05000321/LER-2012-003, Regarding Leak in Reactor Pressure Boundary at Small Bore Piping Fillet Weld

From kanterella
(Redirected from 05000321/LER-2012-003)
Jump to navigation Jump to search
Regarding Leak in Reactor Pressure Boundary at Small Bore Piping Fillet Weld
ML12135A392
Person / Time
Site: Hatch 
Issue date: 05/10/2012
From: Madison D
Southern Nuclear Operating Co
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
NL-12-0944 LER 12-003-00
Download: ML12135A392 (8)


LER-2012-003, Regarding Leak in Reactor Pressure Boundary at Small Bore Piping Fillet Weld
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(6)

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3212012003R00 - NRC Website

text

Dennis R. Madison SCl uthern Nuclear Vice President Hutch Operating Company, Inc.

Plalll Edwin I Hatch

. I02H Hil l1:h Parkway Nort I Sa., ry. G(!of~i d 3151 3 Tel ~12 531 rJ859 FiI.~ 9' 2 36(; 2077 SOUTHER May 10, 2012 COMPANY Docket Nos. : 50-321 NL-12-0944 U. S. Nuclear Regulatory Commission ATIN: Document Control Desk Washington, D. C. 20555-0001 Edwin I. Hatch Nuclear Plant Licensee Event Report 2012-003-0 Leak in Reactor Pressure Boundary at Small Bore Piping Fillet Weld Ladies and Gentlemen:

In accordance with the requirements of 1 OCFR50. 73(a)(2)(i)(8), Southern Nuclear Operating Company hereby submits the enclosed Licensee Event Report concerning an event of non-compliance with Technical Specification 3.4.4 for Reactor Coo/ant System operational leakage from a through-wall crack in a small bore piping fillet weld.

This letter contains no NRC commitments. If you have any questions, please contact Mr. B. D. McKinney at (205) 992-5982.

Respectfully submitted, D. R. Madison Vice President - Hatch DRMIWEBI Enclosure: LER 1-2012-003, Revision 0 cc:

Southern Nuclear Operating Company Mr. S. E. Kuczynski, Chairman, President & CEO Mr. D. G. 80st, Executive Vice President & Chief Nuclear OHicer Mr. B. L. Ivey, Vice President - Regulatory AHairs Mr. B. J. Adams, Vice President - Fleet Operations Mr. M. J. Ajluni, Nuclear Licensing Director RTYPE: CHA02.004

U. S. Nuclear Regulatory Commission NL-12-0944 Page 2 U. S. Nuclear Regulatory Commission Mr. V. M. McCree, Regional Administrator Mr. P. G. Boyle, NRR Senior Project Manager - Hatch Mr. E. D. Morris, Senior Resident Inspector - Hatch

Enclosure NL-12-0944 Edwin I. Hatch Nuclear Plant - Unit 1 Licensee Event Report 2012-003-0 Leak In Reactor Pressure Boundary at Small Bore Piping Fillet Weld

[NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150*0104 EXPIRES: 10/31/2013

. 9-20(7)

Eslimaled burden per response 10 comply wilh Ihis mandalOry collecllon request 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />. Reported lessons learned are incorporaled inlo !he licensing process and fed back 10 indUSlry. Send commenlS re~ardi"3 burden eslimale 10 lhe Records and FOIAIPrivacy Service Branch ( *5 F 3). U.S.

LICENSEE EVENT REPORT (LER)

Nuclear Re~ulBlory Commission. WBshinglon. DC 20555*0001, or by inlernel e*mail 10 in ocollects.resources@nrc.gov. and 10 Ihe Desk Officer. Office 01 Informallon and R~UIBIOry Affairs. NEOB*I0202. (3150-0104). Office of ManB~emenl and Bu Hel. Washinglon. DC 20503. If a means used 10 impose an in ormallon co1lec Ion does nol dispfay a curranlly valid OMB oonlrol number. Ihe NRC may nol conducl or sponsor. and a person Is nol required 10 resoond 10. Ihe informallon collecllon.

Edwin I. Hatch Nuclear Plant Unit 1 05000321 1 OF 5

4. TITLE Leak in Reactor Pressure Boundary at Small Bore Piping Fillet Weld
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED FACILITY NAME DOCKET NUMBER SEQUENTIAL REV MONTH DAY YEAR YEAR MONTH DAY YEAR NUMBER NO.

