05000266/FIN-2011003-05
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Diesel-Driven Fire Pump Loss of Suction During Surveillance Testing |
| Description | The inspectors identified a URI when the diesel-driven fire pump failed a routine surveillance test. On June 21, 2011, the licensee unsatisfactorily performed surveillance test, O-PT-FP-014, Z-935 Portable Diesel-Driven Fire Water Pump Quarterly Functional Test, Revision 4, when the pump was unable to take suction from the lake using the portable strainer. Specifically, on the first of two attempts, the pump strainer clogged with grass; and on the second attempt, when the strainer was moved further into the lake, the strainer turned upright into the air space and the pump lost suction. The inspectors were unable, at the completion of this inspection period, to ascertain the impact of the failures relative to the regulatory requirements which established the need for the pump. This issue is unresolved pending a review of the failure and procedural adequacy relative to the current licensing basis (URI 05000266/2011003-05; 05000301/2011003-05, Diesel-Driven Fire Pump Loss of Suction During Surveillance Testing). |
| Site: | Point Beach |
|---|---|
| Report | IR 05000266/2011003 Section 1R22 |
| Date counted | Jun 30, 2011 (2011Q2) |
| Type: | URI: |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.22 |
| Inspectors (proximate) | R Langstaff R Winter T Bilik M Phalen M Kunowski S Burton M Thorpe-Kavanaugh J Beavers P Cardona-Morales K Carrington S Belld Jonesk Carrington M Thorpe Kavanaugh N Feliz Adomo P Cardona Morales S Burton T Bilik |
| INPO aspect | |
| ' | |
Finding - Point Beach - IR 05000266/2011003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Point Beach) @ 2011Q2
Self-Identified List (Point Beach)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||