05000305/LER-2012-001, Regarding Pressurizer PORV and Reactor Coolant System Vent Valves Appendix R Spurious Operation Concerns

From kanterella
Revision as of 03:18, 12 January 2025 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Regarding Pressurizer PORV and Reactor Coolant System Vent Valves Appendix R Spurious Operation Concerns
ML12125A040
Person / Time
Site: Kewaunee 
Issue date: 04/19/2012
From: Jordan A
Dominion Energy Kewaunee
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
12-266, IR-12-001 LER 12-001-00
Download: ML12125A040 (7)


LER-2012-001, Regarding Pressurizer PORV and Reactor Coolant System Vent Valves Appendix R Spurious Operation Concerns
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)
3052012001R00 - NRC Website

text

Dominion Dominion Energy Kewaunee, Inc.

N490 Hwy 42, Kewaunee, WI 54216 Web Address: www.dom.com APR 19 2012 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001 Serial No.12-266 LIC/NW/RO Docket No.: 50-305 License No.:

DPR-43 DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION LICENSEE EVENT REPORT 2012-001-00 Pursuant to 10 CFR 50.73, Dominion Energy Kewaunee, Inc., hereby submits the following Licensee Event Report applicable to Kewaunee Power Station.

Report No. 50-305/2012-001-00 This report has been reviewed by the Facility Safety Review Committee and will be forwarded to the Management Safety Review Committee for its review.

If you have any further questions, please contact Mr. Richard Repshas at (920) 388-8217.

Very truly yours, Site Vice President, Kewaunee Power Station Attachment(s)

Commitments made by this letter: NONE NL

Serial No.12-266 Page 2 of 2 cc:

Regional Administrator, Region III U.S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Mr. K. D. Feintuch Project Manager U.S. Nuclear Regulatory Commission One White Flint North, Mail Stop 08-H4A 11555 Rockville Pike Rockville, MD 20852-2738 NRC Senior Resident Inspector Kewaunee Power Station

NRC FORM 366 U.S. NUCLEAR V

t/IFJJ BY OMB: NO. 3150-0104 EXPIRES:

REGULATORYCOMMISSION (10-2010)

Estimated burden per response to comply with this mandatory collection request: 80 hrs.

Reported lessons learned are incorporated into the licensing process and fed back to industry. Send comments regarding burden estimate to the FOIA/Privacy Service (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by internet e-mail LICENSEE EVENT REPORT (LER) to infocollects.resource@nrc.gov, and to the Desk Officer, Office of Sefor required number of Information and Regulatory Affairs, NEOB-10202, (3150-0104), Office of (See reverse for ea blo f Management and Budget, Washington, DC 20503. If a means used to digits/characters ~or each block) impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. PAGE Kewaunee Power Station 05000305 1

OF

4. TITLE Pressurizer PORV and Reactor Coolant System Vent Valves Appendix R Spurious Operation Concerns 5, EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED FACILITY NAME DOCKET MONTH DAY YEAR YEAR SEQUENTIAL REV MONTH DAY YEAR NUMBER NUMBER NO 0

I J05000 02 22 2012 2012 001 00 04 19 2012 05000

9. OPERATING
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply)

MODE [I

20.2201(b)

[j 20.2203(a)(3)(i)

[I 50.73(a)(2)(i)(C) 0 50.73(a)(2)(vii)

[I 20.2201(d)

[I 20.2203(a)(3)(ii)

[I 50.73(a)(2)(ii)(A) 0 50.73(a)(2)(viii)(A) 1

[

20.2203(a)(1)

[I 20.2203(a)(4) 0 50.73(a)(2)(ii)(B) 0 50.73(a)(2)(viii)(B) 0]

20.2203(a)(2)(t) 0 50.36(c)(1)(i)(A) 0 50.73(a)(2)(iii) 0 50.73(a)(2)(ix)(A) o[

20.2203(a)(2)(ii)

[I 50.36(c)(1)(ii)(A) 0 50.73(a)(2)(iv)(A)

[0 50.73(a)(2)(x)

10.

