05000263/FIN-2010003-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Unacceptable Preconditioning of 250 Vdc Battery Chargers |
Description | The inspectors identified a finding of very low safety significance and associated NCV of Technical Specification (TS) 5.4.1 for the licensees failure to appropriately implement an applicable procedure recommended in Regulatory Guide 1.33, Appendix A, Revision 2, February 1978. Specifically, the licensee approved TS surveillance activities to commence for the 250 Vdc battery chargers in 2008 without ensuring that the equipment was tested in the as-found condition. Due to improper sequencing of preventive maintenance activities for the battery chargers, and subsequent inadequate review of the maintenance and testing order, the 250 Vdc battery chargers were unacceptably preconditioned prior to performing testing to satisfy the 24 month TS Surveillance Requirement 3.8.4.2. These issues were identified by the inspectors prior to the 2010 performance of the same surveillance tests. The licensee took immediate corrective actions and entered the issues into their corrective action program. The inspectors determined that the performance deficiency affected the cross-cutting area of Human Performance, having work control components, and involving aspects associated with appropriately coordinating work activities by incorporating actions to address the impact of the work on different job activities. H.3(b)
The inspectors determined that the issue was a performance deficiency because it was the result of the failure to meet a requirement, and the cause was reasonably within the licensees ability to foresee and correct, and should have been prevented. The inspectors determined that the performance deficiency was more than minor and a finding because, if left uncorrected, it would have had the potential to lead to a more significant safety concern. The inspectors applied IMC 0609, Attachment 4, \"Phase 1 Initial Screening and Characterization of Findings\" to this finding. Under Column 2 of the Table 4a worksheet, the inspectors answered \"Yes\" to Question 1 because the finding did not result in loss of operability or functionality. Therefore, the finding was considered to be of very low safety significance. |
Site: | Monticello |
---|---|
Report | IR 05000263/2010003 Section 1R22 |
Date counted | Jun 30, 2010 (2010Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.22 |
Inspectors (proximate) | K Riemer M Phalen S Thomas L Haeg M Jones |
CCA | H.5, Work Management |
INPO aspect | WP.1 |
' | |
Finding - Monticello - IR 05000263/2010003 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Monticello) @ 2010Q2
Self-Identified List (Monticello)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||