05000423/FIN-2014008-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Provide Adequate Maintenance Instructions for the Turbine Driven Auxiliary Feedwater Pump Governor Control Valve Linkage |
Description | The inspectors identified a self-revealing Green NCV of TS 6.8.1, Procedures and Programs, when Dominion did not maintain an adequate maintenance procedure to ensure reliable performance of the TDAFW system. Specifically, TDAFW properly started following the August 9, 2013, reactor trip, but was subsequently shut down after observed flow and pressure oscillations. Dominion staff discovered the control valve linkage misaligned due to a loose cam follower bearing retaining nut. As part of the repair, Dominion implemented a revision to the C MP 711 procedure to require application of thread-locker to the cam follower bearing retaining nut during reassembly. Additionally, Dominion entered this issue in their CAP as CR 522896. The finding was more than minor because it is associated with the procedure quality attribute of the Mitigating Systems cornerstone and adversely affected its objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the maintenance procedure did not provide sufficient written instructions to ensure adequate torque of the retaining nut and thereby reliable performance of the TDAFW system three months after reassembly. The finding was evaluated using IMC 0609, Attachment 4 and Appendix A, Exhibit 2.A, and determined to be of very low safety significance (Green) since it was not associated with a design or qualification deficiency, not a loss of system/function, and not an actual loss of its TS function. This finding had a cross-cutting aspect in the area of Human Performance, Documentation, in that licensee organizations are expected to create and maintain complete, accurate, and up-to-date documentation. Specifically, Dominion did not maintain a comprehensive, high-quality maintenance procedure that was thorough to assure assembly of critical TDAFW components. |
Site: | Millstone ![]() |
---|---|
Report | IR 05000423/2014008 Section 4OA5 |
Date counted | Sep 30, 2014 (2014Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 93812 |
Inspectors (proximate) | F Arner H Nieh M Chambers P Finney W Cook |
Violation of: | Technical Specification - Procedures Technical Specification |
CCA | H.7, Documentation |
INPO aspect | WP.3 |
' | |