Finding | |
|---|---|
| Title | Inadequate Procedure Used as a Compensatory Measure |
| Description | The team identified a non-cited violation of License Condition 2.C.(3)(b), Fire Protection, for use of an inadequate procedure as a compensatory measure. Specifically, a procedure for providing temporary cooling to the safety parameter display system room when the normal room cooler is unavailable did not adequately address the impact of the temporary configuration on the ability to maintain safe and stable plant conditions for fires that require shutdown from outside the control room. The temporary room cooler did not have a power supply assured to remain available during a shutdown from outside the control room. The licensee entered this violation into their corrective action program as Condition Reports CR-ANO-2-2016-02143 and CR-ANO-C-2016-02638. In response to this issue, the licensee developed a thermal analysis of the safety parameter display system room temperature during this scenario and confirmed that the maximum room temperature would not challenge the operation to the safety parameter display system. The failure to provide an adequate procedure for use as a compensatory measure was a performance deficiency. The performance deficiency was more than minor because it was associated with the Mitigating Systems cornerstone attribute of procedure quality and adversely affected the associated cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events (fire) to prevent undesirable consequences. Specifically, loss of cooling to the safety parameter display system room could adversely affect the availability, reliability, and capability of the safety parameter display system which is required to respond to a fire resulting in the evacuation of the Unit 2 control room. A senior reactor analyst performed a detailed risk evaluation of this finding because IMC 0609, Appendix F, does not include explicit treatment of fires in the control room. An evaluation of the survivability of the safety parameter display system compared to the best estimate of the heatup of the room housing its equipment demonstrated that the safety parameter display system would survive with high probability until the plant reached a safe and stable condition for the postulated fires. As a result, the finding was determined to be of very low safety significance (Green). This finding did not have a cross-cutting aspect since it was not indicative of present performance in that the performance deficiency occurred more than three years ago. |
| Site: | Arkansas Nuclear |
|---|---|
| Report | IR 05000368/2016009 Section 1R05 |
| Date counted | Jun 30, 2016 (2016Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | G Pick G Werner H Barrett J Mateychick N Okonkwo R Deese S Alferink S Makor |
| Violation of: | License Condition - Fire Protection |
| INPO aspect | |
| ' | |
Finding - Arkansas Nuclear - IR 05000368/2016009 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Arkansas Nuclear) @ 2016Q2
Self-Identified List (Arkansas Nuclear)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||