05000333/LER-2013-006, Regarding Loss of HPCI Safety Function Due to Failure of B CST Level Switches
| ML14045A286 | |
| Person / Time | |
|---|---|
| Site: | FitzPatrick (DPR-059) |
| Issue date: | 02/18/2014 |
| From: | Coyle L Entergy Nuclear Northeast, Entergy Nuclear Operations |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| JAFP-14-0019 LER 13-006-00 | |
| Download: ML14045A286 (7) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(ix)(A) 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 3332013006R00 - NRC Website | |
text
Entergy JAFP-1 4-0019 February 18, 2014 United States Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001 Entergy Nuclear Northeast Entergy Nuclear Operations, Inc.
James A. Fitzpatrick NPP P.O. Box 110 Lycoming, NY 13093 Tel 315-349-6024 Fax 315-349-6480 Lawrence M. Coyle Site Vice President JAF
Subject:
Dear Sir or Madam:
LER: 201 3-006, Loss of HPCI Safety Function Due to Failure of B CST Level Switches James A. FitzPatrick Nuclear Power Plant Docket No. 50-333 License No. DPR-59 This report is submitted in accordance with 10 CFR 50.73(a)(2)(v)(D), An Event or Condition that Could Have Prevented Fulfillment of a Safety Function.
There are no commitments contained in this report.
Questions concerning this report may be addressed to Mr. Chris M. Adner, Regulatory Assurance Manager, at (315) 349-6766.
LMC/CMA/ds I
Enclosure(s): JAF LER 2013-006, Loss of HPCI Safety Function Due to Failure of B CST Level Switches cc:
USNRC, Region 1 USNRC, Project Directorate USNRC, Resident Inspector INPO Records Center (ICES)
Sincerel
.~ M. Coyle ite Vice President
NRC FORM 366 (01-2014)
NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION (01-2014)
LICENSEE EVENT REPORT (LER)
(See Page 2 for required number of digits/characters for each block)
APPROVED BY OMB: NO. 3150-0104 EXPIRES: 01/31/2017 Estimated burden per response to comply with this mandatory collection request: 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />.
Reported lessons learned are incorporated into the licensing process and fed back to industry.
Send comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by internet e-mail to Infocollects.Resource@nrc.gov, and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202, (3150-0104), Office of Management and Budget, Washington, DC 20503. If a means used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
- 1. FACILITY NAME James A. FitzPatrick Nuclear Power Plant
- 2. DOCKET NUMBER 05000333
- 3. PAGE 1 OF 6
- 5. EVENT DATE
- 6. LER NUMBER
- 7. REPORT DATE
- 8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL NUMBER REV NO.
MONTH DAY YEAR FACILITY NAME N/A DOCKET NUMBER N/A 12 17 2013 2013 - 006 00 02 18 2014 FACILITY NAME N/A DOCKET NUMBER N/A
- 9. OPERATING MODE
- 11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply) 1
20.2201(b)
20.2203(a)(3)(i)
50.73(a)(2)(i)(C)
50.73(a)(2)(vii)
20.2201(d)
20.2203(a)(3)(ii)
50.73(a)(2)(ii)(A)
50.73(a)(2)(viii)(A)
20.2203(a)(1)
20.2203(a)(4)
50.73(a)(2)(ii)(B)
50.73(a)(2)(viii)(B)
20.2203(a)(2)(i)
50.36(c)(1)(i)(A)
50.73(a)(2)(iii)
50.73(a)(2)(ix)(A)
- 10. POWER LEVEL
20.2203(a)(2)(ii)
50.36(c)(1)(ii)(A)
50.73(a)(2)(iv)(A)
50.73(a)(2)(x) 100
20.2203(a)(2)(iii)
50.36(c)(2)
50.73(a)(2)(v)(A)
73.71(a)(4)
20.2203(a)(2)(iv)
50.46(a)(3)(ii)
50.73(a)(2)(v)(B)
73.71(a)(5)
20.2203(a)(2)(v)
50.73(a)(2)(i)(A)
50.73(a)(2)(v)(C)
OTHER
20.2203(a)(2)(vi)
50.73(a)(2)(i)(B) 9 50.73(a)(2)(v)(D)
Specify in Abstract below or in
BACKGROUND The High Pressure Coolant Injection (HPCI) System [EIIS Identifier: BJ] at James A. FitzPatrick (JAF) is a part of the Emergency Core Cooling System (ECCS); HPCI provides and maintains an adequate coolant inventory inside the Reactor Pressure Vessel [RPV] to prevent damage to the reactor core under postulated accident scenarios. The system is comprised of various components which include pumps, valves, piping, and instrumentation. The HPCI System may be initiated by automatic or manual means, although manual initiation requires manipulation of individual pump and valve control switches. Automatic initiation occurs for conditions of Reactor Vessel Water Level - Low Low or Drywell Pressure - High.