05000 FACILITY NAME DOCKET NUMBER 03 13 2012 2012 - 003 -

00 05 10 2012 05000

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR§: (Check all that apply) o 20.2201 (b) o 20.2203(a)(3)(i) o 5O.73(a)(2)(i)(C) o 50.73(a)(2)(vii) 4 o 20.2201 (d) o 20.2203(a)(3)(ii) o 50.73(a)(2)(li)(A) o 50.73(a)(2)(viii)(A) o 20. 2203(a)(1 )

o 20.2203(a)(4) o 50.73(a)(2)(Ii)(B) o 50.73(a)(2)(viii)(B) o 20.2203(a)(2)(i) o 5O.36(c)(1 )(i)(A) o 50.73(a)(2)(iii) o 50.73(a)(2)(ix)(A)

10. POWER LEVEL o 20.2203(a)(2)(ii) o 50.36(c)(1 )(ii)(A) o 50.73(a)(2)(lv)(A) o 5O.73(a)(2)(x) o 20. 2203(a)(2)(iii) o 50.36(c)(2) o 50.73(a)(2)(v)(A) o 73.71(a)(4) o 20. 2203(a)(2)(iv) o 50.46(a)(3)(ii) o 5O.73(a)(2)(v)(B) o 73.71(a)(5) 0 o 20. 2203(a)(2)(v) o 50.73(a)(2)(i)(A) o 50.73(a)(2)(v)(C) o OTHER o 20. 2203(a)(2)(vi)

~ 50.73(a)(2)(i)(6) o 50.73(a)(2)(v)(D)

Specify In Abslracl below or in NRC Form 366A

12. LICENSEE CONTACT FOR THIS LER ACIUTYNAME I~ELEPHONE NUMBER (Indude Area Code)

Edwin I. Hatch 1Steven Tipps - Lead Engineer - Licensing 912-537 -5880

13. COMPLETE ONE UNE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT MANU*

REPORTABLE MANU*

REPORTABLE

CAUSE

SYSTEM COMPONENT

CAUSE

SYSTEM COMPONENT FACTURER TO EPIX FACTURER TO EPIX B

SB PSF NIA Y

14. SUPPLEMENTAL REPORT EXPECTED
15. EXPECTED MONTH DAY YEAR SUBMISSION 181 YES (If yes, complete 15. EXPECTED SUBMISSION DATE)

ONO DATE 12 01 2012 ABSTRACT (Limit to 1400 spaces, i.e., approximately 15 single-spaced typewritten lines)

On 3/13/2012, during the Reactor Pressure Vessel (RPV) Pressure Test walk-down with the unit in Mode 4 for leakage testing, a through-wall leak was identified in a small bore line located upstream of a High Pressure Coolant Injection (HPCI) valve inboard of the piping's connection to the Main Steam piping. The leak identified during this event was in the thicker portion of the fillet weld adjacent to the socket elbow. Initial evaluation of the crack in the subject HPCI piping and elbow by an experienced site Quality Control inspector and a senior Southern Nuclear metallurgist concluded that the most apparent cause of the weld defect that led to the leak was inadequate root penetration in the weld. The actual cause has not yet been fully determined. The section of piping in which the leak was located will be sent to a vendor for inspection and expert determination of the most probable cause of the through-wall leak. Following removal and repair of the subject piping, a leak test was performed at 920 psig with no leaks identified. The Technical Specification (TS) definition of pressure boundary leakage is leakage through a non-isolable fault in the reactor coolant system: By its location, the leak met this definition. Inspection of the weld and adjacent areas determined the leak had existed when the Unit was in Mode 1, and no such leakage is allowed by TS.

NRC FORM 366 (9-2007)

PRINTEO ON RECYCLEO PAPER

PLANT AND SYSTEM IDENTIFICATION

General Electric - Boiling Water Reactor Energy Industry Identification System codes appear in the text as (EllS Code XX).

DESCRIPTION OF EVENT

On 3113/2012, with the unit in Mode 4 for conducting a Reactor Pressure Vessel (RPV)

Pressure Test inspection following refueling, a through-wall leak was identified in a small bore line (specifically in a JA inch elbow) located inboard of the HPCI 1 E41-F002 valve prior to the point at which the line connects to the Main Steam Line "B" piping (EllS Code SB).

The physical discoloration of the pipe and surrounding insulation surrounding the leak appear to support the judgment that the leak had existed for some period of time during the previous cycle. Initial evaluation of the crack in the subject HPCI piping and elbow concluded that the most apparent cause of the weld defect that led to the leak was inadequate root penetration in the weld that over time likely propagated through the wall of the pipe. The actual cause has not yet been fully determined.

Following removal and repair of the subject piping, a leak test was performed at 920 psig with no leaks identified.

