPECTED SUBMISSION DATE) 0 NO DATE ABSTRACT (Limit to 1400 spaces, i.e., approximately 15 single-spaced typewritten lines)

During performance of a post-fire safe shutdown (PFSSD) circuit analysis, a commitment from Wolf Creek Generating Station LER 2010-003, the following issues were identified for a potential fire in the control room: (1) Certain fuses associated with the Train B emergency diesel generator (EDG) exciter/voltage regulator could fail, that would result in no power being available to supply credited PFSSD equipment. (2) The pressurizer power operated relief valves could fail open and not be closed within 3 minutes as required by the thermal hydraulic analysis. (3) Dampers in the Train B essential service water and Train B EDG rooms could fail and cause the room temperature to exceed the maximum design temperature for the rooms or drop below the minimum design temperature.

The cause was determined to be an inadequate review of control room circuitry for impact on PFSSD. A number of opportunities should have identified the issues including a root cause evaluation conducted in 2007. An hourly fire watch is in place in the control room and procedure OFN RP-017, "Control Room Evacuation," has been revised to address these issues. These issues have low safety significance.

NRC FORM 366 (10-2010)U.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE I

SEQUENTIAL REV WOLF CREEK GENERATING STATION 05000 482 YEAR NUMBER

.NO.

2 OF 4

2010

-- 013 00 PLANT CONDITIONS PRIOR TO EVENT Mode 1 100% power No structures, components, or structures were inoperable that contributed to this event.

EVENT DESCRIPTION

As a result of a commitment in Wolf Creek Generating Station (WCGS) LER 2010-003, Fire Protection performed a post-fire safe shutdown (PFSSD) circuit analysis for the Train B emergency diesel generator (EDG) [EIIS Code: EK] to ensure the diesel generator would remain available in the event of a fire in the control room. On November 18, 2010, during performance of the circuit analysis for the Train B EDG, it was discovered that certain fuses installed within Train B ExciterNoitage Regulator cabinet would be susceptible to failure in the event of postulated fire-induced hot shorts within the control room. If the fuse fails prior to flashing the field, then the generator will not be capable of generating voltage and no power will be available to supply credited PFSSD equipment.

Additionally, a circuit analysis was performed for all components credited for hot standby following a control room fire as directed by procedure OFN RP-017, "Control Room Evacuation." As a result of that circuit analysis, on December 17, 2010, the following issues were discovered:

1. A fire in the control room could cause the pressurizer power operated relief valves (PORVs) [EIIS Code: PZR-RV] to fail open. Actions currently proceduralized in OFN RP-017 may not be sufficient to close the PORVs within 3 minutes as required by the thermal hydraulic analysis. Based on the step sequence in OFN RP-017, it could take approximately 20 minutes to ensure all potential hot short sources are removed.
2. The ventilation alignment in the Train B essential service water (ESW) pump room [EIIS Code:

MK-DMP] and Train B EDG Room [EIIS Code: NB-DMP], in accordance with OFN RP-017, may not be adequate for all outside temperature conditions. A fire in the control room could cause the respective recirculation dampers to fail in any position. In the winter months, if the recirculation damper fails closed, then 100% outside air would be brought into the room with no mixing. This could cause the room temperature to drop below the minimum design temperature. In the summer months, if the recirculation damper fails full open, then maximum recirculation would occur and possibly cause the room temperature to exceed the maximum design temperature.

BASIS FOR REPORTABILITY A PFSSD issue identified as a condition where no or insufficient guidance is available to Operators, to readily mitigate the postulated fire induced equipment maloperation, is considered an unanalyzed condition in accordance with Section 50.72(b)(3)(ii)(B). This is based on NUREG 1022, Rev. 2,' Section 3.2.4, which provides the following example:

.... if fire barriers are found to be missing, such that the required degree of separation for redundant safe shutdown trains is lacking, the event would be reportable as an unanalyzed condition that

.significantly degraded plant safety.

1U.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE I

SEQUENTIAL REV WOLF CREEK GENERATING STATION 05000 482 YEAR NUMBER NO.

3 OF 4

2010

-- 013 00 Therefore, 10 CFR 50 Appendix R circuit separation issues that could result in undesired equipment maloperation with a resulting adverse affect on PFSSD capability, is considered by Wolf Creek Nuclear Operating Corporation (WCNOC) to be a condition where fire barrier protection is deficient.

As such, WCNOC is reporting these conditions pursuant to 10 CFR 50.73(a)(2)(ii)(B) for any event or condition that resulted in the nuclear power plant being in an unanalyzed condition that significantly degraded plant safety. Additionally, WCNOC made two eight-hour Emergency Notification System calls, Event Notification 46428 and 46488, in accordance with 10 CFR 50.72(b)(3)(ii)(B).

ROOT CAUSE Consistent with the apparent cause conclusion for LER 2010-003, the apparent cause for the issues identified in this LER is inadequate review of control room circuitry for impact on PFSSD following a control room fire. A number of opportunities were found that should have identified the issues including a root cause evaluation conducted in 2007.

CORRECTIVE ACTIONS

An hourly fire watch was in place in the control room to mitigate various control room PFSSD circuit issues, including the issues in this LER. The hourly fire watch will not be lifted until all control room PFSSD circuit issues are corrected.

Procedure OFN RP-017, "Control Room Evacuation," was revised to include the following compensatory actions:

1. Instructions were provided to operators on how to replace a blown fuse within the Train B ExciterNoltage Regulator cabinet. Spare fuses were staged in the emergency equipment locker and procedure STN GP-009, "Emergency Equipment Verification," was revised to list the spare fuses in the attachment
2. Potential 125 VDC sources located in control room that were de-energized later in procedure OFN RP-017, were moved to earlier in the procedure. This will ensure the pressurizer

'PORVs are closed within the time required by the thermal hydraulic analysis.

3. Directions have been added for operators to monitor room temperature extremes in the Train B ESW pump house and Train B EDG room and take needed actions.

SAFETY SIGNIFICANCE

These issues have low safety significance. A fire in the control room of such magnitude and severity as to cause an evacuation and plant shutdown is extremely unlikely. Based on the Fire Hazards Analysis, the combustible loading in the control room is low and interior finish materials meet or exceed the surface flammability requirements of applicable standards. Cables entering the control room are IEEE 383 rated. Large concentrations of cables in the control room trenches are protected with an automatic Halon extinguishing system and automatic smoke detectors are located in the control cabinets and trenches.U.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE SEQUENTIAL I REV WOLF CREEK GENERATING STATION 05000 482 YEAR NUMBER NO.

4 OF 4

2010

-- 013 00 OPERATING EXPERIENCE/PREVIOUS EVENTS LER 2010-003-00 identified that a fire induced hot short could energize the unit parallel relay and place the emergency diesel generator in droop mode of operation. In addition, other circuit issues were identified that could adversely affect the diesel generator voltage regulator. This issue could have prevented operation of the Train B EDG if a fire occurred in the control room involving these circuits.