Finding | |
---|---|
Title | Unanalyzed Flood Source From Technical Support Center Building |
Description | A finding of very low safety significance and associated NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, was identified by the inspectors for the failure to identify and analyze a potential flooding source that was within the Kewaunee licensing basis. Specifically, during the internal flood basis reconstitution in 2005, the licensee failed to realize and assess the potential for fire main piping in the technical support center (TSC) building to be ruptured during a tornado or seismic event. Water from a ruptured fire main had the potential to accumulate in the basement of the TSC building, flow into the attached auxiliary building, and potentially affect safety-related (SR) equipment. The licensee initiated a condition report (CR) and completed calculations and analyses to demonstrate the existing barriers, although not credited at the time, were adequate to support this internal flood scenario. In addition, the licensee performed an extent of condition analysis to determine if any additional internal flood scenarios were missed. The inspectors determined that the finding was more than minor in accordance with IMC 0612, Power Reactor Inspection Reports, Appendix B, Issue Screening, dated December 24, 2009, because it was associated with the Mitigating Systems (MS) Cornerstone attribute of Equipment Performance, and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to analyze all potentially credible internal flood sources could affect the availability of SR systems. The inspectors determined that the finding could be evaluated using the significance determination process in accordance with IMC 0609, Significance Determination Process, Attachment 0609.04, Phase 1 - Initial Screening and Characterization of Findings, Table 4a, for the MS Cornerstone, dated January 10, 2008. The inspectors answered No to the MS questions and screened the finding as having very low safety significance (Green). The inspectors did not identify a cross-cutting aspect associated with this finding because the internal flood design basis reconstitution occurred in 2005 and the inspectors determined that there was not an opportunity to identify this deficiency in the past three years. |
Site: | Kewaunee |
---|---|
Report | IR 05000305/2011005 Section 1R06 |
Date counted | Dec 31, 2011 (2011Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.06 |
Inspectors (proximate) | D Mcneil R Winter K Riemer J Cassidy D Betancourt K Barclay N Feliz-Adomo M Jones J Beavers V Myers S Shah M Ziolkowski |
INPO aspect | |
' | |
Finding - Kewaunee - IR 05000305/2011005 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Kewaunee) @ 2011Q4
Self-Identified List (Kewaunee)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||