Pages that link to "05000395/LER-1983-006, Forwards LER 83-006/03L-0.Detailed Event Analysis Encl"
Jump to navigation
Jump to search
The following pages link to 05000395/LER-1983-006, Forwards LER 83-006/03L-0.Detailed Event Analysis Encl:
Displayed 21 items.
- 05000395/LER-1983-005, Forwards LER 83-005/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-004, Forwards LER 83-004/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-006 (redirect page) (← links)
- ML20070V312 (redirect page) (← links)
- 05000395/LER-1983-006, Forwards Updated LER 83-006/03L-1.Detailed Event Analysis Encl (redirect page) (← links)
- 05000395/LER-1983-001, Updated LER 83-001/01T-1:on 830119,three Refueling Water Storage Tank Level Transmitters Failed High.Caused by Transmitter Base Freezing.Transmitters Thawed.Insulated Encls & Addl Permanent Heat Trace Will Be Installed (← links)
- ML20071B833 (redirect page) (← links)
- 05000395/LER-1983-060, /03L-0:on 831117,investigation Into Previously Submitted LER 83-060 Revealed Four Testable Components Not Tested on Quarterly Basis.Caused by Inadequate Procedure.Test Procedures Revised (← links)
- 05000395/LER-1983-009, Forwards LER 83-009/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-038, Forwards LER 83-038/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-034, Forwards LER 83-034/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-031, Forwards LER 83-031/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-030, Forwards LER 83-030/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-025, Forwards LER 83-025/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-026, Forwards LER 83-026/03L-0 (← links)
- 05000395/LER-1983-021, Forwards LER 83-021/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-023, Forwards LER 83-023/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-022, Forwards LER 83-022/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-024, Forwards LER 83-024/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-020, Forwards LER 83-020/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-019, Forwards LER 83-019/01L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-017, Forwards LER 83-017/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-018, Forwards LER 83-018/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-008, Forwards Updated LER 83-008/03L-1.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-014, Forwards LER 83-014/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-015, Forwards LER 83-015/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-094-03, /03L-0:on 830821,ambient Temp in Svc Water Pump House Exceeded Tech Specs.Caused by Unusually High Outside Air Temp (← links)
- 05000395/LER-1983-085-03, /03L-0:on 830721-24,ambient Temp in Svc Water Pump House Exceeded Tech Spec Limits.Caused by Outside Air Temp Above Average.Mod to Evaluate Need for Installing Cooling Coils Being Processed (← links)
- 05000395/LER-1983-049-03, /03L-0:on 830606,svc Water Booster Pump a Discharge Check valve,XVC-3135A-SW Declared Inoperable Due to Failure to Close on Reverse Flow.Caused by Worn Linkage. Hinge & Key Replaced & Valve Disk Lapped (← links)
- 05000395/LER-1983-043-03, /03L-0:on 830506,while in Mode 5,operations Personnel Stepped Through Maronite Board Fire Barrier.Caused by Personnel Error.Fire Watch Established.Area Posted. Barrier Repaired (← links)
- 05000395/LER-1983-041-01, /01T-0:on 830520,plant Entered Mode 3 W/Train B of Heat Tracing Associated W/Boron Injection Tank Flow Path Deenergized.Caused by Personnel Error & Inadequate Procedure.Panel Energized (← links)
- 05000395/LER-1983-035-03, /03L-0:on 830420,horizontal Fire Barrier Above Svc Water Booster Pump a Found Damaged.Caused by Maint Activities in Immediate Area of Fire Barrier.Damaged Barrier Replaced (← links)
