Finding | |
---|---|
Title | Untimely Identification and Corrective Actions for a Condition Adverse to Quality related to 480 VAC Masterpact Breakers |
Description | A self-revealing Green NCV of Title 10 of the Code of Federal Regulations (10 CFR) Part 50, Appendix B, Criterion XVI, Corrective Actions, was identified because PSEG failed to assure that a condition adverse to quality (CAQ) was promptly identified and corrected. Specifically, PSEG did not initiate a timely notification for a potential design flaw in the operation of some 480 volt alternating current (VAC) Masterpact breakers control logic scheme. PSEGs corrective actions included an extensive operability evaluation, compensatory measures conducted every shift by operators to ensure the operability and reliability of these breakers in the short-term, and a proposed design change to remove the design flaw in the breaker control logic by 2015. The performance deficiency was determined to be more than minor because it was associated with the equipment performance and design control attributes of the Mitigating Systems cornerstone, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). The inspectors determined that this finding was of very low safety significance (Green) using NRC IMC 0609, Appendix A, The Significance Determination Process (SDP) for Findings At-Power, Exhibit 2 Mitigating Systems Screening Questions, dated June 19, 2012, because although the breakers design is affected, the operability of the breakers is maintained. The inspectors determined that the contributing cause that provided the most insight into the performance deficiency was associated with the cross-cutting aspect of Problem Identification and Resolution, Identification, because PSEG failed to identify issues completely, accurately, and in a timely manner in accordance with the corrective action program (CAP). |
Site: | Hope Creek ![]() |
---|---|
Report | IR 05000354/2014002 Section 1R15 |
Date counted | Mar 31, 2014 (2014Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | B Reyes E Burket H Nieh J Hawkins M Orr S Ibarrola |
Violation of: | 10 CFR 50 Appendix B Criterion XVI |
CCA | P.1, Identification |
INPO aspect | PI.1 |
' | |