CAUSE OF EVENT

The leak identified during this event was in the thicker portion of the fillet weld adjacent to the socket elbow. The subject weld was an original construction Class 1 Tungsten Inert Gas (TIG) weld that was inspected both visually and by Penetration Test (PT) at the time the weld was performed. Initial evaluation of the crack in the subject HPCI piping and elbow by a Southern Nuclear (SNC) Metallurgist Principal Engineer (PE) and a person from Quality Control (QC), each with over thirty years of experience with weld processes and inspections, concluded that the most apparent cause of the weld defect that led to the leak was inadequate root penetration in the weld. This conclusion was reached based on the characteristics of the failed weld after consideration of High Cycle Fatigue (HCF),

Intergranular Stress Corrosion Cracking (ICSCC), possible imposed stress from work conducted in the course of the subject outage, improper weld fusion, original weld defect caused by slag or porosity at the root, or inadequate root penetration.

At the time of the performance of the subject weld some years ago, it was permissible to use a welding rod with a diameter of 1/8 inch in such welds, and this practice may have contributed to the suspected inadequate root penetration. Applicable welding procedures were revised in 2008 to specify that the root pass of all socket welds be performed using filler material with a maximum diameter of 3/32 of an inch to provide proper root penetration.

A subsurface or root defect resulting from inadequate root penetration most likely propagated over time through the wall, and eventually caused the leak. The actual cause of the weld failure that led to the observed leak has not yet been fully determined. The section of piping in which the leak was located will be sent to an appropriate vendor (Altran) for inspection and expert determination of the most probable cause of the through-wall leak.

When that evaluation of the apparent cause has been completed, this report will be revised to disclose the final results of the analYSis.

NRC FORM J66A (10-2010) LICENSEE EVENT REPORT (LER) u.s. NUCLEAR REGULATORY COMMISSION (10-2010' I

CONTINUA~ION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE Edwin I. Hatch Nuclear Plant Unit 1 05000321 YEAR I SEQUENTIAL NUMBER

[ REVISION NUMBER 3

OF 5

2012 003 00 REPORTABILITY ANALYSIS AND SAFETY ASSESSMENT Assessment Information:

This report is required per 10 CFR 50.73(a)(2)(i)(B) because a condition existed which was prohibited by the plant's Technical Specification (TS). The TS definition of pressure boundary leakage is "LEAKAGE through a non-isolable fault in a Reactor Coolant System (RCS) component body, pipe wall, or vessel wall." Due to its location, this leak met this definition. Based on inspection of the weld and adjacent areas, it was determined the leak had existed when the Unit was in Mode 1, and no such leakage is allowed by TS. Therefore, this event comprises an operation or condition which was prohibited by LCO 3.4.4.a and is thus reportable under the requirements of 10CFRSO.73(a)(2)(i)(B).

The reactor coolant system (RCS) includes systems and components that contain or transport the coolant to and from the reactor core. The pressure retaining components of the RCS and the portions of connecting systems out to and including the isolation valves define the reactor coolant pressure boundary. During plant life, the joint and valve interlaces can produce varying amounts of reactor coolant leakage through either normal operational wear or mechanical deterioration. Umits on RCS operational leakage are required to ensure appropriate action is taken before the integrity of the reactor coolant pressure boundary is compromised. The TS delineate the limits on the specific types of leakage. The unidentified leakage flow limit allows time for corrective action to be taken before the reactor coolant pressure boundary can be compromised significantly. The five gallons per minute (gpm) limit is a small fraction of the calculated flow from a critical crack in the primary system piping. A critical crack is one large enough to propagate rapidly, ultimately leading to failure of the affected component. As discussed in the FSAR, crack behavior from experimental programs shows that leakage rates of over a hundred gallons per minute will precede crack instability.

In this event, a small leak was identified and investigated as a result of a RPV Pressure Test walk-down. This leak was determined to meet the TS definition of pressure boundary leakage due to its location in a portion of the RCS piping which could not be isolated from the reactor coolant pressure boundary. At the time it was discovered and corrective action taken, the leak was not unstable and would not have resulted in catastrophic failure of the line. However, a worst-case instantaneous and complete severing of the line due to the presence of such a leak would not result in a significant loss of reactor coolant or present any challenge to core cooling. In addition, even if the inventory loss were completely water as compared to steam or a steam-water mix, the break would still be bounded by both the Loss of Coolant Accident analysis and the Feedwater Une break analysis. This hypothetical leak would be significantly less than the rated capacity of the High Pressure Coolant Injection, HPCI (EllS Code BJ) system, which is sized to provide adequate coolant make-up for pipe breaks up to four inches, and approximates the rated capacity of the Reactor Core Isolation Cooling, RCIC (EllS Code BN) system. Consequently, either system would have been capable of indefinitely maintaining normal reactor water level. Additionally, a leak of several hundred gallons per minute (gpm) would be adequately accommodated by the feedwater system (EllS Code SJ), which has a flow rate capacity margin at rated conditions of at least 10 percent. Therefore, anyone of three diverse and independent high pressure injection systems could have provided sufficient make-up flow to maintain water level well above the top of the active fuel. Based upon the preceding considerations, it is concluded that this event had no adverse impact on nuclear safety. This analysis is applicable to all operating conditions under which the subject leak might have propagated to line failure.