20.2203(a)(2)(iii)

[I 50.36(c)(2) 0 50.73(a)(2v)(A)

[

73.71(a)(4) o 20.2203(a)(2)(iv)

C0 50.46(a)(3Xii) 50.73(a)(2)(v)(B) 0 73.71(a)(5)

[o 20.2203(a)(2)(v)

[0 50.73(a)(2)(i)(A) 0 50.73(a)(2)(v)(C) 0 OTHER 100 [1

20.2203(a)(2)(vi)

[I 50.73(a)(2)(i)(B) 0 50.73(a)(2)(vMD)

Specify in Abstract below or in NRC Form 366A

12. LICENSEE CONTACT FOR THIS LER FACILITY NAME TELEPHONE NUMBER (include Area Code)

Brian Koehler 920-388-8390CAUSE SYSTEM COMPONENT MANU-REPORTABLE

CAUSE

SYSTEM COMPONENT MANU-REPORTABLE FACTURER TO EPIX

14. SUPPLEMENTAL REPORT EXPECTED
15. EXPECTED ii YES (If yes, complete 15. EXPECTED SUBMISSION DATE)

[

NO SUBMISSION DATE ABSTRACT (Limit to 1400 spaces, i.e., approximately 15 single-spaced typewritten lines)

On February 22, 2012, while developing Design Change KW-12-01049 to address inadequate Appendix R reactor coolant system high/low interface valve cable separation issues for pressurizer power operated relief valves (PORVs) PR-2A and PR-2B, additional concerns were raised regarding the condition originally identified in Condition Report CR109107 and discussed in LER 2008-001-00.

Subsequently, on February 28, 2012, additional Appendix R fire spurious operation concerns (related to a postulated fire in the relay room or 480 volt Bus 51/52 area) were identified for the pressurizer and reactor head vent valves PR-33A, RC-45A, and RC-46 than as originally identified in Condition Report CR114409 and discussed in LER 2008-001-00.

An evaluation of these concerns determined that the control cables for the valves in question were not adequately protected from potential fire damage in the alternate and dedicated safe shutdown areas and spurious opening of these high/low interface valves could be postulated in the event of a fire.

This event is being reported pursuant to 10 CFR 50.73(a)(2)(ii)(B) for any event that resulted in the nuclear power plant being in an unanalyzed condition that significantly degraded plant safety.

NRC FORM 366 (10-2010)

Event Description

On February 22, 2012, while developing Design Change KW-12-01049 to address inadequate Appendix R reactor coolant system high/low interface valve cable [CBL4] separation issues for pressurizer power operated relief valves (PORVs) PR-2A [PCV] and PR-2B [PCV], additional concerns were raised regarding the condition originally identified in Condition Report CR109107 and discussed in LER 2008-001-00. This additional concern was identified in Condition Report CR 463680 and entered in the Station's Corrective Action Program. Subsequently, on February 28, 2012, additional Appendix R fire spurious operation concerns (related to a postulated fire in the relay room and 480 volt Bus 51/52 area) were identified for the pressurizer [PZR] and reactor [RCT] head vent valves [FSV] PR-33A, RC-45A, and RC-46 than as originally identified in Condition Report CR114404 and discussed in LER 2008-001-00. This condition was identified in Condition Report CR464393 and also entered into the Corrective Action Program.

Per 10 CFR 50, Appendix R, and NRC guidance for reactor coolant system (RCS) [AB] high/low pressure interfaces, components required to achieve and maintain safe shutdown conditions must be capable of performing their required safe shutdown function in the event of a fire in either the dedicated or alternate fire area. The Kewaunee Power Station (KPS) licensing basis term for fire area is fire zone. The KPS licensing basis fire event is a single worst case fire in either fire zone, but not simultaneously in both fire zones.

Condition Report CR109107, Pressurizer PORV PR-2B Control Cable Appendix R Spurious Operation Concern, discussed that the current routing of PORV PR-2B alternate solenoid SV33731 control cables 1 $6C1 228 and 1 S6C1 229 did not meet current NRC guidance and could lead to the spurious opening of this valve during an Appendix R fire event in the relay room. The extent of condition evaluation previously performed for the other PORV control circuits, specifically, PR-2B normal solenoid SV33113 and PR-2A solenoid SV33114, concluded that the same issue did not apply. However, while developing a resolution for the solenoid SV33731 cables, the other circuits were re-evaluated and the extent of condition conclusion was questioned, as documented in Condition Report CR463680.

