Finding | |
|---|---|
| Title | Failure to Install Safety-Related Components that are Designed to Withstand the Effects of a Design Basis Tornado |
| Description | The NRC identified a non-cited violation of Title 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the licensees failure to install emergency diesel generator components that could withstand the effects of a design basis tornado as required by Section 3.1.2 of the Update Final Safety Analysis Report (UFSAR). The licensee entered the issue into the corrective action program and implemented compensatory measures to protect the affected components. This performance deficiency was determined to be more than minor because it was associated with the Design Control attribute of the Mitigating Systems cornerstone and adversely affects the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the capability of the equipment to withstand the effects of a tornado was not ensured. The team determined the finding to be of very low safety significance (Green) because of the low frequency of tornados/high winds and the potential for recovery by the operators on site. This finding was not assigned a crosscutting aspect because the issue did not reflect present licensee performance. |
| Site: | Sequoyah |
|---|---|
| Report | IR 05000327/2016007 Section 1R21 |
| Date counted | Jun 30, 2016 (2016Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | B Bishop G Ottenberg J Bartley M Riley M Yeminy O Mazzoni R Patterson |
| Violation of: | 10 CFR 50 Appendix B 10 CFR 50 Appendix B Criterion III, Design Control |
| INPO aspect | |
| ' | |
Finding - Sequoyah - IR 05000327/2016007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Sequoyah) @ 2016Q2
Self-Identified List (Sequoyah)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||