NRC FORM 368Ajlo-2010)

5 LICENSEE EVENT REPORT (LER) u.s. NUCLEAR REGULATORY COMMISSION (10-20101 CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE SEQUENTIAL I REVISION YEAR NUMBER NUMBER Edwin I. Hatch Nuclear Plant Unit 1 05000321 I

4 OF 2012 003 00

CORRECTIVE ACTIONS

Short-term corrective actions included removal and replacement of that portion of the piping which contained the leak, and the inspection of the repaired piping to assure that the leak had been properly corrected. Inspection of other potential leak sites had been performed as part of the Reactor Pressure Vessel Pressure Test walk-down during which the subject leak was identified.

Longer-term corrective actions include the determination of the most probable cause of the cracking and once the metallurgical evaluation of the piping/elbow has been performed by Altran, any necessary actions prompted by that evaluation will be considered. The apparent cause of the defective weld, performed many years ago, is likely due to the weld not having proper root penetration. Appropriate corrective actions were taken in the past (albeit after the welding of the subject piping) to ensure the Weld Process Control Procedure was revised to mitigate the probability of future small bore piping weld failures.

The extent of condition potentially includes the Class 1 small bore piping in the Unit 1 and Unit 2 drywells. The Class 1 drywell small bore piping is tested in accordance with the RPV Leak test performed during refueling outages. Therefore, any small bore piping leaks will be identified during these walkdowns. It should also be noted that dryweilleakage is monitored daily, and any significant leak would be identified by an increase in dryweilleakage.

ADDITIONAL INFORMATION

Other Systems Affected: None Commitment Information: This report does not create any new permanent licensing

commitments

Previous Similar Events

Non-isolable ASME Class-1 pressure boundary leaks were discovered during three previous refueling outages; one each in Unit 2 piping in years 2005 and 2007, and one in Unit 1 piping in 2008. All three leaks were identified during the RPV System Leakage Tests at the end of refueling outages. The three leaks occurred on non-isolable 1" stainless steel instrumentation piping associated with the main steam system. In each of these instances, the plant had to be returned to cold shutdown in order to perform the repairs. In each case, it was apparent that the leak, although small in magnitude, had existed for some period of time during the preceding run cycle. Upon completion of the failure analysis for the affected pipe elbow this section will be updated to determine if there were actually any identified previous similarities.

The piping leak discovered on Unit 2 in the Spring of 2005, occurred in the 1" stainless steel instrumentation piping associated with the 4" steam supply to the RCIC system. The failed component was shipped to a vendor (Altran) for failure analysis. High Cycle Fatigue (HCF) was determined to be the predominant failure mechanism. The failed piping section was replaced with the identical material and original weld geometry.

The second piping leak discovered on Unit 2 in the Spring of 2007, occurred in 1" stainless steel instrumentation piping associated with the main steam flow-measurement manifold, on NAC FORM 386A (10-2010)

5 NRC FORM 386A u.s. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT (LER)

(10.2010)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET I
6. LER NUMBER
3. PAGE YEAR I SEQUENTIAL IREVISION NUMBER NUMBER Edwin I. Hatch Nuclear Plant Unit 1 05000321 5

OF 2012 003 -

00 the downstream side of a condensing chamber. A root cause analysis was performed and the failed component was shipped to Altran for failure analysis. HCF was again determined to be the predominant failure mechanism. The failed piping section was replaced with the identical material.

During the Spring 2008 Unit 1 refueling outage, a piping leak was discovered on a 1" stainless steel instrumentation line associated with the main steam flow-measurement manifold on the upstream side of a condensing chamber. A root cause investigation was performed and the failed component was shipped to Altran for analysis. In this case, IGSCC was determined to be the predominant failure mechanism. Additionally, a piping strap (restraint) shown on the isometric drawing was found missing during inspections following this failure. The failed piping section was replaced with the same material using the original weld geometry.

NRC FOAM 366A (10-2010)