Finding | |
|---|---|
| Title | Failure to Implement Fire Protection Program Requirements |
| Description | A self-revealing NCV of TS 5.4.1.c, Fire Protection Program Implementation, was identified for the licensees failure to establish and implement adequate procedures required to maintain functionality of the Unit 2 auxiliary building fire protection system (pyro panel). On January 18, 2014, the operations shift crew determined the Unit 2 pyro panel was nonfunctional when multiple suppression alarms came in on a main control room panel and all of the detection alarms came in on Unit 2 pyro panel. The licensee entered this issue into their corrective action program as CR 760108 and established continuous fire watches, as compensatory measures, until the Unit 2 pyro panel was returned to service on January 20, 2014. The failure to establish and implement adequate procedures to maintain functionality of the Unit 2 auxiliary building fire protection pyro panel was a performance deficiency. The performance deficiency was more than minor because it adversely affected the protection against external factors (fire) attribute of the mitigating systems cornerstone objective to ensure the availability, reliability and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to establish and implement adequate procedures to maintain functionality of the Unit 2 auxiliary building fire protection pyro panel led to a degraded fire indicating unit, which resulted in a non-functional Unit 2 fire protection pyro panel and certain auxiliary building fire detection systems. The finding was evaluated using IMC 0609, Appendix F, Fire Protection Significance Determination Process, issued September 20, 2013. According to question 1.4.2-G, the finding screened to Green because the Unit 2 auxiliary building suppression system was still able to suppress a fire such that no additional equipment important to safety would be affected by a fire. The inspectors determined the finding had a cross-cutting aspect of change management in the human performance area, because licensee staff failed to maintain functionality of the Unit 2 pyro panel before a design change could be implemented. |
| Site: | Farley |
|---|---|
| Report | IR 05000364/2014002 Section 1R19 |
| Date counted | Mar 31, 2014 (2014Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71111.19 |
| Inspectors (proximate) | S Sandal A Alen A Vargas B Collins F Ehrhardt J Sowa P Niebaum |
| Violation of: | Technical Specification - Procedures Technical Specification |
| CCA | H.3, Change Management |
| INPO aspect | LA.5 |
| ' | |
Finding - Farley - IR 05000364/2014002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Farley) @ 2014Q1
Self-Identified List (Farley)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||