05000327/FIN-2015007-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to maintain control of and update safety related design out documents (electrical calculations |
| Description | The inspectors identified a Green non-cited violation (NCV) of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the licensees failure to control safety related calculations that reviewed equipment essential to the function of Class 1E electrical systems. The issue was entered into the licensees corrective action program as CRs 1059281 and 1064042. Planned corrective actions were to revise the calculations. The inspectors determined that the performance deficiency was determined to be more than minor because it was associated with the Design Control attribute of the Mitigating Systems Cornerstone. The failure to plan and control updates to safety related calculations to review the suitability of new molded case circuit breakers in Class 1E electrical systems adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of the systems that respond to initiating events to prevent undesirable consequences. The finding was determined to have a cross-cutting aspect in the resolution area of Problem Identification and Resolution [P.3], because the licensee failed to take effective corrective actions to address issues in a timely manner commensurate with their safety significance. |
| Site: | Sequoyah |
|---|---|
| Report | IR 05000327/2015007 Section 1R17 |
| Date counted | Sep 30, 2015 (2015Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.17 |
| Inspectors (proximate) | D Terry-Ward J Bartley P Carman R Bennett T Fanelli |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
| CCA | P.3, Resolution |
| INPO aspect | PI.3 |
| ' | |