05000341/FIN-2013008-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Battery Rack Configuration Not in Accordance with Design Basis |
Description | The inspectors identified a finding of very low safety significance and associated Non-Cited Violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the failure to assure the battery rack end rail configuration for battery 2P-29 was in accordance with the design basis Seismic Category I qualification. Specifically, the licensee failed to install battery 2P-29 with the battery rack end rails within 1/8 inch from the battery. The inspectors found one end rail gap for battery 2P-29 greater than 1/8 inch and up to approximately 1/4 inch. The licensee entered this concern into its corrective action program, provided reasonable assurance the installed oversized battery rack end rail gap did not result in a loss of battery 2P-29 battery rack system functionality, completed corrective actions to install a battery rack end rail shim and readjust the battery rack end rail gap within 1/8 inch
The performance deficiency was determined to be more than minor because it was associated with the Mitigating Systems cornerstone attribute of design control and affected the cornerstone objective of ensuring the capability and reliability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as very low safety significance (Green), because the finding was a design deficiency that did not result in a loss of battery functionality. The inspectors did not identify a cross-cutting aspect associated with this finding, because the finding was not representative of current performance. |
Site: | Fermi ![]() |
---|---|
Report | IR 05000341/2013008 Section 1R21 |
Date counted | Sep 30, 2013 (2013Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | M Jones P Wagner R Petitti B Jose C Brown B Palagi J Neurauter S Spiegelman |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
INPO aspect | |
' | |