ML20101M439

From kanterella
Revision as of 16:05, 28 April 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Proposed TS Table 4.8-1, DG Test Schedule
ML20101M439
Person / Time
Site: Seabrook NextEra Energy icon.png
Issue date: 07/01/1992
From:
NORTH ATLANTIC ENERGY SERVICE CORP. (NAESCO)
To:
Shared Package
ML20101M275 List:
References
NUDOCS 9207080234
Download: ML20101M439 (1)


Text

- . ..

TABLE 4.8-1 DIESEL GENERATOR TEST SCHEDULE NUMBER OF FAILURES IN NUMBER OF FAILURES IN LAST 20 VAllD TESTS

  • LAST 100 VAL 10 TESTS
  • TEST FRE0VENCY s1 s5 At least once per 31 days t2 26 At least once per 7 days **

r in ct c c. e ed % c c w; 6L. Be r odn <. S e dlwc e- R ep&c m e dS e,4 q.S.I.I. D. ct. C a ,J 4. g. I. I. 9. 4 . G ,

  • Criteria for determining the number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, Revision 1, August, 1977, but determined on a per diesel generator basis.

For the purpose of determining tha required test frequency, the previous test failure count may be reduced to zero if a complete diesel overiaul to likt new condition is completed, provided that the overhaul, incluuing appropriate post-maintenance operation and testing, is specifically approved by the manufacturer and if acceptable reliability has been demonstrated. The reliability criterion shall be the successful completion of 14 conseative tests in a single seriep. Ten of thcsc tests shal' be in accordance 'ith

---the. rcu t ine Survei' l ance Requ irements A .B.1 1. 2. a ,5 Md M .S.1.1. 2. 2.6-e4--

four tests in accordance ..ith the 18" day testing requirement of Survcil kncc

- Rcquiremcats 4.S.1.1.2.a.5 and 4.0.1.1.2.a.$. If this criterion is not satisfied during the first series of tests, any alternate criterion to be used to transvalue the failure count to zero requires NRC approval. >

    • This test frequency shall be maintained until seven consecutive failure-free demands have been performed and the aa @er of failures in the last 20 valid demands has been reduced to one or le..u.

SEABROOK - UNIT 1 3/4 8-10 9207080234 920701 3 DR ADOCK 0500

. -