Finding | |
---|---|
Title | Failure to maintain safety-related cables in a non-submerged environment |
Description | An NRC-identified Green NCV of 10 CFR 50, Appendix B, Criterion III, Design Control, was identified for the licensees failure to implement measures to assure that safety-related cables remained in an environment for which they were certified. Safetyrelated cables purchased and installed in underground electrical pull boxes at Farley Nuclear Plant have been subjected to submergence, a condition for which they are not designed. To address this issue, the licensee has performed the immediate corrective action of increasing the frequency of measuring water level in the pull boxes and removing excess water to ensure cables are not submerged. The licensee entered the issue into their corrective action program as CR 2010100512. Failure to maintain safety-related electrical cables in a physical environment for which the cables are designed to operate is a performance deficiency. This performance deficiency is more than minor because it is associated with the Design Control attribute of the Mitigating Events cornerstone, and adversely affected the cornerstone objective to ensure the reliability of systems responding to initiating events to prevent undesirable consequences. Specifically; because 1) testing of these cables has not been performed, 2) the cables have not been maintained within the parameters they are designed, and 3) there have been documented failures of cables throughout the nuclear industry due to degradation caused by submergence in water. The significance of this finding was screened using the Phase 1 of the SDP in accordance with NRC Inspection Manual Chapter 0609 Attachment 4. The finding screened as Green, because the finding is a design or qualification deficiency confirmed not to result in loss of operability or functionality. The inspectors determined the inadequate assessment of available information in the CAP caused the licensee to fail to aggregate the programmatic and common cause problems reflective of cross-cutting aspect P.1(b). |
Site: | Farley |
---|---|
Report | IR 05000348/2010003 Section 4OA2 |
Date counted | Jun 30, 2010 (2010Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | E Crowe S Shaeffer A Nielsen T Morrissey S Rose R Berryman S Sandal M Coursey J Sowa C Dykes |
CCA | P.4, Trending |
INPO aspect | PI.4 |
' | |
Finding - Farley - IR 05000348/2010003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Farley) @ 2010Q2
Self-Identified List (Farley)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||