As discussed in Operability Determination OD000194, the control cabling is routed in dedicated conduit [CND] from the control room to containment. This is true for SV33114 cable 1 S6C1 426 and SV33113 cables 1S5C1 545 and 1 S5C1 542. However, additional cables within these circuits are not routed in dedicated conduit and do not appear to have been evaluated in the original Condition Report. The effects from a fire event on these additional cables associated with PR-2B are evaluated as follows:

1 S5C380 (PR-2B normal solenoid SV33113): Routed in cable tray between terminal cabinet [CAB] TC1 2S5 and relay rack RR142 within the relay room. An intra-cable short circuit between conductors 3311302 and 331130 will bypass the normally open contacts from relays [RLY] PC429/FX and PC430/BX. This combined with normally closed contact 2L of control switch 46414 creates a conductive path from the positive leg of the circuit to the solenoid.

1 S5C887 (PR-2B normal solenoid SV33113): Routed in cable tray between fuse [FU] panel [PL] RR1 71 and Mechanical Control Console [CSL] C. This cable consists of seven conductors, two of which support this control circuit. Four of the remaining five conductors support two 125VDC non-Appendix R control circuits (valves NG-107 and RC-507). Step Al.a.1 of procedure OP-KW-AOP-FP-002, Fire in Alternate Fire Zone, de-energizes the SV33113 circuit however the other two circuits are not de-energized. Two intra-cable hot shorts of proper polarity, combined with the intra-cable short discussed for cable 1S5C380, could lead to spurious opening of PR-2B for a fire in the relay room.U.S. NUCLEAR REGULATORY COMMISSIONU.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE SEQUENTIAL I

REV YEAR NUMBER NO.

Kewaunee Power Station 05000305 3

OF 5

2011 001 00 The "Response Not Obtained" (RNO) portion of step Al.a of OP-KW-AOP-FP-002, Fire in Alternate Fire Zone, has operators open the supply breaker [BKR] to fuse panel RR1 71, which de-energizes all of the circuits discussed above. However, since PR-2B is designated as a high/low pressure interface valve in the Appendix R program and cable 1S5C887 is routed in the same cable tray, two inter-cable hot shorts of proper polarity must be assumed to occur (according to NRC guidance). This again, combined with the intra-cable short on 1S5C380, could lead to spurious opening of PR-2B.

A review of the control circuits associated with PR-2A concluded the following:

Cable 1S6C290 (PR-2A solenoid SV33114): Routed in cable tray between Mechanical Control Console C in the Control Room and relay rack RR147 in the relay room. An intra-cable short circuit between conductors 3311402 and 331140 will bypass the normally open contacts from relays PC431/BX and PC449/BX. This, combined with normally closed contact 2L of control switch 46415, creates a conductive path from the positive leg of the circuit to the solenoid.

Cable 1 S6C806 (PR-2A solenoid SV33114): Routed in cable tray between fuse panel RR1 76 and Mechanical Control Console C. This cable consists of seven conductors, two of which support this control circuit. Four of the remaining five conductors support two 125VDC non-Appendix R control circuits (valves MG(R)-504 and MG(R)-51 0). Step Al.c.3 of OP-KW-AOP-FP-002, Fire in Alternate Fire Zone, de-energizes the SV33114 circuit; however, the other two circuits are not de-energized. Two intra-cable hot shorts of proper polarity, combined with the intra-cable short discussed for cable 1S6C290, could lead to spurious opening of PR-2A for a fire in the Relay Room.

The RNO portion of step Al.c of OP-KW-AOP-FP-002, Fire in Alternate Fire Zone, has operators open the supply breaker to panel RR1 76, which de-energizes all of the circuits discussed above. However, since PR-2A is designated as a high/low pressure interface valve in the Appendix R program and cable 1S6C806 is routed in a cable tray, two inter-cable hot shorts of proper polarity must be assumed to occur (according to NRC guidance). This again, combined with the intra-cable short on 1S6C290, could lead to spurious opening of PR-2A.

While reviewing pressurizer and reactor head vent valve (PR-33A/B, RC-45A/B, RC-46 and RC-49) control circuit cable routings for Reasonable Assurance of Safety, RAS0001 99, it was discovered that an Appendix R fire event could also cause spurious operation of PR-33A, RC-45A, and RC-46.

Condition report CR114404 identified that a fire event in an Alternate fire zone could cause spurious operation of PR-33B, RC-45B and RC-49. Operability Determination OD00021 1, was created from this condition report. The extent of condition performed in OD000211 focused on the opposite train valves (PR-33A, RC-45A and RC-46) and stated, "For a fire in an Alternate fire zone (such as the Relay Room) the valves could spuriously open. For a fire in the Alternate area, the spurious opening of these valves would be mitigated by OP-KW-AOP-FP-002, Rev. 2, and Step A6.a, which directs the operator to place all DSP local/remote switches to LOCAL. This step will isolate the head vent valve circuits from the Alternate area, which will de-energize the circuit and the valves will close."