The HPCI System monitors the levels in the Condensate Storage Tanks (CST) [TK] and suppression pool [BT], because these are the two sources of water for HPCI operation. Reactor grade water in the CSTs is the normal source. The CST suction source consists of two CSTs connected in parallel to the HPCI pump suction.
Upon receipt of a HPCI initiation signal, the CST suction valve is automatically signaled to open (it is normally in the open position) unless both suppression suction valves are open. If the water level in both CSTs falls below the pre-selected level defined in the TS, first the suppression pool suction valves automatically open, and then the CST suction valves automatically close. This action completes the automatic suction source alignment function.
Two level switches [LS] are used to detect low water level in each CST, and initiate the automatic suction source alignment function. The level switches are arranged in a one-out-of-two taken twice logic. The actuation of two switches (one on each opposing A and B CST) can cause the suppression pool suction valves to open and the CST suction valve to close. The four channels of low CST level function are required to be Operable when HPCI is required to be Operable in order to ensure that no single instrument failure can preclude HPCI automatic suction source alignment to suppression pool. The two B CST level switches are 23LS-74B and 23LS-75B.
Preceding events ISP-75 was performed successfully for all four HPCI CST level switches on September 30, 2013.
EVENT DESCRIPTION
I&C commenced ISP-75, HPCI CST Low Water Level Switch Functional Test/Calibration, at 0810 EST on the morning of December 17th, 2013, with the plant at 100 percent power. This test is designed to functionally test and calibrate the CST Low Water Level instrument channels of the HPCI System. All channels of the HPCI automatic suction source alignment logic are tested during this surveillance. The HPCI level switches on the A CST were tested first, and performed satisfactorily.
At 0938 on December 17th, the Chief Instrumentation and Controls (I&C) technician performing ISP-75 reported failure of level switch 23LS-74B to the Control Room Supervisor. The I&C Supervisor responsible for the testing was also informed of the failure and documented the deficiency via Condition Report (CR) CR-JAF-2013-06304 at 0852 EST. The Shift Manager (SM) and I&C Supervisor discussed the equipment failure andU.S. NUCLEAR REGULATORY COMMISSION (01-2014)
LICENSEE EVENT REPORT (LER)
CONTINUATION SHEET
- 1. FACILITY NAME
- 2. DOCKET
- 6. LER NUMBER
- 3. PAGE James A. FitzPatrick Nuclear Power Plant 05000333 YEAR SEQUENTIAL NUMBER REV N0.
3 OF 6 2013 -
006 00the SM determined that the switch was Inoperable per TS. The SM then directed the Control Room Supervisor (CRS) to initiate an emergent active LCO and develop a status control tagout equipment failure. The Chief I&C technician was directed to continue testing per ISP-75. As-Left testing was performed on 23LS-74B with satisfactory results.
Subsequent testing determined that the 23LS-75B level switch actuated below the required simulated CST level. Actuation of this level switch occurred at a simulated CST level of 58.5 inches vice the required level per ISP-75 of between 59.95 and 61.05 inches. The actuation of the second level switch below the Technical Specification (TS) allowable value was communicated to the CRS and I&C Supervisor at 1025 EST and documented (via CR-JAF-2013-06306) at 1019 EST. Calibration of 23LS-75B was performed and As-Left functional testing was conducted with satisfactory results.
EVENT ANALYSIS
High Pressure Coolant Injection Operability The prerequisites to ISP-75 require the Shift Manager to review TS Table 3.3.5.1-1, Emergency Core Cooling System Instrumentation (specifically Function 3d), and ensure that one of the following actions have been taken:
- 2. Declared the HPCI System Inoperable The HPCI System was declared Inoperable at 0810 EST for performance of ISP-75. The failure of 23LS-74B was reported to the control room supervisor at 0938 EST. The actuation of 23LS-75B at below the TS allowable value was reported to the Control Room Supervisor at 1025 EST.
