05000482/LER-2010-013

From kanterella
Jump to navigation Jump to search
LER-2010-003, WOLF CREEK GENERATING STATION
Wolf Creek Generating Station
Event date: 11-18-2010
Report date: 01-17-2011
Reporting criterion: 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition
Initial Reporting
ENS 46428 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
4822010003R00 - NRC Website

As a result of a commitment in Wolf Creek Generating Station (WCGS) LER 2010-003, Fire Protection performed a post-fire safe shutdown (PFSSD) circuit analysis for the Train B emergency diesel generator (EDG) [EIIS Code: EK] to ensure the diesel generator would remain available in the event of a fire in the control room. On November 18, 2010, during performance of the circuit analysis for the Train B EDG, it was discovered that certain fuses installed within Train B ExciterNoltage Regulator cabinet would be susceptible to failure in the event of postulated fire-induced hot shorts within the control room. If the fuse fails prior to flashing the field, then the generator will not be capable of generating voltage and no power will be available to supply credited PFSSD equipment.

Additionally, a circuit analysis was performed for all components credited for hot standby following a control room fire as directed by procedure OFN RP-017, "Control Room Evacuation." As a result of that circuit analysis, on December 17, 2010, the following issues were discovered:

1. A fire in the control room could cause the pressurizer power operated relief valves (PORVs) [EllS Code: PZR-RV] to fail open. Actions currently proceduralized in OFN RP-017 may not be sufficient to close the PORVs within 3 minutes as required by the thermal hydraulic analysis. Based on the step sequence in OFN RP-017, it could take approximately 20 minutes to ensure all potential hot short sources are removed.

2. The ventilation alignment in the Train B essential service water (ESW) pump room [EllS Code:

MK-DMP] and Train B EDG Room [EIIS Code: NB-DMP], in accordance with OFN RP-017, may not be adequate for all outside temperature conditions. A fire in the control room could cause the respective recirculation dampers to fail in any position. In the winter months, if the recirculation damper fails closed, then 100% outside air would be brought into the room with no mixing. This could cause the room temperature to drop below the minimum design temperature. In the summer months, if the recirculation damper fails full open, then maximum recirculation would occur and possibly cause the room temperature to exceed the maximum design temperature.

BASIS FOR REPORTABILITY

A PFSSD issue identified as a condition where no or insufficient guidance is available to Operators, to readily mitigate the postulated fire induced equipment maloperation, is considered an unanalyzed condition in accordance with Section 50.72(b)(3)(ii)(B). This is based on NUREG 1022, Rev. 2, Section 3.2.4, which provides the following example:

.... if fire barriers are found to be missing, such that the required degree of separation for redundant safe shutdown trains is lacking, the event would be reportable as an unanalyzed condition that significantly degraded plant safety.

Therefore, 10 CFR 50 Appendix R circuit separation issues that could result in undesired equipment maloperation with a resulting adverse affect on PFSSD capability, is considered by Wolf Creek Nuclear Operating Corporation (WCNOC) to be a condition where fire barrier protection is deficient.

As such, WCNOC is reporting these conditions pursuant to 10 CFR 50.73(a)(2)(ii)(B) for any event or condition that resulted in the nuclear power plant being in an unanalyzed condition that significantly degraded plant safety. Additionally, WCNOC made two eight-hour Emergency Notification System calls, Event Notifications 46428 and 46488, in accordance with 10 CFR 50.72(b)(3)(ii)(B).

ROOT CAUSE

Consistent with the apparent cause conclusion for LER 2010-003, the apparent cause for the issues identified in this LER is inadequate review of control room circuitry for impact on PFSSD following a control room fire. A number of opportunities were found that should have identified the issues including a root cause evaluation conducted in 2007.

CORRECTIVE ACTIONS

An hourly fire watch was in place in the control room to mitigate various control room PFSSD circuit issues, including the issues in this LER. The hourly fire watch will not be lifted until all control room PFSSD circuit issues are corrected.

Procedure OFN RP-017, "Control Room Evacuation," was revised to include the following compensatory actions:

1. Instructions were provided to operators on how to replace a blown fuse within the Train B ExciterNoltage Regulator cabinet. Spare fuses were staged in the emergency equipment locker and procedure STN GP-009, "Emergency Equipment Verification," was revised to list the spare fuses in the attachment 2. Potential 125 VDC sources located in control room that were de-energized later in procedure OFN RP-017, were moved to earlier in the procedure. This will ensure the pressurizer PORVs are closed within the time required by the thermal hydraulic analysis.

3. Directions have been added for operators to monitor room temperature extremes in the Train B ESW pump house and Train B EDG room and take needed actions.

SAFETY SIGNIFICANCE

These issues have low safety significance. A fire in the control room of such magnitude and severity as to cause an evacuation and plant shutdown is extremely unlikely. Based on the Fire Hazards Analysis, the combustible loading in the control room is low and interior finish materials meet or exceed the surface flammability requirements of applicable standards. Cables entering the control room are IEEE 383 rated. Large concentrations of cables in the control room trenches are protected with an automatic Halon extinguishing system and automatic smoke detectors are located in the control cabinets and trenches.

the emergency diesel generator in droop mode of operation. In addition, other circuit issues were identified that could adversely affect the diesel generator voltage regulator. This issue could have prevented operation of the Train B EDG if a fire occurred in the control room involving these circuits.