- 05000395/LER-1983-010-03, /03L-0:on 830206,only One Isotopic Iodine Analysis Performed During Power Reduction from 50% to 5%.Caused by Personnel Misinterpreting Power Changes.Chemistry Lab Policy Issued Re Need for Analysis (← links)
- 05000395/LER-1983-007, Forwards LER 83-007/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-006, Forwards LER 83-006/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-007-03, /03L-0:on 830124,9% Discrepancy Found Between Main Control Board & Control Room Evacuation Panel (Crep) Indication for Pressurized Relief Tank Level.Caused by Instrument Drift.Crep Calibr & Returned to Svc (← links)
- 05000395/LER-1983-007, Forwards LER 83-007/03L-0.Detailed Event Analysis Encl (← links)
- 05000395/LER-1983-006-03, /03L-0:on 830113,while in Mode 1,post-accident Hydrogen Analyzer a Declared Inoperable.Caused by Excessive Heat Damage to Wiring & Detector Cell Failing to Adequately Insulate Cover.Cover,Detector Cell & Wiring Replaced (← links)
- 05000395/LER-1983-028-01, /01T-0:on 830406,out-of-tolerance Measurement Found on Undervoltage (UV) Trip Device Between Moving Core & Rolling Bracket.Caused by Mfg Variation of UV Trip Devices. Devices Will Be Replaced (← links)
- 05000395/LER-1983-029-03, /03L-0:on 830320,w/reactor Bldg Purge Initiated, Radiation Monitor RM-A4 Read Higher than Normal Pump RM-A4 & Detector Secured to Change Filter,Leaving Purge Unmonitored for 5 Minutes.No Activity Released During Event (← links)
- 05000395/LER-1983-027-03, /03L-0:on 830318,main Control Board Temp Indication TE-413 for Reactor Coolant Outlet Temp Exhibited Erratic Indications.Caused by Varying Resistance Between Compensated Lead & Low Side Resistance Leg of TE-413 (← links)
- 05000395/LER-1983-011-03, /03L-0:on 830208 & 17,during Mode 1 Operation, Nuclear Sampling Sys Valves 9398 A,B & C Failed to Close. Caused by Limit Switch Failure on One Valve & Crud Buildup on Other Valve Seats.Crud Dislodged.Limit Switches Repaired (← links)
- 05000395/LER-1983-013-03, /03L-0:on 830113 & 19,condensate Storage Tank Level Transmitters LT-3631 & LT-3631A Failed Due to Frozen Instrument Lines.Caused by Temp Sensing Element Not Being Located Per Design Specs.Element Relocated (← links)
- 05000395/LER-1983-003-03, /03L-0:on 830108 & 20,main Control Board Indication for Steam Generator a Feedwater Flow IFI-477 Failed Low.Caused by High Instrument Cabinet Temp.Power Supply Card Replaced & Recalibr (← links)
- 05000395/LER-1983-091-03, /03L-0:on 830802,while in Mode 1,borated Water Vol of Accumulator a Decreased to 7,354 Gallons.Caused by Valve Leakage in ECCS Check Valve Leakage Detection Sys.Valves Verified in Locked Position.Flange Installed (← links)
- 05000395/LER-1983-075-03, /03L-0:on 830703,emergency Feedwater Valve IFV-3536 to Steam Generator a Tripped Shut on High Flow & Failed to Reset.Caused by Signal Comparator Card Failure. Card Replaced (← links)
- 05000395/LER-1983-074-03, /03L-0:on 830603,during Emergency Diesel Generator a Operability Surveillance Test,Normal 115 Kv Power Supply to Vital Bus Lost & Diesel Generator Output Breaker Tripped Open.Caused by Electrical Surge (← links)
- 05000395/LER-1983-057-03, /03L-0:on 830606,nitrogen Low Pressure Alarm on Low Pressure Accumulator for PORV Received in Control Room. Caused by Valve Position Indicator Lights Not Showing Full Actual Position.Limit Switches Adjusted (← links)
- 05000395/LER-1983-036-03, /03L-0:on 830414,during Performance of Channel Calibr,Pressurizer Safety Valve Position Indication on Valves Failed to Function Properly.Caused by Excessive Current Flow During Contact Closure.Switch Assembly Changed (← links)
- 05000395/LER-1983-033-03, /03L-0:on 830331,while in Mode 5,source Range Detectors N-31 & N-32 Lost for Approx 5 Minutes.Caused by Maint Personnel Error in Placing Trains of Solid State Protection Sys in Wrong Position.Personnel Cautioned (← links)
- 05000395/LER-1983-033, Forwards LER 83-033/03L-0.Detailed Event Analysis Encl (← links)