TS Limiting Condition of Operation (LCO) 3.3.5.1 Condition D, requires the HPCI System to be declared Inoperable within one hour of discovery of loss of automatic suction source alignment capability. The combination of these two deficiencies would have potentially prevented the HPCI automatic suction source alignment function until the CST B level dropped to 58.5 inches. This level is less than the Technical Specification allowable value of >/= 59.5 inches CST water level. This would have resulted in the HPCI System being declared Inoperable (per TS), and represents a loss of safety function for the single-train HPCI System. The JAF SM notified the NRC via the Emergency Notification System (ENS 49660) pursuant to 10 CFR 50.72(b)(3)(v)(D).
CAUSE OF EVENT
The direct mechanistic cause of the failure of 23LS-74B, as determined by a causal analysis, was binding in the float chamber caused by the presence of corrosion products. Further consideration of this mechanistic cause led to the determination that this failure was due to inadequate preventative maintenance resulting in the degradation of 23LS-74B. Improvements in future preventative maintenance are applicable to all Magetrol Model 291MPG-S1MD4DC level switches of common construction (carbon steel float chambers).
The direct mechanistic cause for the actuation of 23LS-75B at less than the TS allowable set point has not been determined. A follow-up action exists for the removal, disassembly, and inspection of 23LS-75B, and is scheduled for March of 2014.U.S. NUCLEAR REGULATORY COMMISSION (01-2014)
LICENSEE EVENT REPORT (LER)
CONTINUATION SHEET
- 1. FACILITY NAME
- 2. DOCKET
- 6. LER NUMBER
- 3. PAGE James A. FitzPatrick Nuclear Power Plant 05000333 YEAR SEQUENTIAL NUMBER REV N0.
4 OF 6 2013 -
006 00EXTENT OF CONDITION The extent of condition discussed herein only considers the failure mode(s) associated with 23LS-74B, because (as stated above) the disassembly and inspection of 23LS-75B is not complete.
The extent of condition for this event extends to the remaining HPCI CST level switches (associated with the A CST), as well as the Reactor Core Isolation Cooling (RCIC) [BN] CST level switches as they are connected to the same tanks (CST). The RCIC level switches are similar in design and function; however, the float chambers are constructed of stainless steel.
A Condition Report has been written to determine the existence of other level switches at JAF of similar design, and their susceptibility to this failure mode.
HPCI System:
The condition was discovered on 23LS-74B which makes the other HPCI CST level switches susceptible to this failure mode. The other HPCI level switches are of the same manufacturer and provide a redundant function for the HPCI suction transfer logic. Previous RCIC CST switch failures were due to microswitch plunger corrosion preventing switch actuation. As part of the extent of condition on the previous RCIC failures, the HPCI level switch microswitches were inspected for corrosion. The inspections were satisfactory with no microswitch deficiencies noted. In addition, the HPCI topworks unit is sealed with cap o-ring and conduit seal, which RCIC does not have. Since the remaining HPCI switches are similar (construction and function) there is a reasonable likelihood that they may exhibit a common failure mode.
RCIC System:
The RCIC CST level switches are susceptible to this failure mode due to the similar design and function. The HPCI level switch float chamber is constructed of carbon steel with a stainless steel float. RCIC level switches are constructed with a stainless steel float chamber and float. No evidence of corrosion products were found during a previous inspection of the float chamber internals associated with the B CST RCIC level switch 13LS-76B. These results coupled with the corrosion resistant material makeup of the RCIC level switches provides reasonable assurance that there is a low risk of this condition being present in the CST level switches associated with the RCIC System. No additional corrective actions associated with this extent of condition are planned for the RCIC level switches.
FAILED COMPONENT IDENTIFICATION:
Manufacturer:
Magnetrol Manufacturer Model Number:
291MPG-S1MD4DC NPRDS Manufacturer Code:
M040 NPRDS Component Code:
LS FitzPatrick Component ID:
CORRECTIVE ACTIONS
Completed Actions x
Replaced 23LS-74B on January 10, 2014 x
Performed a CST water sample to determine the suspended solids level and/or presence of foreign materials on January 26, 2014 x
Increased ISP-75 performance frequency from an approximate ninety day periodicity to an approximate forty-five day periodicity.U.S. NUCLEAR REGULATORY COMMISSION (01-2014)
LICENSEE EVENT REPORT (LER)
CONTINUATION SHEET
- 1. FACILITY NAME
- 2. DOCKET
- 6. LER NUMBER
- 3. PAGE James A. FitzPatrick Nuclear Power Plant 05000333 YEAR SEQUENTIAL NUMBER REV N0.
