05000443/LER-2016-001, Regarding Automatic Reactor Trip Due to Turbine Trip
| ML16123A118 | |
| Person / Time | |
|---|---|
| Site: | Seabrook (NPF-086) |
| Issue date: | 04/26/2016 |
| From: | Ossing M NextEra Energy Seabrook |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| SBK-L-16067 LER 16-001-00 | |
| Download: ML16123A118 (5) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(ix)(A) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i) |
| 4432016001R00 - NRC Website | |
text
U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 April 26, 2016 10 CFR 50.73 Docket No. 50-443 SBK-L-16067 Seabrook Station Licensee Event Report (LER) 2016-001-00 Automatic Reactor Trip Due to Turbine Trip Enclosed is Licensee Event Report (LER) 2016-001-00. This LER reports an event that occurred at Seabrook Station on March 2, 2016. This event is being reported pursuant to the requirements of 10 CFR 50.73(a)(2)(iv)(A).
Should you require further information regarding this matter, please contact me at (603) 773-7512.
cc:
D. Dorman, NRC Region I Administrator R. Gladney, NRC Project Manager P. Cataldo, NRC Senior Resident Inspector Sincerely, NextEra Energy Seabrook, LLC Micha 1 Ossing Licensing Manager NextEra Energy Seabrook, LLC, P.O. Box 300, Lafayette Road, Seabrook, NH 03874
Enclosure to SBK-L-16067
NRC,FORM 366 U.S. NUCLEAR REGULA TORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 10/31/2018 (11-2015)
Estimated burden per response to comply with this mandatory collection request: 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />.
- - 1i;P"~l.c~~
Reported lessons learned are incorporated into the licensing process and fed back to industry.
~
Send comments regarding burden estimate to the FOIA, Privacy and Information Collections
~
\\
- ..l LICENSEE EVENT REPORT (LER)
Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by internet e-mail to lnfocollects.Resource@nrc.gov, and to the Desk Officer, Office of Information and (See Page 2 for required number of Regulatory Affairs, NEOB-10202, (3150-0104), Office of Management and Budget, Washington, DC 20503. If a means used to impose an information collection does not display a currently valid digits/characters for each block)
OMB control *number, the NRG may not conduct or sponsor, and a person is not required to respond to, the information collection.
- 3. PAGE Seabrook 05000 443 1 OF 3
- 4. TITLE Automatic Reactor Trip Due to Turbine Trip
- 5. EVENT DATE
- 6. LER NUMBER
- 7. REPORT DATE
- 8. OTHER FACILITIES INVOLVED I
SEQUENTIAL I REV FACILITY NAME DOCKET NUMBER MONTH DAY YEAR YEAR NUMBER NO.
MONTH DAY YEAR 05000 FACILITY NAME DOCKET NUMBER 03 02 2016 2016 -
001 -
00 04 26 2016 05000
- 9. OPERA TING MODE
- 11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply)
D 20.2201 (b)
D 20.2203(a)(3)(i)
D 50.73(a)(2)(ii)(A)
D 50.73(a)(2)(viii)(A) 1 D 20.2201 (d)
D 20.2203(a)(3)(ii)
D 50.73(a)(2)(ii)(B)
D 50.73(a)(2)(viii)(B)
D 20.2203(a)(1)
D 20.2203(a)(4)
D so.73(a)(2)(iii)
D 50.73(a)(2)(ix)(A)
D 20.2203(a)(2)(i)
D 50.36(c)(1)(i)(A)
[{] 50.73(a)(2)(iv)(A)
D 50.73(a)(2)(x)
- 10. POWER LEVEL D 20.2203(a)(2)(ii)
D 50.36(c)(1)(ii)(A)
D 50.73(a)(2)(v)(A)
D 73.71(a)(4)
D 20.2203(a)(2)(iii)
D so.36(c)(2)
D 50.73(a)(2)(v)(B)
D 73.71(a)(5)
D 20.2203(a)(2)(iv)
D so.46(a)(3)(ii)
D 50.73(a)(2)(v)(C)
D 73.77(a)(1) 100 D 20.2203(a)(2)(v)
D 50.73(a)(2)(i)(A)
D 50.73(a)(2)(v)(D)
D 73.77(a)(2)(i)
D 20.2203(a)(2)(vi)
D 50.73(a)(2)(i)(B)
D 50.73(a)(2)(vii)
D 73.77(a)(2)(ii)
D 50.73(a)(2)(i)(C)
D OTHER Specify in Abstract below or in Description of the Event On March 2, 2016 at 0253 while operating at 100% power, Seabrook Station experienced an automatic reactor trip due to a turbine trip.
