Finding | |
---|---|
Title | Licensee-Identified Violation |
Description | The following violation of not high safety significance (i.e., not Red) was identified by the licensee and is a violation of NRC requirements. This violation has been screened and determined to warrant enforcement discretion per the Interim Enforcement Policy Regarding Enforcement Discretion for Certain Fire Protection Issues. A violation of 10 CFR Part 50, Appendix R, Section III.G.2 was identified by the licensee for the failure to ensure safe-shutdown capability for Unit 1. Specifically, the licensee identified that, due to inadequate cable separation, there was a potential for a fire in the Auxiliary Feedwater (AFW) room to propagate to the vital switchgear room, causing a fire in two separate fire areas the loss of all AFW decay heat removal capability for Unit 1. This issue is discussed in Section 4OA3.2 of this report. |
Site: | Point Beach ![]() |
---|---|
Report | IR 05000266/2010008 Section 4OA7 |
Date counted | Jun 30, 2010 (2010Q2) |
Type: | Violation: Severity level Enforcement Discretion |
cornerstone | Mitigating Systems |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | R Daley R Langstaff A Dahbur C Moore D Passehl L Jones |