5 OF 6 2013 -
006 00Future Actions x
Perform an Extent of Condition review to identify level switches at JAF of similar design, and their susceptibility to this failure mode.
x Perform disassembly, inspection, and replacement of the remaining HPCI level switches identified in the Extent of Condition review.
x Perform sample of any corrosion products and foreign material found in the remaining HPCI CST level switches to determine composition.
x Develop and implement replacement Preventative Maintenance (PM) for the HPCI level switches.
SAFETY SIGNIFICANCE
Nuclear Safety Actual Consequences There were no actual nuclear safety consequences during this period as a result of this event.
Potential Consequences - Delayed Shifting of the HPCI Suction from the CST to the Suppression Pool The aggregate effect of the combined deficiencies is a loss of redundancy in the opening circuit for the HPCI suppression pool suction valves due to failure of 23LS-74B to actuate along with a delay in the time at which the suction transfer would have been initiated as a result of the lower actuation point for 23LS-75B.
The safety significance of delayed shifting of the HPCI suction from the CST to the suppression pool is a higher potential for air entrainment in the HPCI suction flow due to lower tank level at completion of the suction source transfer. An engineering evaluation determined that the minimum CST level for initiation of automatic suction source transfer to preclude air entrainment in the HPCI suction is 34.14 inches. Actuation of 23LS-75B during the December 17, 2013 performance of ISP-75 occurred at 58.5 inches, which is well above this lower limit. Therefore, the risk associated with the HPCI automatic suction source transfer occurring at the As Found level is minimal.
Potential Consequences - Probabilistic Risk Assessment Implications Equipment Out of Service (EOOS) Probabilistic Risk Assessment (PRA) was used to analyze the failure of 23LS-74B, and the subsequent loss of HPCI automatic suction source alignment (failure of 23LS-75B to actuate at the TS allowable value of >/= 59.5 inches). The loss of HPCI automatic suction source alignment does not result in an increase in core damage frequency. The JAF EOOS PRA model does not account for the HPCI automatic suction source alignment function; instead, the model assumes that the HPCI System takes suction from the CSTs for the entire twenty-four hour mission time. The twenty-four hour HPCI mission time is based on the ASME PRA standard. Thus the loss of automatic suction source alignment does not result in an increase in core damage frequency.
Radiological Safety There was no radiological safety impact. No release, exposure, or increase in potential risk thereof was consequence of this condition.
Industrial Safety There was no industrial safety impact, as this condition was associated with HPCI CST level switch
component failures
U.S. NUCLEAR REGULATORY COMMISSION (01-2014)
LICENSEE EVENT REPORT (LER)
CONTINUATION SHEET
- 1. FACILITY NAME
- 2. DOCKET
- 6. LER NUMBER
- 3. PAGE James A. FitzPatrick Nuclear Power Plant 05000333 YEAR SEQUENTIAL NUMBER REV N0.
6 OF 6 2013 -
006
00SIMILAR EVENTS
No similar events associated with the HPCI System were identified.
The following Condition Reports (CR) document similar events associated with the RCIC Low Level CST automatic suction source alignment function.
RCIC Level Switches Fail to Trip on Low CST Level Condition Report
Cause
Applicability CR-JAF-2013-00061 Intermittent failure due to water intrusion Not applicable; The HPCI switches used at JAF have a sealed conduit entrance and a cap and o-ring.
CR-JAF-2013-04311 CR-JAF-2013-04312 Corrosion of the microswitch contacts due to water intrusion Not applicable; water intrusion and corrosion is not an issue based on EOC inspections on the HPCI switches.
CR-JAF-2013-05576 Maladjustment during installation due to lack of vendor manual instructions Not applicable; The HPCI level switch mechanisms are a different design and have not underwent adjustments to the actuator plate or microswitch position.
Although the internal operating experience (OE) tabulated above establishes a similarity in potential impact (defeating the automatic suction source transfer function), the causal evaluations did not identify a similar failure mode associated with binding due to corrosion in the float chamber.
REFERENCES x
Condition Report: CR-JAF-2013-06304 Equipment Apparent Cause Evaluation x
Condition Report: CR-JAF-2013-06344 x
Condition Report: CR-JAF-2013-06306 Failure of 23LS-75B to Actuate at the TS Allowable Value x
Technical Specifications and Bases, 3.3.5.1, Emergency Core Cooling System (ECCS)
Instrumentation x
Technical Specifications and Bases, 3.5.1, Emergency Core Cooling Systems (ECCS) and Reactor Core Isolation Cooling (RCIC) System x
ISP-75, HPCI CST Low Water Level Switch Functional Test / Calibration