A failure associated with inverter [JJ, INVT] ED-1-11 caused a voltage transient to a remote control panel that is part of the Turbine Control System (TCS) [JJ]. When this failure occurred, ED-1-11 was one of two power supplies to the turbine control system along with ED-1-12. The TCS is designed with redundant inverters so that the loss of one inverter will not cause a system failure. However, during this event, the inverter failure caused a momentary voltage increase which exceeded the voltage limits of the TCS 28 vdc power supplies causing them to momentarily shut down, resulting in the internal processors in the remote panel rebooting.
The remote processors send their outputs to the main TCS control processors. Upon the loss of output from the remote processors, the 2/3 logic for two separate system parameters was satisfied and an automatic turbine trip signal was initiated. The turbine trip signal initiated a reactor trip.
The*operating crew processed through E-0, Reactor Trip or Safety Injection (exited the procedure at step 4 a RNO, (response not obtained)) to ES-0.1, Reactor Trip Response (exited at step 14 a RNO) to OSl000.11, Post Trip to Hot Standby.
Cause of the Event
The direct cause of the event was a failure of inverter ED-1-11 which resulted in an overvoltage condition. to the turbine control system.
At this time, the cause of the inverter failure has not been determined.
The troubleshooting of the inverter ED-1-11 failure is still in progress. Efforts are being made to replace potentially faulty components and re-install software and perform additional testing on components that were in service at the time of the event. If additional troubleshooting identifies a cause, the root cause evaluation team will be reconvened and this LER will be supplemented.
Analysis of the Event
The Reactor Trip System automatically initiates a reactor trip when any monitored variable or combination of variables approaches pre-established limits. Sufficient redundancy is provided to permit periodic testing while maintaining capability to meet single failure criteria. The Reactor Protection System acts to shut down the reactor, close isolation valves, and initiate operation of the Engineered Safety Features should any or all of these actions be required. The reactor trip on a turbine trip is actuated by two out of three logic from emergency trip header fluid pressure signals or by all closed signals from the turbine steam stop valves. A turbine trip causes a direct reactor trip above P-9. The reactor trip on turbine trip provides additional protection and conservatism beyond that required for the health and safety of the public. This trip is included as part of good engineering practice and prudent design.
A valid actuation of the reactor protection system occurred as the result of a turbine trip. The turbine trip was caused by an overvoltage condition to the 28 vdc power supplies in the turbine control system. The inverter failure caused a momentary voltage increase which exceeded the voltage limits of the TCS 28 vdc power supplies causing them to momentarily shut down, resulting in the remote processors rebooting. Upon the loss of output from the remote processors, the 2/3 logic for two separate system parameters was satisfied and an automatic turbine trip signal was initiated. The plant was at 100% power, above the P-9 set point of 45%. Above P-9 a turbine trip will automatically initiate a reactor trip. An automatic reactor trip signal successfully actuated as designed with the "first out" (indicator of what caused the reactor trip) being "Turbine Trip."
Plant computer data was reviewed to verify that the plant responded as designed during this event. All equipment required to remove decay heat was available prior to the event and functioned properly during the event. The event posed no actual or potential hazard to public health or safety.
I~ (11-2015)
LICENSEE EVENT REPORT (LER)
CONTINUATION SHEET Page 3 of3 U.S. NUCLEAR REGULATORY COMMISSION
- 3. LER NUMBER lseabmokStation I OS000-1 443 I B-1SE*~?o~;:'1-db This event resulted ma valld actuatron otthe reactor protectron system and met the reportmg cntena oT 10 CFR 50.72tb)t2ytrv)(B). A four hour report was made to the NRC at approximately 0427 on March 2, 2016 (event number 51762). The operators responded to the plant trip in accordance with approved procedures, and safety systems functioned as expected. No adverse consequences resulted from this event and this incident had no adverse impact on the health and safety of the public or the plant and its personnel. This event did,not involve a safety system functional failure. No inoperable structures, systems or components contributed to this event.
Corrective Actions
Completed corrective action was the implementation of a temporary modification to energize ED-PP-1 lA to eliminate single point vulnerability.
Planned corrective actions are to continue troubleshooting and repair of inverter ED-I-11, install overvoltage protection for GE Mark Vie TCS cabinets and upgrade GE Mark Vle TCS power supplies to the higher input voltage phoenix units.
Similar Events
There have been no previous licensee event reports at Seabrook for this issue.
Additional Information
The Energy Industry Identification System (EIIS) codes are included in this LER in the following format: [EIIS system identifier, EIIS component identifier].