This latest review for Reasonable Assurance of Safety RAS0001 99 focused on a fire event in a dedicated fire zone (such as the 480V Bus 51/52 Room, where the Dedicated Shutdown Panel (DSP) is located). For a fire in this, or any other dedicated fire zone, valves PR-33A, RC-45A and RC-46 are to remain closed. The Appendix R Design Description (ARDD), sections 4.1.3.3 and 5.5, credits RC-46 for remaining closed by removing its power and routing its solenoid valve cable in dedicated conduit to prevent spurious operationU.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE SEQUENTIAL I

REV YEAR NUMBER NO.

Kewaunee Power Station 05000305 4

OF 5

2011 001 00 from a hot short. However, the following scenario could cause a fire induced spurious operation of RC-46 (and PR-33A and RC-45A).

Cables 1S5C1295 and 1S5C1279 share cable tray routing point 1TT104S5 and support all three valves. An intra-cable short on 1S5C1 279 bypasses the normally open contact from the Control Room control switches. This, combined with a proper polarity inter-cable hot short on 1S5C1 295, could cause any or all of these valves to spuriously open. Turning off the power supply to RC-46, or the entire SD-101 panel as prescribed in step B2.b of procedure OP-KW-AOP-FP-003, Fire in Dedicated Zone, will not prevent this from occurring as other 125VDC circuits exist in cable tray 1TT1 04S5 that could provide the external hot short.

Immediate notification of the above described conditions was previously provided in Event Notification#47686 on February 22, 2012 and Event Notification#47707 on February 28, 2012 per 10 CFR 50.72(b)(3)(ii)(B), for any event or condition that results in the nuclear plant being in an unanalyzed condition that significantly degrades plant safety.

This event is hereby being reported pursuant to 10 CFR 50.73(a)(2)(ii)(B) for any event that resulted in the nuclear power plant being in an unanalyzed condition that significantly degraded plant safety.

Event and Safety Consequence Analysis:

An assessment was made of the combined risk of the four scenarios discussed in this report. This assessment use the methodology from NUREG/CR-6850 to determine the frequency for fires that could affect the cables in question, the severity factors for these fires, and the probability of the hot shorts required to produce a loss of reactor coolant inventory. The assessment conservatively assumed that the loss of inventory would result directly in core damage. Given that methodology, the sum total for all of these scenarios is below the threshold for very low risk (green) in the Significance Determination Process.

Cause

An insufficient extent of condition (EOC) was performed from Operability Determination OD000194 in September 2008, associated with the protection of specific circuits/cables for pressurizer PORVs PR-2A and PR-2B from fire induced spurious operation.

Enforcement discretion for the pertinent 2008 Triennial Fire Protection Inspection violation was in effect because the Station had committed to resolve the issue through NFPA 0805 (July 21, 2008 commitment letter), if required to do so. Since further analysis work was already part of the NFPA 0805 transition project scope, and reanalysis of Appendix R was not warranted (because there were no consequences), both the Operability Determination (OD) and the Reasonable Assurance of Safety (RAS) were updated without further EOC analysis. Therefore, management and administrative process decision-making did not consider any additional or immediate actions as necessary.

Corrective Actions

The current compensatory measure for an hourly fire watch that was already in place for the previous issue

NRC FORM 368A U.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET

1. FACILITY NAME
2. DOCKET
6. LER NUMBER
3. PAGE Y

SEQUENTIAL I

REV YEAR NUMBER NO.

Kewaunee Power Station 05000305 5

OF 5

2011 001 00 was expanded to include the 480 volt Bus 51/52 area. This measure satisfies KPS Fire Protection Program Plan requirements for non-functional fire protection systems, barriers, and Appendix R safe shutdown systems.

Corrective Action CA228092 initiated actions to perform an evaluation and extent of condition review of outstanding 10 CFR 50, Appendix R, issues for the station including the pressurizer and head vent valves PR-33A/B, RC-45A/B, RC-46, and RC-49 potential spurious operation concerns.

Design change KW-12-01049 has been created to address the Appendix R spurious valve operation concerns for pressurizer PORVs PR-2A and PR-2B.

Similar Events

LER 2008-001 -00, Pressurizer PORV and Reactor Coolant System Vent Valves Appendix R Spurious Operation Concern.